Regl. 5293, art. 725-16 dup3
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 725-16 dup3
Ethylene
Table 402-3 (Continued)
Max.
Trade
Type
Thickness of
Outer
Operating
Application
Name
Letter
Insulation
AWG
Insulation
Mils
Covering
Temp.
Provisions
Tape Insulated
KF-1
Aromatic
18-10
5.5
None
200°C
Fixture Wiring.
Fixture Wire-
Polyimide
392°F
Limited to 300 volts.
Solid or
Tape
7-Strand
KF-2
Aromatic
18-10
8.4
None
200°C
Fixture wiring, and as permitted
Polyimide
392°F
in Sections 725-16 and 760-16.
Tape
Tape Insulated
KFF-1
Aromatic
18-10
5.5
None
200°C
Fixture Wiring.
Fixture Wire-
Polyimide
392°F
Limited to 300 volts.
Flexible
Tape
Stranding
KFF-2
Aromatic
18-10
8.4
None
200°C
Fixture wiring, and as permitted
Polyimide
392°F
in Section 725-16.
Tape
Perfluoro-
PAF
Perfluoro- 18-14
20
None
250°C
Fixture wiring, and as permitted
alkoxy-Solid
alkoxy
482°F
in Sections 725-16 and 760-16.
or 7-Strand
(Nickel or nickel-coated copper)
ARTICLE 402 FIXTURE WIRES
(Nickel or
Nickel-Coated
Copper)
Perfluoro-
PAFF
Perfluoro- 18-14
20
None
150°C
Fixture wiring, and as permitted
alkoxyalkoxy
302°F
in Section 725-16.
Flexible
Stranding
Fluorinated
PF
Fluorinated 18-14
20
None
200°C
Fixture wiring, and as permitted
Ethylene Pro-
Ethylene
392°F
in Sections 725-16 and 760-16.
pylene Fixture
Propylene
Wire-Solid or
7-Strand
70-325
Table 402-3 (Continued)
Max.
70-326
Trade
Type
Thickness of
Outer
Operating
Application
Name
Letter
Insulation
AWG
Insulation
Mils
Covering
Temp.
Provisions
Fluorinated
PFF
Fluorinated 18-14
20
None
150°C
Fixture witing, and as permit-
Ethylene Pro-
Ethylene
302°F
ted in Section 725-16.
pylene Fixture
Propylene
Wire-Flexible
Stranding
Fluorinated
PGF
Fluorinated 18-14
14
Glass Braid
200°C
Fixture wiring, and as permit-
Ethylene Pro-
Ethylene
392°F
ted in Sections 725-16 and
pylene Fixture
Propylene
760-16.
Wire-Solid or
7-Strand
Fluorinated
PGFF
Fluorinated 18-14
14
Glass Braid
150°C
Fixture wiring, and as permit-
Ethylene Pro-
Ethylene
302°F
ted in Section 725-16.
pylene Fixture
Propylene
Wire-Flexible
NATIONAL ELECTRICAL CODE
Stranding
Extruded
PTF
Extruded 18-14
20
None
250°C
Fixture wiring, and as permit-
Polytetra-
Polytetra-
482°F
ted in Sections 725-16 and
Fluoroethylene
Fluoro-
760-16. (Nickel or nickel-
Solid or
ethylene
coated copper)
7-Strand
(Nickel or
Nickel-Coated
Copper)
Table 402-3 (Continued)
Max.
Trade
Type
Thickness of
Outer
Operating
Application
Name
Letter
Insulation
AWG
Insulation
Mils
Covering
Temp.
Provisions
Extruded
PTFF
Extruded
18-14
20
None
150°C
Fixture wiring, and as permit-
Polytetra-
Polytetra-
302°F
ted in Section 725-16. (Silver
Fluoroethylene
Fluoroethylene
or nickel-coated copper)
Flexible
Stranding
26-36 AWG
Silver or
Nickel-Coated
Copper)
Heat-Resistant
RFH-1
Heat-Resistant
Nonmetallic
75°C
Fixture wiring.
Rubber-
Rubber
18
15
Covering
167°F
Limited to 300 volts.
Covered Fixture Wire-
Heat-Resistant
Solid or
Rubber
18-16
30
Nonmetallic
75°C
Fixture wiring, and as permit-
RFH-2
ted in Sections 725-16 and
7-Strand
Covering
167°F
Heat-Resistant
760-16.
ARTICLE 402 FIXTURE WIRES
Latex Rubber
18-16
18
Heat-Resistant
RFHH-2*
18-16
30
Cross-Linked
Synthetic
Cross-Linked
Synthetic
18-16
45
Polymer-
Insulated Fix-
Polymer
Fixture wiring, and as permitted in Sections 725-16 and
ture Wire-
None or
760-16. Multiconductor cable
Solid or
Nonmetallic
90°C
Stranded
as permitted in Sections 725-16
RFHH-3*
Covering
194°F
and 760-16.
* Insulations and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
70-327
Table 402-3 (Continued)
Max.
70-328
Trade
Type
Thickness of
Outer
Operating
Application
Name
Letter
Insulation
AWG
Insulation
Mils
Covering
Temp.
