Regl. 5293, art. 760-16(b)-770
OPTICAL FIBER CABLES AND RACEWAYS
Cite as Reglamento Núm. 5293, Art. 760-16(b)-770
A. General
770-1. Scope. The provisions of this article apply to the installation of
optical fiber cables and raceways. This article does not cover the construction of optical fiber cables and raceways.
770-2. Locations and Other Articles. Circuits and equipment shall comply with (a) and (b) below.
(a) Spread of Fire or Products of Combustion. See Section 300-21.
(b) Ducts, Plenums, and Other Air-Handling Spaces. Section 300-22,
where installed in ducts or plenums or other space used for environmental air.
Exception to (b): As permitted in Section 770-53(a).
770-3. Optical Fiber Cables. Optical fiber cables transmit light for control, signaling, and communications through an optical fiber.
770-4. Types. Optical fiber cables can be grouped into three types.
(a) Nonconductive. These cables contain no metallic members and no
other electrically conductive materials.
(b) Conductive. These cables contain noncurrent-carrying conductive
members such as metallic strength members and metallic vapor barriers.
(c) Composite. These cables contain optical fibers and current-carrying
electrical conductors, and shall be permitted to contain noncurrentcarrying conductive members such as metallic strength members and
metallic vapor barriers. Composite optical fiber cables shall be classified as
electrical cables in accordance with the type of electrical conductors.
770-5. Optical Fiber Raceway System. A raceway system designed for
enclosing and routing only nonconductive optical fiber cables. Where optical fiber cables are installed in a raceway, the raceway shall be of a type
permitted in Chapter 3 and installed in accordance with Chapter 3.
ARTICLE 770 - OPTICAL FIBER CABLES AND RACEWAYS
70-783
Exception: Listed optical fiber raceway.
(FPN): Plastic innerduct commonly used for underground or outside plant construction may not have appropriate fire safety characteristics for use as an optical
fiber optic cable wiring method within buildings.
770-6. Cable Trays. Optical fiber cables of the types listed in Table
770-50 shall be permitted to be installed in cable trays.
(FPN): It is not the intent to require that these optical fiber cables be listed specifically for use in cable trays.
770-7. Access to Electrical Equipment Behind Panels Designed to Allow
Access. Access to equipment shall not be denied by an accumulation of
wires and cables that prevents removal of panels, including suspended
ceiling panels.
B. Protection
770-33. Grounding of Entrance Cables. Where exposed to contact with
electric light or power conductors, the noncurrent-carrying metallic members of optical fiber cables entering buildings shall be grounded as close to
the point of entrance as practicable or shall be interrupted as close to the
point of entrance as practicable by an insulating joint or equivalent device.
For purposes of this section, the point of entrance shall be considered to
be at the point of emergence through an exterior wall, a concrete floor slab,
or from a rigid metal conduit or an intermediate metal conduit grounded in
accordance with Article 250.
C. Cables Within Buildings
770-49. Fire Resistance of Optical Fiber Cables. Optical fiber cables
installed as wiring within buildings shall be listed as being resistant to the
spread of fire in accordance with Sections 770-50 and 770-51.
770-50. Listing, Marking, and Installation of Optical Fiber Cables.
Optical fiber cables in a building shall be listed as being suitable for the
purpose, and cables shall be marked in accordance with Table 770-50.
Exception No. 1: Optical fiber cables shall not be required to be listed
and marked where the length of cable within the building does not exceed
50 feet (15.2 m) and the cable enters the building from the outside and is
terminated in an enclosure.
(FPN): Splice cases or terminal boxes, both metallic and plastic types, are typically used as enclosures for splicing or terminating optical fiber cables.
Exception No. 2: Conductive optical fiber cable shall not be required to
be listed and marked where the cable enters the building from the outside and
is run in rigid metal conduit or intermediate metal conduit and such conduits
are grounded to an electrode in accordance with Section 800-40(b).
Exception No. 3: Nonconductive optical fiber cables shall not be
required to be listed and marked where the cable enters the building from
the outside and is run in raceway installed in compliance with Chapter 3.
70-784
NATIONAL ELECTRICAL CODE
Table 770-50. Cable Markings
Cable
Marking
Type
Reference
OFNP
Nonconductive optical
Sections 770-51(a)
fiber plenum cable
and 770-53(a)
OFCP
Conductive optical
Sections 770-51(a)
fiber plenum cable
and 770-53(a)
OFNR
Nonconductive optical
Sections 770-51(b)
fiber riser cable
and 770-53(b)
OFCR
Conductive optical
Sections 770-51(b)
fiber riser cable
and 770-53(b)
OFNG
Nonconductive optical
Sections 770-51(c)
fiber general-purpose cable
and 770-53(c)
OFCG
Conductive optical
Sections 770-51(c)
fiber general-purpose cable
and 770-53(c)
OFN
Nonconductive optical
Sections 770-51(d)
fiber general-purpose cable
and 770-53(c)
OFC
Conductive optical
Sections 770-51(d)
fiber general-purpose cable
and 770-53(c)
(FPN No. 1): Cable types are listed in descending order of fire resistance rating.
Within each fire resistance rating, nonconductive cable is listed first, since it may
substitute for the conductive cable.
(FPN No. 2): See the referenced sections for requirements and permitted uses.
