5. Shell Seams
1/4 inch
0.250
6.35
0.240
6.10
5.1
A shell seam of a tank shall be one of the
forms shown by Figure 5.1.
7
0.179
4.55
0.167
4.24
9
0.150
3.81
0.138
3.51
5.2
Shell seam No. 4 shall not be used on tanks
10
0.135
3.43
0.123
3.12
larger than 96 inches (2.44 m) in diameter.
12
0.105
2.67
0.093
2.36
14
0.075
1.91
0.067
1.70
5.3
Shell seam No. 7 shall not be used on tanks
larger than 65 inches (1.65 m) in diameter.
FIGURE 5.1
SHELL SEAMS
C
C
D
CF
C
B
CF
NO. I-ALL DIAM.
NO. 2-ALL DIAM.
NO. 3-ALL DIAM.
3.E MIN.
D
E
C
CF
CF
T
1/2"
MIN.
NO.4-MAX. DIAM. 96"
NO.5-ALL DIAM.
NO. 6-ALL DIAM.
5/32" (4.0mm)
C
Min. Separation
D
CF
t-2
I-1/2" Min.
T
(38.1 mm)
NO. 7-MAX, DIAM. 65"
TA48-4
NO.8-ALL DIAM.
B - Overlap - 1/2 inch (12.7 mm) minimum.
E - 1/2 inch (12.7 mm) minimum diameter lock weld, not over 12
C
- Continuous welds.
inches (305 mm) apart.
CF - All lap welds shall be continuous full fillet welds.
T
-
D - Overlap - 1/2 inch (12.7 mm) minimum for diameters 48 inches
Tack weld 1 inch (25 mm) spots, not over 12 inches (305 mm)
apart.
(1.2 m) or less;3/4 inch (19.1 mm) minimum for diameters over
48 inches (1.2 ml.
t - Thickness of backup bar to be same as shell thickness.
Figure 6.1 revised November 28, 1977
*Replaces page 6 dated October 29, 1976
COPYRIGHT © 1976, 1977 UNDERWRITERS LABORATORIES INC.
OCTOBER 29, 1976
STEEL UNDERGROUND TANK FOR FLAMMABLE AND OMBUSTIBLE LIQUIDS - UL 58
7
6. Heads and Head Joints
6.2
A head of a tank may be flat, dished, or
conical.
6.1
A head of a tank shall be fabricated of not
more than two pieces for diameters of 48 inches
6.3
A head of a tank shall be attached to the
(1.22 m) or less; three pieces for diameters of from
shell by one of the joints shown by Figure 6.1.
49 to 96 inches (1.24 to 2.44 m); and four pieces
for diameters of from 97 to 144 inches (2.46 to
6.4 An unflanged flathead of a tank shall be
3.66 m). When two or more pieces are used, seams
braced in accordance with Figure 6.2, No. 1 or 2,
shall be one of the forms shown by Figure 5.1,
and the head and shell shall be made of not less
observing the diameter limits as noted.
than No. 7 gage (see Table 4.1) material.
FIGURE 6.1
HEADS AND HEAD JOINTS FOR ALL
DIAMETER TANKS
B
C
C
CF
C
F
NO.10
NO.11
NO. 12
8
C
C
CF
C
NO. 13
NO.14
NO.15
F
C
B
B
C
B
CF
F
F
F
NO. 16
NO. 17
NO. 18
t
t
CF
t
CF
CF
F
F
J
NO. I9
NO.20
NO.21
B
B
1
CF
CF
CF
T
K
CF
F
F
TA48-2
NO.22
NO.23
NO.24
K - Joint No. 22 - Heads require bracing. (see No. 1 and 2 of Figure
B - Overlap - 1/2 inch (12.7 mm) minimum.
6.2). Minimum Gage No. 7, (0.179 inch) (4.55 mm) nominal.
C
- Continuous welds.
T
- Tack weld 1 inch (25 mm) spots, not over 12 inches (305 mm)
apart.
CF - Shall be continuous full fillet welds.
t - Minimum, 1 X shell thickness.
