Regl. 1277, art. 111.8b

Reglamento General de Seguridad e Higiene Industrial, Cap. IV -- Ascensores de personas. No incluido en el índice bajo Ley 149 de 12 dic, 2005

Last amended: 2005Length: 177 wordsOfficial source

Cite as Reglamento Núm. 1277, Art. 111.8b

bination Mechanical Lock and Electric Contacts, or with Hoistway-Door Electric Contacts. Hoistway-doors provided with hoistway-door combination mechanical locks and electric contacts, and hoistway doors provided with hoistway door electric contacts, shall be considered to be in the closed position under the following conditions: 1. For horizontally sliding or swinging doors, when the clear open space between the leading edge of the door and the nearest face of the door jamb does not exceed two (2) inches. 2. For vertically counterweighted doors, when the clear open space between the - 38 - ENGLISH TEXT leading edge of the door and the landing sill does not exceed two (2) inches. 3. For center-opening bi-parting horizontally sliding doors or bi-parting vertically sliding counterbalanced doors, when the door panels are within two (2) inches of contact with each other. 4. For center-opening horizontally swinging doors, when the clear open space between each panel and its jamb does not exceed two (2) inches; provided that if a hoistwaydoor electric contact is used on the door panel which open last (See Section 111,