Provisions
Silicone Insu-
Silicone
Nonmetallic
200°C
Fixture wiring.
lated Fixture
SF-1
Rubber
18
15
Covering
392°F
Limited to 300 volts.
Wire-Solid or
7-Strand
Fixture wiring, and as permit-
Silicone
Nonmetallic
200°C
ted in Sections 725-16 and
SF-2
Rubber
18-14
30
Covering
392°F
760-16.
Silicone Insu-
Silicone
Nonmetallic
150°C
Fixture wiring.
lated Fixture
SFF-1
Rubber
18
15
Covering
302°F
Limited to 300 volts.
Wire-Flexible
Stranding
Silicone
Nonmetallic
150°C
Fixture wiring, and as permit-
SFF-2
Rubber
18-14
30
Covering
302°F
ted in Section 725-16.
Thermoplastic
Covered Fix-
60°C
Fixture wiring, and as permitture Wire-
TF*
Thermoplastic 18-16
30
None
ted in Sections 725-16 and
140°F
Solid or
760-16.
7-Strand
NATIONAL ELECTRICAL CODE
Thermoplastic
Covered Fix-
60°C
ture Wire-
TFF*
Thermoplastic 18-16
30
None
Fixture wiring, and as permit-
140°F
ted in Section 725-16.
Flexible
Stranding
Heat-Resistant
Thermoplastic-
Covered Fix-
Nylon-
90°C
Fixture wiring, and as permit-
TFN*
Thermoplastic 18-16
15
Jacketed or
ted in Sections 725-16 and
ture Wire-
194°F
equivalent
760-16.
Solid or
7-Strand
*Insulations and outer coverings that meet the requirements of flame-retardant limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
Table 402-3 (Continued)
Max.
Trade
Type
Thickness of
Outer
Operating
Application
Name
Letter
Insulation
AWG
Insulation
Mils
Covering
Temp.
Provisions
Heat-Resistant
Thermoplastic
Covered Fix-
Nylon-
90°C
TFFN*
Thermoplastic 18-16
15
Jacketed or
Fixture wiring, and as permitture Wire-
194°F
ted in Section 725-16.
Flexible
equivalent
Stranded
Cross-Linked
XF*
Cross-Linked
18-14
30
None
150°C
Fixture wiring.
Polyolefin In-
Polyolefin
12-10
45
302°F
Limited to 300 volts.
sulated Fixture
Wire-Solid or
7-Strand
Cross-Linked
XFF*
Cross-Linked
18-14
30
None
150°C
Fixture wiring.
Polyolefin In-
Polyolefin
12-10
45
302°F
Limited to 300 volts.
sulated Fixture
Wire-Flexible
Stranded
Modified
ZF
Modified
18-14
15
None
150°C
Fixture wiring, and as permit-
ARTICLE 402 FIXTURE WIRES
ETFE
Ethylene
302°F
ted in Sections 725-16 and
Solid or
Tetrafluoro-
760-16.
7-Strand
Ethylene
Flexible
ZFF
Modified
18-14
15
None
150°C
Fixture wiring, and as permit-
Stranding
Ethylene
302°F
ted in Section 725-16.
Tetrafluoro-
Ethylene
High Temp.
ZHF
Modified
18-14
15
None
200°C
Fixture wiring, and as permit-
Modified
Ethylene
392°F
ted in Sections 725-16 and
ETFE-Solid
Tetrafluoro-
760-16
or 7-Strand
ethylene
70-329
* Insulations and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
70-330
NATIONAL ELECTRICAL CODE
Table 402-5.
Size (AWG)
Allowable Ampacity
18
6
16
8
14
17
12
23
10
28
402-6. Minimum Size. Fixture wires shall not be smaller than No. 18.
402-7. Number of Conductors in Conduit or Tubing. The number of fixture
wires permitted in a single conduit or tubing shall be as shown in Table 2 of
Chapter 9.
402-8. Grounded-Conductor Identification. One conductor of fixture
wires that is intended to be used as a grounded conductor shall be identified by means of stripes or by the means described in Sections 400-22(a)
through (e).
402-9. Marking.
(a) Required Information. All fixture wires shall be marked to indicate
the information required in Section 310-11(a).
(b) Method of Marking. Thermoplastic-insulated fixture wire shall be
durably marked on the surface at intervals not exceeding 24 inches (610 mm).
All other fixture wire shall be marked by means of a printed tag attached to
the coil, reel, or carton.
(c) Optional Marking. Fixture wire types listed in Table 402-3 shall be
permitted to be surface marked to indicate special characteristics of the
cable materials.
(FPN): Examples of these markings include, but are not limited to, "LS" for
limited-smoke or markings such as "sunlight-resistant."
402-10. Uses Permitted. Fixture wires shall be permitted (1) for installation in lighting fixtures and in similar equipment where enclosed or protected and not subject to bending or twisting in use, or (2) for connecting
lighting fixtures to the branch-circuit conductors supplying the fixtures.
402-11. Uses Not Permitted. Fixture wires shall not be used as branchcircuit conductors.
Exception: As permitted by Section 725-16 for Class 1 circuits and Section 760-16 for fire protective signaling circuits.
402-12. Overcurrent Protection. Overcurrent protection for fixture wires
shall be as specified in Section 240-4.