F
- Not less than five times head thickness - minimum 1/2 inch
(12.7 mm).
Heads may be fiat, dished, or cone.
Height of cone heads - not less than one-tweifth
J
- Joint No. 21 - Minimum Gage No. 7, (0.179 inch) (4.55 mm)
diameter.
nominal.
Height of dished heads shall conform to Table 6.1.
8
STEEL UNDERGROUND TAN
OR FLAMMABLE AND COMBUSTIBLE LIQUIDS
JL 58
OCTOBER 29, 1976
FIGURE 6.2
BRACING FOR UNFLANGED FLAT HEADS AND
BULKHEADS
C-Weld.
S-From center, approximately 1/4 of
U
diameter.
V
is
U-Weld three sides
W
each foot.
C
V-Bracing.
W-Minimum length
of foot.
W
NO. 1
Not greater
than 45°
See Table 6.2
V
T-Tack welds, not
X
X
over 12 inches (305 mm)
T
T
apart.
X
X
V-Bracing.
T
X-Not over 2 inches (51 mm)
X
X
from shell.
NO. 2
See Table 6.3
BRACING FOR FLANGED FLAT BULKHEADS
T-Tack welds, not
over 12 inches (305 mm)
apart.
T
X-Not over 2 inches (51 mm)
from shell.
X
X
Y-Bracing (locate 6
inches (150 mm)
below center of head).
NO. 3
TA 44-1
See Table 6.4
TABLE 6.1
TP-5
DISHED HEADS - MINIMUM HEIGHT
Diameter
Minimum Dish
Diameter
Minimum Dish
Inches
m
Inches
mm
Inches
m
Inches
mm
Up to 60
Up to 1.52
1-1/2
38
97-108
2.46-2.74
4-1/2
114
61-72
1.55-1.83
2
51
109-120
2.77-3.05
5-1/2
140
73-84
1.85-2.13
2-1/2
64
121-132
3.07-3.35
I
7
178
85-96
2.16-2.44
3-1/2
89
133-144
3.38-3.66
8
203
OCTOBER 29, 1976
STEEL UNDERGROUND TANK FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - UL 58
9
NOTE - The use of standard S.I. (metric) sizes and weights of angles, channels, and I-beams as substitutes for
the U.S.A. structural units specified in Tables 6.2, 6.3, and 6.4 shall be based on those sizes and weights having
an equal or greater section modulus (S).
TABLE 6.2
STRUT BRACING FOR UNFLANGED FLAT HEADS AND BULKHEADSᵃ
TP-2
Diameter Head
Channels
Angles
wa
Section Modulus(s)
Section Medulus(s)
Inches
m
Size, Inches
In.³
Size, Inches
In.³
Inches
mm
Up to - 60
Up to 1.52
1 by 3/8 by 1/8
0.048ᵇ
1 by 1 by 1/8
0.031
1
25.0
61-72
1.55-1.83
1 by 3/8 by 1/8
0.048ᵇ
1-1/4 by 1-1/4 by 1/8
0.049
1-1/4
32.0
73-84
1.85-2.13
1 by 1/2 by 1/8
0.063b
1-1/2 by 1-1/2 by 1/8
0.072
1-1/2
38.0
85-96
2.16-2.44
1 by 1/2 by 1/8
0.063°
1-3/4 by 1-3/4 by 3/16
0.140
1-3/4
44.0
97-108
2.46-2.74
1-1/2 by 3/4 by 1/8
0.147ᵇ
2 by 2 by 3/16
0.190
2
51.0
109-120
2.77-3.05
3 inches - 4.1 pounds
1.15
2 by 2 by 1/4
0.250
2
51.0
121-132
3.07-3.35
3 inches - 4.1 pounds
1.1°
2-1/2 by 2-1/2 by 5/16
0.480
2-1/2
64.0
133-144
3.38-3.66
3 inches - 4.1 pounds 1.1°
2-1/2 by 2-1/2 by 5/16
0.480
2-1/2
64.0
a
See Figure 6.2, No. 1.
b
Flange of channel welded to head or bulkhead and shell.