770-51. Listing Requirements for Optical Fiber Cables and Raceways.
Optical fiber cables shall be listed in accordance with (a) through (d) below,
and optical fiber raceways shall be listed in accordance with (e) and (f)
below.
(a) Types OFNP and OFCP. Types OFNP and OFCP nonconductive
and conductive optical fiber plenum cables shall be listed as being suitable
for use in ducts, plenums, and other space used for environmental air and
shall also be listed as having adequate fire-resistant and low-smokeproducing characteristics.
(FPN): One method of defining low-smoke-producing cables is by establishing
an acceptable value of the smoke produced when tested in accordance with the Test
I
for Fire and Smoke Characteristics of Wires and Cables, NFPA 262-1990 (ANSI) to
a maximum peak optical density of 0.5 and a maximum average optical density of
0.15. Similarly, one method of defining fire-resistant cables is by defining maximum
allowable flame travel distance of 5 feet (1.52 m) when tested in accordance with the
same test.
(b) Types OFNR and OFCR. Types OFNR and OFCR nonconductive
and conductive optical fiber riser cables shall be listed as being suitable for
use in a vertical run in a shaft or from floor to floor and shall also be listed
as having fire-resistant characteristics capable of preventing the carrying of
fire from floor to floor.
(FPN): One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of
the Standard Test for Flame Propagation Height of Electrical and Öptical-Fiber
Cable Installed Vertically in Shafts, ANSI/UL 1666-1986.
ARTICLE 770 - OPTICAL FIBER CABLES AND RACEWAYS
70-785
(c) Types OFNG and OFCG. Types OFNG and OFCG nonconductive
and conductive general-purpose optical fiber cables shall be listed as being
suitable for general-purpose use, with the exception of risers and plenums,
and shall also be listed as being resistant to the spread of fire.
(FPN): One method of defining resistance to the spread of fire is for the damage
(char length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical
Flame Test - Cables in Cable Trays," as described in Test Methods for Electrical
Wires and Cables, CSA C22.2 No. 0.3-M 1985.
(d) Types OFN and OFC. Types OFN and OFC nonconductive and
conductive optical fiber cables shall be listed as being suitable for generalpurpose use, with the exception of risers, plenums, and other space used
for environmental air, and shall also be listed as being resistant to the
spread of fire.
(FPN): One method of defining resistant to the spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical-Tray Flame Test" in the
Reference Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
1581-1985.
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical Flame
Test - Cables in Cable Trays," as described in Test Methods for Electrical Wires
and Cables, CSA C22.2 No. 0.3-M 1985.
(e) Plenum Optical Fiber Raceway. Plenum optical fiber raceways shall
be listed as having adequate fire-resistant and low-smoke-producing characteristics.
(f) Riser Optical Fiber Raceway. Riser optical fiber raceways shall be
listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor.
770-52. Installation of Optical Fibers and Electrical Conductors.
(a) With Conductors for Electric Light, Power, or Class 1 Circuits.
Optical fibers shall be permitted within the same composite cable for electric light, power, or Class 1 circuits operating at 600 volts or less only
where the functions of the optical fibers and the electrical conductors are
associated. Nonconductive optical fiber cables shall be permitted to
occupy the same cable tray or raceway with conductors for electric light,
power, or Class 1 circuits operating at 600 volts or less. Conductive optical fiber cables shall not be permitted to occupy the same cable tray or
raceway with conductors for electric light, power, or Class 1 circuits. Composite optical fiber cables containing only current-carrying conductors for
electric light, power, or Class 1 circuits rated 600 volts or less shall be permitted to occupy the same cabinet, cable tray, outlet box, panel, raceway,
or other termination enclosure with conductors for electric light, power, or
Class 1 circuits operating at 600 volts or less.
Nonconductive optical fiber cables shall not be permitted to occupy the
same cabinet, outlet box, panel, or similar enclosure housing the electrical
terminations of an electric light, power, or Class 1 circuit.
Exception No. 1: Occupancy of the same cabinet, outlet box, panel, or
similar enclosure shall be permitted where nonconductive optical fiber
cable is functionally associated with the electric light, power, or Class 1
circuit.
70-786
NATIONAL ELECTRICAL CODE
Exception No. 2: Occupancy of the same cabinet, outlet box, panel, or
similar enclosure shall be permitted where nonconductive optical fiber
cables are installed in factory- or field-assembled control centers.
Exception No. 3: In industrial establishments only, where conditions of
maintenance and supervision assure that only qualified persons will service
the installation, nonconductive optical fiber cables shall be permitted with
circuits exceeding 600 volts.
Exception No. 4: In industrial establishments only, where conditions of
maintenance and supervision assure that only qualified persons will service
the installation, hybrid optical fiber cables shall be permitted to contain
current-carrying conductors operating over 600 volts.
Installations in raceway shall comply with Section 300-17.
(b) With Other Conductors. Optical fibers shall be permitted in the
same cable, and conductive and nonconductive optical fiber cables shall be
permitted in the same cable tray, enclosure, or raceway with conductors of
any of the following:
(1) Class 2 and Class 3 remote-control, signaling, and power-limited
circuits in compliance with Article 725.
(2) Power-limited fire protective signaling systems in compliance with