Regl. 5293, art. 800-40(b)
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 800-40(b)
For purposes of this section, primary protectors located at mobile home
service equipment located in sight from and not more than 30 feet (9.14 m)
from the exterior wall of the mobile home it serves, or at a mobile home
disconnecting means grounded in accordance with. Section 250-24 and
located in sight from and not more than 30 feet (9.14 m) from the exterior
wall of the mobile home it serves, shall be considered to meet the requirements of this section.
70-796
NATIONAL ELECTRICAL CODE
(FPN): Selecting a primary protector location to achieve the shortest practicable primary protector grounding conductor will help limit potential differences
between communications circuits and other metallic systems.
(c) Hazardous (Classified) Locations. The primary protector shall not
be located in any hazardous (classified) location as defined in Article 500,
nor in the vicinity of easily ignitible material.
Exception: As permitted in Sections 501-14, 502-14, and 503-12.
800-31. Primary Protector Requirements. The primary protector shall
consist of an arrester connected between each line conductor and ground
in an appropriate mounting. Primary protector terminals shall be marked to
indicate line and ground as applicable.
(FPN): One way to determine applicable requirements for a listed primary protector is to refer to the Standard for Protectors for Communications Circuits,
ANSI/UL 497-1978.
800-32. Secondary Protector Requirements. Where a secondary protector is installed in series with the indoor communications wire and cable
between the primary protector and the equipment, it shall be listed for the
purpose. The secondary protector shall provide means to safely limit currents to less than the current-carrying capacity of listed indoor communications wire and cable, listed telephone set line cords, and listed communications terminal equipment having ports for external wire line
communications circuits. Any overvoltage protection, arresters, or
grounding connection shall be connected on the equipment terminals side
of the secondary protector current-limiting means.
(FPN No. 1): One way to determine applicable requirements for a listed secondary protector is to refer to the Standard for Secondary Protectors for Communications, UL497A-1990.
(FPN No. 2): Secondary protectors on exposed circuits are not intended for use
without primary protectors.
800-33. Cable Grounding. The metallic sheath of communications cables
entering buildings shall be grounded as close as practicable to the point of
entrance or shall be interrupted as close to the point of entrance as practicable by an insulating joint or equivalent device.
For purposes of this section, the point of entrance shall be considered to
be at the point of emergence through an exterior wall, a concrete floor slab,
or from a rigid metal conduit or an intermediate metal conduit grounded to
an electrode in accordance with Section 800-40(b).
D. Grounding Methods
800-40. Cable and Primary Protector Grounding. The metallic member(s) of the cable sheath, where required to be grounded by Section
800-33, and primary protectors shall be grounded as specified in (a)
through (d) below.
(a) Grounding Conductor.
(1) Insulation. The grounding conductor shall be insulated and shall be
listed as suitable for the purpose.
ARTICLE 800 - COMMUNICATIONS CIRCUITS
70-797
(2) Material. The grounding conductor shall be copper or other
corrosion-resistant conductive material, stranded or solid.
(3) Size. The grounding conductor shall not be smaller than No. 14.
(4) Run in Straight Line. The grounding conductor shall be run to the
grounding electrode in as straight a line as practicable.
(5) Physical Damage. Where necessary, the grounding conductor
shall be guarded from physical damage. Where the grounding conductor is
run in a metal raceway, both ends of the raceway shall be bonded to the
grounding conductor or the same. terminal or electrode to which the
grounding conductor is connected.
(b) Electrode. The grounding conductor shall be connected as follows:
(1) To the nearest accessible location on (1) the building or structure
grounding electrode system as covered in Section 250-81, (2) the grounded
interior metal water piping system as covered in Section 250-80(a), (3) the
power service accessible means external to enclosures as covered in
Section 250-71(b), (4) the metallic power service raceway, (5) the service
equipment enclosure, (6) the grounding electrode conductor or the grounding electrode conductor metal enclosure, or (7) to the grounding conductor
or the grounding electrode of a building or structure disconnecting means
that is grounded to an electrode as covered in Section 250-24.
For purposes of this section, the mobile home service equipment or the
mobile home disconnecting means, as described in Section 800-30(b), shall
be considered accessible.
(2) If the building or structure served has no grounding means, as
described in b(1), to any one of the individual electrodes described in