NATIONAL ELECTRICAL CODE
Exception: In a separate and uninterrupted area supplied by a minimum
of three normal lighting circuits, a separate branch circuit for unit equipment shall be permitted if it originates from the same panelboard as that
of the normal lighting circuits and is provided with a lock-on feature.
D. Emergency System Circuits for Lighting and Power
700-15. Loads on Emergency Branch Circuits. No appliances and no
lamps, other than those specified as required for emergency use, shall be
supplied by emergency lighting circuits.
700-16. Emergency Illumination. Emergency illumination shall include
all required means of egress lighting, illuminated exit signs, and all other
lights specified as necessary to provide required illumination.
Emergency lighting systems shall be so designed and installed that the
failure of any individual lighting element, such as the burning out of a light
bulb, cannot leave in total darkness any space that requires emergency
illumination.
Where high-intensity discharge lighting such as high- and low-pressure.
sodium, mercury vapor, and metal halide is used as the sole source of normal illumination, the emergency lighting system shall be required to operate until normal illumination has been restored.
Exception: Where alternative means have been taken to ensure that the
emergency lighting illumination level is maintained.
700-17. Circuits for Emergency Lighting. Branch circuits that supply
emergency lighting shall be installed to provide service from a source complying with Section 700-12 when the normal supply for lighting is interrupted. Such installations shall provide either one of the following: (1) an
emergency lighting supply, independent of the general lighting supply, with
provisions for automatically transferring the emergency lights upon the
event of failure of the general lighting system supply, or (2) two or more
separate and complete systems with independent power supply, each system providing sufficient current for emergency lighting purposes. Unless
both systems are used for regular lighting purposes and are both kept
lighted, means shall be provided for automatically energizing either system
upon failure of the other. Either or both systems shall be permitted to be
a part of the general lighting system of the protected occupancy if circuits
supplying lights for emergency illumination are installed in accordance
with other sections of this article.
700-18. Circuits for Emergency Power. For branch circuits that supply
equipment classed as emergency, there shall be an emergency supply
source to which the load will be transferred automatically upon the failure
of the normal supply.
E. Control - Emergency Lighting Circuits
700-20. Switch Requirements. The switch or switches installed in emergency lighting circuits shall be so arranged that only authorized persons
will have control of emergency lighting.