Regl. 7470, art. 171.2-2.00 dup2
Phosphorus (max)
Cite as Reglamento Núm. 7470, Art. 171.2-2.00 dup2
.030
.045
.030
.030
Sulphur (max)
.030
.030
.030
.030
Silicon (max)
.75
1.00
.75
.75
Nickel
8.0/11.0
10.0/14.0
9.0/13.0
9.0/13.0
Chromium
18.0/20.0
16.0/18.0
17.0/20.0
17.0/20.0
Molybdenum
2.0/3.0
Titanium
(')
Columbium
(2)
1 Titanium may not be less than 5C and not more than 0.60%
2 Columbium may not be less than 10C and not more than 1.0%.
TABLE 3-CHECK ANALYSIS TOLERANCES
Tolerance (percent) over
the maximum limit or
Element
Limit or maximum specified
under the minimum limit
(percent)
Under min-
Over maximum limit
imum limit
Carbon
To 0.15 Incl
0.01
0.01
Over 0.15 to 0.40 incl
.03
.04
Manganese
To 0.60 incl
.03
.03
Over 1.15 to 2.50 incl
.05
.05
Phosphorus 1
All ranges
.01
Sulphur
All ranges
.01
Silicon
To 0.30 incl
.02
.03
Over 0.30 to 1.00 incl
.05
.05
Nickel
Over 5.30 to 10.00 incl
.10
.10
Over 10.00 to 14.00 incl
.15
.15
Chromium
To 0.90 ind
.03
.03
Over 0.90 to 2.10 incl
.05
.05
Over 15.00 to 20.00 incl
.20
.20
866
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.53
TABLE 3-CHECK ANALYSIS TOLERANCES-Confinued
Tolerance (percent) over
the maximum limit or
Limit or maximum specified
under the minimum limit
Element
(percent)
Under min-
Over maximum limit
Imum limit
Molybdenum
To 0.20 Incl
.01
.01
Over 0.20 to 0.40 incl
.02
.02
Over 1.75 to 3.0 incl
.10
.10
Titanium
All ranges
.05
.05
Columbium
All ranges
.05
.05
1 Rephosphorized steels not subject to check analysis for phosphorus.
(c) Identification of material. Material
E = 1.0 (for all other areas).
must be identified by any suitable
(2) Calculation for a cylinder must be
method except that plates and billets
made by the formula:
for hotdrawn cylinders must be marked
with the heat number.
S = [P(1.3D² + 0.4d²)] / (D² - dT¹²)
(d) Manufacture. Cylinders must be
Where:
manufactured using equipment and
S = wall stress in psi;
processes adequate to ensure that each
P = test pressure prescribed for water jacket
cylinder produced conforms to the retest, i.e., at least two times service presquirements of this subpart. No defect is
sure, in psig;
permitted that is likely to weaken the
D = outside diameter in inches;
finished container appreciably. A rea-
d = inside diameter in inches.
sonably smooth and uniform surface
(f) Heat treatment. The completed cylfinish is required. Welding procedures
inders must be uniformly and properly
and operators must be qualified in acheat-treated prior to tests.
cordance with CGA Pamphlet C-3 (IBR,
(g) Openings in container. Openings in
see $171.7 of this subchapter).
cylinders must comply with the fol-
(e) Wall thickness. The wall stress at
lowing:
the minimum test pressure may not ex-
(1) Each opening in the container, exceed 24,000 psi, except where steels
cept those for safety devices, must be
commercially known as 4130X, types
provided with a fitting, boss, or pad, se-
304, 316, 321, and 347 stainless steels are
curely attached to the container by
used, stress at the test pressures may
brazing or by welding or by threads. If
not exceed 37,000 psi. The minimum
threads are used, they must comply
wall thickness for any container havwith the following:
ing a capacity of 1,100 cubic inches or
(i) Threads must be clean cut, even,
less is 0.04 inch. The minimum wall
without checks, and tapped to gauge.
thickness for any container having a
(ii) Taper threads must be of a length
capacity in excess of 1,100 cubic inches
not less than that specified for Ameris 0.095 inch. Calculations must be done
ican Standard taper pipe threads.
by the following:
(iii) Straight threads, having at least
(1) Calculation for a "sphere" must
4 engaged threads, must have a tight
be made by the formula:
fit and calculated shear strength of at
least 10 times the test pressure of the
S = PD / 4tE
container. Gaskets, adequate to pre-
Where:
vent leakage. are required.
S = wall stress in psi;
(2) Closure of a fitting, boss, or pad
P = test pressure prescribed for water jacket
must be adequate to prevent leakage.
test, i.e., at least two times service pres-
(h) Hydrostatic test. Each cylinder
sure, in psig;
must successfully withstand a hydro-
D = outside diameter in inches;
static test, as follows:
t - minimum wall thickness in inches;
(1) The test must be by water-jacket,
E = 0.85 (provides 85 percent weld efficiency
or other suitable method, operated so
factor which must be applied in the girth
weld area and heat affected zones which
as to obtain accurate data. A pressure
zone must extend a distance of 6 times wall
gauge must permit a reading to an acthickness from center line of weld):
curacy of 1 percent. An expansion
867
$ 178.53
49 CFR Ch. I (10-1-06 Edition)
gauge must permit reading of total ex-
(1) Physical test for spheres are repansion to an accuracy of either 1 perquired on 2 specimens cut from a flat
cent or 0.1 cubic centimeter.
representative sample plate of the
(2) Pressure must be maintained for
same heat taken at random from the
at least 30 seconds and sufficiently
steel used to produce the sphere. This
longer to ensure complete expansion.
flat steel from which the 2 specimens
Any internal pressure applied after
are to be cut must receive the same
heat-treatment and previous to the ofheat-treatment as the spheres themficial test may not exceed 90 percent of
selves. Sample plates must be taken for
the test pressure. If, due to failure of
each lot of 200 or less spheres.
the test apparatus, the test pressure
(2) Specimens for spheres must have
cannot be maintained, the test may be
a gauge length 2 inches with a width
repeated at a pressure increased by 10
not over 1½ inches, or a gauge length
percent or 100 psig. whichever is the
at least 24 times the thickness with a
lower.
width not over 6 times the thickness is
(3) Permanent volumetric expansion
authorized when a wall is not over 3/16
may not exceed 10 percent of the total
inch thick.
volumetric expansion at test pressure.
(3) Physical test for cylinders is re-
(4) Containers must be tested as folquired on 2 specimens cut from 1 cyllows:
inder taken at random out of each lot
(i) Each container to at least 2 times
of 200 or less. For lots of 30 or less,
service pressure; or
physical tests are authorized to be
(ii) One container out of each lot of
made on a ring at least 8 inches long
200 or less to at least 3 times service
cut from each cylinder and subjected to
pressure. Others must be examined
the same heat treatment as the finunder pressure of 2 times service presished cylinder.
sure and show no defects.
(4) Specimens for cylinders must con-
(i) Flattening test for spheres and cylform to the following:
inders. Spheres and cylinders must be
(i) A gauge length of 8 inches with a
subjected to a flattening test as folwidth not over 1½ inches, or a gauge
lows:
length of 2 inches with a width not
(1) One sphere taken at random out
over 1½ inches, or a gauge length at
of each lot of 200 or less must be subleast 24 times the thickness with a
jected to a flattening test as follows:
width not over 6 times the thickness is
(i) The test must be performed after
authorized when a cylinder wall is not
the hydrostatic test.
over 3/15 inch thick.
(ii) The test must be between parallel
(ii) The specimen, exclusive of grip
steel plates on a press with a welded
ends. may not be flattened. Grip ends
seam at right angles to the plates. Any
may be flattened to within 1 inch of
projecting appurtenances may be cut
each end of the reduced section. Heatoff (by mechanical means only) prior to
ing of the specimen for any purpose is
crushing.
not authorized.
(2) One cylinder taken at random out
(5) The yield strength in tension
of each lot of 200 or less must be submust be the stress corresponding to a
jected to a flattening test, as follows:
permanent strain of 0.2 percent of the
(i) The test must be performed after
gauge length. The following conditions
the hydrostatic test.
apply:
(ii) The test must be between knife
(i) The yield strength must be deteredges, wedge shaped, 60° angle, rounded
mined by either the "offset" method or
to 1/2 inch radius. For lots of 30 or less,
the "extension under load" method as
physical tests are authorized to be
prescribed in ASTM E 8 (IBR, see $171.7
made on a ring at least 8 inches long
of this subchapter).
cut from each cylinder and subjected to
(ii) In using the "extension under
the same heat treatment as the finload" method, the total strain (or "exished cylinder.
tension under load") corresponding to
(j) Physical test and specimens for
the stress at which the 0.2 percent perspheres and cylinders. Spheres and cylmanent strain occurs may be deterinders must be subjected to a physical
mined with sufficient accuracy by caltest as follows:
culating the elastic extension of the
868
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.55
gauge length under appropriate load
The maximum water capacity of this
and adding thereto 0.2 percent of the
cylinder is 12 pounds or 333 cubic
gauge length. Elastic extension calinches and the service must be 240 psig.
culations must be based on an elastic
The maximum outside diameter of the
modulus of 30,000,000. In the event of
shell must be five inches and maximum
controversy, the entire stress-strain
length of the shell is 21 inches. Cyldiagram must be plotted and the yield
inders closed in by a spinning process
strength determined from the 0.2 perare authorized.
cent offset.
(b) Steel. Open-hearth, basic oxygen,
(iii) For the purpose of strain measor electric steel of uniform quality
urement, the initial strain must be set
must be used. Plain carbon steel conwhile the specimen is under a stress of
tent may not exceed the following: Car-
12,000 psi and the strain indicator readbon, 0.25; phosphorus, 0.045; sulfur,
ing being set at the calculated cor-
0.050. The addition of other elements
responding strain.
for alloying effect is prohibited.
(iv) Cross-head speed of the testing
(c) Identification of material. Material
machine may not exceed 1/8 inch per
must be identified by any suitable
minute during yield strength determethod.
mination.
(d) Manufacture. Cylinders must be
(k) Acceptable results for physical and
manufactured using equipment and
flattening tests. Either of the following
processes adequate to ensure that each
is an acceptable result:
(1) An elongation of at least 40 percylinder produced conforms to the recent for a 2 inch gauge length or at
quirements of this subpart. No defect is
least 20 percent in other cases and
permitted that is likely to weaken the
yield strength not over 73 percent of
finished cylinder appreciably. A reatensile strength. In this instance, the
sonably smooth and uniform surface
flattening test is not required.
finish is required. Heads may be at-
(2) An elongation of at least 20 pertached to shells by lap brazing or may
cent for a 2 inch gauge length or 10 perbe formed integrally. The thickness of
cent in other cases. Flattening is rethe bottom of cylinders welded or
quired to 50 percent of the original outformed by spinning is, under no condiside diameter without cracking.
tion, to be less than two times the min-
(1) Rejected cylinders. Reheat-treatimum wall thickness of the cylindrical
ment is authorized for rejected cylshell. Such bottom thicknesses must be
inders. Subsequent thereto, containers
measured within an area bounded by a
must pass all prescribed tests to be acline representing the points of contact
ceptable. Repair of welded seams by
between the cylinder and the floor
welding prior to reheat-treatment is
when the cylinder is in a vertical posiauthorized.
tion. Seams must conform to the fol-
(m) Marking. Marking on each conlowing:
tainer by stamping plainly and perma-
(1) Circumferential seams must be by
nently are only authorized where the
brazing only. Heads must be attached
metal is at least 0.09 inch thick, or on
to shells by the lap brazing method and
a metal nameplate permanently semust overlap not less than four times
cured to the container by means other
the wall thickness. Brazing material
than soft solder, or by means that
must have a melting point of not less
would not reduce the wall thickness.
than 1000 °F. Heads must have a driving
fit with the shell unless the shell is
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
amended at 66 FR 45386, 45388, Aug. 28, 2001;
crimped, swedged, or curled over the
67 FR 51653, Aug. 8, 2002: 68 FR 75748, Dec. 31.
skirt or flange of the head and be thor-
2003)
oughly brazed until complete penetration of the joint by the brazing mate-
§ 178.55 Specification 4B240ET welded
rial is secured. Brazed joints may be reor brazed cylinders.
paired by brazing.
(a) Type, spinning process, size and
(2) Longitudinal seams in shell must
service pressure. A DOT 4B240ET cylbe by electric resistance welded joints
inder is a brazed type cylinder made
only. No repairs to longitudinal joints
from electric resistance welded tubing.
is permitted.
869
$ 178.55
49 CFR Ch. I (10-1-06 Edition)
(3) Welding procedures and operators
(iii) Straight threads, having at least
must be qualified in accordance with
4 engaged threads, to have tight fit and
CGA C-3 (IBR, see § 171.7 of this subcalculated shear strength at least 10
chapter).
times the test pressure of the cylinder;
(e) Welding or brazing. Only the atgaskets required. adequate to prevent
tachment, by welding or brazing, to the
leakage.
tops and bottoms of cylinders of
(2) Closure of a fitting, boss, or pad
neckrings, footrings, handles, bosses,
must be adequate to prevent leakage.
pads, and valve protection rings is au-
(i) Hydrostatic test. Each cylinder
thorized. Provided that such attachmust successfully withstand a hydroments and the portion of the container
static test as follows:
to which they are attached are made of
(1) The test must be by water-jacket,
weldable steel, the carbon content of
or other suitable method, operated so
which may not exceed 0.25 percent.
as to obtain accurate data. The pres-
(f) Wall thickness. The wall stress
sure gauge must permit reading to an
must be at least two times the service
accuracy of 1 percent. The expansion
pressure and may not exceed 18,000 psi.
gauge must permit reading of total ex-
The minimum wall thickness is 0.044
pansion to an accuracy of either 1 perinch. Calculation must be made by the
cent or 0.1 cubic centimeter.
following formula:
(2) Pressure must be maintained for
at least 30 seconds and sufficiently
S = [P(1.3D² + 0.4d²)] / (D² - d2)
longer to ensure complete expansion.
Where:
Any internal pressure applied after
heat-treatment and previous to the of-
S - wall stress in psig;
ficial test may not exceed 90 percent of
P = 2 times service pressure;
D = outside diameter in inches;
the test pressure. If, due to failure of
d = Inside diameter in inches.
the test apparatus, the test pressure
cannot be maintained, the test may be
(g) Heat treatment. Heads formed by
repeated at a pressure increased by 10
drawing or pressing must be uniformly
percent or 100 psig, whichever is the
and properly heat treated prior to
lower.
tests. Cylinders with integral formed
(3) Permanent volumetric expansion
heads or bases must be subjected to a
may not exceed 10 percent of total volnormalizing operation. Normalizing
umetric expansion at test pressure.
and brazing operations may be com-
(4) Cylinders must be tested as folbined, provided the operation is carried
lows:
out at a temperature in excess of the
(i) At least one cylinder selected at
upper critical temperature of the steel.
random out of each lot of 200 or less
(h) Openings in cylinders. Openings in
must be tested as outlined in paracylinders must comply with the folgraphs (i)(1), (i)(2), and (i)(3) of this seclowing:
tion to at least two times service pres-
(1) Each opening in cylinders, except
sure.
those for safety devices, must be pro-
(ii) All cylinders not tested as outvided with a fitting, boss, or pad, selined in paragraph (i)(4)(i) of this seccurely attached to the cylinder by
tion must be examined under pressure
brazing or by welding or by threads. A
of at least two times service pressure
fitting, boss, or pad must be of steel
and show no defect.
suitable for the method of attachment
(5) Each 1000 cylinders or less succesemployed, and which need not be idensively produced each day must contifled or verified as to analysis, except
stitute a lot. One cylinder must be sethat if attachment is by welding, carlected from each lot and
bon content may not exceed 0.25 perhydrostatically tested to destruction.
cent. If threads are used, they must
If this cylinder bursts below five times
comply with the following:
the service pressure, then two addi-
(i) Threads must be clean cut, even
tional cylinders must be selected and
without checks, and tapped to gauge.
subjected to this test. If either of these
(ii) Taper threads to be of length not
cylinders fails by bursting below five
less than as specified for American
times the service pressure then the en-
Standard taper pipe threads.
tire lot must be rejected. All cylinders
870
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.55
constituting a lot must be of identical
prescribed in ASTM E 8 (IBR, see $171.7
size, construction heat-treatment, finof this subchapter).
ish, and quality.
(ii) In using the "extension under
(j) Flattening test. Following the hyload" method, the total strain (or "exdrostatic test, one cylinder taken at
tension under load") corresponding to
random out of each lot of 200 or less,
the stress at which the 0.2 percent permust be subjected to a flattening test
manent strain occurs may be deterthat is between knife edges, wedge
mined with sufficient accuracy by calshaped, 60° angle, rounded to 1/2 inch raculating the elastic extension of the
dius.
gauge length under appropriate load
(k) Physical test. A physical test must
and adding thereto 0.2 percent of the
be conducted to determine yield
gauge length. Elastic extension calstrength, tensile strength, elongation,
culations must be based on an elastic
and reduction of area of material, as
modulus of 30,000,000. In the event of
follows:
controversy, the entire stress-strain
(1) The test is required on 2 specidiagram must be plotted and the yield
mens cut from 1 cylinder, or part
strength determined from the 0.2 perthereof heat-treated as required, taken
cent offset.
at random out of each lot of 200 or less
(iii) For the purpose of strain measin the case of cylinders of capacity
urement, the initial strain must be set
greater than 86 cubic inches and out of
while the specimen is under a stress of
each lot of 500 or less for cylinders hav-
12,000 psi and the strain indicator reading a capacity of 86 cubic inches or
ing being set at the calculated corless.
responding strain.
(2) Specimens must conform to the
(iv) Cross-head speed of the testing
following:
machine may not exceed 1/8 inch per
(i) A gauge length of 8 inches with a
minute during yield strength deterwidth not over 1½ inches, a gauge
mination.
length of 2 inches with a width not
(1) Acceptable results for physical and
over 1½ inches, or a gauge length at
flattening tests. Acceptable results for
least 24 times the thickness with a
the physical and flattening tests are an
width not over 6 times the thickness is
elongation of at least 40 percent for a 2
authorized when a cylinder wall is not
inch gauge length or at least 20 percent
over 3/16 inch thick.
in other cases and a yield strength not
(ii) The specimen, exclusive of grip
over 73 percent of tensile strength. In
ends, may not be flattened. Grip ends
this instance the flattening test is remay be flattened to within one inch of
quired, without cracking, to six times
each end of the reduced section.
the wall thickness with a weld 90° from
(iii) When size of cylinder does not
the direction of the applied load. Two
permit securing straight specimens,
rings cut from the ends of length of
the specimens may be taken in any lopipe used in production of a lot may be
cation or direction and may be
used for the flattening test provided
straightened or flattened cold by presthe rings accompany the lot which
sure only, not by blows. When specithey represent in all thermal procmens are so taken and prepared, the inessing operations. At least one of the
spector's report must show in connecrings must pass the flattening test.
tion with record of physical tests de-
(m) Leakage test. All spun cylinders
tailed information in regard to such
and plugged cylinders must be tested
specimens.
for leakage by gas or air pressure after
(iv) Heating of a specimen for any
the bottom has been cleaned and is free
purpose is not authorized.
from all moisture, subject to the fol-
(3) The yield strength in tension
lowing conditions:
must be the stress corresponding to a
(1) Pressure, approximately the same
permanent strain of 0.2 percent of the
as but no less than service pressure,
gauge length. The following conditions
must be applied to one side of the finapply:
ished bottom over an area of at least
(i) The yield strength must be deter-
1/16 of the total area of the bottom but
mined by either the "offset" method or
not less than 3/4 inch in diameter, inthe "extension under load" method as
cluding the closure, for at least 1
871
§ 178.56
49 CFR Ch. I (10-1-06 Edition)
minute, during which time the other
psig. Closures welded by spinning procside of the bottom exposed to pressure
ess not permitted.
must be covered with water and closely
(b) Steel. The limiting chemical comexamined for indications of leakage.
position of steel authorized by this
Except as provided in paragraph (n) of
specification must be as shown in table
this section, cylinders which are leak-
I of appendix A to this part.
ing must be rejected.
(c) Identification of material. Material
(2) A spun cylinder is one in which an
must be identified by any suitable
end closure in the finished cylinder has
method except that plates and billets
been welded by the spinning process.
for hotdrawn cylinders must be marked
(3) A plugged cylinder is one in which
with the heat number.
a permanent closure in the bottom of a
(d) Manufacture. Cylinders must be
finished cylinder has been effected by a
manufactured using equipment and
plug.
processes adequate to ensure that each
(4) As a safety precaution, if the
cylinder produced conforms to the remanufacturer elects to make this test
quirements of this subpart. No defect is
before the hydrostatic test, he should
permitted that is likely to weaken the
design his apparatus so that the presfinished cylinder appreciably. A reasure is applied to the smallest area
sonably smooth and uniform surface
practicable, around the point of clofinish is required. Exposed bottom
sure, and so as to use the smallest poswelds on cylinders over 18 inches long
sible volume of air or gas.
must be protected by footrings. Min-
(n) Rejected cylinders. Repairs of re-
Imum thickness of heads and bottoms
jected cylinders is authorized. Cylmay not be less than 90 percent of the
inders that are leaking must be rerequired thickness of the side wall.
jected, except that:
Seams must be made as follows:
(1) Spun cylinders rejected under the
(1) Circumferential seams must be
provisions of paragraph (m) of this secwelded. Brazing is not authorized.
tion may be removed from the spun
(2) Longitudinal seams are not percylinder category by drilling to remove
mitted.
defective material, tapping, and plug-
(3) Welding procedures and operators
ging.
must be qualified in accordance with
(2) Brazed joints may be rebrazed.
CGA C-3 (IBR, see $171.7 of this sub-
(3) Subsequent to the operations
chapter).
noted in paragraphs (n)(1) and (n)(2) of
(e) Welding. Only the welding of
this section, acceptable cylinders must
neckrings, footrings, bosses, pads, and
pass all prescribed tests.
valve protection rings to the tops and
(o) Marking. Markings on each cylbottoms of cylinders is authorized.
inder must be by stamping plainly and
Provided that such attachments are
permanently on shoulder, top head,
made of weldable steel, the carbon conneck or valve protection collar which
tent of which does not exceed 0.25 peris permanently attached to the cylcent.
inders and forming an integral part
(f) Wall thickness. The wall thickness
thereof, provided that cylinders not
of the cylinder must conform to the
less than 0.090 inch thick may be
following:
stamped on the side wall adjacent to
(1) For cylinders with an outside ditop head.
ameter over 5 inches, the minimum
wall thickness is 0.078 inch. In any
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
amended at 66 FR 45386, Aug. 28, 2001; 67 FR
case, the minimum wall thickness
51653, Aug. 8, 2002; 68 FR 75748, 75749, Dec. 31,
must be such that the calculated wall
2003]
stress at the minimum test pressure (in
paragraph (i) of this section) may not
§ 178.56 Specification 4AA480 welded
exceed the lesser value of either of the
steel cylinders.
following:
(a) Type, size, and service pressure. A
(i) One-half of the minimum tensile
DOT 4AA480 cylinder is a welded steel
strength of the material determined as
cylinder having a water capacity
required in paragraph (j) of this sec-
(nominal) not over 1,000 pounds water
tion; or
capacity and a service pressure of 480
(ii) 35,000 psi.
872
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.56
(2) Calculation must be made by the
(1) The test must be by water jacket,
formula:
or other suitable method, operated so
S = [P(1.3D² + 0.4d²)] / (D² - d²)
as to obtain accurate data. The pressure gauge must permit reading to an
Where:
accuracy of 1 percent. The expansion
S - wall stress in psi;
gauge must permit reading of total ex-
P = minimum test pressure prescribed for
pansion to an accuracy of either 1 perwater jacket test;
cent or 0.1 cubic centimeter.
D = outside diameter in inches;
(2) Pressure must be maintained for
d = inside diameter in inches.
at least 30 seconds or sufficiently
(3) The ratio of tangential length to
longer to assure complete expansion.
outside diameter may not exceed 4.0 for
Any internal pressure applied after
cylinders with a wall thickness less
heat-treatment and before the official
than 0.100 inch.
test may not exceed 90 percent of the
(g) Heat treatment. Each cylinder
test pressure. If, due to failure of test
must be uniformly and properly heat
apparatus, the test pressure cannot be
treated prior to tests. Any suitable
maintained, the test may be repeated
heat treatment in excess of 1100 °F is
at a pressure increased by 10 percent or
authorized except that liquid quench-
100 psig, whichever is lower.
ing is not permitted. Heat treatment
(3) Permanent volumetric expansion
must be accomplished after all forming
may not exceed 10 percent of the total
and welding operations. Heat treatvolumetric expansion at test pressure.
ment is not required after welding
(4) Cylinders must be tested as folweldable low carbon parts to attachlows:
ments of similar material which have
(i) At least one cylinder selected at
been previously welded to the top or
random out of each lot of 200 or less
bottom of cylinders and properly heat
must be tested as described in paratreated, provided such subsequent
graphs (i)(1), (i)(2), and (1)(3) of this secwelding does not produce a temperation, to at least two times service presture in excess of 400 °F., in any part of
sure. If a selected cylinder fails, then
the top or bottom material.
two additional specimens must be se-
(h) Openings in cylinders. Openings in
lected at random from the same lot and
cylinders must conform to the folsubjected to the prescribed test. If eilowing:
ther of these falls the test, then each
(1) All openings must be in the heads
cylinder in that lot must be so tested;
or bases.
and
(2) Each opening in the cylinder, ex-
(ii) Each cylinder not tested as precept those for safety devices, must be
scribed in paragraph (i)(4)(i) of this secprovided with a fitting boss, or pad, setion must be examined under pressure
curely attached to the cylinder by
of at least two times service pressure
welding or by threads. If threads are
and must show no defect. A cylinder
used they must comply with the folshowing a defect must be rejected unlowing:
less it may be requalified under para-
(i) Threads must be clean-cut, even
graph (m) of this section.
without checks and cut to gauge.
