Hoistway Doors with Car Door or Gates.
112.6a - Where Required
Art. 112.6a
Sequence operations shall be provided under the
following conditions:
*1. Sequence opening and closing shall be
provided for power-operated vertically
sliding bi-parting counterbalanced or poweroperated vertically sliding hoistway doors
which slide down to open, where used on passenger elevators or on freight elevators
permitted to carry employees (See Part II,
Section 207.4) in conjuction with a poweroperated vertically sliding car door or
gate.
Exception: Doors at openings used exclusively for
freight.
2. Sequence closing shall be provided for
power operated vertically sliding hoistway
doors and vertically sliding car doors or
gates which are closed by momentary pressure or by timing device.
112.6b* - Operating Requirements
112.6b
The sequence operation of a hoistway door and
adjacent power-operated vertically sliding car door
or gate shall conform to the following:
1. In opening, the hoistway door shall be
opened at least two thirds (2/3) of its
travel before the car door or gate can
start to open.
USAS, A17.1
Ibid
2. In closing, the car door or gate shall be
112.6 b
closed at least two thirds (2/3) of its
travel before the hoistway door car start
to closed.