Regl. 1277, art. 111.8a dup2

Reglamento General de Seguridad e Higiene Industrial, Cap. IV -- Ascensores de personas. No incluido en el índice bajo Ley 149 de 12 dic, 2005

Last amended: 2005Length: 146 wordsOfficial source

Cite as Reglamento Núm. 1277, Art. 111.8a dup2

Interlocks. Hoistway doors shall be considered to be in the closed position under the following conditions. 1. For horizontally sliding or swinging doors, or vertically sliding counterweighted doors: a. Only when the leading edge of the door is within four (4) inches of the nearest face of the jamb or when the door panels of bi-parting type doors are within four (4) inches of contact with each other, provided that: (1) The car is being operated USAS, A17.1 from within the car only. Ibid (2) The doors are of the horizontally sliding type. (3) The doors are power closed or equipped with doors closers (4) The hoistway-door interlock is provided with means to lock 35 TEXTO EN ESPAÑOL Excepción: Los artículos 4 y 5 son aplicables solamente cuando la leva de retroceso de un dispositivo inmovilizador sea requerido (Vea Regla 111.3c y la definición 3.31d) Ibid