(j) Physical test. A physical test must
(ii) Taper threads to be of length not
be conducted to determine yield
less than as specified for American
strength, tensile strength, elongation,
Standard taper pipe threads.
and reduction of area of material, as
(iii) Straight threads having at least
follows:
6 engaged threads, must have a tight
(1) The test is required on 2 specifit and a calculated shear strength at
mens cut from one cylinder having
least 10 times the test pressure of the
passed the hydrostatic test, or part
cylinder. Gaskets, adequate to prevent
thereof heat-treated as required, taken
leakage, are required.
at random out of each lot of 200 or less.
(3) Closure of a fitting, boss or pad
(2) Specimens must conform to the
must be adequate to prevent leakage.
following:
(i) Hydrostatic test. Each cylinder
(i) A gauge length of 8 inches with a
must successfully withstand a hydrowidth not over 1½ inches, a gauge
static test as follows:
length of 2 inches with a width not
873
§ 178.56
49 CFR Ch. I (10-1-06 Edition)
over 1½ inches, or a gauge length at
(k) Elongation. Physical test specileast 24 times the thickness with a
mens must show at least a 40 percent
width not over 6 times thickness is auelongation for 2-inch gauge lengths or
thorized when the cylinder wall is not
at least a 20 percent elongation in
over 3/10 inch thick.
other cases. Except that these elon-
(ii) The specimen, exclusive of grip
gation percentages may be reduced nuends, may not be flattened. Grip ends
merically by 2 for 2-inch specimens and
may be flattened to within one inch of
by 1 in other cases for each 7,500 psi ineach end of the reduced section.
crement of tensile strength above 50,000
(iii) When size of cylinder does not
psi to a maximum of four such increpermit securing straight specimens,
ments.
the specimens may be taken in any lo-
(1) Tests of welds. Welds must be testcation or direction and may be
ed as follows:
straightened or flattened cold, by pres-
(1) Tensile test. A specimen must be
sure only, not by blows. When specicut from one cylinder of each lot of 200
mens are so taken and prepared, the inor less, or a welded test plate. The
spector's report must show in connecwelded test plate must be of one of the
heats in the lot of 200 or less which it
tion with record of physical tests detailed information in regard to such
represents, in the same condition and
specimens.
approximately the same thickness as
(iv) Heating of a specimen for any
the cylinder wall except that it may
not be of a lesser thickness than that
purpose is not authorized.
required for a quarter size Charpy im-
(3) The yield strength in tension
pact specimen. The weld must be made
must be the stress corresponding to a
by the same procedures and subjected
permanent strain of 0.2 percent of the
to the same heat treatment as the
gauge length. The following conditions
major weld on the cylinder. The speciapply:
mens must be taken across the major
(i) The yield strength must be deterseam and must be prepared and tested
mined by either the "offset" method or
in accordance with and must meet the
the "extension under load" method as
requirements of CGA Pamphlet C-3.
prescribed in ASTM E 8 (IBR, see § 171.7
Should this specimen fail to meet the
of this subchapter).
requirements, specimens may be taken
(ii) In using the "extension under
from two additional cylinders or weldload" method, the total strain (or "exed test plates from the same lot and
tension under load"), corresponding to
tested. If either of the latter specimens
the stress at which the 0.2 percent perfail to meet the requirements. the enmanent strain occurs may be detertire lot represented must be rejected.
mined with sufficient accuracy by cal-
(2) Guided bend test. A root bend test
culating the elastic extension of the
specimen must be cut from the cylgauge length under appropriate load
inder or a welded test plate, used for
and adding thereto 0.2 percent of the
the tensile test specified in paragraph
gauge length. Elastic extension cal-
(1)(1) of this section. Specimens must
culations must be based on an elastic
be taken from across the major seam
modulus of 30,000,000. In the event of
and must be prepared and tested in accontroversy, the entire stress-strain
cordance with and must meet the rediagram must be plotted and the yield
quirements of CGA Pamphlet C-3.
strength determined from the 0.2 per-
(3) Alternate guided-bend test. This
cent offset.
test may be used and must be as re-
(iii) For the purpose of strain measquired by CGA Pamphlet C-3. The specurement, the initial strain reference
imen must be bent until the elongation
must be set while the specimen is
at the outer surface, adjacent to the
under a stress of 12,000 psi and the
root of the weld, between the lightly
strain indicator reading being set at
scribed gage lines-a to b, is at least 20
the calculated corresponding strain.
percent, except that this percentage
(iv) Cross-head speed of the testing
may be reduced for steels having a tenmachine may not exceed 1/8 inch per
sile strength in excess of 50,000 psi, as
minute during yield strength deterprovided in paragraph (k) of this secmination.
tion.
874
Pipellne and Hazardous Materials Safety Admin., DOT
§ 178.57
(m) Rejected cylinders. Reheat treat-
(b) Material. Material use in the conment of rejected cylinders is authorstruction of this specification must
ized. Subsequent thereto, cylinders
conform to the following:
must pass all prescribed tests to be ac-
(1) Inner containment vessel (cylinder).
ceptable. Repair of welded seams by
Designations and limiting chemical
welding is authorized.
compositions of steel authorized by
(n) Markings. Markings must be
this specification must be as shown in
stamped plainly and permanently in
table 1 in paragraph (o) of this section.
one of the following locations on the
(2) Outer jacket. Steel or aluminum
cylinder:
may be used subject to the require-
(1) On shoulders and top heads not
ments of paragraph (o)(2) of this secless than 0.087 inch thick.
tion.
(2) On neck, valve boss, valve protec-
(c) Identification of material. Material
tion sleeve, or similar part permamust be identified by any suitable
nently attached to top end of cylinder.
method.
(3) On a plate attached to the top of
(d) Manufacture. Cylinders must be
the cylinder or permanent part thereof:
manufactured using equipment and
sufficient space must be left on the
processes adequate to ensure that each
plate to provide for stamping at least
cylinder produced conforms to the resix retest dates: the plate must be at
quirements of this subpart and to the
least 1/16 inch thick and must be atfollowing requirements:
tached by welding or by brazing at a
(1) No defect is permitted that is
temperature of at least 1100 °F,
likely to weaken the finished cylinder
throughout all edges of the plate.
appreciably. A reasonably smooth and
(4) Variations in location of markuniform surface finish is required. The
ings authorized only when necessitated
shell portion must be a reasonably true
by lack of space.
cylinder.
(2) The heads must be seamless, con-
[Amdt. 178-114, 61 FR 25942. May 23, 1996, as
amended at 66 FR 45386, Aug. 28, 2001: 67 FR
cave side to the pressure, hemi-
51653, Aug. 8, 2002; 68 FR 75748, 75749, Dec. 31,
spherical or ellipsoidal in shape with
2003)
the major diameter not more than
twice the minor diameter. Minimum
§ 178.57 Specification 4L welded insuthickness of heads may not be less
lated cylinders.
than 90 percent of the required thick-
(a) Type, size, service pressure, and deness of the sidewall. The heads must be
sign service temperature. A DOT 4L cylreasonably true to shape, have no abinder is a fusion welded insulated cylrupt shape changes, and the skirts
inder with a water capacity (nominal)
must be reasonably true to round.
not over 1,000 pounds water capacity
(3) The surface of the cylinder must
and a service pressure of at least 40 but
be insulated. The insulating material
not greater than 500 psig conforming to
must be fire resistant. The insulation
the following requirements:
on non-evacuated jackets must be cov-
(1) For liquefied hydrogen service,
ered with a steel jacket not less than
the cylinders must be designed to stand
0.060-inch thick or an aluminum jacket
on end, with the axis of the cylindrical
not less than 0.070 inch thick, so conportion vertical.
structed that moisture cannot come in
(2) The design service temperature is
contact with the insulating material. If
the coldest temperature for which a
a vacuum is maintained in the insulacylinder is suitable. The required detion space, the evacuated jacket must
sign service temperatures for each
be designed for a minimum collapsing
cryogenic liquid is as follows:
pressure of 30 psig differential whether
made of steel or aluminum. The con-
Cryogenic liquid
Design service temperature
struction must be such that the total
Argon
Minus 320 °F or colder.
heat transfer, from the atmosphere at
Helium
Minus 452 °F or colder.
ambient temperature to the contents
Hydrogen
Minus 42 3 °F or colder.
of the cylinder, will not exceed 0.0005
Neon
Minus 411 °F or colder.
Btu per hour, per Fahrenheit degree
Nitrogen
Minus 320 °F or colder.
Oxygen
Minus 320 °F or colder.
differential in temperature, per pound
of water capacity of the cylinder. For
875
§ 178.57
49 CFR Ch. I (10-1-06 Edition)
hydrogen, cryogenic liquid service, the
(3) One-half of the minimum tensile
total heat transfer, with a temperature
strength of the base metal determined
differential of 520 Fahrenheit degrees,
as required in paragraph (j) of this secmay not exceed that required to vent
tion.
30 SCF of hydrogen gas per hour.
(4) The yield strength of the base
(4) For a cylinder having a design
metal determined as required in paraservice temperature colder than minus
graph (1) of this section.
320 °F, a calculation of the maximum
(5) Further provided that wall stress
weight of contents must be made and
for cylinders having longitudinal
that weight must be marked on the
seams may not exceed 85 percent of the
cylinder as prescribed in $178.35.
above value, whichever applies.
(5) Welding procedures and oper-
(6) Calculation must be made by the
ations must be qualified in accordance
following formula:
with CGA Pamphlet C-3 (IBR, see
S = [P(1.3D² + 0.4d²)] / (D² - d²)
§ 171.7 of this subchapter). In addition,
an impact test of the weld must be perwhere:
formed in accordance with paragraph
S = wall stress in pounds psi;
(1) of this section as part of the quali-
P = minimum test pressure prescribed for
fication of each welding procedure and
pressure test in psig;
D = outside diameter in inches;
operator.
(e) Welding. Welding of the cylinder
d = inside diameter in inches.
must be as follows:
(g) Heat treatment. Heat treatment is
(1) All seams of the cylinder must be
not permitted.
fusion welded. A means must be pro-
(h) Openings in cylinder. Openings in
vided for accomplishing complete penecylinders must conform to the foltration of the joint. Only butt or joggle
lowing:
butt joints for the cylinder seams are
(1) Openings are permitted in heads
authorized. All joints in the cylinder
only. They must be circular and may
must have reasonably true alignment.
not exceed 3 inches in diameter or one
(2) All attachments to the sidewalls
third of the cylinder diameter, whichand heads of the cylinder must be by
ever is less. Each opening in the cylfusion welding and must be of a
inder must be provided with a fitting,
weldable material complying with the
boss or pad, either integral with, or seimpact requirements of paragraph (1) of
curely attached to, the cylinder body
this section.
by fusion welding. Attachments to a
(3) For welding the cylinder, each
fitting, boss or pad may be made by
procedure and operator must be qualiwelding, brazing, mechanical attachfied in accordance with the sections of
ment, or threading.
CGA Pamphlet C-3 that apply. In addi-
(2) Threads must comply with the foltion, impact tests of the weld must be
lowing:
performed in accordance with para-
(i) Threads must be clean-cut, even,
graph (1) of this section as part of the
without checks and cut to gauge.
qualification of each welding procedure
(ii) Taper threads to be of a length
and operator.
not less than that specified for NPT.
(4) Brazing, soldering and threading
(iii) Straight threads must have at
are permitted only for joints not made
least 4 engaged threads, tight fit and
directly to the cylinder body. Threads
calculated shear strength at least 10
must comply with the requirements of
times the test pressure of the cylinder.
paragraph (h) of this section.
Gaskets, which prevent leakage and
(f) Wall thickness. The minimum wall
are inert to the hazardous material,
thickness of the cylinder must be such
are required.
that the calculated wall stress at the
(i) Pressure test. Each cylinder, before
minimum required test pressure may
insulating and jacketing. must be exnot exceed the least value of the folamined under a pressure of at least 2
lowing:
times the service pressure maintained
(1) 45,000 psi.
for at least 30 seconds without evidence
(2) One-half of the minimum tensile
of leakage, visible distortion or other
strength across the welded seam deterdefect. The pressure gauge must permit
mined in paragraph (I) of this section.
reading to an accuracy of 1 percent.
876
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.57
(j) Physical test. A physical test must
yield strength determined from the 0.2
be conducted to determine yield
percent offset.
strength, tensile strength, and elon-
(iii) For the purpose of strain measgation as follows:
urement, the initial strain reference
(1) The test is required on 2 specimust be set while the specimen is
mens selected from material of each
under a stress of 12,000 psi and the
heat and in the same condition as that
strain indicator reading being set at
in the completed cylinder.
the calculated corresponding strain.
(2) Specimens must conform to the
(iv) Cross-head speed of the testing
following:
machine may not exceed 1/8 inch per
(i) A gauge length of 8 inches with a
minute during yield strength determination.
width not over 1½ inches, a gauge
length of 2 inches with width not over
(k) Acceptable results for physical tests.
1½ inches, or a gauge length at least 24
Physical properties must meet the limtimes thickness with a width not over
its specified in paragraph (o)(1), table 1,
6 times thickness (authorized when cylof this section, for the particular steel
inder wall is not over 1/16 inch thick).
in the annealed condition. The specimens must show at least a 20 percent
(ii) The specimen, exclusive of grip
elongation for a 2-inch gage length. Exends, may not be flattened. Grip ends
cept that the percentage may be remay be flattened to within one inch of
duced numerically by 2 for each 7,500
each end of the reduced section.
psi increment of tensile strength above
(iii) When size of the cylinder does
100,000 psi to a maximum of 5 such innot permit securing straight specicrements. Yield strength and tensile
mens, the specimens may be taken in
strength must meet the requirements
any location or direction and may be
of paragraph (o)(1), table 1, of this secstraightened or flattened cold by prestion.
sure only, not by blows. When speci-
(1) Tests of welds. Welds must be testmens are so taken and prepared, the ined as follows:
spector's report must show in connec-
(1) Tensile test. A specimen must be
tion with record of physical tests decut from one cylinder of each lot of 200
tailed information in regard to such
or less, or welded test plate. The weldspecimens.
ed test plate must be of one of the
(iv) Heating of a specimen for any
heats in the lot of 200 or less which it
purpose is not authorized.
represents, in the same condition and
(3) The yield strength in tension
approximately the same thickness as
must be the stress corresponding to a
the cylinder wall except that it may
permanent strain of 0.2 percent of the
not be of a lesser thickness than that
gauge length. The following conditions
required for a quarter size Charpy imapply:
pact specimen. The weld must be made
(i) The yield strength must be deterby the same procedures and subjected
mined by either the "offset" method or
to the same heat treatment as the
the "extension under load" method as
major weld on the cylinder. The speciprescribed in ASTM E 8 (IBR, see $171.7
men must be taken across the major
of this subchapter).
seam and must be prepared in accord-
(ii) In using the "extension under
ance with and must meet the requireload" method, the total strain (or "exments of CGA Pamphlet C-3. Should
tension under load"), corresponding to
this specimen fail to meet the requirethe stress at which the 0.2 percent perments, specimens may be taken from
manent strain occurs may be detertwo additional cylinders or welded test
mined with sufficient accuracy by calplates from the same lot and tested. If
culating the elastic expansion of the
either of the latter specimens fails to
gauge length under appropriate load
meet the requirements, the entire lot
and adding thereto 0.2 percent of the
represented must be rejected.
gauge length. Elastic extension cal-
(2) Guided bend test. A "root" bend
culations must be based on the elastic
test specimen must be cut from the
modulus of the material used. In the
cylinder or welded test plate, used for
event of controversy, the entire stressthe tensile test specified in paragraph
strain diagram must be plotted and the
(1)(1) of this section and from any other
877
§ 178.57
49 CFR Ch. I (10-1-06 Edition)
seam or equivalent welded test plate if
imum, but not necessarily from one of
the seam is welded by a procedure difthe heats used in the lot of cylinders.
ferent from that used for the major
The test piece must be welded by the
seam. Specimens must be taken across
same welding procedure as used on the
the particular seam being tested and
particular cylinder seam being qualimust be prepared and tested in accordfied and must be subjected to the same
ance with and must meet the requireheat treatment.
ments of CGA Pamphlet C-3.
(vi) Impact test specimens must be
(3) Alternate guided-bend test. This
cooled to the design service temperatest may be used and must be as specified in CGA Pamphlet C-3. The speciture. The apparatus for testing the
men must be bent until the elongation
specimens must conform to requirements of ASTM Standard E 23. The test
at the outer surface, adjacent to the
root of the weld, between the lightly
piece, as well as the handling tongs,
scribed gage lines a to b, is at least 20
must be cooled for a length of time sufpercent, except that this percentage
ficient to reach the service temperamay be reduced for steels having a tenture. The temperature of the cooling
sile strength in excess of 100,000 psig, as
device must be maintained within a
provided in paragraph (c) of this secrange of plus or minus 3 °F. The specition.
men must be quickly transferred from
(4) Impact tests. One set of three imthe cooling device to the anvil of the
pact test specimens (for each test)
testing machine and broken within a
must be prepared and tested for detertime lapse of not more than six secmining the impact properties of the deonds.
posited weld metal-
(vii) The impact properties of each
(i) As part of the qualification of the
set of impact specimens may not be
welding procedure.
less than the values in the following
(ii) As part of the qualification of the
table:
operators.
(iii) For each "heat" of welding rodor
Minimum
Minimum
wire used.
Impact value
required for
Impact value
(iv) For each 1,000 feet of weld made
Size of specimen
avg. of each
permitted on
with the same heat of welding rod or
set of three
one only of a
set of three
specimens
wire.
(ft.-lb.)
(ft-lb.)
(v) All impact test specimens must be
10 mmx10 mm
15
10
of the charpy type, keyhole or milled
10 mmx7.5 mm
12.5
8.5
U-notch, and must conform in all re-
10 mmx5 mm
10
7.0
spects to ASTM E 23 (IBR, see $171.7 of
10 mmx2.5 mm
5
3.5
this subchapter). Each set of Impact
specimens must be taken across the
(viii) When the average value of the
weld and have the notch located in the
three specimens equals or exceeds the
weld metal. When the cylinder mateminimum value permitted for a single
rial thickness is 2.5 mm or thicker, imspecimen and the value for more than
pact specimens must be cut from a cylone specimen is below the required avinder or welded test plate used for the
erage value, or when the value for one
tensile or bend test specimens. The dispecimen is below the minimum value
mension along the axis of the notch
must be reduced to the largest possible
permitted for a single specimen, a
of 10 mm, 7.5 mm, 5 mm or 2.5 mm, deretest of three additional specimens
must be made. The value of each of
pending upon cylinder thickness. When
the material in the cylinder or welded
these retest specimens must equal or
test plate is not of sufficient thickness
exceed the required average value.
to prepare 2.5 mm impact test speci-
When an erratic result is caused by a
mens, 2.5 mm specimens must be predefective specimen, or there is uncerpared from a welded test plate made
tainty in test procedure, a retest is aufrom 1/8 inch thick material meeting
thorized.
the requirements specified in para-
(m) Radiographic examination. Cylgraph (o)(1), table 1, of this section and
inders must be subject to a radiohaving a carbon analysis of .05 mingraphic examination as follows:
878
Pipeline and Hazardous Materials Safety Admin., DOT
$ 178.57
(1) The techniques and acceptability
TABLE 2-PHYSICAL PROPERTIES
of radiographic inspection must conform to the standards set forth in CGA
Physical
properties
Pamphlet C-3.
(annealed)
(2) One finished longitudinal seam
Tensile strength, p.s.i. (minimum)
75,000
must be selected at random from each
Yield strength, p.s.i. (minimum)
30,000
lot of 100 or less successively produced
Elongation In 2 Inches (minimum) percent
30.0
and be radiographed throughout its en-
Elongation other permissible gauge lengths
tire length. Should the radiographic
(minimum) percent
15.0
examination fail to meet the requirements of paragraph (m) of this sec-
TABLE 3-CHECK ANALYSIS TOLERANCES
tion, two additional seams of the same
Tolerance
lot must be examined, and if either of
over the
these fail to meet the requirements of
Elements
Limit or specified range
maximum
(m) (1) of this section, only those pass-
(percent)
limit or under
the minimum
ing are acceptable.
limit
(n) Rejected cylinders. Reheat treat-
Carbon
To 0.030, incl
0.005
ment of rejected cylinders is author-
Over 0.30 to 0.20, incl
0.01
ized. Subsequent thereto, cylinders
Manganese
To 1.00 incl
.03
must pass all prescribed tests to be ac-
Over 1.00 to 3.00, incl
0.04
Phosphorus
To 0.040, incl
0.005
ceptable. Welds may be repaired by
Over 0.040 to 0.020 incl
0.010
suitable methods of fusion welding.
Sulphur
To .40 incl
0.005
(o) Authorized materials of construc-
Silicon
To 1.00, incl
0.05
tion. Authorized materials of construc-
Nickel
Over 5.00 to 10.00, incl
0.10
Over 10.00 to 20.00, incl
0.15
tion are as follows:
Chromium
Over 15.00 to 20.00, incl
0.20
(1) Inner containment vessel (cylinder).
Rephosphorized steels not subject to check analysis for
Electric furnace steel of uniform qualphosphorus.
ity must be used. Chemical analysis
must conform to ASTM A 240/A 240M
(2) Outer jacket. (i) Nonflammable
(IBR, see $171.7 of this subchapter),
cryogenic liquids. Cylinders intended
Type 304 stainless steel. Chemical analfor use in the transportation of nonysis must conform to ASTM A240, Type
flammable cryogenic liquid must have
304 Stainless Steel. A heat of steel
an outer jacket made of steel or aluminum.
made under table 1 and table 2 in this
paragraph (o)(1) is acceptable, even
(ii) Flammable cryogenic liquids.
though its check chemical analysis is
Cylinders intended for use in the transslightly out of the specified range, if it
portation of flammable cryogenic liqis satisfactory in all other respects,
uid must have an outer jacket made of
steel.
provided the tolerances shown in table
3 in this paragraph (o)(1) are not ex-
(p) Markings. (1) Markings must be
ceeded. The following chemical analstamped plainly and permanently on
yses and physical properties are aushoulder or top head of jacket or on a
thorized:
permanently attached plate or head
protective ring.
TABLE 1-AUTHORIZED MATERIALS
(2) The letters "ST", followed by the
design service temperature (for exam-
Designation
Chemical analysis,
ple, ST-423F). must be marked on cyllimits in percent
inders having a design service tempera-
Carbon
0.08 max.
ture of colder than minus 320 °F only.
Manganese
2.00 max.
Location to be just below the DOT
Phasphorus
0.045 max.
mark.
Sulphur
0.030 max.
(3) The maximum weight of contents,
Silicon
1.00 max.
in pounds (for example, "Max. Content
Nickel
8.00-10.50.
Chromium
18.00-20.00.
51 #''), must be marked on cylinders
Molybdenum
None.
having a design service temperature
Titanium
None.
colder than minus 320 °F only. Loca-
Columbium
None.
tion to be near symbol.
¹The carbon analysis must be reported to the nearest hun-
(4) Special orientation instructions
dredth of one percent.
must be marked on the cylinder (for
879
$ 178.58
49 CFR Ch. I (10-1-06 Edition)
example, THIS END UP). if the cyl-
TABLE 1-AUTHORIZED MATERIALS-Continued
inder is used in an orientation other
4130
Percent
than vertical with openings at the top
of the cylinder.
Chromium
0.80/1.10.
(5) If the jacket of the cylinder is
Molybdenum
0.15/0.25.
constructed of aluminum, the letters
"AL" must be marked after the service
TABLE 2-CHECK ANALYSIS TOLERANCES
pressure marking. Example: DOT-4L150
AL.
Tolerance (percent) over the
(6) Except for serial number and jackmaximum limit or
et material designation, each marking
under the min-
Limit or maximum
imum limit
prescribed in this paragraph (p) must
Element
specified (parcent)
be duplicated on each cylinder by any
Under
Over
minmax-
suitable means.
Imum
imum
(q) Inspector's report. In addition to
limit
limit
the information required by 178.35, the
Carbon
Over 0.15 to 0.40 incl
.03
.04
inspector's reports must contain infor-
Manganese
To 0.60 Incl
03
.03
mation on:
Phosphorus¹
All ranges
.01
Sulphur
All ranges
.01
(1) The jacket material and insula-
Silicon
To 0.30 incl
.02
.03
tion type;
Over 0.30 to 1.00 incl
.05
.05
(2) The design service temperature
Chromium
To 0.90 incl
.03
.03
Over 0.90 to 2.10 incl
.05
.05
(°F); and
Molybdenum
To 0.20 incl
.01
.01
(3) The impact test results, on a lot
Over 0.20 to 0.40, Incl
.02
.02
basis.
Rephosphorized steels not subject to check analysis for
phosphorus.