TABLE 6.3
SURFACE BRACING FOR UNFLANGED FLAT HEADS AND BULKHEADSᵃ
TP-3
Diameter Head
Channels
Angles
Section Modulus(s)
Min. Section Modulusis)
Inches
m
Size
In.3
Sizes, Inches
In.3
Up to 60
Up to 1.52
3 inches - 4.1 pounds
1.1ᵇ
2 by 2 by 3/8 or
0.35
2-1/2 by 2-1/2 by 1/4
61-72
1.55-1.83
3 inches - 4.1 pounds
1.1b
3 by 3 by 7/16 or
0.95
3-1/2 by 3-1/2 by 5/16
73-84
1.85-2.13
4 inches - 5.4 pounds
1.9b
3-1/2 by 3-1/2 by 1/2 or
1.50
4 by 4 by 3/8
85-96
2.16-2.44
5 inches - 6.7 pounds
3.0b
4 by 4 by 1/2 or
2.00ᵇ
5 by 3-1/2 by 3/8
97-108
2.46-2.74
5 inches - 6.7 pounds
3.0ᵇ
4 by 4 by 3/4 or
2.80b
6 by 4 by 3/8
109-120
2.77-3.05
6 inches - 8.2 pounds
4.3b
5 by 5 by 5/8 or
3.90b
6 by 4 by 1/2
121-132
3.07-3.35
7 inches - 9.8 pounds
6.0ᵇ
5 by 5 by 3/4 or
4.50b
6 by 4 by 9/16
133-144
3.38-3.66
7 inches - 9.8 pounds
6.0ᵇ
5 by 5 by 3/4 or
4.50ᵇ
6 by 4 by 9/16
a
See Figure 6.2, No. 2.
b
Short leg of angle or flange of channel welded to head or bulkhead.
10
STEEL UNDERGROUND TAR
OR FLAMMABLE AND COMBUSTIBLE LIQUID
UL 58
OCTOBER 29, 1976
TABLE 6.4
SURFACE BRACING FOR FLANGED FLAT BULKHEADSᵃ
TP-4
Diameter Head
I-Beams
Channels
Section Modulus(s)
Section Modulus(s)
Inches
m
Size
In.³
Size
In.3
72-84
1.83-2.13
3 inches - 5.7 pounds
1.7b
3 inches 4.1 pounds
1.1b
85-96
2.16-2.44
3 inches - 5.7 pounds
1.7ᵇ
4 inches - 5.4 pounds
1.9b
97-108
2.46-2.74
4 inches - 7.7 pounds
3.0ᵇ
5 inches - 6.7 pounds
3.0ᵇ
109-120
2.77-3.05
5 inches - 10 pounds
4.8b
5 inches - 6.7 pounds
3.0b
121-132
3.07-3.35
5 inches - 10 pounds
4.8b
6 inches - 8.2 pounds
4.3ᵇ
133-144
3.38-3.66
5 inches 10 pounds
4.8b
6 inches - 8.2 pounds
4.3b
a
See Figure 6.2, No. 3.
b Flange of 1-beam or channel welded to bulkhead.
6.5
A flanged flathead of a tank is not required
7.3
A bulkhead of a double bulkhead tank,
to be braced.
shown by No. 100, Figure 7.1, shall be fabricated
of not more than two pieces for diameters of 48
6.6 A conical head of a tank shall have a height
inches (1.22 m) or less; three pieces for diameters
of not less than one-twelfth the diameter of the
of from 49 to 96 inches (1.24 to 2.44 m); and four
tank.
pieces for diameters of from 97 to 144 inches
(2.46 to 3.66 m). When two or more pieces are
6.7
A dished head shall have a dish height of
used, seams shall be one of the forms shown by
not less than that specified in Table 6.1.
Figure 5.1, observing the diameter limits as noted.
7.4 The thickness of metal employed for a
bulkhead depends upon its diameter and shall be
not less than that specified in Table 3.1.
