Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)

Last amended: 1993Length: 351 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 700-9-690

(3) Overcurrent protection for a transformer with a source(s) on each side shall be provided in accordance with Section 450-3 by considering first one side of the transformer, then the other side of the transformer, as the primary. 705-32. Ground-Fault Protection. Where ground-fault protection is used, the output of an interactive system shall be connected to the supply side of the ground-fault protection. Exception: Connection shall be permitted to be made to the load side of ground-fault protection provided that there is ground-fault protection for equipment from all ground-fault current sources. 705-40. Loss of Primary Source. Upon loss of primary source, an electric power production source shall be automatically disconnected from all ungrounded conductors of the primary source and shall not be reconnected until the primary source is restored. (FPN No. 1): Risks to personnel and equipment associated with the primary source may occur if an interactive electric power production source can operate as an island. Special detection methods may be required to determine that a primary source supply system outage has occurred, and whether there should be automatic disconnection. When the primary source supply system is restored, special detection methods may be required to limit exposure of power production sources to outof-phase reconnection. (FPN No. 2): Induction generating equipment on systems with significant capacitance may become self-excited upon loss of primary source and experience severe over-voltage as a result. 705-42. Unbalanced Interconnections. A 3-phase electric power production source shall be automatically disconnected from all ungrounded conductors of the interconnected systems when one of the phases of that source opens. Exception: An electric power production source providing power for an emergency or legally required standby system. 705-43. Synchronous Generators. Synchronous generators in a parallel system shall be provided with the necessary equipment to establish and maintain a synchronous condition. 705-50. Grounding. Interconnected electric power production sources shall be grounded in accordance with Article 250. Exception: For direct-current systems connected through an inverter directly to a grounded service, other methods that accomplish equivalent system protection and that utilize equipment listed and identified for the use shall be permitted. 70-738 NATIONAL ELECTRICAL CODE
Regl. 5293, art. 700-9-690: Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435) | Justis AI