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
amended at 66 FR 45386-45388, Aug. 28, 2001: 67
(c) Identification of material. Materials
FR 51653, Aug. 8, 2002; 68 FR 75748, Dec. 31,
must be identified by any suitable
2003]
method except that plates and billets
for hot-drawn containers must be
§ 178.58 Specification 4DA welded steel
marked with the heat number.
cylinders for aircraft use.
(d) Manufacture. Cylinders must be
(a) Type, size, and service pressure. A
manufactured in accordance with the
DOT 4DA is a welded steel sphere (two
following requirements:
seamless hemispheres) or a circum-
(1) By best appliances and methods.
ferentially welded cylinder (two seam-
No defect is acceptable that is likely to
less drawn shells) with a water capacweaken the finished container appreity not over 100 pounds and a service
ciably. A reasonably smooth and unipressure of at least 500 but not over 900
form surface finish is required. No abpsig.
rupt change in wall thickness is per-
(b) Steel. Open-hearth or electric steel
mitted. Welding procedures and operaof uniform quality must be used. A
tors must be qualified in accordance
heat of steel made under table 1 in this
with CGA Pamphlet C-3 (IBR, see
paragraph (b), check chemical analysis
§ 171.7 of this subchapter).
of which is slightly out of the specified
(2) All seams of the sphere or cylrange, is acceptable, if satisfactory in
Inders must be fusion welded. Seams
all other respects, provided the tolermust be of the butt or joggle butt type
ances shown in table 2 in this paraand means must be provided for accomgraph (b) are not exceeded except as applishing complete penetration of the
proved by the Associate Administrator.
joint.
The following chemical analyses are
(e) Welding. Attachments to the conauthorized:
tainer are authorized by fusion welding
provided that such attachments are
TABLE 1-AUTHORIZED MATERIALS
made of weldable steel, the carbon con-
4130
Percent
tent of which may not exceed 0.25 percent except in the case of 4130 steel.
Carbon
0.28/0.33.
(f) Wall thickness. The minimum wall
Manganese
0.40/0.60.
thickness must be such that the wall
Phosphorus
0.040 max.
Suffer
0.040 max.
stress at the minimum specified test
Silicon
0.15/0.35.
pressure may not exceed 67 percent of
880
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.58
the minimum tensile strength of the
cooling rate in excess of 80 percent of
steel as determined from the physical
the cooling rate of water, must be inand burst tests required and may not
spected by the magnetic particle or dye
be over 70,000 p.s.i. For any diameter
penetrant method to detect the prescontainer, the minimum wall thickness
ence of quenching cracks. Any cylinder
is 0.040 inch. Calculations must be
found to have a quench crack must be
made by the formulas in (f)(1) or (f)(2)
rejected and may not be requalified.
of this section:
(h) Openings in container. Openings in
(1) Calculation for a sphere must be
the container must comply with the
made by the following formula:
following requirements:
S = PD / 4tE
(1) Each opening in the container
must be provided with a fitting, boss,
Where:
or pad of weldable steel securely at-
S - wall stress in pounds psi:
tached to the container by fusion weld-
P = test pressure prescribed for water jacket
ing.
test, i.e., at least 2 times service pressure,
(2) Attachments to a fitting. boss, or
in psig:
D = outside diameter in Inches;
pad must be adequate to prevent leak-
t = minimum wall thickness in inches;
age. Threads must comply with the fol-
E - 0.85 (provides 85 percent weld efficiency
lowing:
factor which must be applied in the girth
(i) Threads must be clean cut, even,
weld area and heat affected zones which
without checks, and tapped to gauge.
zone must extend a distance of 6 times wall
thickness from center line of weld);
(ii) Taper threads to be of length not
E = 1.0 (for all other areas).
less than as specified for American
Standard taper pipe threads.
(2) Calculation for a cylinder must be
(iii) Straight threads, having at least
made by the following formula:
4 engaged threads, to have tight fit and
S = [P(1.3D² + 0.4d 2)] / (D² - d²)
calculated shear strength at least 10
times the test pressure of the con-
Where:
tainer; gaskets required, adequate to
S = wall stress in pounds psi;
P = test pressure prescribed for water jacket
prevent leakage.
test, i.e., at least 2 times service pressure,
(i) Hydrostatic test. Each cylinder
in psig:
must successfully withstand a hydro-
D = outside diameter in inches;
static test as follows:
d = inside diameter in inches.
(1) The test must be by water-jacket,
(g) Heat treatment. The completed
or other suitable method, operated so
containers must be uniformly and
as to obtain accurate data. The presproperly heat-treated prior to tests.
sure gauge must permit reading to an
Heat-treatment of containers of the auaccuracy of 1 percent. The expansion
thorized analysis must be as follows:
gauge must permit reading of total ex-
(1) All containers must be quenched
pansion to accuracy either of 1 percent
by oil, or other suitable medium except
or 0.1 cubic centimeter.
as provided in paragraph (g)(4) of this
(2) Pressure must be maintained for
section.
at least 30 seconds and sufficiently
(2) The steel temperature on quenchlonger to ensure complete expansion.
ing must be that recommended for the
Any internal pressure applied after
steel analysis, but may not exceed 1,750
heat-treatment and previous to the of-
°F.
ficial test may not exceed 90 percent of
(3) The steel must be tempered at the
the test pressure. If, due to failure of
temperature most suitable for the
the test apparatus, the test pressure
analysis except that in no case shall
cannot be maintained, the test may be
the tempering temperature be less than
repeated at a pressure increased by 10
1,000 F.
percent or 100 psig, whichever is the
(4) The steel may be normalized at a
lower.
temperature of 1,650 °F instead of being
(3) Permanent volumetric expansion
quenched, and containers so normalmay not exceed 10 percent of total volized need not be tempered.
umetric expansion at test pressure.
(5) All cylinders, if water quenched or
(4) Each container must be tested to
quenched with a liquid producing a
at least 2 times service pressure.
881
$ 178.58
49 CFR Ch. I (10-1-06 Edition)
(j) Burst test. One container taken at
width not over 6 times thickness is aurandom out of 200 or less must be
thorized when wall of sphere is not
hydrostatically tested to destruction.
over 3/16 inch thick.
The rupture pressure must be included
(3) A physical test for cylinders is reas part of the inspector's report.
quired on 2 specimens cut from 1 cyl-
(k) Flattening test. Spheres and cylinder taken at random out of each lot
inders must be subjected to a flatof 200 or less.
tening test as follows:
(4) Specimens for cylinder must con-
(1) Flattening test for spheres. One
form to the following:
sphere taken at random out of each lot
(i) A gauge length of 8 inches with a
of 200 or less must be subjected to a
width not over 1½ inches, a gauge
flattening test as follows:
length of 2 inches with a width not
(i) The test must be performed after
over 1½ inches, a gauge length at least
the hydrostatic test.
24 times thickness with a width not
(ii) The test must be at the weld beover 6 times thickness is authorized
tween the parallel steel plates on a
when a cylinder wall is not over 3/16
press with a welded seam, at right an-
Inch thick.
gles to the plates. Any projecting ap-
(ii) The specimen, exclusive of grip
purtenances may be cut off (by meends, may not be flattened. Grip ends
chanical means only) prior to crushing.
may be flattened to within 1 inch of
(2) Flattening test for cylinders. One
each end of the reduced section.
cylinder taken at random out of each
(iii) Heating of a specimen for any
lot of 200 or less, must be subjected to
purpose is not authorized.
a flattening test as follows:
(5) The yield strength in tension
(i) The test must be performed after
must be the stress corresponding to a
the hydrostatic test.
permanent strain of 0.2 percent of the
(ii) The test cylinder must be placed
gauge length. The following conditions
between wedge-shaped knife edges havapply:
ing a 60° angle, rounded to a 1/2-inch ra-
(i) The yield strength must be deterdius.
mined by either the "offset" method or
(1) Radiographic inspection. Radiothe "extension under load" method as
graphic examinations is required on all
prescribed in ASTM E 8 (IBR, see $171.7
welded joints which are subjected to inof this subchapter).
ternal pressure, except that at the dis-
(ii) In using the "extension under
cretion of the disinterested inspector,
load" method, the total strain (or "exopenings less than 25 percent of the
tension under load") corresponding to
sphere diameter need not be subjected
the stress at which the 0.2 percent perto radiographic inspection. Evidence of
manent strain occurs may be deterany defects likely to seriously weaken
mined with sufficient accuracy by calthe container must be cause for rejecculating the elastic extension of the
tion.
gauge length under appropriate load
(m) Physical test and specimens for
and adding thereto 0.2 percent of the
spheres and cylinders. Spheres and cylgauge length. Elastic extension calinders must be subjected to a physical
culations must be based on an elastic
test as follows:
modulus of 30,000,000. In the event of
(1) A physical test for a sphere is recontroversy, the entire stress-strain
quired on 2 specimens cut from a flat
diagram must be plotted and the yield
representative sample plate of the
strength determined from the 0.2 persame heat taken at random from the
cent offset.
steel used to produce the sphere. This
(iii) For the purpose of strain measflat steel from which the 2 specimens
urement, the initial strain must be set
are to be cut must receive the same
while the specimen is under a stress of
heat-treatment as the spheres them-
12,000 psi and the strain indicator readselves. Sample plates to be taken for
ing being set at the calculated coreach lot of 200 or less spheres.
responding strain.
(2) Specimens for spheres have a
(iv) Cross-head speed of the testing
gauge length of 2 inches with a width
machine may not exceed 1/8 inch per
not over 1½ inches, or a gauge length
minute during yield strength deterat least 24 times thickness with a
mination.
882
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.59
(n) Acceptable results for physical, flatfinished cylinder appreciably. A reatening, and burst tests. The following are
sonably smooth and uniform surface
acceptable results of the physical, flatfinish is required. Welding procedures
tening and burst test:
and operators must be qualified in ac-
(1) Elongation must be at least 20
cordance with CGA Pamphlet C-3 (IBR,
percent for a 2-inch gauge length or 10
see § 171.7 of this subchapter).
percent in other cases.
(e) Exposed bottom welds. Exposed bot-
(2) Flattening is required to 50 pertom welds on cylinders over 18 inches
cent of the original outside diameter
long must be protected by footrings.
without cracking.
(f) Heat treatment. Body and heads
(3) Burst pressure must be at least 3
formed by drawing or pressing must be
times service pressure.
uniformly and properly heat treated
(o) Rejected containers. Reheat-treatprior to tests.
ment of rejected cylinders is author-
(g) Openings. Openings in the cylized. Subsequent thereto, containers
inders must comply with the following:
must pass all prescribed tests to be ac-
(1) Standard taper pipe threads are
ceptable. Repair of welded seams by
required;
welding prior to reheat-treatment is
(2) Length may not be less than as
authorized.
specified for American Standard pipe
(p) Marking. Markings on each conthreads; tapped to gauge; clean cut,
tainer must be stamped plainly and
even, and without checks.
permanently on a permanent attach-
(h) Hydrostatic test. Each cylinder
ment or on a metal nameplate permamust successfully withstand a hydronently secured to the container by
static test as follows:
means other than soft solder.
(1) The test must be by water-jacket,
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
or other suitable method, operated so
amended at 66 FR 45386, 45388, Aug. 28, 2001;
as to obtain accurate data. The pres-
67 FR 51654, Aug. 8, 2002; 67 FR 61015, Sept. 27,
sure gauge must permit reading to an
2002; 68 FR 75748, Dec. 31, 2003]
accuracy of 1 percent. The expansion
gauge must permit reading of total ex-
§ 178.59 Specification 8 steel cylinders
pansion to an accuracy of either 1 perwith porous fillings for acetylene.
cent or 0.1 cubic centimeter.
(a) Type and service pressure. A DOT 8
(2) Pressure must be maintained for
cylinder is a seamless cylinder with a
at least 30 seconds and sufficiently
service pressure of 250 psig. The follonger to ensure complete expansion.
lowing steel is authorized:
Any internal pressure applied after
(1) A longitudinal seam if forge lap
heat-treatment and previous to the ofwelded;
ficial test may not exceed 90 percent of
(2) Attachment of heads by welding
the test pressure.
or by brazing by dipping process; or
(3) Permanent volumetric expansion
(3) A welded circumferential body
may not exceed 10 percent of total volseam if the cylinder has no longituumetric expansion at test pressure.
dinal seam.
(4) One cylinder out of each lot of 200
(b) Steel. Open-hearth, electric or
or less must be hydrostatically tested
basic oxygen process steel of uniform
to at least 750 psig. Cylinders not so
quality must be used. Content percent
tested must be examined under presmay not exceed the following: Carbon,
sure of between 500 and 600 psig and
0.25; phosphorus, 0.045; sulphur, 0.050.
show no defect. If hydrostatically test-
(c) Identification of steel. Materials
ed cylinder fails, each cylinder in the
must be identified by any suitable
lot may be hydrostatically tested and
method except that plates and billets
those passing are acceptable.
for hot-drawn cylinders must be
(i) Leakage test. Cylinders with botmarked with the heat number.
toms closed in by spinning must be
(d) Manufacture. Cylinders must be
subjected to a leakage test by setting
manufactured using equipment and
the interior air or gas pressure to not
processes adequate to ensure that each
less than the service pressure. Cylcylinder produced conforms to the reinders which leak must be rejected.
quirements of this subpart. No defect is
(j) Physical test. A physical test must
acceptable that is likely to weaken the
be conducted as follows:
883
§ 178.59
49 CFR Ch. I (10-1-06 Edition)
(1) The test is required on 2 speci-
(1) Porous filling. (1) Cylinders must
mens cut longitudinally from 1 cylbe filled with a porous material in acinder or part thereof taken at random
cordance with the following:
out of each lot of 200 or less, after heat
(i) The porous material may not distreatment.
integrate or sag when wet with solvent
(2) Specimens must conform to a
or when subjected to normal service;
gauge length of 8 inches with a width
(ii) The porous filling material must
not over 1½ inches, a gauge length of 2
be uniform in quality and free of voids,
inches with width not over 1½, or a
except that a well drilled into the fillgauge length at least 24 times thicking material beneath the valve is authorized if the well is filled with a maness with a width not over 6 times
thickness is authorized when a cylinder
terial of such type that the functions
wall is not over 3/16 inch thick.
of the filling material are not im-
(3) The yield strength in tension
paired;
(iii) Overall shrinkage of the filling
must be the stress corresponding to a
material is authorized if the total
permanent strain of 0.2 percent of the
clearance between the cylinder shell
gauge length. The following conditions
and filling material, after solvent has
apply:
been added, does not exceed 1/2 of 1 per-
(i) The yield strength must be detercent of the respective diameter or
mined by either the "offset" method or
length, but not to exceed 1/8 inch, measthe "extension under load" method as
ured diametrically and longitudinally;
prescribed in ASTM E 8 (IBR, see $171.7
(iv) The clearance may not impair
of this subchapter).
the functions of the filling material;
(ii) In using the "extension under
(v) The installed filling material
load" method, the total strain (or "exmust meet the requirements of CGA C-
tension under load") corresponding to
12 (IBR, see $171.7 of this subchapter);
the stress at which the 0.2 percent perand
manent strain occurs may be deter-
(vi) Porosity of filling material may
mined with sufficient accuracy by calnot exceed 80 percent except that fillculating the elastic extension of the
ing material with a porosity of up to 92
gauge length under appropriate load
percent may be used when tested with
and adding thereto 0.2 percent of the
satisfactory results in accordance with
gauge length. Elastic extension cal-
CGA Pamphlet C-12.
culations must be based on an elastic
(2) When the porosity of each cylmodulus of 30,000,000. In the event of
inder is not known, a cylinder taken at
controversy, the entire stress-strain
random from a lot of 200 or less must
diagram must be plotted and the yield
be tested for porosity. If the test cylstrength determined from the 0.2 offinder fails, each cylinder in the lot
set.
may be tested individually and those
(iii) For the purpose of strain meascylinders that pass the test are accepturement, the initial strain must be set
able.
while the specimen is under a stress of
(3) For filling that is molded and
12,000 psi and the strain indicator readdried before insertion in cylinders, poing being set at the calculated corrosity test may be made on a sample
responding strain.
block taken at random from material
(iv) Cross-head speed of the testing
to be used.
machine may not exceed 1/8 inch per
(4) The porosity of the filling mateminute during yield strength deterrial must be determined. The amount
mination.
of solvent at 70 °F for a cylinder:
(4) Yield strength may not exceed 73
(i) Having shell volumetric capacity
percent of tensile strength. Elongation
above 20 pounds water capacity (nomimust be at least 40 percent in 2 inch or
nal) may not exceed the following:
20 percent in other cases.
Maximum
(k) Rejected cylinders. Reheat treatacetone sol-
Percent porosity of filler
vent percent
ment of rejected cylinder is authorized.
shell capac-
Subsequent thereto, cylinders must
ity by volume
pass all prescribed tests to be acceptable. Repair by welding is authorized.
90 to 92
43.4
884
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.60
Maximum
facture of the cylinders and, upon reacetone sol-
Percent porosity of filler
vent percent
quest, to the purchaser. The test reshell capacports must be retained by the inspector
ity by volume
for fifteen years from the original test
date of the cylinder.
87 to 90
42.0
83 to 87
40.0
(o) Marking. (1) Marking on each cyl-
80 to 83
38.6
inder must be stamped plainly and per-
75 to 80
36.2
manently on or near the shoulder, top
70 to 75
33.8
head, neck or valve protection collar
65 to 70
31.4
which is permanently attached to the
(ii) Having volumetric capacity of 20
cylinder and forming integral part
pounds or less water capacity (nomithereof.
nal), may not exceed the following:
(2) Tare weight of cylinder. in pounds
and ounces, must be marked on the
Maximum
acetone solcylinder.
Percent porosity of filler
vent percent
(3) Cylinders, not completed, when
shell capacdelivered must each be marked for
ity by volume
identification of each lot of 200 or less.
90 to 92
41.8
[Amdt. 178-114, 61 FR 25942. May 23, 1996, as
83 to 90
38.5
amended at 66 FR 45386, Aug. 28, 2001; 67 FR
80 to 83
37.1
61016, Sept. 27, 2002; 67 FR 51654, Aug. 8, 2002;
75 to 80
34.8
32.5
68 FR 75748, 75749, Dec. 31, 2003)
70 to 75
65 to 70
30.2
$178.60 Specification 8AL steel cyl-
(m) Tare weight. The tare weight is
inders with porous fillings for
the combined weight of the cylinder
acetylene.
proper, porous filling. valve, and sol-
(a) Type and service pressure. A DOT
vent, without removable cap.
8AL cylinder is a seamless steel cyl-
(n) Duties of inspector. In addition to
inder with a service pressure of 250
the requirements of $178.35, the inspecpsig. However, the attachment of heads
tor is required toby welding or by brazing by dipping
(1) Certify chemical analyses of steel
process and a welded circumferential
used, signed by manufacturer thereof;
body seam is authorized. Longitudinal
also verify by, check analyses of samseams are not authorized.
ples taken from each heat or from 1 out
(b) Authorized steel. The authorized
of each lot of 200 or less, plates, shells,
steel is as specified in table I of appenor tubes used.
dix A to this part.
(2) Verify compliance of cylinder
(c) Identification of steel. Material
shells with all shell requirements; inmust be identified by any suitable
spect inside before closing in both ends;
method except that plates and billets
verify heat treatment as proper; obtain
all samples for all tests and for check
for hot-drawn cylinders must be
marked with heat number.
analyses; witness all tests; verify
threads by gauge; report volumetric ca-
(d) Manufacture. Cylinders must be
pacity and minimum thickness of wall
manufactured using equipment and
noted.
processes adequate to ensure that each
(3) Prepare report on manufacture of
cylinder produced conforms to the resteel shells in form prescribed in
quirements of this subpart. No defect is
§ 178.35. Furnish one copy to manufacpermitted that is likely to weaken the
turer and three copies to the company
finished cylinder appreciably. A reathat is to complete the cylinders.
sonably smooth and uniform surface
(4) Determine porosity of filling and
finish is required. Welding procedures
tare weights; verify compliance of
and operators must be qualified in acmarking with prescribed requirements;
cordance with CGA Pamphlet C-3 (IBR,
obtain necessary copies of steel shell
see $171.7 of this subchapter).
reports; and furnish complete reports
(e) Footrings. Exposed bottom welds
required by this specification to the
on cylinders over 18 inches long must
person who has completed the manube protected by footrings.
885
$ 178.60
49 CFR Ch. I (10-1-06 Edition)
(f) Welding or brazing. Welding or
that when brazed joints are used, heat
brazing for any purpose whatsoever is
treatment must follow any forming
prohibited except as follows:
and welding operations but may be
(1) The attachment to the tops or
done before, during, or after the brazbottoms of cylinders of neckrings,
ing operations. Liquid quenching is not
footrings, handlers, bosses, pads, and
authorized.
valve protecting rings is authorized
(i) Openings. Standard taper pipe
provided that such attachments and
threads required in all openings. The
the portion of the container to which
length of the opening may not be less
they are attached are made of weldable
than as specified for American Standsteel, the carbon content of which may
ard pipe threads; tapped to gauge;
not exceed 0.25 percent.
clean cut, even, and without checks.
(2) Heat treatment is not required
(j) Hydrostatic test. Each cylinder
after welding or brazing weldable low
must successfully withstand a hydrocarbon parts to attachments, specified
static test as follows:
in paragraph (f)(1) of this section, of
(1) The test must be by water-jacket,
similar material which have been preor other suitable method, operated so
viously welded or brazed to the top or
as to obtain accurate data. The presbottom of cylinders and properly heat
sure gauge must permit reading to an
treated, provided such subsequent
accuracy of 1 percent. The expansion
welding or brazing does not produce a
gauge must permit reading of total extemperature in excess of 400 °F in any
pansion to an accuracy of either 1 perpart of the top or bottom material.
cent or 0.1 cubic centimeter.
(g) Wall thickness; wall stress. The wall
(2) Pressure must be maintained for
thickness/wall stress of the cylinder
at least 30 seconds and sufficiently
must conform to the following:
longer to ensure complete expansion.
(1) The calculated wall stress at 750
Any internal pressure applied after
psi may not exceed 35,000 psi, or oneheat-treatment and previous to the ofhalf of the minimum ultimate strength
ficial test may not exceed 90 percent of
of the steel as determined in paragraph
the test pressure.
(1) of this section, whichever value is
(3) Permanent volumetric expansion
the smaller. The measured wall thickmay not exceed 10 percent of total volness may not include galvanizing or
umetric expansion at test pressure.
other protective coating.
(4) One cylinder out of each lot of 200
(i) Calculation of wall stress must be
or less must be hydrostatically tested
made by the formula:
to at least 750 psig. Cylinders not so
S = [P(1.3D² + 0.4d2)] / (D² - d²)
tested must be examined under pressure of between 500 and 600 psig and
Where:
show no defect. If a hydrostatically
S = wall stress in pounds psi:
tested cylinder fails, each cylinder in
P = 750 psig (minimum test pressure):
the lot may be hydrostatically tested
D = outside diameter in inches;
and those passing are acceptable.
d = inside diameter in inches.
(k) Leakage test. Cylinders with bot-
(ii) Either D or d must be calculated
toms closed in by spinning must be
from the relation D = d + 2t, where t =
leakage tested by setting the interior
minimum wall thickness.
air or gas pressure at not less than the
(2) Cylinders with a wall thickness
service pressure. Any cylinder that
less than 0.100 inch, the ratio of
leaks must be rejected.
straight side wall length to outside di-
(1) Physical test. A physical test must
ameter may not exceed 3.5.
be conducted as follows;
(3) For cylinders having outside di-
(1) The test is required on 2 speciameter over 5 Inches, the minimum
mens cut longitudinally from 1 cylwall thickness must be 0.087 inch.
inder or part thereof taken at random
(h) Heat treatment. Each cylinder
out of each lot of 200 or less, after heat
must be uniformly and properly heat
treatment.
treated, prior to tests, by any suitable
(2) Specimens must conform to a
method in excess of 1100 °F. Heat treatgauge length of 8 inches with a width
ment must be accomplished after all
not over 1½ inches, a gauge length 2
forming and welding operations, except
inches with a width not over 1½ inches,
886
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.60
or a gauge length at least 24 times
(1) Tensile test. A specimen must be
thickness with a width not over 6 times
cut from one cylinder of each lot of 200
thickness is authorized when a cylinder
or less, or welded test plate. The speciwall is not over 3/16 inch thick.
men must be taken from across the
(3) The yield strength in tension
major seam and must be prepared and
must be the stress corresponding to a
tested in accordance with and must
permanent strain of 0.2 percent of the
meet the requirements of CGA Pamgauge length. The following conditions
phlet C-3. Should this specimen fail to
apply:
meet the requirements, specimens may
(i) The yield strength must be deterbe taken from two additional cylinders
mined by either the "offset" method or
or welded test plates from the same lot
the "extension under load" method as
and tested. If either of the latter speciprescribed in ASTM E 8 (IBR, see $171.7
mens fail to meet the requirements,
of this subchapter).
the entire lot represented must be re-
(ii) In using the "extension under
jected.
load" method, the total strain (or "ex-
(2) Guided bend test. A root bend test
tension under load") corresponding to
specimen must be cut from the cylthe stress at which the 0.2 percent perinder or welded test plate, used for the
manent strain occurs may be detertensile test specified in paragraph
mined with sufficient accuracy by cal-
(n)(1) of this section. Specimens must
culating the elastic extension of the
be prepared and tested in accordance
gauge length under appropriate load
with and must meet the requirements
and adding thereto 0.2 percent of the
of CGA Pamphlet C-3.
gauge length. Elastic extension cal-
(3) Alternate guided-bend test. This
culations must be based on an elastic
test may be used and must be as remodulus of 30,000,000. In the event of
quired by CGA Pamphlet C-3. The speccontroversy, the entire stress-strain
imen must be bent until the elongation
diagram must be plotted and the yield
at the outer surface, adjacent to the
strength determined from the 0.2 offroot of the weld, between the lightly
set.
scribed gage lines-a to b, must be at
(iii) For the purpose of strain measleast 20 percent, except that this perurement, the initial strain must be set
centage may be reduced for steels havwhile the specimen is under a stress of
ing a tensile strength in excess of 50,000
12,000 psi, the strain indicator reading
psi, as provided in paragraph (m) of
being set at the calculated corthis section.
responding strain.