7. Compartment Tanks
7.5 An unflanged flat bulkhead of a compartment tank shall be braced in accordance with
7.1
Bulkheads of compartment tanks shall be of
Figure 6.2, No. 1 or 2, and shall be made of not
such construction that any leakage through joints
less than No. 7 gage (see Table 4.1) material.
will be directed to the outside of the tank rather
than from one compartment to another. See Figure
7.6
A flanged flat bulkhead of a compartment
7.1 for acceptable bulkhead constructions.
tank more than 72 inches (1.83m) in diameter shall
be made of not less than 5/16-inch (see Table 4.1)
7.2
A single bulkhead of a compartment tank,
thick material or it shall be braced in accordance
shown by Nos. 101 and 102, Figure 7.1, shall be
with Figure 6.2, No. 3.
fabricated of one piece of material and may be flat
or dished. The height of a dished bulkhead shall be
7.7
A flanged flat bulkhead 72 inches (1.83 m)
not less than that specified in Table 6.1.
or less in diameter does not require bracing.
OCTOBER 29, 1976's
STEEL UNDERGROUND TANK FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - UL 58
11
FIGURE 7.1
BULKHEADS FOR COMPARTMENT TANKS
A
NO. 100
FLANGE FOR TESTING
C
B
A
D
Straight Flange
Tangent line on head
NO. IOI
E
TA44-3
NO. 102
t MIN.
A - Bracing as per Table 6.4 if diameter exceeds 72 inches (1.8 ml
B - 1/2 inch (12.7 mm)
C - 3/4 inch (19.1 mm)
D - - 1-1/4 inch (31.8 mm)
E - Bracing as per Table 6.2 or 6.3
12
STEEL UNDERGROUND TAN
OR FLAMMABLE AND COMBUSTIBLE LIQUIDS
JL 58
OCTOBER 29, 1976
8. Pipe Connections
8.3
Pipe-connecting fittings shall be of steel of a
good welding quality. The minimum length of
8.1
Pipe connections shall be supplied by
thread shall conform to the values specified by
welding to the tank, standard threaded pipe
Table 8.1.
couplings, substantial threaded flanges, standard
half pipe nipples, or by bolted and gasketed
8.4
Pressed-steel pipe-connecting fittings shall
flanged connections welded to pipe nipples which,
be installed with the hub section on the inside of
in turn, are welded to the tank.
the tank only and of the form shown by No. 62,
Figure 8.1. The thickness of the flange section shall
8.2
Conventional types of pipe connections are
be as specified in Table 8.1 with tolerances as
illustrated by Figure 8.1.
permitted by Table 4.1.
FIGURE 8.1
PIPE CONNECTIONS
NO.60
NO.61
NO.62
NO.63
NO. 65
NO. 64
NO. 66
NO. 67
TA45-1
All welds shall be full fillet welds.
No. 60 - Half pipe coupling.
No. 61 - Half pipe coupling.
No. 62 - Pressed steel, hub inside tank only.
No. 63 - Forged steel, hub inside tank.
No. 64 - Full pipe coupling.
No. 65 - Forged steel, with pilot.
No. 66 - Forged steel, without pilot.
No. 67 - Standard pipe nipple and welding flange.
OCTOBER 29, 1976
STEEL UNDERGROUND TANK FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS - UL 58
13
TABLE 8.1
PIPE CONNECTIONS
TP-6
Thickness of Flange Section of Pressed-Steel
Pipe Sizea Nominal
Minimum Length of Thread
Fittings
Inches
Inches
mm
Gage No.
Nominal, Inches
mm
1/8
1/4
6.4
1/4
3/8
9.5
3/8
3/8
9.5
1/2
1/2
12.7
3/4
5/8
15.9
10
0.135
3.4
1
5/8
15.9
9
0.150
3.8
1-1/4
11/16
17.5
9
0.150
3.8
1-1/2
3/4
19.1
9
0.150
3.8
2
3/4
19.1
9
0.150
3.8
2-1/2
1
25.4
7
0.179
4.6
3
1
25.4
7
0.179
4.6
3-1/2
1
25.4
7
0.179
4.6
4
1-1/8
28.6
7
0.179
4.6
5
1-3/16
30.2
6
1-1/4
31.7
8
1-3/8
34.9
a
American Standard, ANSI 836.10.