(o) Rejected cylinders. Reheat treat-
(iv) Cross-head speed of the testing
ment of rejected cylinders is authormachine may not exceed 1/8 inch per
ized. Subsequent thereto, cylinders
minute during yield strength determust pass all prescribed tests to be acmination.
ceptable. Repair by welding is author-
(m) Elongation. Physical test speciized.
mens must show at least a 40 percent
(p) Porous filling. (1) Cylinders must
elongation for a 2 inch gauge length or
be filled with a porous material in acat least a 20 percent elongation in
cordance with the following:
other cases. Except that these elon-
(i) The porous material may not disgation percentages may be reduced nuintegrate or sag when wet with solvent
merically by 2 for 2 inch specimens and
or when subjected to normal service;
1 in other cases for each 7,500 psi incre-
(ii) The filling material must be uniment of tensile strength above 50,000
form in quality and free of voids, expsi to a maximum of four such increcept that a well drilled into the filling
ments.
material beneath the valve is author-
(n) Weld tests. Specimens taken
ized if the well is filled with a material
across the circumferentially welded
of such type that the functions of the
seam must be cut from one cylinder
filling material are not impaired:
taken at random from each lot of 200 or
(iii) Overall shrinkage of the filling
less cylinders after heat treatment and
material is authorized if the total
must pass satisfactorily the following
clearance between the cylinder shell
tests:
and filling material, after solvent has
887
§ 178.60
49 CFR Ch. I (10-1-06 Edition)
been added, does not exceed 1/2 of 1 perproper, porous filling, valve, and solcent of the respective diameter or
vent, but without removable cap.
length but not to exceed 1/8 inch, meas-
(r) Duties of inspector. In addition to
ured diametrically and longitudinally;
the requirements of § 178.35, the inspec-
(iv) The clearance may not impair
tor shallthe functions of the filling material;
(1) Certify chemical analyses of steel
(v) The installed filling material
used, signed by manufacturer thereof;
must meet the requirements of CGA C-
also verify by check analyses, of sam-
12 (IBR, see $171.7 of this subchapter);
ples taken from each heat or from 1 out
and
of each lot of 200 or less plates, shells,
(vi) Porosity of filling material may
or tubes used.
not exceed 80 percent except that fill-
(2) Verify compliance of cylinder
ing material with a porosity of up to 92
shells with all shell requirements, inpercent may be used when tested with
spect inside before closing in both ends,
satisfactory results in accordance with
verify heat treatment as proper; obtain
CGA Pamphlet C-12.
all samples for all tests and for check
(2) When the porosity of each cylanalyses, witness all tests; verify
inder is not known, a cylinder taken at
threads by gauge, report volumetric carandom from a lot of 200 or less must
pacity and minimum thickness of wall
be tested for porosity. If the test cylnoted.
inder fails, each cylinder in the lot
(3) Report percentage of each specimay be tested individually and those
fied alloying element in the steel. Precylinders that pass the test are acceptpare report on manufacture of steel
able.
shells in form prescribed in $178.35.
(3) For filling that is molded and
Furnish one copy to manufacturer and
dried before insertion in cylinders, pothree copies to the company that is to
rosity test may be made on sample
complete the cylinders.
block taken at random from material
(4) Determine porosity of filling and
to be used.
tare weights; verify compliance of
(4) The porosity of the filling matemarking with prescribed requirements;
rial must be determined; the amount of
obtain necessary copies of steel shell
solvent at 70 °F for a cylinder:
reports prescribed in paragraph (b) of
(i) Having shell volumetric capacity
this section; and furnish complete test
above 20 pounds water capacity (nomireports required by this specification
nal) may not exceed the following:
to the person who has completed the
manufacturer of the cylinders and,
Maximum acetone
Percent porosity of filler
solvent percent shell
upon request, to the purchaser. The
capacity by volume
test reports must be retained by the in-
43.4
spector for fifteen years from the origi-
90 to 92
B7 to 90
42.0
nal test date of the cylinder.
83 to 87
40.0
(s) Marking. (1) Tare weight of cyl-
80 to 83
38.6
inder, in pounds and ounces, must be
75 to 80
36.2
70 to 75
33.8
marked on the cylinder.
65 to 70
31.4
(2) Cylinders, not completed, when
delivered must each be marked for
(ii) Having volumetric capacity of 20
identification of each lot of 200 or less.
pounds or less water capacity (nomi-
(3) Markings must be stamped plainly
nal), may not exceed the following:
and permanently in locations in accordance with the following:
Maximum acetone
Percent porosity of filler
solvent percent shell
(i) On shoulders and top heads not
capacity by volume
less than 0.087 inch thick; or
90 to 92
41.8
(ii) On neck, valve boss, valve protec-
83 to 90
38.5
tion sleeve, or similar part perma-
80 to 83
37.1
nently attached to the top end of cyl-
75 to 80
34.8
32.5
inder; or
70 to 75
65 to 70
30.2
(iii) On a plate of ferrous material attached to the top of the cylinder or
(q) Tare weight. The tare weight is
permanent part thereof; the plate must
the combined weight of the cylinder
be at least 1/16 inch thick, and must be
888
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.61
attached by welding, or by brazing at a
footrings. Minimum thickness of heads
temperature of at least 1,100 °F
may not be less than 90 percent of the
throughout all edges of the plate. Suffirequired thickness of the sidewall.
cient space must be left on the plate to
Heads must be concave to pressure.
provide for stamping at least four (4)
(2) Circumferential seams must be by
retest dates.
electric-arc welding. Joints must be
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
butt with one member offset (joggle
amended at 66 FR 45386, 45388, Aug. 28, 2001;
butt) or lap with minimum overlap of
67 FR 51654. Aug. 8, 2002; 68 FR 75748, 75749,
at least four times nominal sheet
Dec. 31, 2003]
thickness.
(3) Longitudinal seams in shells must
§ 178.61 Specification 4BW welded
conform to the following:
steel cylinders with electric-arc
(i) Longitudinal electric-arc welded
welded longitudinal seam.
seams must be of the butt welded type.
(a) Type, size and service pressure. A
Welds must be made by a machine
DOT 4BW cylinder is a welded type
process including automatic feed and
steel cylinder with a longitudinal elecwelding guidance mechanisms. Longitric-arc welded seam, a water capacity
tudinal seams must have complete
(nominal) not over 1,000 pounds and a
joint penetration, and must be free
service pressure at least 225 and not
from undercuts, overlaps or abrupt
over 500 psig gauge. Cylinders closed in
ridges or valleys. Misalignment of matby spinning process are not authorized.
ing butt edges may not exceed 1/6 of
(b) Authorized steel. Steel used in the
nominal sheet thickness or 1/32 inch
construction of the cylinder must conwhichever is less. All joints with nomiform to the following:
nal sheet thickness up to and including
(1) The body of the cylinder must be
1/8 inch must be tightly butted. When
constructed of steel conforming to the
nominal sheet thickness is greater
limits specified in table 1 of appendix A
than 1/8 inch, the joint must be gapped
to this part.
with maximum distance equal to one-
(2) Material for heads must meet the
half the nominal sheet thickness or 1/32
requirements of paragraph (a) of this
inch whichever is less. Joint design,
section or be open hearth, electric or
preparation and fit-up must be such
basic oxygen carbon steel of uniform
that requirements of this paragraph (d)
quality. Content percent may not exare satisfied.
ceed the following: Carbon 0.25, Man-
(ii) Maximum joint efficiency must
ganese 0.60, Phosphorus 0.045, Sulfur
be 1.0 when each seam is radiographed
0.050. Heads must be hemispherical or
completely. Maximum joint efficiency
ellipsoidal in shape with a maximum
must be 0.90 when one cylinder from
ratio of 2.1. If low carbon steel is used,
each lot of 50 consecutively welded cylthe thickness of such heads must be deinders is spot radiographed. In additermined by using a maximum wall
tion, one out of the first five cylinders
stress of 24,000 p.s.i. in the formula dewelded following a shut down of weldscribed in paragraph (f)(4) of this secing operations exceeding four hours
tion.
must be spot radiographed. Spot
(c) Identification of material. Material
radiographs, when required, must be
must be identified by any suitable
made of a finished welded cylinder and
method.
must include the girth weld for 2
(d) Manufacture. Cylinders must be
inches in both directions from the
manufactured using equipment and
intersection of the longitudinal and
processes adequate to ensure that each
girth welds and include at least 6
cylinder produced conforms to the reinches of the longitudinal weld. Maxquirements of this subpart and the folimum joint efficacy of 0.75 must be perlowing:
missible without radiography.
(1) No defect is permitted that is
(4) Welding procedures and operators
likely to weaken the finished cylinder
must be qualified in accordance with
appreciably. A reasonably smooth and
CGA Pamphlet C-3 (IBR. see $171.7 of
uniform surface is required. Exposed
this subchapter).
bottom welds on cylinders over 18
(e) Welding of attachments. The atinches long must be protected by
tachment to the tops and bottoms only
889
§ 178.61
49 CFR Ch. I (10-1-06 Edition)
of cylinders by welding of neckrings,
(1) All openings must be in the heads
footrings, handles, bosses, pads and
or bases.
valve protection rings is authorized
(2) Openings in cylinders must be proprovided that such attachments and
vided with adequate fittings, bosses, or
the portion of the container to which
pads, integral with or securely atthey are attached are made of weldable
tached to the cylinder by welding.
steel, the carbon content of which may
(3) Threads must comply with the folnot exceed 0.25 percent.
lowing:
(f) Wall thickness. For outside diame-
(i) Threads must be clean cut and to
ters over 6 inches the minimum wall
gauge.
thickness must be 0.078 inch. For a cyl-
(ii) Taper threads must be of length
inder with a wall thickness less than
not less than as specified for American
0.100 inch, the ratio of tangential
Standard Taper Pipe threads.
length to outside diameter may not ex-
(iii) Straight threads, having at least
ceed 4 tol (4:1). In any case the min-
4 engaged threads, to have tight fit and
imum wall thickness must be such that
calculated shear strength at least 10
the wall stress calculated by the fortimes the test pressure of the cylinder;
mula listed in paragraph (f)(4) of this
gaskets required, adequate to prevent
section may not exceed the lesser value
leakage.
of any of the following:
(4) Closure of fittings, boss or pads
(1) The value referenced in paragraph
must be adequate to prevent leakage.
(b) of this section for the particular
(1) Hydrostatic test. Cylinders must
material under consideration.
withstand a hydrostatic test, as fol-
(2) One-half of the minimum tensile
lows:
strength of the material determined as
(1) The test must be by water-jacket,
required in paragraph (j) of this secor other suitable method, operated so
tion.
as to obtain accurate data. The pres-
(3) 35,000 psi.
sure gauge must permit readings to an
(4) Stress must be calculated by the
accuracy of 1 percent. The expansion
following formula:
gauge must permit readings of total
S = [2P(1.3D² + 0.4d²)] / [E(D² - d²)]
volumetric expansion to an accuracy
either of 1 percent or 0.1 cubic centiwhere:
meter.
S = wall stress, psi;
(2) Pressure must be maintained for
P - service pressure, psig;
at least 30 seconds and sufficiently
D = outside diameter, inches;
longer to ensure complete expansion.
d = inside diameter, inches;
Any internal pressure applied after
E = joint efficiency of the longitudinal seam
heat treatment and previous to the of-
(from paragraph (d) of this section).
ficial test may not exceed 90 percent of
(g) Heat treatment. Each cylinder
the test pressure.
must be uniformly and properly heat
(3) Permanent volumetric expansion
treated prior to test by the applicable
may not exceed 10 percent of the total
method referenced in Table 1 of appenvolumetric expansion at test pressure.
dix A to this part. Heat treatment
(4) Cylinders must be tested as folmust be accomplished after all forming
lows:
and welding operations. Heat treat-
(i) At least 1 cylinder selected at ranment is not required after welding or
dom out of each lot of 200 or less must
brazing of weldable low carbon parts to
be tested as outlined in paragraphs
attachments of similar material which
(i)(1), (i)(2). and (i)(3) of this section to
have been previously welded to the top
at least two times service pressure.
or bottom of cylinders and properly
(ii) All cylinders not tested as outheat treated, provided such subsequent
lined in paragraph (i)(4)(i) of this secwelding or brazing does not produce a
tion must be examined under pressure
temperature in excess of 400 °F in any
of at least two times service pressure
part of the top or bottom material.
and show no defect.
(h) Openings in cylinders. Openings in
(5) One finished cylinder selected at
the cylinder must conform to the folrandom out of each lot of 500 or less
lowing:
successively produced must be
890
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.61
hydrostatically tested to 4 times servor the "extension under load" method
ice pressure without bursting.
as prescribed in ASTM E 8 (IBR, see
(j) Physical tests. Cylinders must be
$171.7 of this subchapter).
subjected to a physical test as follows:
(ii) In using the "extension under
(1) Specimens must be taken from
load" method, the total strain (or "exone cylinder after heat treatment and
tension under load"), corresponding to
chosen at random from each lot of 200
the stress at which the 0.2-percent peror less, as follows:
manent strain occurs may be deter-
(i) Body specimen. One specimen
mined with sufficient accuracy by calmust be taken longitudinally from the
culating the elastic extension of the
body section at least 90 degrees away
gauge length under appropriate load
from the weld.
and adding thereto 0.2 percent of the
(ii) Head specimen. One specimen
must be taken from either head on a
gauge length. Elastic extension calculations must be based on an elastic
cylinder when both heads are made of
modulus of 30,000,000. In the event of
the same material. However, if the two
heads are made of differing materials,
controversy, the entire stress-strain
a specimen must be taken from each
diagram must be plotted and the yield
head.
strength determined from the 0.2-per-
(iii) If due to welded attachments on
cent offset.
the top head there is insufficient sur-
(iii) For the purpose of strain measface from which to take a specimen, it
urement, the initial strain reference
may be taken from a representative
must be set while the specimen is
head of the same heat treatment as the
under a stress of 12,000 psi and the
test cylinder.
strain indicator reading being set at
(2) Specimens must conform to the
the calculated corresponding strain.
following:
(iv) Cross-head speed of the testing
(i) A gauge length of 8 inches with a
machine may not exceed 1/8 inch per
width not over 1½ inches, a gauge
minute during yield strength deterlength of 2 inches with a width not
mination.
over 1½ inches, or a gauge length at
(k) Elongation. Physical test specileast 24 times thickness with a width
mens must show at least a 40 percent
not over 6 times thickness is authorelongation for a 2-inch gauge length or
ized when a cylinder wall is not over 3/16
at least a 20 percent elongation in
inch thick.
other cases. Except that these elon-
(ii) The specimen, exclusive of grip
gation percentages may be reduced nuends, may not be flattened. Grip ends
merically by 2 for 2-inch specimens and
may be flattened to within 1 inch of
by 1 in other cases for each 7,500 psi ineach end of the reduced section.
crement of tensile strength above 50,000
(iii) When size of the cylinder does
psi to a maximum of four increments.
not permit securing straight speci-
(1) Tests of welds. Welds must be submens, the specimens may be taken in
jected to the following tests:
any location or direction and may be
straightened or flattened cold, by pres-
(1) Tensile test. A specimen must be
sure only, not by blows when specicut from one cylinder of each lot of 200
mens are so taken and prepared, the inor less. The specimen must be taken
spector's report must show in connecfrom across the longitudinal seam and
tion with record of physical tests demust be prepared and tested in accordtailed information in regard to such
ance with and must meet the requirespecimens.
ments of CGA Pamphlet C-3.
(iv) Heating of a specimen for any
(2) Guided bend test. A root test specipurpose is not authorized.
men must be cut from the cylinder
(3) The yield strength in tension
used for the tensile test specified in
must be the stress corresponding to a
paragraph (1)(1) of this section. Specipermanent strain of 0.2 percent of the
mens must be taken from across the
gauge length. The following conditions
longitudinal seam and must be preapply:
pared and tested in accordance with
(i) The yield strength must be deterand must meet the requirements of
mined by either the "off-set" method
CGA Pamphlet C-3.
891
§ 178.65
49 CFR Ch. I (10-1-06 Edition)
(3) Alternate guided bend test. This
tached by welding, or by brazing. The
test may be used and must be as rebrazing rod is to melt at a temperature
quired by CGA Pamphlet C-3. The specof 1100 °F Welding or brazing must be
imen must be bent until the elongation
along all the edges of the plate.
at the outer surface, adjacent to the
(3) On the neck, valve boss, valve proroot of the weld, between the lightly
tection sleeve, or similar part permascribed gauge lines a to b, must be at
nently attached to the top of the cylleast 20 percent, except that this perinder.
centage may be reduced for steels hav-
(4) On the footring permanently ating a tensile strength in excess of 50,000
tached to the cylinder, provided the
psi, as provided in paragraph (k) of this
water capacity of the cylinder does not
section.
exceed 25 pounds.
(m) Radiographic examination. Welds
(p) Inspector's report. In addition to
of the cylinders must be subjected to a
the information required by $178.35, the
radiographic examination as follows:
inspector's report must indicate the
(1) Radiographic inspection must
type and amount of radiography.
conform to the techniques and accept-
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
ability criteria set forth in CGA Pamamended at 64 FR 51919. Sept. 27, 1999: 66 FR
phlet C-3. When fluoroscopic inspection
45386, 45388, Aug. 28, 2001; 67 FR 51654, Aug. 6,
is used, permanent film records need
2002; 67 FR 61016, Sept. 27, 2002; 68 FR 57633,
not be retained.
Oct. 6, 2003; 68 FR 75748, Dec. 31, 2003)
(2) Should spot radiographic examination fail to meet the requirements
§ 178.65 Specification 39 non-reusable
of paragraph (m)(1) of this section, two
(non-refillable) cylinders.
additional welds from the same lot of
(a) Type, size, service pressure, and test
50 cylinders or less must be examined,
pressure. A DOT 39 cylinder is a seamand if either of these fail to meet the
less, welded, or brazed cylinder with a
requirements, each cylinder must be
service pressure not to exceed 80 perexamined as previously outlined; only
cent of the test pressure. Spherical
those passing are acceptable.
pressure vessels are authorized and
(n) Rejected cylinders. (1) Unless othcovered by references to cylinders in
erwise stated, if a sample cylinder or
this specification.
specimen taken from a lot of cylinders
(1) Size limitation. Maximum water cafails the prescribed test, then two addipacity may not exceed: (i) 55 pounds
tional specimens must be selected from
(1,526 cubic inches) for a service presthe same lot and subjected to the presure of 500 p.s.i.g. or less, and (ii) 10
scribed test. If either of these fails the
pounds (277 cubic inches) for a service
test, then the entire lot must be repressure in excess of 500 p.s.i.g.
jected.
(2) Test pressure. The minimum test
(2) Reheat treatment of rejected cylpressure is the maximum pressure of
inders is authorized. Subsequent therecontents at 130 °F or 180 p.s.i.g. whichto, cylinders must pass all prescribed
ever is greater.
tests to be acceptable. Repair of welded
(3) Pressure of contents. The term
seams by welding is authorized pro-
"pressure of contents" as used in this
vided that all defective metal is cut
specification means the total pressure
away and the joint is rewelded as preof all the materials to be shipped in the
scribed for original welded joints.
cylinder.
(o) Markings. Markings must be
(b) Material: steel or aluminum. The
stamped plainly and permanently in
cylinder must be constructed of either
any of the following locations on the
steel or aluminum conforming to the
cylinder:
following requirements:
(1) On shoulders and top heads when
(1) Steel. (i) The steel analysis must
they are not less than 0.087-inch thick.
conform to the following:
(2) On a metal plate attached to the
Ladle
Check
top of the cylinder or permanent part
analysis
analysis
thereof; sufficient space must be left on
the plate to provide for stamping at
Carbon, maximum percent
0.12
0.15
least six retest dates; the plate must be
Phosphorus, maximum percent
.04
.05
Sulfur, maximum percent
.05
.06
at least 1/16-inch thick and must be at-
892
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.65
(ii) For a cylinder made of seamless
minimum strength of the shell matesteel tubing with integrally formed
rial in the finished cylinder.
ends, hot drawn, and finished, content
(3) Attachments to the cylinder are
percent for the following may not expermitted by any means which will not
ceed: Carbon, 0.55; phosphorous, 0.045;
be detrimental to the integrity of the
sulfur, 0.050.
cylinder. Welding or brazing of attach-
(iii) For non-heat treated welded
ments to the cylinder must be comsteel cylinders, adequately killed deep
pleted prior to all pressure tests.
drawing quality steel is required.
(4) Welding procedures and operators
(iv) Longitudinal or helical welded
must be qualified in accordance with
cylinders are not authorized for service
CGA Pamphlet C-3 (IBR, see $171.7 of
pressures in excess of 500 p.s.i.g.
this subchapter).
(2) Aluminum. Aluminum is not au-
(d) Wall thickness. The minimum wall
thorized for service pressures in excess
thickness must be such that the wall
of 500 psig. The analysis of the alustress at test pressure does not exceed
minum must conform to the Aluminum
the yield strength of the material of
Association standard for alloys 1060,
the finished cylinder wall. Calculations
1100, 1170, 3003, 5052, 5086, 5154, 6061, and
must be made by the following for-
6063, as specified in its publication enmulas:
titled "Aluminum Standards and
(1) Calculation of the stress for cyl-
Data" (IBR, see $171.7 of this subinders must be made by the following
chapter).
formula:
(3) Material with seams, cracks, lam-
S = [P(1.3D² + 0.4d2)] / (D² - d²)
inations, or other injurious defects not
permitted.
Where:
(4) Material used must be identified
S = Wall stress, in psi;
by any suitable method.
P = Test pressure in psig:
(c) Manufacture. (1) General manufac-
D = Outside diameter, in inches;
d = Inside diameter, in inches.
turing requirements are as follows:
(i) The surface finish must be uni-
(2) Calculation of the stress for
form and reasonably smooth.
spheres must be made by the following
(ii) Inside surfaces must be clean,
formula:
dry, and free of loose particles.
S = PD / 4t
(iii) No defect of any kind is permitted if it is likely to weaken a fin-
Where:
ished cylinder.
S = Wall stress. in psi:
(2) Requirements for seams:
P = Test pressure 1 psig:
(i) Brazing is not authorized on alu-
D = Outside diameter, in inches;
t = Minimum wall thickness, in inches.
minum cylinders.
(ii) Brazing material must have a
(e) Openings and attachments. Openmelting point of not lower than 1,000
ings and attachments must conform to
°F.
the following:
(iii) Brazed seams must be assembled
(1) Openings and attachments are
with proper fit to ensure complete penpermitted on heads only.
etration of the brazing material
(2) All openings and their reinforcethroughout the brazed joint.
ments must be within an imaginary
(iv) Minimum width of brazed joints
circle, concentric to the axis of the cylmust be at least four times the thickinder. The diameter of the circle may
ness of the shell wall.
not exceed 80 percent of the outside di-
(v) Brazed seams must have design
ameter of the cylinder. The plane of
strength equal to or greater than 1.5
the circle must be parallel to the plane
times the minimum strength of the
of a circumferential weld and normal
shell wall.
to the long axis of the cylinder.
(vi) Welded seams must be properly
(3) Unless a head has adequate thickaligned and welded by a method that
ness, each opening must be reinforced
provides clean, uniform joints with
by a securely attached fitting, boss,
adequate penetration.
pad, collar, or other suitable means.
(vii) Welded joints must have a
(4) Material used for welded openings
strength equal to or greater than the
and attachments must be of weldable
893
$ 178.65
49 CFR Ch. I (10-1-06 Edition)
quality and compatible with the mate-
(4) Cylinders and test rings may not
rial of the cylinder.
crack when flattened so that their
(f) Pressure tests. (1) Each cylinder
outer surfaces are not more than six
must be tested at an internal pressure
times wall thickness apart when made
of at least the test pressure and must
of steel or not more than ten times
be held at that pressure for at least 30
wall thickness apart when made of aluseconds.
minum.
(i) The leakage test must be con-
(5) If any cylinder or ring cracks
ducted by submersion under water or
when subjected to the specified flatby some other method that will be
tening test, the lot of cylinders repequally sensitive.
resented by the test must be rejected
(ii) If the cylinder leaks, evidences
(see paragraph (h) of this section).
visible distortion, or any other defect,
(h) Rejected cylinders. Rejected cylwhile under test, it must be rejected
inders must conform to the following
(see paragraph (h) of this section).
requirements:
(2) One cylinder taken from the be-
(1) If the cause for rejection of a lot
ginning of each lot, and one from each
is determinable, and if by test or in-
1,000 or less successively produced
spection defective cylinders are elimiwithin the lot thereafter, must be
nated from the lot, the remaining cylhydrostatically tested to destruction.
inders must be qualified as a new lot
The entire lot must be rejected (see
under paragraphs (f) and (g) of this secparagraph (h) of this section) if:
tion.
(i) A failure occurs at a gage pressure
(2) Repairs to welds are permitted.
less than 2.0 times the test pressure;
Following repair, a cylinder must pass
(ii) A failure initiates in a braze or a
the pressure test specified in paragraph
weld or the heat affected zone thereof;
(f) of this section.
(iii) A failure is other than in the
(3) If a cylinder made from seamless
sidewall of a cylinder longitudinal with
steel tubing fails the flattening test deits long axis; or
scribed in paragraph (g) of this section,
(iv) In a sphere. a failure occurs in
suitable uniform heat treatment must
any opening, reinforcement. or at a
be used on each cylinder in the lot. All
point of attachment.
prescribed tests must be performed
(3) A "lot" is defined as the quantity
subsequent to this heat treatment.
of cylinders successively produced per
(i) Markings. (1) The markings reproduction shift (not exceeding 10
quired by this section must be durable
hours) having identical size, design,
and waterproof. The requirements of
construction, material, heat treat-
$178.35(h) do not apply to this section.
ment, finish, and quality.
(2) Required markings are as follows:
(g) Flattening test. One cylinder must
(i) DOT-39.
be taken from the beginning of produc-
(ii) NRC.
tion of each lot (as defined in para-
(iii) The service pressure.
graph (f)(3) of this section) and sub-
(iv) The test pressure.
jected to a flattening test as follows:
(v) The registration number (M****)
(1) The flattening test must be made
of the manufacturer.
on a cylinder that has been tested at
(vi) The lot number.
test pressure.
(vii) The date of manufacture if the
(2) A ring taken from a cylinder may
lot number does not establish the date
be flattened as an alternative to a test
of manufacture.
on a complete cylinder. The test ring
(viii) With one of the following statemay not include the heat affected zone
ments:
or any weld. However, for a sphere, the
(A) For cylinders manufactured prior
test ring may include the circumferento October 1, 1996: "Federal law forbids
tial weld if it is located at a 45 degree
transportation if refilled-penalty up to
angle to the ring, ±5 degrees.
$25,000 fine and 5 years imprisonment
(3) The flattening must be between 60
(49 U.S.C. 1809)" or "Federal law fordegrees included-angle, wedge shaped
bids transportation if refilled-penalty
knife edges, rounded to a 0.5 inch raup to $500,000 fine and 5 years imprisondius.
ment (49 U.S.C. 5124)."
894
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.68
(B) For cylinders manufactured on or
TABLE 1-AUTHORIZED MATERIALS-Continued
after October 1, 1996: "Federal law for-
Chemical analysis-limits in
bids transportation if refilled-penalty
Designation
percent 5154
up to $500,000 fine and 5 years imprisonment (49 U.S.C. 5124)."
Aluminum
remainder.
(3) The markings required by para-
1 Analysis must regularly be made only for the elements
graphs (i)(2)(i) through (i)(2)(v) of this
specifically mentioned in this table. If, however, the presence
of other elements is indicated in the course of routine analsection must be in numbers and letters
ysis, further analysis should be made to determine conformat least 1/8 inch high and displayed seance with the limits specified for other elements.
quentially. For example:
(c) Identification. Material must be
DOT-39 NRC 250/500 M1001.
identified by any suitable method that
will identify the alloy and manufactur-
(4) No person may mark any cylinder
er's lot number.
with the specification identification
(d) Manufacture. Cylinders must be
"DOT-39" unless it was manufactured
manufactured using equipment and
in compliance with the requirements of
this section and its manufacturer has a
processes adequate to ensure that each
registration number (M****) from the
cylinder produced conforms to the re-
Associate Administrator.
quirements of this subpart. No defect is
permitted that is likely to weaken the
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
finished cylinder appreciably. A reaamended at 65 FR 58631, Sept. 29. 2000; 66 FR
sonably smooth and uniform surface
45389, Aug. 28. 2001; 67 FR 51654, Aug. 8, 2002:
finish is required. All welding must be
68 FR 75748, 75749, Dec. 31, 2003]
by the gas shielded arc process.
§ 178.68 Specification 4E welded alu-
(e) Welding. The attachment to the
minum cylinders.
tops and bottoms only of cylinders by
(a) Type, size and service pressure. A
welding of neckrings or flanges,
DOT 4E cylinder is a welded aluminum
footrings, handles, bosses and pads and
cylinder with a water capacity (nomivalve protection rings is authorized.
nal) of not over 1,000 pounds and a serv-
However, such attachments and the
ice pressure of at least 225 to not over
portion of the cylinder to which it is
500 psig. The cylinder must be conattached must be made of weldable alustructed of not more than two seamless
minum alloys.
drawn shells with no more than one
(f) Wall thickness. The wall thickness
circumferential weld. The circumferenof the cylinder must conform to the
tial weld may not be closer to the point
following:
of tangency of the cylindrical portion
(1) The minimum wall thickness of
with the shoulder than 20 times the
the cylinder must be 0.140 inch. In any
cylinder wall thickness. Cylinders or
case, the minimum wall thickness
shells closed in by spinning process and
must be such that calculated wall
cylinders with longitudinal seams are
stress at twice service pressure may
not authorized.
not exceed the lesser value of either of
(b) Authorized material. The cylinder
the following:
must be constructed of aluminum of
(i) 20,000 psi.
uniform quality. The following chem-
(ii) One-half of the minimum tensile
ical analyses are authorized:
strength of the material as required in
TABLE 1-AUTHORIZED MATERIALS
paragraph (j) of this section.
(2) Calculation must be made by the
Designation
Chemical analysis-limits in
percent 51541
following formula:
S = [P(1.3D² + 0.4d²)] / (D² - d²)
Iron plus silicon
0.45 maximum.
Copper
0.10 maximum.
Where:
Manganese
0.10 maximum.
Magnesium
3.10/3.90.
S = wall stress in psi;
Chromium
0.15/0.35.
P = minimum test pressure prescribed for
Zinc
0.20 maximum.
water jacket test;
Titanium
0.20 maximum.
D = outside diameter in inches;
Others, each
0.05 maximum.
d - inside diameter in inches.
Others, total
0.15 maximum.
895
§ 178.68
49 CFR Ch. I (10-1-06 Edition)
(3) Minimum thickness of heads and
(i) At least one cylinder selected at
bottoms may not be less than the minrandom out of each lot of 200 or less
imum required thickness of the side
must be tested in accordance with
wall.
paragraphs (h)(1). (h)(2), and (h)(3) of
(g) Opening in cylinder. Openings in
this section.
cylinders must conform to the fol-
(ii) All cylinders not tested as prolowing:
vided in paragraph (h)(4)(i) of this sec-
(1) All openings must be in the heads
tion must be examined under pressure
or bases.
of at least 2 times service pressure and
(2) Each opening in cylinders, except
show no defect.
those for safety devices, must be pro-
(5) One finished cylinder selected at
vided with a fitting, boss, or pad, serandom out of each lot of 1,000 or less
curely attached to cylinder by welding
must be hydrostatically tested to 4
by inert gas shielded arc process or by
times the service pressure without
threads. If threads are used, they must
bursting. Inability to meet this recomply with the following:
quirement must result in rejection of
(i) Threads must be clean-cut, even,
the lot.
without checks and cut to gauge.
(i) Flattening test. After hydrostatic
(ii) Taper threads to be of length not
testing, a flattening test is required on
less than as specified for American
one section of a cylinder, taken at ran-
Standard taper pipe threads.
dom out of each lot of 200 or less as fol-
(iii) Straight threads, having at least
lows:
4 engaged threads, to have tight fit and
(1) If the weld is not at midlength of
calculated shear strength at least 10
the cylinder, the test section must be
times the test pressure of the cylinder;
no less in width than 30 times the cylgaskets required, adequate to prevent
inder wall thickness. The weld must be
leakage.
in the center of the section. Weld rein-
(3) Closure of a fitting, boss, or pad
forcement must be removed by machinmust be adequate to prevent leakage.
ing or grinding so that the weld is flush
(h) Hydrostatic test. Each cylinder
with the exterior of the parent metal.
must successfully withstand a hydro-
There must be no evidence of cracking
static test, as follows:
in the sample when it is flattened be-
(1) The test must be by water jacket,
tween flat plates to no more than 6
or other suitable method, operated so
times the wall thickness.
as to obtain accurate data. The pres-
(2) If the weld is at midlength of the
sure gauge must permit reading to an
cylinder, the test may be made as specaccuracy of 1 percent. The expansion
ified in paragraph (i)(f) of this section
gauge must permit a reading of the
or must be made between wedge shaped
total expansion to an accuracy either
knife edges (60° angle) rounded to a 1/2
of 1 percent or 0.1 cubic centimeter.
inch radius. There must be no evidence
(2) Pressure of 2 times service presof cracking in the sample when it is
sure must be maintained for at least 30
flattened to no more than 6 times the
seconds and sufficiently longer to inwall thickness.
sure complete expansion. Any internal
(j) Physical test. A physical test must
pressure applied previous to the official
be conducted to determine yield
test may not exceed 90 percent of the
strength, tensile strength, elongation,
test pressure. If, due to failure of the
and reduction of area of material as
test apparatus, the test pressure canfollows:
not be maintained, the test may be re-
(1) The test is required on 2 specipeated at a pressure increased by 10
mens cut from one cylinder or part
percent over the pressure otherwise
thereof taken at random out of each
specified.
lot of 200 or less.
(3) Permanent volumetric expansion
(2) Specimens must conform to the
may not exceed 12 percent of total volfollowing:
umetric expansion at test pressure.
(i) A gauge length of 8 inches with a
(4) Cylinders having a calculated wall
width not over 1½ inches, a gauge
stress of 18,000 psi or less at test preslength of 2 inches with a width not
sure may be tested as follows:
over 1½ inches.
896
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.69
(ii) The specimen, exclusive of grip
ments, the entire lot represented must
ends, may not be flattened. Grip ends
be rejected.
may be flattened to within 1 inch of
(2) Guided bend test. A bend test specieach end of the reduced section.
men must be cut from the cylinder
(iii) When size of cylinder does not
used for the physical tests specified in
permit securing straight specimens,
paragraph (j) of this section. Specimen
the specimens may be taken in any lomust be taken across the seam, must
cation or direction and may be
be 1½ inches wide, edges must be parstraightened or flattened cold, by presallel and rounded with a file, and backsure only, not by blows; when speciup strip, if used, must be removed by
mens are so taken and prepared, the inmachining. The specimen must be bent
spector's report must show in connecto refusal in the guided bend test jig iltion with record of physical test delustrated in paragraph 6.10 of CGA
tailed information in regard to such
Pamphlet C-3 (IBR, see § 171.7 of this
specimens.
subchapter). The root of the weld (in-
(iv) Heating of a specimen for any
side surface of the cylinder) must be lopurpose is not authorized.
cated away from the ram of the jig. No
(3) The yield strength in tension
specimen must show a crack or other
must be the stress corresponding to a
open defect exceeding 1/8 inch in any dipermanent strain of 0.2 percent of the
rection upon completion of the test.
gauge length. The following conditions
Should this specimen fall to meet the
apply:
requirements, specimens may be taken
(i) The yield strength must be deterfrom each of 2 additional cylinders
mined by the "offset" method as prefrom the same lot and tested. If either
scribed in ASTM E 8 (IBR, see $171.7 of
of the latter specimens fail to meet rethis subchapter).
quirements, the entire lot represented
(ii) Cross-head speed of the testing
must be rejected.
machine may not exceed 1/8 inch per
(m) Rejected cylinders. Repair of weldminute during yield strength detered seams is authorized. Acceptable cylmination.
inders must pass all prescribed tests.
(k) Acceptable results for physical tests.
(n) Inspector's report. In addition to
An acceptable result of the physical
the information required by $178.35, the
test requires an elongation to at least
record of chemical analyses must also
7 percent and yield strength not over 80
include applicable information on iron,
percent of tensile strength.
titanium, zinc, and magnesium used in
(1) Weld tests. Welds of the cylinder
the construction of the cylinder.
are required to successfully pass the
following tests:
[Amdt. 178-114, 61 FR 25942, May 23, 1996, as
(1) Reduced section tensile test. A speciamended at 62 FR 51561, Oct. 1, 1997; 66 FR
men must be cut from the cylinder
45386, Aug. 28, 2001: 67 FR 51654, Aug. 8, 2002;
used for the physical tests specified in
68 FR 75748. Dec. 31. 2003; 69 FR 54046, Sept.
paragraph (j) of this section. The speci-
7. 2004]
men must be taken from across the
§ 178.69 Responsibilities and requireseam, edges must be parallel for a disments for manufacturers of UN
tance of approximately 2 inches on eipressure receptacles.
ther side of the weld. The specimen
must be fractured in tension. The ap-
(a) Each manufacturer of a UN presparent breaking stress calculated on
sure receptacle marked with "USA" as
the minimum wall thickness must be
a country of approval must comply
at least equal to 2 times the stress calwith the requirements in this section.
culated under paragraph (f)(2) of this
The manufacturer must maintain a
section, and in addition must have an
quality system, obtain an approval for
actual breaking stress of at least 30,000
each initial pressure receptacle design
psi. Should this specimen fail to meet
type, and ensure that all production of
the requirements, specimens may be
UN pressure receptacles meets the aptaken from 2 additional cylinders from
plicable requirements.
the same lot and tested. If either of the
(1) Quality system. The manufacturer
latter specimens fails to meet requireof a UN pressure receptacle must have
897
§ 178.70
49 CFR Ch. I (10-1-06 Edition)
its quality system approved by the Asity system as approved by the Assosociate Administrator. The quality sysciate Administrator. The manufacturer
tem will initially be assessed through
shall notify the Associate Adminisan audit by the Associate Administrator of any intended changes to the
trator or his or her representative to
approved quality system prior to makdetermine whether it meets the Γe-
ing the change. The Associate Adminisquirements of this section. The Assotrator will evaluate the proposed
clate Administrator will notify the
change to determine whether the
manufacturer in writing of the results
amended quality system will satisfy
of the audit. The notification will conthe requirements. The Associate Adtain the conclusions of the audit and
ministrator will notify the manufacany corrective action required. The Asturer of the findings.
sociate Administrator may perform
(b) Design type approvals. The manuperiodic audits to ensure that the manfacturer must have each pressure reufacturer operates in accordance with
ceptacle design type reviewed by an IIA
the quality system. Reports of periodic
and approved by the Associate Adminaudits will be provided to the manufacistrator in accordance with $178.70. A
turer. The manufacturer must bear the
cylinder is considered to be of a new
cost of audits.
design, compared with an existing ap-
(2) Quality system documentation. The
proved design, as stated in the applicamanufacturer must be able to demble ISO design, construction and testonstrate a documented quality system.
ing standard.
Management must review the adequacy
(c) Production inspection and certifiof the quality system to assure that it
cation. The manufacturer must ensure
is effective and conforms to the rethat each UN pressure receptacle is inquirements in $178.70. The quality sysspected and certified in accordance
tem records must be in English and
with $178.71.
must include detailed descriptions of
[71 FR 33885, June 12, 2006]
the following:
(i) The organizational structure and
§ 178.70 Approval of UN pressure reresponsibilities of personnel with receptacles.
gard to design and product quality;
(a) Initial design-type approval. The
(ii) The design control and design
manufacturer of a UN pressure recepverification techniques, processes, and
tacle must obtain an initial design
procedures used when designing the
type approval from the Associate Adpressure receptacles;
ministrator. The initial design type ap-
(iii) The relevant procedures for presproval must be of the pressure recepsure receptacle manufacturing, quality
tacle design as it is intended to be procontrol, quality assurance, and process
duced. The manufacturer must arrange
operation instructions;
for an IIA, approved by the Associate
(iv) Inspection and testing meth-
Administrator in accordance with subodologies, measuring and testing equippart I of part 107 of this chapter, to
ment, and calibration data;
perform a pre-audit of its pressure re-
(v) The process for meeting customer
ceptacle manufacturing operation prior
requirements;
to having an audit conducted by the
(vi) The process for document control
Associate Administrator or his desand document revision;
ignee.
(vii) The system for controlling non-
(b) IIA pre-audit. The manufacturer
conforming material and records, inmust submit an application for initial
cluding procedures for identification,
design type approval to the IIA for resegregation, and disposition;
view. The IIA will examine the manu-
(viii) Production, processing and fabfacturer's application for initial design
rication, including purchased compotype approval for completeness. An innents, in-process and final materials;
complete application will be returned
and
to the manufacturer with an expla-
(ix) Training programs for relevant
nation. If an application is complete,
personnel.
the IIA will review all technical docu-
(3) Maintenance of quality system. The
mentation, including drawings and calmanufacturer must maintain the qualculations, to verify that the design
898
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.70
meets all requirements of the applica-
(4) Details of any refusal of approval
ble UN pressure receptacle standard
of a similar application by a designated
and specification requirements. If the
approval agency of another country.
technical documentation shows that
(5) The name and address of the prothe pressure receptacle prototype deduction IIA that will perform the funcsign conforms to the applicable standtions prescribed in paragraph (e) of this
ards and requirements in $178.70, the
section. The IIA must be approved in
manufacturer will fabricate a protowriting by the Associate Administrator
type lot of pressure receptacles in conin accordance with subpart I of part 107
formance with the technical docuof this chapter.
mentation representative of the design.
(6) Documentation on the manufac-
The IIA will verify that the prototype
turing facility as specified in $178.69.
lot conforms to the applicable require-
(7) Design specifications and manuments by selecting pressure receptacles
facturing drawings, showing compoand witnessing their testing. After pronents and subassemblies if relevant, detotype testing has been satisfactorily
sign calculations, and material specicompleted, showing the pressure recepfications necessary to verify complitacles fully conform to all applicable
ance with the applicable pressure respecification requirements, the certiceptacle design standard.
fying IIA must prepare a letter of rec-
(8) Manufacturing procedures and
any applicable standards that describe
ommendation and a design type apin detail the manufacturing processes
proval certificate. The design type apand control.
proval certificate must contain the
(9) Design type approval test reports
name and address of the manufacturer
detailing the results of examinations
and the ILA certifying the design type,
and tests conducted in accordance with
the test results, chemical analyses, lot
the relevant pressure receptacle standidentification, and all other supporting
ard, to include any additional data,
data specified in the applicable ISO desuch as suitability for underwater apsign, construction and testing standplications or compatibility with hydroard. The IIA must provide the certifigen embrittlement gases.
cate and documentation to the manu-
(d) Modification of approved pressure
facturer.
receptacle design type. Modification of
(c) Application for initial design type
an approved UN pressure receptacle deapproval. If the pre-audit is found satissign type is not authorized without the
factory by the IIA, the manufacturer
approval of the Associate Adminiswill submit the letter of recommendatrator. A manufacturer seeking modition from the IIA and an application
fication of an approved UN pressure refor design type approval to the Assoceptacle design type may be required
clate Administrator. An application for
to submit design qualification test
initial design type approval must be
data to the Associate Administrator
submitted for each manufacturing fabefore production. An audit may be recility. The application must be in
quired as part of the process to modify
English and, at a minimum, contain
an approval.
the following information:
(e) Responsibilities of the production
(1) The name and address of the man-
IIA. The production IIA is responsible
ufacturing facility. If the application is
for ensuring that each pressure recepsubmitted by an authorized representatacle conforms to the design type aptive on behalf of the manufacturer, the
proval. The production IIA must perform the following functions:
application must include the represent-
(1) Witness all inspections and tests
ative's name and address.
specified in the UN pressure receptacle
(2) The name and title of the indistandard to ensure compliance with the
vidual responsible for the manufacturstandard and that the procedures
er's quality system, as required by
adopted by the manufacturer meet the
$178.69.
requirements of the standard;
(3) The designation of the pressure
(2) Verify that the production inspecreceptacle and the relevant pressure retions were performed in accordance
ceptacle standard.
with this section;
899
§ 178.70
49 CFR Ch. I (10-1-06 Edition)
(3) Select UN pressure receptacles
(g) Recordkeeping. The production IIA
from a prototype production lot and
and the manufacturer must retain a
witness testing as required for the decopy of the design type approval cersign type approval;
tificate and certificate of compliance
(4) Ensure that the various design
records for at least 20 years.
type approval examinations and tests
(h) Denial of design type application. If
are performed accurately;
the design type application is denied,
(5) Verify that each pressure recepthe Associate Administrator will notacle is marked in accordance with the
tify the applicant in writing and proapplicable requirements in $178.72; and
vide the reason for the denial. The
(6) Furnish complete test reports to
manufacturer may request that the Asthe manufacturer and upon request to
sociate Administrator reconsider the
the purchaser. The test reports and
decision. The application request
certificate of compliance must be remust-
tained by the IIA for at least 20 years
(1) Be written in English and filed
from the original test date of the preswithin 60 days of receipt of the decisure receptacles.
sion;
(f) Production inspection audit and cer-
(2) State in detail any alleged errors
tification. (1) If the application, design
of fact and law; and
drawing and quality control documents
(3) Enclose any additional informaare found satisfactory, PHMSA will
tion needed to support the request to
schedule an on-site audit of the presreconsider.
sure receptacle manufacturer's quality
(i) Appeal. (1) A manufacturer whose
system, manufacturing processes, inreconsideration request is denied may
spections, and test procedures.
appeal to the PHMSA Administrator.
(2) During the audit, the manufac-
The appeal mustturer will be required to produce pres-
(i) Be written in English and filed
sure receptacles to the technical standwithin 60 days of receipt of the Assoards for which approval is sought.
clate Administrator's decision on re-
(3) The production IIA must witness
consideration;
the required inspections and
verifications on the pressure recep-
(ii) State in detail any alleged errors
of fact and law;
tacles during the production run. The
IIA selected by the manufacturer for
(iii) Enclose any additional informaproduction inspection and testing may
tion needed to support the appeal; and
be different from the IIA who per-
(iv) State in detail the modification
formed the design type approval
of the final decision sought.
verifications.
(2) The PHMSA Administrator will
(4) If the procedures and controls are
grant or deny the relief and inform the
deemed acceptable, test sample presappellant in writing of the decision.
sure receptacles will be selected at ran-
PHMSA Administrator's decision is the
dom from the production lot and sent
final administrative action.
to a laboratory designated by the Asso-
(j) Termination of a design type apciate Administrator for verification
proval certificate. (1) The Associate Adtesting.
ministrator may terminate an approval
(5) If the pressure receptacle test
certificate issue under this section if it
samples are found to conform to all the
is determined that, because of a change
applicable requirements, the Associate
in circumstances, the approval no
Administrator will issue approvals to
longer is needed or no longer would be
the manufacturer and the production
granted if applied for; information
IIA to authorize the manufacture of
upon which the approval was based is
the pressure receptacles. The approved
fraudulent or substantially erroneous;
design type approval certificate will be
or termination of the approval is necreturned to the manufacturer.
essary to adequately protect against
(6) Upon the receipt of the approved
risks to life and property.
design type approval certificate from
(2) Before an approval is terminated,
the Associate Administrator, the presthe Associate Administrator will prosure receptacle manufacturer must
vide the manufacturer and the apsign the certificate.
proval agency-
900
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.71
(i) Written notice of the facts or con-
(1) Following the final heat treatduct believed to warrant the withment, all cylinders, except those sedrawal;
lected for batch testing must be sub-
(ii) Opportunity to submit oral and
jected to a hydraulic volumetric expanwritten evidence, and
sion test.
(iii) Opportunity to demonstrate or
(2) The standard requirements appliachieve compliance with the applicacable to UN pressure receptacles may
tion requirement.
be varied only if approved in writing by
(3) If the Associate Administrator dethe Associate Administrator.
termines that a certificate of approval
(3) The test pressure of UN cylinders,
must be withdrawn to preclude a sigtubes, and bundles of cylinders must
nificant and imminent adverse affect
conform to the requirements in part
on public safety, the procedures in
178 of this subchapter.
paragraph (j)(2)(ii) and (iii) of this sec-
(d) Service equipment. (1) Except for
tion need not be provided prior to withdrawal of the approval, but shall be
pressure relief devices, UN pressure receptacle equipment, including valves,
provided as soon as practicable thereafter.
piping, fittings, and other equipment
subjected to pressure must be designed
[71 FR 33886, June 12, 2006, as amended at 71
and constructed to withstand at least
FR 54397, Sept. 14, 2006)
1.5 times the test pressure of the pressure receptacle.
§ 178.71 Specifications for UN pressure
receptacles.
(2) Service equipment must be configured or designed to prevent damage
(a) General. Each UN pressure recepthat could result in the release of the
tacle must meet the requirements of
pressure receptacle contents during
this section. Requirements for apnormal conditions of handling and
proval, qualification, maintenance, and
transport. Manifold piping leading to
testing are contained in $178.70, and
shut-off valves must be sufficiently
subpart C of part 180 of this subchapter.
flexible to protect the valves and the
(b) Definitions. The following definipiping from shearing or releasing the
tions apply for the purposes of design
pressure receptacle contents. The filland construction of UN pressure receping and discharge valves and any protacles under this subpart:
tective caps must be secured against
Alternative arrangement means an approval granted by the Associate Adunintended opening. The valves must
ministrator for a MEGC that has been
conform to ISO 10297 (IBR, see $171.7 of
designed, constructed or tested to the
this subchapter) and be protected as
technical requirements or testing
specified in § 173.301b(f) of this submethods other than those specified for
chapter.