8.5
Half pipe nipples shall be welded to the
8.10 Each tank shall have a pipe connection of a
tank as shown by No. 67, Figure 8.1.
size not less than that specified in Table 8.2 for
attachment of a vent pipe.
8.6
Except as indicated in paragraphs 8.7 and
8.8, all openings in a tank shall be located in the
8.11
An opening for connection of a vent pipe
top, parallel with the longitudinal axis of the tank.
shall not be located in a manhole cover.
8.7
If the application of a tank is such that
pipe-connecting openings in the top are required to
be grouped, the openings may be located off center
of the longitudinal axis under the conditions
TABLE 8.2
SIZE OF VENT-PIPE FITTING
specified in paragraph 8.8.
TP-7
8.8
No opening in the shell of a tank shall be
Capacity of Tank,
U.S. Gallons
dm³
Pipe Sizeᵃ Nominal
located more than 12 inches (305 mm) from the
Inches
longitudinal center line of the top, and the upper
end of the pipe coupling or other pipe-connecting
0 to 500
Up to 1,895
1-1/4
fitting welded to the tank shall terminate above the
501 to 3,000
1,900 to 11,355
1-1/2
top of the shell.
3,001 to 10,000
11,360 to 37,855
2
10,001 to 20,000
37,860 to 75,710
2-1/2
20,001 to 35,000
75,715 to 132,490
3
8.9
All openings in a tank shall be closed with
35,001 to 50,000
132,495 to 189,270
4
wooden plugs, metal covers, or their equivalent, to
protect the threads and exclude foreign matter
a
American Standard, ANSI B36.10.
while in storage or in transit.
14
STEEL UNDERGROUND TA
OR FLAMMABLE AND COMBUSTIBLE LIQUID
UL 58
OCTOBER 29, 1976
9. Manholes
9.2 A manhole-cover joint shall be provided
with a gasket of material determined to be suitable
9.1
A manhole, if provided in a tank, shall be
for the liquid to be stored and shall have a
located above the highest normal liquid level and
thickness of not less than 1/8 inch (3.2 mm).
shall be of the bolted-cover type as shown by
Figure 9.1.
FIGURE 9.1
CONVENTIONAL MANHOLES
Q
P
R
CF
t
NO.90
Q
t
P
R
CF
NO.91
Q
t
P
R
CF
NO.92
Q
t
P
ALTERNATE
COLLARS
C
CF
CF
R
CF
CF
NO. 93
NO.94
NO.95
TA48-3
CF
-
Continuous full fillet weld.
P
- Gasket material, 1/8 inch (3.2 mm) thick minimum - ring or
face gasket.
Q
- Minimum, 1/2 inch (12.7 mm) bolts spaced 4 inch (102 mm)
centers maximum.
R
- Minimum, 2 inches (51 mm) for tanks 6 feet (1.8 m) in diameter
or larger.
t
- Not less than No. 7 gage (0.179 inch) (4.55 mm) nominal.
OCTOBER 29; 1976
STE
UNDERGROUND TANK FOR FLAMMABLE AN
OMBUSTIBLE LIQUIDS - UL 58
15
10. Heating Coils and Hot Wells
B. By completely filling the tank with water
and applying an additional 5 psig (34.5 kPa)
10.1 A heating coil or hot well, if provided as a
pressure. When using this method, the tank is to
part of a tank assembly and if handling a fluid
be placed in the position in which it will be
other than that stored in the tank, such as steam or
installed.
hot water, shall have no joints in that portion
located within the tank unless such joints are
11.2 If leaks are noted during the test, the tank
continuously welded or brazed.
shall be made tight by welding and retested.
Defects in welds shall be repaired by chipping or
10.2 Inlet and outlet connections of a heating
melting out from one or both sides of the joint, as
coil or a hot well shall be located above the highest
required, and rewelding.
normal liquid level. A continuous weld shall be
made where a connection pierces the shell of the
11.3 Each compartment of compartment tanks
tank or a manhole cover.
shall be separately tested for leakage.
MANUFACTURING AND PRODUCTION
TESTS
MARKING
11. General
12. General
11.1 Each tank, before painting, shall be tested
by the manufacturer and proved tight against
12.1 Each tank shall be marked with the name of
leakage in accordance with one of the following
the manufacturer or a distinctive marking, which
methods:
may be in code, by which it may be identified as
the product of a particular manufacturer.
A. By applying internal air pressure and using
soapsuds, linseed oil, or equivalent material for
12.2 If a manufacturer produces tanks at more
the detection of leaks. The test pressure is to be
than one factory, each tank shall have a distinctive
not less than 5 nor more than 7 pounds per
marking to identify it as the product of a
square inch gauge (psig) (34.5-48.3 kPa).
particular factory.
16
STEEL UNDERGROUND TAN OR FLAMMABLE AND COMBUSTIBLE LIQUIDS UL
58
OGTOBER 29, 1976
APPENDIX A
TABLE I
TABLE Il
TD-3
GALLON CAPACITY PER FOOT OF LENGTH
LITER CAPACITY PER METER
TD-4
OF LENGTH
Dia-
U.S.
Dia-
U.S.
Dia-
U.S.
meter
Gallons
meter
Gallons
meter
Gallons
in
1-Foot
in
1-Foot
in
1-Foot
Diameter in mm
Liters (dm3) 1-meter Length
Inches
Length
Inches
Length
Inches
Length
600
282.7
24
23.50
65
172.38
105
449.82
700
384.8
25
25.50
66
177.72
800
502.7
106
458.30
26
67
900
636.2
27.58
183.15
107
467.70
1000
785.4
27
29.74
68
188.66
108
475.89
1100
958.2
28
31.99
69
194.25
109
485.00
1200
1131.0
29
34.31
70
199.92
110
493.70
1300
1327.3
30
36.72
71
205.67
111
502.70
1400
1539.4
31
39.21
72
211.51
112
511.90
1500
1767.2
32
41.78
73
217.42
113
521.40
1600
2010.6
33
44.43
74
223.42
114
530.24
1700
2269.8
34
47.16
75
229.50
115
540.00
1800
2544.7
35
49.98
76
235.66
116
549.50
1900
2835.3
36
52.88
77
241.90
117
558.51
2000
3141.6
37
55.86
78
248.23
118
568.00
2100
3463.6
38
58.92
79
254.63
119
577.80
2200
3801.3
39
62.06
80
261.12
120
587.52
2300
4154.8
40
65.28
81
267.69
121
597.70
2400
4523.9
41
68.58
82
274.34
122
607.27
2500
4908.8
42
71.97
83
281.07
123
617.26
2600
5309.3
43
75.44
84
287.88
124
627.00
2700
5725.6
44
78.99
85
294.78
125
638.20
2800
6157.5
45
82.62
86
301.76
126
647.74
2900
6605.2
46
86.33
87
308.81
127
658.60
3000
7068.6
47
90.13
88
315.95
128
668.47
3100
7547.7
48
94.00
89
323.18
129
678.95
3200
8042.5
49
97.96
90
330.48
130
690.30
3300
8553.0
50
102.00
91
131
700.17
3400
9079.2
337.86
51
92
3500
9621.2
106.12
345.33
132
710.90
3600
10178.8
52
110.32
93
352.88
133
721.71
3700
10752.1
53
114.61
94
360.51
134
732.60
3800
11341.2
54
118.97
95
368.22
135
743.58
55
123.42
96
376.01
136
754.64
56
127.95
97
383.89
137
765.78
57
132.56
98
391.84
138
776.99
58
137.25
99
399.88
139
788.30
59
142.02
100
408.00
140
799.68
60
146.88
101
416.00
141
811.14
61
151.82
102
424.48
142
822.69
62
156.83
103
433.10
143
834.32
63
161.93
104
441.80
144
846.03
64
167.12