UN pressure receptacles in part 178 or
(3) UN pressure receptacles that canpart 180 of this subchapter.
not be handled manually or rolled,
Bundle of cylinders. See $171.8 of this
must be equipped with devices (e.g.
subchapter.
skids, rings, straps) ensuring that they
Design type means a pressure recepcan be safely handled by mechanical
tacle design as specified by a particular
means and so arranged as not to impair
pressure receptacle standard.
the strength of, nor cause undue
Design type approval means an overall
stresses, in the pressure receptacle.
approval of the manufacturer's quality
(4) Pressure receptacles filled by volsystem and design type of each presume must be equipped with a level insure receptacle to be produced within
dicator.
the manufacturer's facility.
(e) Bundles of cylinders. UN pressure
UN tube. See $171.8 of this subreceptacles assembled in bundles must
chapter.
be structurally supported and held to-
(c) General design and construction.
gether as a unit and secured in a man-
UN pressure receptacles and their cloner that prevents movement in relasures must be designed, manufactured,
tion to the structural assembly and
tested and equipped in accordance with
movement that would result in the
the requirements contained in this secconcentration of harmful local
tion.
stresses. The frame design must ensure
901
$ 178.71
49 CFR Ch. I (10-1-06 Edition)
stability under normal operating conother means that will not become disditions.
lodged by operational impact loads.
(1) The frame must securely retain
Valves that need to be operated in norall the components of the bundle and
mal service or in an emergency must
must protect them from damage during
be accessible.
conditions normally incident to trans-
(f) [Reserved]
portation. The method of cylinder re-
(g) Design and construction requirestraint must prevent any vertical or
ments for UN refillable seamless steel cylhorizontal movement or rotation of the
inders. In addition to the general recylinder that could cause undue strain
quirements of this section, UN refillon the manifold. The total assembly
able seamless steel cylinders must conmust be able to withstand rough hanform to the following ISO standards, as
dling, including being dropped or overapplicable:
turned.
(1) ISO 9809-1: Gas cylinders-Refill-
(2) The frame must include features
able seamless steel gas cylinders-Dedesigned for the handling and transporsign, construction and testing-Part 1:
tation of the bundle. The lifting rings
Quenched and tempered steel cylinders
must be designed to withstand a design
with tensile strength less than 1 100
load of 2 times the maximum gross
MPa. (IBR, see $171.7 of this subweight. Bundles with more than one
chapter).
lifting ring must be designed such that
(2) ISO 9809-2: Gas cylinders-Refill-
a minimum sling angle of 45 degrees to
able seamless steel gas cylinders-Dethe horizontal can be achieved during
sign, construction and testing-Part 2:
lifting using the lifting rings. If four
Quenched and tempered steel cylinders
lifting rings are used, their design
with tensile strength greater than or
must be strong enough to allow the
equal to 1 100 MPa. (IBR, see $171.7 of
bundle to be lifted by two rings. Where
this subchapter).
two or four lifting rings are used, dia-
(3) ISO 9809-3: Gas cylinders-Refillmetrically opposite lifting rings must
able seamless steel gas cylinders-Debe aligned with each other to allow for
sign, construction and testing-Part 3:
correct lifting using shackle pins. If
Normalized steel cylinders. (IBR, see
the bundle is filled with forklift pock-
$171.7 of this subchapter).
ets, it must contain two forklift pock-
(h) Design and construction requireets on each side from which it is to be
ments for UN refillable seamless aluminum
lifted. The forklift pockets must be poalloy cylinders. In addition to the gensitioned symmetrically consistent with
eral requirements of this section, UN
the bundle center of gravity.
refillable seamless aluminum cylinders
(3) The frame structural members
must conform to ISO 7866: Gas cylmust be designed for a vertical load of
inders-Refillable seamless aluminum
2 times the maximum gross weight of
alloy gas cylinders-Design, constructhe bundle. Design stress levels may
tion and testing. (IBR, see $171.7 of this
not exceed 0.9 times the yield strength
subchapter). The use of Aluminum
of the material.
alloy 6351-T6 or equivalent is prohib-
(4) The frame may not contain any
ited.
protrusions from the exterior frame
(i) Design and construction requirestructure that could cause a hazardous
ments for UN non-refillable metal cylcondition.
inders. In addition to the general re-
(5) The frame design must prevent
quirements of this section, UN non-recollection of water or other debris that
fillable metal cylinders must conform
would increase the tare weight of bunto ISO 11118: Gas cylinders-Non-refilldles filled by weight.
able metallic gas cylinders-Specifica-
(6) The floor of the bundle frame
tion and test methods. (IBR, see $ 171.7
must not buckle during normal operof this subchapter.)
ating conditions and must allow for the
(j) Design and construction requiredrainage of water and debris from
ments for UN refillable seamless steel
around the base of the cylinders.
tubes. In addition to the general re-
(7) If the frame design includes movquirements of this section, UN refillable doors or covers, they must be caable seamless steel tubes must conform
pable of being secured with latches or
to ISO 11120: Gas cylinders-Refillable
902
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.71
seamless steel tubes of water capacity
in the UN pressure receptacle design
between 150 L and 3000 L-Design, conand construction ISO standards, and
struction and testing. (IBR, see $171.7
any restrictions specified in part 173
of this subchapter).
for the gases to be transported, the re-
(k) Design and construction requirequirements of the following standards
ments for UN acetylene cylinders. In admust be applied with respect to matedition to the general requirements of
rial compatibility:
this section, UN acetylene cylinders
(1) ISO 11114-1: Transportable gas cylmust conform to the following ISO
inders-Compatibility of cylinder and
standards, as applicable:
valve materials with gas contents-
(1) For the cylinder shell:
Part 1: Metallic materials. (IBR, see
(i) ISO 9809-1: Gas cylinders-Refillable seamless steel gas cylinders-De-
$171.7 of this subchapter).
sign, construction and testing-Part 1:
(2) ISO 11114-2: Transportable gas cyl-
Quenched and tempered steel cylinders
inders-Compatibility of cylinder and
with tensile strength less than 1 100
valve materials with gas contents-
MPa.
Part 2: Non-metallic materials. (IBR,
(ii) ISO 9809-3: Gas cylinders-Refillsee § 171.7 of this subchapter).
able seamless steel gas cylinders-De-
(n) Protection of closures. Closures and
sign, construction and testing-Part 3:
their protection must conform to the
Normalized steel cylinders.
requirements in $173.301(f) of this sub-
(2) The porous mass in an acetylene
chapter.
cylinder must conform to ISO 3807-2:
(o) Marking of UN refillable pressure re-
Cylinders for acetylene-Basic requireceptacles. UN refillable pressure recepments-Part 2: Cylinders with fusible
tacles must be marked clearly and legplugs. (IBR, see $171.7 of this subibly. The required markings must be
chapter).
permanently affixed by stamping, en-
(1) Design and construction requiregraving, or other equivalent method,
ments for UN composite cylinders. (1) In
on the shoulder, top end or neck of the
addition to the general requirements of
pressure receptacle or on a permathis section, UN composite cylinders
nently affixed component of the presmust be designed for unlimited service
life and conform to the following ISO
sure receptacle, such as a welded colstandards, as applicable:
lar. Except for the "UN" mark, the
minimum size of the marks must be 5
(i) ISO 11119-1: Gas cylinders of composite construction-Specification and
mm for pressure receptacles with a ditest methods-Part 1: Hoop-wrapped
ameter greater than or equal to 140 mm
composite gas cylinders. (IBR, see
and 2.5 mm for pressure receptacles
$171.7 of this subchapter).
with a diameter less than 140 mm. The
(ii) ISO 11119-2: Gas cylinders of comminimum size of the "UN" mark must
posite construction-Specification and
be 5 mm for pressure receptacles with a
test methods-Part 2: Fully-wrapped
diameter less than 140 mm and 10 mm
fibre reinforced composite gas cylfor pressure receptacles with a diameinders with load-sharing metal liners.
ter of greater than or equal to 140 mm.
(IBR, see $171.7 of this subchapter).
The depth of the markings must not
(iii) ISO 11119-3: Gas cylinders of
create harmful stress concentrations.
composite construction-Specification
A refillable pressure receptacle conand test methods-Part 3: Fully
forming to the UN standard must be
wrapped fibre reinforced composite gas
marked as follows:
cylinders with non-load sharing metal-
(1) The UN packaging symbol.
lic or non-metallic liners. (IBR, see
$171.7 of this subchapter).
(2) ISO 11119-2 and ISO 11119-3 gas
cylinders of composite construction
manufactured in accordance with the
requirements for underwater use must
bear the "UW" mark.
(m) Material compatibility. In addition
to the material requirements specified
903
$ 178.71
49 CFR Ch. I (10-1-06 Edition)
to the last digit. For acetylene cylinders, the tare weight must be marked
on the cylinders in kilograms (KG).
The tare weight is the sum of the
empty weight, mass of the valve, any
coating and all permanently attached
parts (e.g. fittings and accessories)
that are not removed during filling.
The tare weight must be expressed to
two significant figures rounded down
to the last digit. The tare weight does
not include the cylinder cap or any
outlet cap or plug not permanently attached to the cylinder.
(2) The ISO standard, for example
(8) The minimum wall thickness of
ISO 9809-1, used for design, constructhe pressure receptacle in millimeters
tion and testing. Acetylene cylinders
followed by the letters "MM". This
must be marked to indicate the porous
mark is not required for pressure remass and the steel shell, for example:
ceptacles with a water capacity less
"ISO 3807-2/ISO 9809-1."
than or equal to 1.0 L or for composite
(3) The mark of the country where
cylinders.
the approval is granted. The letters
(9) For pressure receptacles intended
"USA" must be marked on UN pressure
for the transport of compressed gases
receptacles approved by the United
and UN 1001 acetylene, dissolved, the
States. The manufacturer must obtain
working pressure in bar, proceeded by
an approval number from the Associate
the letters "PW".
Administrator. The manufacturer ap-
(10) For liquefied gases, the water caproval number must follow the country
pacity in liters expressed to three sigof approval mark, separated by a slash
nificant digits rounded down to the
(for example, USA/MXXXX). Pressure
last digit, followed by the letter "L". If
receptacles approved by more than one
the value of the minimum or nominal
national authority may contain the
water capacity is an integer, the digits
mark of each country of approval, sepafter the decimal point may be omitarated by a comma.
ted.
(4) The identity mark or stamp of the
(11) Identification of the cylinder
IIA.
thread type (e.g., 25E).
(5) The date of the initial inspection,
(12) The country of manufacture. The
the year (four digits) followed by the
letters "USA" must be marked on cylmonth (two digits) separated by a
inders manufactured in the United
slash, for example "2006/04".
States.
(6) The test pressure in bar, preceded
(13) The serial number assigned by
by the letters "PH" and followed by
the manufacturer.
the letters "BAR". The test pressure
must be obtained from the results of a
(14) For steel pressure receptacles,
hydraulic volumetric expansion test.
the letter "H" showing compatibility
(7) The empty or tare weight. Except
of the steel, as specified in ISO 11114-1.
for acetylene cylinders, empty weight
(15) Identification of aluminum alloy,
is the mass of the pressure receptacle
if applicable.
in kilograms, including all integral
(16) Stamp for nondestructive testparts (e.g., collar, neck ring, foot ring,
ing, if applicable.
etc.), followed by the letters "KG". The
(17) Stamp for underwater use of
empty weight does not include the
composite cylinders, if applicable.
mass of the valve, valve cap or valve
(p) Marking sequence. The marking reguard or any coating. The empty
quired by paragraph (o) of this section
weight must be expressed to three sigmust be placed in three groups as
nificant figures rounded up to the last
shown in the example below:
digit. For cylinders of less than 1 kg,
(1) The top grouping contains manuthe empty weight must be expressed to
facturing marks and must appear contwo significant figures rounded down
secutively in the sequence given in
904
Pipeline and Hazardous Materials Safety Admin., DOT
$ 178.71
paragraphs (o)(11) through (17) of this
(3) The bottom grouping contains
section.
certification marks and must appear
(2) The middle grouping contains
consecutively in the sequence given in
operational marks described in paraparagraph (o)(1) through (5) of this secgraphs (o)(6) through (10) of this section.
tion.
(11)
(12)
(13)
(14)
(15)
(16) (17)
25E
USA
765432
H
UW
(9)
(6)
(7)
(10)
(8)
PW200
PH300BAR
62.1KG
50L
5.8MM
(1)
(2)
(3)
(4)
(5)
u
n
ISO 9809-1
USA/MXXXX
IB 2005/12
(q) Other markings. Other markings
graphs (o)(7), (8), (11) and (17) are not
are allowed in areas other than the side
applicable. The required serial number
wall, provided they are made in low
marking in paragraph (o)(13) may be
stress areas and are not of a size and
replaced by the batch number.
depth that will create harmful stress
(2) Each receptacle must be marked
concentrations. Such marks must not
with the words "DO NOT REFILL" in
conflict with required marks.
letters of at least 5 mm in height.
(r) Marking of UN non-refillable pres-
(3) A non-refillable pressure recepsure receptacles. Unless otherwise specitacle, because of its size, may subfied in this paragraph, each UN non-restitute the marking required by this
fillable pressure receptacle must be
paragraph with a label. Reduction in
clearly and legibly marked as premarking size is authorized only as prescribed in paragraph (o) of this section.
scribed in ISO 7225, Gas cylinders-Pre-
In addition, permanent stenciling is
cautionary labels. (IBR, see $171.7 of
authorized. Except when stenciled, the
this subchapter).
marks must be on the shoulder, top end
(4) Each non-refillable pressure reor neck of the pressure receptacle or on
ceptacle must also be legibly marked
a permanently affixed component of
by stenciling the following statement:
the pressure receptacle, for example a
"Federal law forbids transportation if
welded collar.
refilled-penalty up to $500,000 fine and 5
(1) The marking requirements and seyears in imprisonment (49 U.S.C.
quence listed in paragraphs (o)(1)
5124)."
through (17) of this section are re-
(5) No person may mark a non-refillquired, except the markings in paraable pressure receptacle as meeting the
905
§ 178.74
49 CFR Ch. I (10-1-06 Edition)
requirements of this section unless it
ing all drawings and calculations, to
was manufactured in conformance with
ensure that the design of the MEGC
this section.
meets all requirements of the relevant
[7] FR 33887, June 12, 2006, as amended at 71
specification and to determine whether
FR 54397, Sept. 14, 2006)
it is complete and conforms to the requirements of this section. An incom-
§ 178.74 Approval of MEGCs.
plete application will be returned to
(a) Application for design type apthe applicant with the reasons why the
proval. (1) Each new MEGC design type
application was returned. If the applimust have a design approval certification is complete and all applicable
cate. An owner or manufacturer must
requirements of this section are met,
apply to an approval agency that is apthe approval agency must prepare a
proved by the Associate Administrator
MEGC design approval certificate conin accordance with subpart E of part
taining the manufacturer's name and
107 of this chapter +to obtain approval
address, results and conclusions of the
of a new design. When a series of
examination and necessary data for
MEGCs is manufactured without
identification of the design type. If the
change in the design, the certificate is
Associate Administrator approves the
valid for the entire series. The design
Design Type Approval Certificate apapproval certificate must refer to the
plication, the approval agency and the
prototype test report, the materials of
manufacturer must each maintain a
construction of the manifold, the
copy of the approved drawings, calculastandards to which the pressure receptions, and test data for at least 20
tacles are made and an approval numyears.
ber. The compliance requirements or
(c) Approval agency's responsibilities.
test methods applicable to MEGCs as
The approval agency is responsible for
specified in this subpart may be varied
ensuring that the MEGC conforms to
when the level of safety is determined
the design type approval. The approval
to be equivalent to or exceed the reagency must:
quirements of this subchapter and is
(1) Witness all tests required for the
approved in writing by the Associate
approval of the MEGC specified in this
Administrator. A design approval may
section and $ 178.75.
serve for the approval of smaller
(2) Ensure, through appropriate in-
MEGCs made of materials of the same
spection, that each MEGC is fabricated
type and thickness, by the same fabin all respects in conformance with the
rication techniques and with identical
approved drawings, calculations, and
supports, equivalent closures and other
test data.
appurtenances.
(3) Determine and ensure that the
(2) Each application for design ap-
MEGC is suitable for its intended use
proval must be in English and contain
and that it conforms to the requirethe following information:
ments of this subchapter.
(i) Two complete copies of all engi-
(4) Apply its name, identifying mark
neering drawings, calculations, and
or identifying number, and the date the
test data necessary to ensure that the
approval was issued, to the metal idendesign meets the relevant specificatification marking plate attached to
tion.
the MEGC upon successful completion
(ii) The manufacturer's serial number
of all requirements of this subpart.
that will be assigned to each MEGC.
Any approvals by the Associate Admin-
(iii) A statement as to whether the
istrator authorizing design or condesign type has been examined by any
struction alternatives (Alternate Arapproval agency previously and judged
rangements) of the MEGC (see paraunacceptable. Affirmative statements
graph (a) of this section) must be indimust be documented with the name of
cated on the metal identification plate
the approval agency, reason for non-acas specified in $178.75(j).
ceptance, and the nature of modifica-
(5) Prepare an approval certificate
tions made to the design type.
for each MEGC or, in the case of a se-
(b) Actions by the approval agency. The
ries of identical MEGCs manufactured
approval agency must review the applito a single design type, for each series
cation for design type approval, includof MEGCs. The approval certificate
906
Pipeline and Hazardous Materials Safety Admin., DOT
$ 178.74
must include all of the following infor-
(e) Denial of application for approval.
mation:
If the Associate Administrator finds
(i) The information displayed on the
that the MEGC will not be approved for
metal identification plate required by
any reason, the Associate Adminis-
$178.75(j):
trator will notify the applicant in writ-
(ii) The results of the applicable
ing and provide the reason for the deframework test specified in ISO 1496-3
nial. The manufacturer may request
(IBR, see $171.7 of this subchapter);
that the Associate Administrator re-
(iii) The results of the initial inspecconsider the decision. The application
tion and test specified in paragraph (h)
request mustof this section;
(1) Be written in English and filed
(iv) The results of the impact test
within 90 days of receipt of the decispecified in § 178.75(i) (4):
sion;
(v) Certification documents verifying
(2) State in detail any alleged errors
that the cylinders and tubes conform
of fact and law; and
to the applicable standards; and
(3) Enclose any additional informa-
(vi) A statement that the approval
tion needed to support the request to
agency certifies the MEGC in accordreconsider.
ance with the procedures in this sec-
(f) Appeal. (1) A manufacturer whose
tion and that the MEGC is suitable for
reconsideration request is denied may
its intended purpose and meets the reappeal to the PHMSA Administrator.
quirements of this subchapter. When a
The appeal mustseries of MEGCs is manufactured with-
(i) Be in writing and filed within 90
out change in the design type, the ceΓ-
days of receipt of the Associate Admintificate may be valid for the entire seistrator S decision on reconsideration;
ries of MEGCs representing a single de-
(ii) State in detail any alleged errors
sign type. The approval number must
of fact and law;
consist of the distinguishing sign or
(iii) Enclose any additional informamark of the country ("USA" for the
tion needed to support the appeal; and
United States of America) where the
(iv) State in detail the modification
approval was granted and a registraof the final decision sought.
tion number.
(2) The Administrator will grant or
(6) Retain on file a copy of each apdeny the relief and inform the appelproval certificate for at least 20 years.
lant in writing of the decision. The Ad-
(d) Manufacturers' responsibilities. The
ministrator's decision is the final admanufacturer is responsible for compliministrative action.
ance with the applicable specifications
(g) Modifications to approved MEGCs.
for the design and construction of
(1) Prior to modification of any ap-
MEGCs. The manufacturer of a MEGC
proved MEGC that may affect conformmust:
ance and safe use, and that may in-
(1) Comply with all the requirements
volve a change to the design type or afof the applicable ISO standard specified
fect its ability to retain the hazardous
in $178.71;
material in transportation. the
(2) Obtain and use an approval agen-
MEGC's owner must inform the apcy to review the design, construction
proval agency that prepared the initial
and certification of the MEGC;
approval certificate for the MEGC or, if
(3) Provide a statement in the manuthe initial approval agency is unavailfacturers' data report certifying that
able, another approval agency, of the
each MEGC manufactured complies
nature of the modification and request
with the relevant specification and all
certification of the modification. The
the applicable requirements of this
owner must supply the approval agency
subchapter; and
with all revised drawings, calculations,
(4) Retain records for the MEGCs for
and test data relative to the intended
at least 20 years. When required by the
modification. The MEGC's owner must
specification, the manufacturer must
also provide a statement as to whether
provide copies of the records to the apthe intended modification has been exproval agency, the owner or lessee of
amined and determined to be unacceptthe MEGC, and to a representative of
able by any approval agency. The writ-
DOT, upon request.
ten statement must include the name
907
§ 178.75
49 CFR Ch. I (10-1-06 Edition)
of the approval agency, the reason for
(iii) Termination of the approval is
non-acceptance, and the nature of
necessary to adequately protect
changes made to the modification since
against risks to life and property: or
its original rejection.
(iv) The MEGC does not meet the
(2) The approval agency must review
specification.
the request for modification. If the ap-
(2) Before an approval is terminated,
proval agency determines that the prothe Associate Administrator will proposed modification does not conform to
vide the personthe relevant specification, the approval
(i) Written notice of the facts or conduct believed to warrant the termiagency must reject the request in acnation;
cordance with paragraph (d) of this sec-
(ii) An opportunity to submit oral
tion. If the approval agency determines
and written evidence; and
that the proposed modification con-
(3) An opportunity to demonstrate or
forms fully with the relevant specificaachieve compliance with the applicable
tion, the request is accepted. If modirequirements.
fication to an approved MEGC alters
(i) Imminent Danger. If the Associate
any information on the approval cer-
Administrator determines that a certificate, the approval agency must pretificate of approval must be terminated
pare a new approval certificate for the
to preclude a significant and imminent
modified MEGC and submit the certifiadverse effect on public safety, the Ascate to the Associate Administrator for
sociate Administrator may terminate
approval. After receiving approval
the certificate immediately. In such
from the Associate Administrator, the
circumstances, the opportunities of
approval agency must ensure that any
paragraphs (h)(2) and (3) of this section
necessary changes are made to the
need not be provided prior to termimetal identification plate. A copy of
nation of the approval, but must be
each newly issued approval certificate
provided as soon as practicable theremust be retained by the approval agenafter.
cy and the MEGC's owner for at least
[71 FR 33890, June 12, 2006]
20 years. The approval agency must
perform the following activities:
§ 178.75 Specifications for MEGCs.
(i) Retain a set of the approved re-
(a) General. Each MEGC must meet
vised drawings, calculations, and data
the requirements of this section. In a
as specified in § 178.69(b) (4) for at least
MEGC that meets the definition of a
20 years;
"container" within the terms of the
(ii) Ensure through appropriate in-
International Convention for Safe Conspection that all modifications containers (CSC) must meet the requireform to the revised drawings, calculaments of the CSC as amended and 49
tions, and test data; and
CFR parts 450 through 453, and must
(iii) Determine the extent to which
have a CSC approval plate.
retesting of the modified MEGC is nec-
(b) Alternate Arrangements. The techessary based on the nature of the pronical requirements applicable to
posed modification, and ensure that all
MEGCs may be varied when the level of
required retests are satisfactorily persafety is determined to be equivalent
formed.
to or exceed the requirements of this
(h) Termination of Approval Certificate.
subchapter. Such an alternate arrangement must be approved in writing by
(1) The Associate Administrator may
the Associate Administrator. MEGCs
terminate an approval issued under
approved to an Alternate Arrangement
this section if he or she determines
must be marked as required by parathat---
graph (j) of this section.
(i) Because of a change in cir-
(c) Definitions. The following definicumstances, the approval no longer is
tions apply:
needed or no longer would be granted if
Leakproofness test means a test using
applied for;
gas subjecting the pressure receptacles
(ii) Information upon which the apand the service equipment of the MEGC
proval was based is fraudulent or subto an effective internal pressure of not
stantially erroneous;
less than 20% of the test pressure.
908
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.75
Manifold means an assembly of piping
Quenched and tempered steel cylinders
and valves connecting the filling and/or
with tensile strength greater than or
discharge openings of the pressure reequal to 1 100 MPa. (IBR, see $171.7 of
ceptacles.
this subchapter);
Maximum permissible gross mass or
(iii) ISO 9809-3: Gas cylinders-Refill-
MPGM means the heaviest load authorable seamless steel gas cylinders-Deized for transport (sum of the tare
sign, construction and testing-Part 3:
mass of the MEGC, service equipment
Normalized steel cylinders. (IBR, see
and pressure receptacle).
$171.7 of this subchapter); or
Service equipment means manifold sys-
(iv) ISO 11120: Gas cylinders-Refilltem (measuring instruments, piping
able seamless steel tubes of water caand safety devices).
pacity between 150 L and 3000 L-De-
Shut-off valve means a valve that
sign, construction and testing. (IBR,
stops the flow of gas.
see $171.7 of this subchapter).
Structural equipment means the rein-
(4) Pressure receptacles of MEGCs,
forcing, fastening, protective and stabifittings, and pipework must be conlizing members external to the presstructed of a material that is compatsure receptacles.
ible with the hazardous materials in-
(d) General design and construction retended to be transported, as specified
quirements. (1) The MEGC must be capain this subchapter.
ble of being loaded and discharged
(5) Contact between dissimilar metwithout the removal of its structural
als that could result in damage by galequipment. It must possess stabilizing
vanic action must be prevented by apmembers external to the pressure repropriate means.
ceptacles to provide structural integ-
(6) The materials of the MEGC, inrity for handling and transport. MEGCs
cluding any devices, gaskets, and acmust be designed and constructed with
cessories, must have no adverse effect
supports to provide a secure base duron the gases intended for transport in
ing transport and with lifting and tiethe MEGC.
down attachments that are adequate
(7) MEGCs must be designed to withfor lifting the MEGC including when
stand, without loss of contents, at
loaded to its maximum permissible
least the internal pressure due to the
gross mass. The MEGC must be decontents, and the static, dynamic and
signed to be loaded onto a transport vethermal loads during normal condihicle or vessel and equipped with skids,
tions of handling and transport. The
mountings or accessories to facilitate
design must take into account the efmechanical handling.
fects of fatigue, caused by repeated ap-
(2) MEGCs must be designed, manuplication of these loads through the exfactured and equipped to withstand,
pected life of the MEGC.
without loss of contents, all normal
(8) MEGCs and their fastenings must,
handling and transportation condiunder the maximum permissible load,
tions. The design must take into acbe capable of withstanding the folcount the effects of dynamic loading
lowing separately applied static forces
and fatigue.
(for calculation purposes, acceleration
(3) Each pressure receptacle of a
due to gravity (g) = 9.81 m/s2):
MEGC must be of the same design type,
(1) In the direction of travel: 2g
seamless steel, and constructed and
(twice the MPGM multiplied by the actested according to one of the following
celeration due to gravity);
ISO standards:
(ii) Horizontally at right angles to
(1) ISO 9809-1: Gas cylinders-Refillthe direction of travel: 1g (the MPGM
able seamless steel gas cylinders-Demultiplied by the acceleration due to
sign, construction and testing-Part 1:
gravity. When the direction of travel is
Quenched and tempered steel cylinders
not clearly determined. the forces must
with tensile strength less than 1 100
be equal to twice the MPGM);
MPa. (IBR, see $171.7 of this sub-
(iii) Vertically upwards: 1g (the
chapter);
MPGM multiplied by the acceleration
(ii) ISO 9809-2: Gas cylinders-Refilldue to gravity): and
able seamless steel gas cylinders-De-
(iv) Vertically downwards: 2g (twice
sign, construction and testing-Part 2:
the MPGM (total loading including the
909
§ 178.75
49 CFR Ch. I (10-1-06 Edition)
effect of gravity) multiplied by the acsion 2.3 liquefied gases must be deceleration due to gravity.
signed so that each pressure receptacle
(9) Under each of the forces specified
can be filled separately and be kept
in paragraph (d)(8) of this section, the
isolated by a valve capable of being
stress at the most severely stressed
closed during transit. For Division 2.1
point of the pressure receptacles must
gases, the pressure receptacles must be
not exceed the values given in the apisolated by an individual shut-off valve
plicable design specifications (e.g., ISO
into assemblies of not more than 3,000
11120).
L.
(10) Under each of the forces specified
(3) For MEGC filling and discharge
in paragraph (d)(8) of this section, the
openings:
safety factor for the framework and
(i) Two valves in series must be
fastenings must be as follows:
placed in an accessible position on each
(i) For steels having a clearly defined
discharge and filling pipe. One of the
yield point, a safety factor of 1.5 in revalves may be a backflow prevention
lation to the guaranteed yield
valve. (ii) The filling and discharge destrength; or
vices may be equipped to a manifold.
(ii) For steels with no clearly defined
(iii) For sections of piping which can
yield point, a safety factor of 1.5 in rebe closed at both ends and where a liqlation to the guaranteed 0.2 percent
uid product can be trapped, a pressureproof strength and, for austenitic
relief valve must be provided to presteels, the 1 percent proof strength.
vent excessive pressure build-up.
(11) MEGCs must be capable of being
(iv) The main isolation valves on a
electrically grounded to prevent elec-
MEGC must be clearly marked to inditrostatic discharge when intended for
cate their directions of closure. All
flammable gases.
shutoff valves must close by a clock-
(12) The pressure receptacles of a
wise motion of the handwheel.
MEGC must be secured in a manner to
(v) Each shut-off valve or other
prevent movement that could result in
means of closure must be designed and
damage to the structure and conconstructed to withstand a pressure
centration of harmful localized
equal to or greater than 1.5 times the
stresses.
test pressure of the MEGC.
(e) Service equipment. (1) Service
(vi) All shut-off valves with screwed
equipment must be arranged so that it
spindles must close by a clockwise mois protected from mechanical damage
tion of the handwheel. For other shutby external forces during handling and
off valves, the open and closed positransportation. When the connections
tions and the direction of closure must
between the frame and the pressure rebe clearly shown.
ceptacles allow relative movement be-
(vii) All shut-off valves must be detween the subassemblies, the equipsigned and positioned to prevent uninment must be fastened to allow movetentional opening.
ment to prevent damage to any work-
(viii) Ductile metals must be used in
ing part. The manifolds, discharge fltthe construction of valves or accestings (pipe sockets, shut-off devices),
sories.
and shut-off valves must be protected
(4) The piping must be designed, confrom damage by external forces. Manistructed and installed to avoid damage
fold piping leading to shut-off valves
due to expansion and contraction, memust be sufficiently flexible to protect
chanical shock and vibration. Joints in
the valves and the piping from sheartubing must be brazed or have an
ing, or releasing the pressure recepequally strong metal union. The melttacle contents. The filling and dising point of brazing materials must be
charge devices, including flanges or
no lower than 525 °C (977 °F). The rated
threaded plugs, and any protective caps
pressure of the service equipment and
must be capable of being secured
of the manifold must be not less than
against unintended opening.
two-thirds of the test pressure of the
(2) Each pressure receptacle intended
pressure receptacles.
for the transport of Division 2.3 gases
(f) Pressure relief devices. Each presmust be equipped with an individual
sure receptacle must be equipped with
shut-off valve. The manifold for Divione or more pressure relief devices as
910
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.75
specified in $ 173.301(f) of this subcaping gas must be directed away from
chapter. When pressure relief devices
the pressure receptacle in such a manare installed, each pressure receptacle
ner that it cannot impinge upon the
or group of pressure receptacles of a
other pressure receptacles. Heat resist-
MEGC that can be isolated must be
ant protective devices that deflect the
equipped with one or more pressure reflow of gas are permissible provided the
lief devices. Pressure relief devices
required pressure relief device capacity
must be of a type that will resist dyis not reduced. Arrangements must be
namic forces including liquid surge and
made to prevent access to the pressure
must be designed to prevent the entry
relief devices by unauthorized persons
of foreign matter, the leakage of gas
and to protect the devices from damage
and the development of any dangerous
caused by rollover.
excess pressure.
(g) Gauging devices. When a MEGC is
(1) The size of the pressure relief deintended to be filled by mass, it must
vices: CGA S-1.1, 2003 edition (IBR, see
be equipped with one or more gauging
$171.7 of this subchapter) must be used
devices. Glass level-gauges and gauges
to determine the relief capacity of inmade of other fragile material are prodividual pressure receptacles.
hibited.
(2) Connections to pressure-relief de-
(h) MEGC supports, frameworks, lifting
vices: Connections to pressure relief
and tie-down attachments. (1) MEGCs
devices must be of sufficient size to enmust be designed and constructed with
able the required discharge to pass un-
a support structure to provide a secure
restricted to the pressure relief device.
base during transport. MEGCs must be
A shut-off valve installed between the
protected against damage to the prespressure receptacle and the pressure resure receptacles and service equipment
lief device is prohibited, except where
resulting from lateral and longitudinal
duplicate devices are provided for
impact and overturning. The forces
maintenance or other reasons, and the
specified in paragraph (d)(8) of this secshut-off valves serving the devices action, and the safety factor specified in
tually in use are locked open, or the
paragraph (d)(10) of this section must
shut-off valves are interlocked so that
be considered in this aspect of the deat least one of the duplicate devices is
sign. Skids, frameworks, cradles or
always operable and capable of meeting
other similar structures are acceptthe requirements of paragraph (f)(1) of
able. If the pressure receptacles and
this section. No obstruction is perservice equipment are so constructed
mitted in an opening leading to or
as to withstand impact and overleaving from a vent or pressure-relief
turning, additional protective support
device that might restrict or cut-off
structure is not required (see parathe flow from the pressure receptacle
graph (h)(4) of this section).
to that device. The opening through all
(2) The combined stresses caused by
piping and fittings must have at least
pressure receptacle mountings (e.g.
the same flow area as the inlet of the
cradles, frameworks, etc.) and MEGC
pressure relief device to which it is
lifting and tie-down attachments must
connected. The nominal size of the disnot cause excessive stress in any prescharge piping must be at least as large
sure receptacle. Permanent lifting and
as that of the pressure relief device.
tie-down attachments must be
(3) Location of pressure-relief deequipped to all MEGCs. Any welding of
vices: For liquefied gases, each presmountings or attachments onto the
sure relief device must, under maxpressure receptacles is prohibited.
imum filling conditions, be in commu-
(3) The effects of environmental cornication with the vapor space of the
rosion must be taken into account in
pressure receptacles. The devices, when
the design of supports and frameworks.
installed, must be arranged to ensure
(4) When MEGCs are not protected
the escaping vapor is discharged upduring transport as specified in parawards and unrestrictedly to prevent
graph (h)(1) of this section, the presimpingement of escaping gas or liquid
sure receptacles and service equipment
upon the MEGC, its pressure recepmust be protected against damage retacles or personnel. For flammable,
sulting from lateral or longitudinal impyrophoric and oxidizing gases, the espact or overturning. External fittings
911
§ 178.75
49 CFR Ch. I (10-1-06 Edition)
must be protected against release of
transport. A listing of acceptable
the pressure receptacles' contents upon
methods for performing the impact test
impact or overturning of the MEGC on
is provided in the UN Recommendaits fittings. Particular attention must
tions (IBR. see $171.7 of this subbe paid to the protection of the manichapter).
fold. Examples of protection include:
(j) Marking. (1) Each MEGC must be
(i) Protection against lateral impact,
equipped with a corrosion resistant
which may consist of longitudinal bars;
metal plate permanently attached to
(ii) Protection against overturning.
the MEGC in a conspicuous place readwhich may consist of reinforcement
ily accessible for inspection. The presrings or bars fixed across the frame;
sure receptacles must be marked ac-
(iii) Protection against rear impact,
cording to this section. Affixing the
which may consist of a bumper or
metal plate to a pressure receptacle is
frame;
prohibited. At a minimum, the fol-
(iv) Protection of the pressure receplowing information must be marked on
tacles and service equipment against
the plate by stamping or by any other
damage from impact or overturning by
equivalent method:
use of an ISO frame according to the
relevant provisions of ISO 1496-3. (IBR,
Country of manufacture
see $171.7 of this subchapter).
UN
(i) Initial inspection and test. The pressure receptacles and items of equipment of each MEGC must be inspected
and tested before being put into service
for the first time (initial inspection
and test). This initial inspection and
test of an MEGC must include the following:
(1) A check of the design characteristics.
(2) An external examination of the
MEGC and its fittings, taking into account the hazardous materials to be
transported.
(3) A pressure test performed at the
Approval Country
test pressures specified in
Approval Number
§173.304b(b)(1) and (2) of this subchapter. The pressure test of the mani-
Alternate Arrangements (see $178.75(b))
fold may be performed as a hydraulic
MEGC Manufacturer's name or mark
test or by using another liquid or gas.
MEGC's serial number
A leakproofness test and a test of the
satisfactory operation of all service
Approval agency (Authorized body for
equipment must also be performed bethe design approval)
fore the MEGC is placed into service.
Year of manufacture
When the pressure receptacles and
Test pressure:
bar gauge
their fittings have been pressure-tested
Design temperature range
°C to
separately, they must be subjected to a
°C
leakproof test after assembly.
(4) An MEGC that meets the defini-
Number of pressure receptacles
tion of "container" in the CSC (see 49
Total water capacity
liters
CFR 450.3(a) must be subjected to an
Initial pressure test date and identiimpact test using a prototype repfication of the Approval Agency
resenting each design type. The prototype MEGC must be shown to be capa-
Date and type of most recent periodic
tests
ble of absorbing the forces resulting
from an impact not less than 4 times (4
Year
Month
Type
g) the MPGM of the fully loaded
(e.g. 2004-05, AE/UE, where "AE" rep-
MEGC, at a duration typical of the meresents acoustic emission and "UE"
chanical shocks experienced in rail
represents ultrasonic examination)
912
Pipeline and Hazardous Materials Safety Admin., DOT Pt. 178, Subpt. C, App. A
Stamp of the approval agency who
Maximum permissible load mass
performed or witnessed the most recent
kg
test
Working pressure at 15 °C:
bar
(2) The following information must
gauge
be marked on a metal plate firmly se-
Maximum permissible gross mass
cured to the MEGC:
(MPGM)
kg
Name of the operator
Unladen (tare) mass
kg
[71 FR 33892, June 12. 2006]
APPENDIX A TO SUBPART C OF PART 178-ILLUSTRATIONS: CYLINDER TENSILE
SAMPLE
The following figures illustrate the recommended locations for test specimens taken from
welded cylinders:
913
Pt. 178, Subpt. C, App. A
49 CFR Ch. I (10-1-06 Edition)
1
4
2
SEAMLESS BODY
SECTIONS REQUIRE ONLY
3
ONE PARENT METAL TEST
5
OPTIONAL
CONVEX HEAD
PARENT MATERIAL TEST
SAMPLE 1 & 3 & 5
WELD TENSILE TEST
И
SAMPLE 4
WELD BEND TEST
SAMPLE 2
THIS FIGURE ILLUSTRATES THE PROPER TENSILE
LOCATION FOR A 3 PIECE CYLINDER WITH THE HEADS
HAVING STRAIGHT SIDEWALL.
FIGURE #1
914
Pipeline and Hazardous Materials Safety Admin., DOT Pf. 178, Subpt. C, App. A
1
4
2
3
OPTIONAL
CONVEX HEAD
PARENT MATERIAL TEST
SAMPLE 1 & 3
WELD TENSILE TEST
a
SAMPLE 4
WELD BEND TEST
SAMPLE 2
THIS FIGURE ILLUSTRATES THE PROPER TENSILE
LOCATION FOR A 2 PIECE CYLINDER WITH THE HEADS
HAVING STRAIGHT SIDEWALLS.
FIGURE #2
915
Pt. 178, Subpt. C, App. A
49 CFR Ch. I (10-1-06 Edition)
1
1
3
ALTERNATIVE
LOCATIONS
2
5
4
5
OPTIONAL, CONVEX HEAD
SAMPLE TO BE TAKEN FROM HEAD
PARENT MATERIAL TEST
SAMPLE 1 & 3 & 5
WELD TENSILE TEST
SAMPLE 4
WELD BEND TEST
SAMPLE 2
THIS FIGURE ILLUSTRATES THE PROPER TENSILE
LOCATION FOR A 2 PIECE CYLINDER THAT HAVE DEEP
DRAWN HEADS.
FIGURE #3
916
Pipeline and Hazardous Materials Safety Admin., DOT Pt. 178, Subpt. C, App. A
1
4
1
3
2
3
SEAMLESS SIDEWALL
TWO PIECE
CONSTRUCTION
CONSTRUCTION
PARENT MATERIAL TEST
SAMPLE 1 & 3
WELD TENSILE TEST
И
SAMPLE 4
WELD BEND TEST
SAMPLE 2
THIS FIGURE ILLUSTRATES THE PROPER TENSILE
LOCATION FOR A 2 PIECE CYLINDER THAT HAVE DEEP
DRAWN HEADS.
FIGURE #4
917
Pt. 178, Subpt. C, App. A
49 CFR Ch. I (10-1-06 Edition)
1
4
2
3
PARENT MATERIAL TEST
SAMPLE 1 & 3
WELD TENSILE TEST
a
SAMPLE 4
WELD BEND TEST
SAMPLE 2
THIS FIGURE ILLUSTRATES THE PROPER TENSILE
LOCATION FOR A 2 PIECE CYLINDER.
FIGURE #5
[67 FR 51654, Aug. 8, 2002]
918
Pipeline and Hazardous Materials Safety Admin., DOT
$ 178.255-6
Subparts D-G [Reserved]
§ 178.255-3 Expansion domes.
(a) Expansion domes, if applied, must
Subpart H-Specifications for
have a minimum capacity of one per-
Portable Tanks
cent of the combined capacity of the
tank and dome.
SOURCE: 29 FR 18972, Dec. 29, 1964, unless
(b) [Reserved]
otherwise noted. Redesignated at 32 FR 5606,
Apr. 5, 1967.
§ 178.255-4 Closures for manholes and
domes.
§§ 178.251-178.253-5 [Reserved]
(a) The manhole cover shall be de-
§ 178.255 Specification 60; steel portsigned to provide a secure closure of
able tanks.
the manhole. All covers, not hinged to
the tanks, shall be attached to the out-
§ 178.255-1 General requirements.
side of the dome by at least 1/8 inch
chain or its equivalent. Closures shall
(a) Tanks must be of fusion welded
be made tight against leakage of vapor
construction, cylindrical in shape with
and liquid by use of gaskets of suitable
seamless heads concave to the presmaterial.
sure. Tank shells may be of seamless
construction.
(b) [Reserved]
(b) Tanks must be designed, con-
§ 178.255-5 Bottom discharge outlets.
structed, certified, and stamped in accordance with Section VIII of the
(a) Bottom discharge outlets prohib-
ASME Code (IBR, see § 171.7 of this subited, except on tanks used for shipchapter).
ments of sludge acid and alkaline cor-
(c) Tanks including all permanent atrosive liquids.
tachments must be postweld heat
(b) If installed, bottom outlets or
treated as a unit.
bottom washout chambers shall be of
(d) Requirements concerning types of
metal not subject to rapid deterioravalves, retesting. and qualification of
tion by the lading, and each shall be
portable tanks contained in §§ 173.32
provided with a valve or plug at its
and 173.315 of this chapter must be obupper end and liquid-tight closure at it
served.
lower end. Each valve or plug shall be
designed to insure against unseating
[29 FR 18972, Dec. 29, 1964. Redesignated at 32
due to stresses or shocks incident to
FR 5606. Apr. 5, 1967. and amended by Amdt.
178-7, 34 FR 18250, Nov. 14, 1969; 68 FR 75750,
transportation. Bottom outlets shall be
Dec. 31, 2003)
adequately protected against handling
damage and outlet equipment must not
§ 178.255-2 Material.
extend to within less than one inch of
the bottom bearing surface of the skids
(a) Material used in the tank must be
steel of good weldable quality and conor tank mounting.
form with the requirements in Sections
[29 FR 18972, Dec. 29, 1964. Redesignated at 32
V, VIII, and IX of the ASME Code (IBR,
FR 5606, Apr. 5, 1967. as amended by Amdt.
see $171.7 of this subchapter).
178-104, 59 FR 49135, Sept. 26, 1994]
(b) The minimum thickness of metal,
exclusive of lining material, for shell
§ 178.255-6 Loading and unloading accessories.
and heads of tanks shall be as follows:
(a) When installed, gauging, loading
Minimum
and air inlet devices, including their
Tank capacity
thickness
(inch)
valves, shall be provided with adequate
means for their secure closure; and
Not more than 1,200 gallons
1/4
Over 1,200 to 1,800 gallons
5/16
means shall also be provided for the
Over 1,800 gallons
3/8
closing of pipe connections of valves.
(b) Interior heater coils, if installed,
[29 FR 18972. Dec. 29, 1964. Redesignated at 32
must be of extra heavy pipe and so con-
FR 5606, Apr. 5, 1967, and amended by Amdt.
structed that breaking off of exterior
178-7, 34 FR 18250, Nov. 14, 1969; 68 FR 75750,
connections will not cause leakage of
Dec. 31, 2003)
tanks.
919
§ 178.255-7
49 CFR Ch. I (10-1-06 Edition)
§ 178.255-7 Protection of valves and
devices shall be deemed to comply with
accessories.
this requirement.
(a) All valves, fittings, accessories,
(b) All tank mountings such as skids,
safety devices, gauging devices, and the
fastenings, brackets, cradles, lifting
like shall be adequately protected
lugs, etc., intended to carry loadings
against mechanical damage by a housshall be permanently secured to tanks
ing closed with a cover plate.
in accordance with the requirements
(b) Protective housing shall comply
under which the tanks are fabricated,
with the requirements under which the
and shall be designed with a factor of
tanks are fabricated with respect to desafety of four, and built to withstand
sign and construction, and shall be deloadings in any direction equal to two
signed with a minimum factor of safety
times the weight of the tanks and atof four to withstand loadings in any ditachments when filled to the maximum
rection equal to two times the weight
permissible loaded weight.
of the tank and attachments when
(c) Lifting lugs or side hold-down
filled with water.
lugs shall be provided on the tank
mountings in a manner suitable for at-
§ 178.255-8 Safety devices.
taching lifting gear and hold-down de-
(a) See § 173.315(i) of this subchapter.
vices. Lifting lugs and hold-down lugs
(b) [Reserved]
welded directly to the tank shall be of
the pad-eye type. Doubling plates weld-
[Amdt. 178-83, 50 FR 11066, Mar. 19, 1985]
ed to the tank and located at the
§ 178.255-9 Compartments.
points of support shall be deemed to
comply with this requirement.
(a) When the interior of the tank is
(d) All tank mountings shall be so dedivided into compartments, each comsigned as to prevent the concentration
partment shall be designed, conof excessive loads on the tank shell.
structed and tested as a separate tank.
Thickness of shell and compartment
§ 178.255-12 Pressure test.
heads shall be determined on the basis
of total tank capacity.
(a) Each completed portable tank
(b) [Reserved]
prior to application of lining shall be
tested before being put into transpor-
§ 178.255-10 Lining.
tation service by completely filling the
(a) If a lining is required, the matetank with water or other liquid having
rial used for lining the tank shall be
a similar viscosity, the temperature of
homogeneous, nonporous, imperforate
which shall not exceed 100 °F during
when applied, not less elastic than the
the test, and applying a pressure of 60
metal of the tank proper. It shall be of
psig. The tank shall be capable of holdsubstantially uniform thickness, not
ing the prescribed pressure for at least
less than 1/32 inch thick if metallic, and
10 minutes without leakage, evidence
not less than 1/16 inch thick if nonof impending failure, or failure. All clometallic, and shall be directly bonded
sures shall be in place while the test is
or attached by other equally satisfacmade and the pressure shall be gauged
tory means. Rubber lining shall be not
at the top of the tank. Safety devices
less than 3/16 inch thick. Joints and
and/or vents shall be plugged during
this test.
seams in the lining shall be made by
fusing the material together or by
(b) [Reserved]
other equally satisfactory means. The
[29 FR 18972. Dec. 29, 1964. Redesignated at 32
interior of the tank shall be free from
FR 5606, Apr. 5, 1967, as amended by Amdt.
scale, oxidation, moisture and all for-
178-104, 59 FR 49135, Sept. 26, 1994]
eign matter during the lining operation.
§ 178.255-13 Repair of tanks.
(b) [Reserved]
(a) Tanks failing to meet the test
may be repaired and retested, provided
§ 178.255-11 Tank mountings.
that repairs are made in complete com-
(a) Tanks shall be designed and fabpliance with the requirements of this
ricated with mountings to provide a sespecification.
cure base in transit. "Skids" or similar
(b) [Reserved]
920
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.270-12
$ 178.255-14 Marking.
§ 178.270-12 Valves, nozzles, piping,
(a) In addition to markings required
and gauging devices.
by Section VIII of the ASME Code
(a) All tank nozzles, except those pro-
(IBR, see $171.7 of this subchapter),
vided for filling and discharge connecevery tank shall bear permanent marks
tions below the normal liquid level of
at least 1/8-inch high stamped into the
the tank, relief devices, thermometer
metal near the center of one of the
wells, and inspection openings, must be
tank heads or stamped into a plate perfitted with manually operated stop
manently attached to the tank by
valves located as near the shell as pracmeans of brazing or welding or other
ticable either internal or external to
suitable means as follows:
the shell. Each filling and discharge
Manufacturer's name
Serial
connection located below the normal
No.
liquid level of the tank must be
DOT specification
equipped with an internal discharge
Nominal capacity
(gallons)
valve. A tank nozzle installed in the
Tare weight
(pounds)
Date of manufacture
vapor space to provide a filling or
cleaning opening, which is closed by a
(b) [Reserved]
blank flange or other suitable means,
[29 FR 18972, Dec. 29, 1964. Redesignated at 32
need not be provided with a manually
FR 5606, Apr. 5, 1967, and amended by Amdt.
operated stop valve. A tank nozzle in-
178-67, 46 FR 49906, Oct. 8. 1981; 68 FR 75750,
stalled for a thermometer well or in-
Dec. 31, 2003]
spection opening need not be provided
§ 178.255-15 Report.
with a manually operated stop valve.
(b) Each valve must be designed and
(a) A copy of the manufacturer's data
report required by Section VIII of the
constructed to a rated pressure not less
ASME Code (IBR, see $171.7 of this subthan the MAWP of the tank. Each stop
chapter) under which the tank is fabvalve with a screwed spindle must be
ricated must be furnished to the owner
closed by a clockwise motion of the
for each new tank.
handwheel. All valves must be constructed to prevent unintentional
Place
opening.
Date
Portable tank
(c) Each internal discharge valve
Manufactured for
Company
shall be self-closing, located inside the
Location
tank, within the welded flange or with-
Manufactured by
Company
in its companion flange.
Location
(d) A shear section must be located
Consigned to
Company
Location
outboard of each internal discharge
Size
feet outside diameter by
valve seat and within 10.2 cm (4 inches)
long.
of the vessel. The shear section must
Marks on tank as prescribed by $178.255-14 of
break under strain without affecting
this specification are as follows:
the product retention capabilities of
Manufacturer's name
Serial number
the tank and any attachments.
Owner's serial number
(e) All piping must be of suitable ma-
DOT specification
terial. Welded joints must be used
ASME Code Symbol (par U-201)
wherever practicable. The bursting
Date of manufacture
strength of all piping and pipe fittings
Nominal capacity
gallons.
must be at least 4 times the MAWP of
It is hereby certified that this tank is in
complete compliance with the requirements
the tank. Piping must be supported in
of DOT specification No. 60.
such a manner as to prevent damage
(Signed)
due to thermal stresses, jarring or vi-
Manufacturer or owner
bration.
(b) [Reserved]
(f) All nozzles and tank shell penetrations for nozzles shall be designed and
[29 FR 18972, Dec. 29, 1964. Redesignated at 32
FR 5606, Apr. 5, 1967, and amended by Amdt.
constructed in accordance with Section
178-83, 50 FR 11066, Mar. 19, 1985; 68 FR 75750,
VIII of the ASME Code (IBR, see § 171.7
Dec. 31, 2003)
of this subchapter).
921
§ 178.270-13
49 CFR Ch. I (10-1-06 Edition)
(g) Glass liquid level gauges, or
port at the lower end of the base strucgauges of other easily destructible mature providing vertical and lateral reterial, which are in direct communicastraint and by support at the upper end
tion with the contents of the tank are
of the base structure providing lateral
prohibited.
restraint only.
[Amdt. 178-65, 46 FR 9898. Jan. 29. 1981; 46 FR
(2) Lateral inertia. The tank loaded to
24184, Apr. 30, 1981, as amended by Amdt. 178-
its maximum gross weight must be po-
117. 61 FR 50628. Sept. 26, 1996; 66 FR 45386,
sitioned for five minutes with its trans-
Aug. 28. 2001; 68 FR 75751, Dec. 31, 2003)
verse axis vertical. It shall be held in
this position for five minutes by sup-
§ 178.270-13 Testing.
port at the lower side of the base struc-
(a) Hydrostatic test. Each portable
ture providing vertical and lateral retank and all piping. valves, and other
straint and by support at the upper
attachments which are subject to the
side of the base structure providing latpressure of the contents of the tank,
eral restraint only.
except pressure relief devices, must be
(d) Approval of smaller tanks of the
hydrostatically tested by completely
same design. Design approval must infilling the tank (including domes, if
clude the prototype testing of at least
any) with water or other liquid having
one tank of each design and each size;
a similar density and viscosity and aphowever, a set of tests made on a tank
plying a pressure of at least 150 percent
of one size may serve for the approval
of the MAWP. The pressure shall be
of smaller tanks with equal or lesser
maintained for at least 10 minutes.
diameter and length) made of the same
While under pressure, the tank shall be
material and thickness by the same
inspected for leakage, undue distorfabrication technique and with idention, or other conditions which inditical supports and equivalent closures
cate weakness or which might render
and other appurtenances.
the tank unsafe for transportation
(e) Pressure and vacuum relief devices.
service. Failure to successfully meet
Each spring loaded relief device must
the test criteria shall be deemed evibe tested for the accuracy of the setdence of failure to meet the requireting prior to installation on a tank and
ments of this specification. Tanks failmust be effectively sealed to maintain
ing to pass the test shall be suitably
the required setting.
repaired and must successfully pass the
(Amdt. 178-65, 46 FR 9898, Jan. 29, 1981; 46 FR
prescribed tests prior to use for trans-
24184, Apr. 30, 1981, as amended by 66 FR
porting any hazardous material.
45387, Aug. 28, 2001]
(b) Testing of internal coils. Internal
coils, if installed, must be
§ 178.270-14 Marking of tanks.
hydrostatically tested to an internal
(a) General. Each tank must bear a
pressure of 13.8 bar (200 psig) or 150 percorrosion resistant metal identificacent of the rated pressure of the coils,
tion plate that is permanently atwhichever is greater.
tached to the portable tank and readily
(c) Tank container qualification test.
accessible for inspection. The informa-
For each tank design, a prototype
tion required in paragraph (b), and,
tank, using a framework for containerwhen appropriate, paragraph (c) of this
ized transport, must fulfill the requiresection must be stamped, embossed or
ments of parts 450-453 of this title for
otherwise marked by an equally duracompliance with the requirements of
ble method on the plate in characters
Annex II of the International Convenat least 3 mm (0.118 inches) high. The
tion for Safe Containers. In addition,
plate must not be painted.
the following tests must be completed
(b) Required information. At least the
without leakage or deformation that
following information must appear on
would render the tank unsuitable for
the metal identification plate for each
use:
tank:
(1) Longitudinal inertia. The tank
(1) US DOT Specification number.
loaded to its maximum gross weight
(2) Country of manufacture.
must be positioned with its longitu-
(3) Manufacturer's name.
dinal axis vertical. It shall be held in
(4) Date of manufacture.
this position for five minutes by sup-
(5) Manufacturer's serial number.
922
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.273
(6) Identification of USA/DOT apapproval agency previously and judged
proval agency and approval number.
unacceptable. Affirmative statements
(7) MAWP, in bar or psig.
must be documented with the name of
(8) Test pressure, in bar or psig.
the approval agency, reason for non-
(9) Total measured water capacity at
acceptance, and the nature of modifica-
20 °C (68 °F), in liters or gallons.
tions made to the design type.
(10) Maximum allowable gross
(b) Action by approval agency. The apweight, in kg or lbs.
proval agency must perform the fol-
(11) Equivalent minimum shell thicklowing activities:
ness in mild steel, in mm or Inches.
(12) Tank material and specification
(1) Review the application for apnumber.
proval to determine whether it is com-
(13) Metallurgical design temperature
plete and conforms with the requirerange, in °C or °F.
ments of paragraph (a) of this section.
(c) Additional information. The fol-
If an application is incomplete, it will
lowing additional information must apbe returned to the applicant with an
pear on the metal identification plate
explanation as to why the application
when applicable:
is incomplete.
(1) Lining material.
(2) Review all drawings and calcula-
(2) Heating coil MAWP in bar and
tions to ensure that the design is in
psig.
compliance with all requirements of
(3) Corrosion allowance, in mm or in.
the relevant specification. If the appli-
(d) In addition to the markings recation is approved, one set of the apquired above, each tank used in interproved drawings, calculations, and test
national transport must have a Safety
data shall be returned to the applicant.
Approval Plate containing the informa-
The second (inspector's copy) set of aption required in §§ 451.21 through 451.25
proved drawings, calculations, and test
of this title.
data shall be retained by the approval
(e) Nothing in this section shall be
agency. Maintain drawings and apdeemed to preclude the display of other
proval records for as long as the portpertinent information on the required
able tank remains in service. The drawmetal identification plate.
ings and records must be provided to
the Department of Transportation
[Amdt. 178-65, 46 FR 9899, Jan. 29, 1981, as
(DOT) upon request.
amended at 62 FR 51561, Oct. 1. 1997; 66 FR
45387, Aug. 28, 2001]
(3) Witness all tests required for the
approval of the portable tank specified
§ 178.273 Approval of Specification IM
in this section and part 180, subpart G
portable tanks and UN portable
of this subchapter.
tanks.
(4) Ensure, through appropriate in-
(a) Application for approval. (1) An
spection that each portable tank is fabowner or manufacturer of a portable
ricated in all respects in conformance
tank shall apply for approval to a deswith the approved drawings, calculaignated approval agency authorized to
tions, and test data.
approve the portable tank in accord-
(5) Determine and ensure that the
ance with the procedures in subpart E,
portable tank is suitable for its inpart 107 of this subchapter.
tended use and that it conforms to the
(2) Each application for approval
requirements of this subchapter.
must contain the following informa-
(6) For UN portable tanks intended
tion:
for non-refrigerated and refrigerated
(i) Two complete copies of all engiliquefied gases and Division 6.1 liquids
neering drawings, calculations, and
which meet the inhalation toxicity critest data necessary to ensure that the
teria (Zone A or B) as defined in
design meets the relevant specifica-
$173.132 of this subchapter, or that are
tion.
designated as toxic by inhalation mate-
(ii) The manufacturer's serial number
rials in the $172.101 Table of this subthat will be assigned to each portable
chapter, the approval agency must entank.
sure that:
(iii) A statement as to whether the
(i) The portable tank has been dedesign type has been examined by any
signed, constructed, certified, and
923
§ 178.273
49 CFR Ch. I (10-1-06 Edition)
stamped in accordance with the retype, the certificate may be valid for
quirements in Division 1 of Section
the entire series of portable tanks rep-
VIII of the ASME Code (IBR, see $171.7
resenting a single design type. For UN
of this subchapter). Other design codes
portable tanks, the certificate must
may be used if approved by the Assorefer to the prototype test report, the
ciate Administrator (see §178.274(b)(1);
hazardous material or group of haz-
(ii) All applicable provisions of the
ardous materials allowed to be transdesign and construction have been met
ported, the materials of construction of
to the satisfaction of the designated
the shell and lining (when applicable)
approval agency in accordance with the
and an approval number. The approval
rules established in the ASME Code
number must consist of the distinand that the portable tank meets the
guishing sign or mark of the country
requirements of the ASME Code and all
("USA" for the United States of Amerthe applicable requirements specified
ica) where the approval was granted
in this subchapter;
and a registration number.
(iii) The inspector has carried out all
(iii) Retain a copy of each approval
the inspections specified by the rules
certificate.
established in the ASME Code; and
(8) For UN portable tanks, the ap-
(iv) The portable tank is marked
proval certificate must also include the
with a U stamp code symbol under the
following:
authority of the authorized independent inspector.
(i) The results of the applicable
(7) Upon successful completion of all
framework and rail impact test specirequirements of this subpart, the apfied in part 180, subpart G, of this subproval agency must:
chapter; and
(i) Apply its name, identifying mark
(ii) The results of the initial inspecor identifying number, and the date
tion and test in $178.274(j).
upon which the approval was issued, to
(9) The approval agency shall be indethe metal identification marking plate
pendent from the manufacturer. The
attached to the portable tank. Any apapproval agency and the authorized inprovals for UN portable tanks authorspector may be the same entity.
izing design or construction alter-
(c) Manufacturers' responsibilities. The
natives (Alternate Arrangements) apmanufacturer is responsible for compliproved by the Associate Administrator
ance with the applicable specifications
(see $178.274(a)(2)) must be indicated on
for the design and construction of portthe plate as specified in $ 178.274(i).
able tanks. In addition to responsi-
(ii) Issue an approval certificate for
bility for compliance, manufacturers
each portable tank or, in the case of a
are responsible for ensuring that the
series of identical portable tanks mancontracted approval agency and auufactured to a single design type, for
thorized inspector, if applicable, are
each series of portable tanks. The apqualified, reputable and competent.
proval certificate must include all the
The manufacturer of a portable tank
information required to be displayed on
shallthe required metal identification plate
(1) Comply with all the applicable Γe-
required by $178.270-14 of this subquirements of the ASME Code and of
chapter for IM portable tanks, $178.245-
this subpart including, but not limited
6 for Specification 51 steel portable
to, ensuring that the quality control,
tanks, or $178.274(i) for UN portable
design calculations and required tests
tanks. The approval certificate must
are performed and that all aspects of
certify that the approval agency desthe portable tank meet the applicable
ignated to approve the portable tank
requirements.
has approved the portable tank in ac-
(2) Obtain and use a designated apcordance with the procedures in subproval agency, If applicable, and obtain
part E of part 107 of this subchapter
and use a DOT-designated approval
and that the portable tank is suitable
agency to approve the design, construcfor its intended purpose and meets the
tion and certification of the portable
requirements of this subchapter. When
tank.
a series of portable tanks is manufac-
(3) Provide a statement in the manutured without change in the design
facturers' data report certifying that
924
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.273
each portable tank that is manufacapproved and the approval agency shall
tured complies with the relevant speciperform the following activities:
fication and all the applicable require-
(i) Return one set of the approved rements of this subchapter.
vised drawings, calculations, and test
(4) Maintain records of the qualificadata to the applicant. The second and
tion of portable tanks for at least 5
third sets of the approved revised drawyears and provide copies to the apings, calculations, and data shall be reproval agency, the owner or lessee of
tained by the approval agency as rethe tank. Upon request, provide these
quired in § 107.404(a)(3) of this subrecords to a representative of DOT.
chapter.
(d) Denial of application for approval.
(ii) Ensure through appropriate in-
If an approval agency finds that a portspection that all modifications conable tank cannot be approved for any
form to the revised drawings, calculareason, it shall notify the applicant in
tions, and test data.
writing and shall provide the applicant
(iii) Determine the extent to which
with the reasons for which the apretesting of the modified tank is necproval is denied. A copy of the notificaessary based on the nature of the protion letter shall be provided to the Asposed modification, and ensure that all
sociate Administrator. An applicant
required retests are satisfactorily peraggrieved by a decision of an approval
formed.
agency may appeal the decision in
(iv) If modification to an approved
writing, within 90 days of receipt, to
tank alters any information on the apthe Associate Administrator.
proval certificate, issue a new approval
(e) Modifications to approved portable
certificate for the modified tank and
tanks. (1) Prior to modification of any
ensure that any necessary changes are
approved portable tank which may afmade to the metal identification plate.
fect conformance and the safe use of an
A copy of each newly issued approval
IM or UN portable tank, which may incertificate shall be retained by the apvolve a change to the design type or
proval agency and by the owner of each
which may affect its ability to retain
portable tank.
the hazardous material in transpor-
(4) If the approval agency determines
tation, the person desiring to make
that the proposed modification is not
such modification shall inform the apin compliance with the relevant DOT
proval agency that issued the initial
specification, the approval agency
approval of the portable tank (or if unshall deny the request in accordance
available another approval agency) of
with paragraph (d) of this section.
the nature of the modification and re-
(f) Termination of Approval Certificate.
quest approval of the modification. The
(1) The Associate Administrator may
person desiring to modify the tank
terminate an approval issued under
must supply the approval agency with
this section if he determines thatthree sets of all revised drawings, cal-
(i) Information upon which the apculations, and test data relative to the
proval was based is fraudulent or subintended modification.
stantially erroneous; or
(2) A statement as to whether the in-
(ii) Termination of the approval is
tended modification has been examined
necessary to adequately protect
and determined to be unacceptable by
against risks to life and property; or
any approval agency. The written
(iii) The approval was not issued by
statement must include the name of
the approval agency in good faith; or
the approving agency, the reason for
(iv) The portable tank does not meet
nonacceptance, and the nature of
the specification.
changes made to the modification since
(2) Before an approval is terminated,
its original rejection.
the Associate Administrator gives the
(3) The approval agency shall review
interested party(ies):
the request for modification, and If it
(i) Written notice of the facts or conis determined that the proposed modiduct believed to warrant the termification is in full compliance with the
nation;
relevant DOT specification, including a
(ii) Opportunity to submit oral and
UN portable tank, the request shall be
written evidence; and
925
§ 178.274
49 CFR Ch. I (10-1-06 Edition)
(iii) Opportunity to demonstrate or
Alternate Arrangement portable tank
achieve compliance with the applicable
means a UN portable tank that has
requirements.
been approved to alternative technical
(3) If the Associate Administrator derequirements or testing methods other
termines that a certificate of approval
than those specified for UN portable
must be terminated to preclude a sigtanks in part 178 or part 180 of this subnificant and imminent adverse affect
chapter.
on public safety, he may terminate the
Approval agency means the descertificate immediately. In such cirignated approval agency authorized to
cumstances, the opportunities of paraapprove the portable tank in accordgraphs (f)(2) (ii) and (iii) of this section
ance with the procedures in subpart E
need not be provided prior to termiof part 107 of this subchapter.
nation of the approval, but shall be
Design pressure is defined according
provided as soon as practicable thereto the hazardous materials intended to
after.
be transported in the portable tank.
See SS 178.275, 178.276 and 178.277, as ap-
[66 FR 33439, June 21, 2001, as amended at 67
plicable.
FR 61016, Sept. 27, 2002; 68 FR 75748, 75751,
Design type means a portable tank or
Dec. 31, 2003]
series of portable tanks made of mate-
§ 178.274 Specifications for UN portrials of the same material specificaable tanks.
tions and thicknesses, manufactured
by a single manufacturer, using the
(a) General. (1) Each UN portable
same fabrication techniques (for examtank must meet the requirements of
ple, welding procedures) and made with
this section. In addition to the requireequivalent structural equipment, cloments of this section, requirements
sures, and service equipment.
specific to UN portable tanks used for
Fine grain steel means steel that has a
liquid and solid hazardous materials,
ferritic grain size of 6 or finer when denon-refrigerated liquefied gases and retermined in accordance with ASTM E
frigerated liquefied gases are provided
112-96 (IBR, see $171.7 of this subin $ 178.275, 178.276 and 178.277, respecchapter).
tively. Requirements for approval,
Fusible element means a non-reclosing
maintenance, inspection, testing and
pressure relief device that is thermally
use are provided in 178.273 and part
activated and that provides protection
180, subpart G, of this subchapter. Any
against excessive pressure buildup in
portable tank which meets the definithe portable tank developed by expotion of a "container" within the terms
sure to heat, such as from a fire (see
of the International Convention for
$178.275(g)).
Safe Containers (CSC) must meet the
Jacket means the outer insulation
requirements of the CSC as amended
cover or cladding which may be part of
and 49 CFR parts 450 through 453 and
the insulation system.
must have a CSC safety approval plate.
Leakage test means a test using gas to
(2) In recognition of scientific and
subject the shell and its service equiptechnological advances, the technical
ment to an internal pressure.
requirements applicable to UN portable
Maximum allowable working pressure
tanks may be varied if approved by the
(MAWP) is defined according to the
Associate Administrator and the porthazardous materials intended to be
able tank is shown to provide a level of
transported in the portable tank. See
safety equal to or exceeding the re-
SS 178.275, 178.276 and 178.277, as applicaquirements of this subchapter. Portble.
able tanks approved to alternative
Maximum permissible gross mass
technical requirements must be
(MPGM) means the sum of the tare
marked "Alternative Arrangement" as
mass of the portable tank and the
specified in paragraph (i) of this secheaviest hazardous material authorized
tion.
for transportation.
(3) Definitions. The following defini-
Mild steel means a steel with a guartions apply for the purposes of design
anteed minimum tensile strength of 360
and construction of UN portable tanks
N/mm2 to 440 N/mm2 and a guaranteed
under this subpart:
minimum elongation at fracture as
926
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.274
specified in paragraph (c)(10) of this
ture must not be less than the maxsection.
imum temperature of the hazardous
Offshore portable tank means a portmaterial during filling, discharge or
able tank specially designed for retransportation. More severe design
peated use in the transportation of haztemperatures must be considered for
ardous materials to, from and between
portable tanks subjected to severe clioffshore facilities. An offshore portable
matic conditions (for example, portable
tank is designed and constructed in actanks transported in arctic regions).
cordance with the Guidelines for the
Shells must be designed and con-
Approval of Containers Handled in
structed in accordance with the re-
Open Seas specified in the IMDG Code
quirements in Section VIII of the
(IBR, see $171.7 of this subchapter).
ASME Code (IBR, see $171.7 of this sub-
Reference steel means a steel with a
chapter), except as limited or modified
tensile strength of 370 N/mm2 and an
in this subchapter. For portable tanks
elongation at fracture of 27%.
used for liquid or solid hazardous mate-
Service equipment means measuring
rials, a design code other than the
instruments and filling, discharge,
ASME Code may be used if approved by
venting, safety, heating, cooling and
the Associate Administrator. Portable
insulating devices.
tanks used for non-refrigerated and re-
Shell means the part of the portable
frigerated liquified compressed gases
tank which retains the hazardous marequire an ASME certification and U
terials intended for transportation, instamp. Shells must be made of metallic
cluding openings and closures, but does
materials suitable for forming. Nonnot include service equipment or extermetallic materials may be used for the
nal structural equipment.
attachments and supports between the
Structural equipment means the reinshell and jacket, provided their mateforcing, fastening, protective and stabirial properties at the minimum and
lizing members external to the shell.
maximum design temperatures are
Test pressure means the maximum
proven to be sufficient. For welded
gauge pressure at the top of the shell
shells, only a material whose
during the hydraulic pressure test
weldability has been fully demequal to not less than 1.5 times the deonstrated may be used. Welds must be
sign pressure for liquids and 1.3 for liqof high quality and conform to a level
uefied compressed gases and refrigof integrity at least equivalent to the
erated liquefied gases. In some inwelding requirements specified in Secstances a pneumatic test is authorized
tion VIII of the ASME Code for the
as an alternative to the hydraulic test.
welding of pressure vessels. When the
The minimum test pressures for portmanufacturing process or the materials
able tanks intended for specific liquid
make it necessary, the shells must be
and solid hazardous materials are specsuitably heat-treated to guarantee adeified in the applicable portable tank T
quate toughness in the weld and in the
codes (such as T1-T23) assigned to
heat-affected zones. In choosing the
these hazardous materials in the
material. the design temperature range
§ 172.101 Table of this subchapter.
must be taken into account with re-
(b) General design and construction respect to risk of brittle fracture, stress
quirements. (1) The design temperature
corrosion cracking, resistance to imrange for the shell must be -40 °C to -50
pact, and suitability for the hazardous
°C (-40 °F to 122 °F) for hazardous matematerials intended for transportation
rials transported under normal condiin the portable tank. When fine grain
tions of transportation, except for
steel is used, the guaranteed value of
portable tanks used for refrigerated
the yield strength must be not more
liquefied gases where the minimum dethan 460 N/mm2 and the guaranteed
sign temperature must not be higher
value of the upper limit of the tensile
than the lowest (coldest) temperature
strength must be not more than 725 N/
(for example, service temperature) of
mm² according to the material specithe contents during filling, discharge
fication. Aluminum may not be used as
or transportation. For hazardous mate-
a construction material for the shells
rials handled under elevated temperaof portable tanks intended for the
ture conditions, the design temperatransport of non-refrigerated liquefied
927
$ 178.274
49 CFR Ch. I (10-1-06 Edition)
gases. For portable tanks intended for
(6) The construction materials of the
the transport of liquid or solid hazportable tank, including any devices,
ardous materials, aluminum may only
gaskets, linings and accessories, must
be used as a construction material for
not adversely affect or react with the
portable tank shells if approved by the
hazardous materials intended to be
Associate Administrator. Portable
transported in the portable tank.
tank materials must be suitable for the
(7) Portable tanks must be designed
external environment where they will
and constructed with supports that
be transported. taking into account the
provide a secure base during transpordetermined design temperature range.
tation and with suitable lifting and tie-
Portable tanks shall be designed to
down attachments.
withstand, without loss of contents, at
(c) Design criteria. (1) Portable tanks
least the Internal pressure due to the
and their fastenings must, under the
contents and the static, dynamic and
maximum permissible loads and maxthermal loads during normal condiimum permissible working pressures,
tions of handling and transportation.
be capable of absorbing the following
The design must take into account the
separately applied static forces (for
effects of fatigue, caused by repeated
calculation purposes, acceleration due
application of these loads through the
to gravity (g) =9.81m/s²):
expected life of the portable tank.
(i) In the direction of travel: 2g
(2) Portable tank shells, fittings, and
(twice the MPGM multiplied by the acpipework shall be constructed from
celeration due to gravity);
materials that are:
(ii) Horizontally at right angles to
(i) Compatible with the hazardous
the direction of travel: 1g (the MPGM
materials intended to be transported;
multiplied by the acceleration due to
or
gravity):
(ii) Properly passivated or neutral-
(iii) Vertically upwards: 1g (the
ized by chemical reaction, if applica-
MPGM multiplied by the acceleration
ble; or
due to gravity); and
(iii) For portable tanks used for liq-
(iv) Vertically downwards: 2g (twice
uid and solid materials, lined with corthe MPGM multiplied by the accelerarosion-resistant material directly
tion due to gravity).
bonded to the shell or attached by
(2) Under each of the forces specified
equivalent means.
in paragraph (c)(1) of this section, the
(3) Gaskets and seals shall be made of
safety factor must be as follows:
materials that are compatible with the
(i) For metals having a clearly dehazardous materials intended to be
fined yield point, a design margin of 1.5
transported.
in relation to the guaranteed yield
(4) When shells are lined, the lining
strength: or
must be compatible with the hazardous
(ii) For metals with no clearly dematerials intended to be transported,
fined yield point, a design margin of 1.5
homogeneous, non-porous, free from
in relation to the guaranteed 0.2%
perforations, sufficiently elastic and
proof strength and, for austenitic
compatible with the thermal expansion
steels. the 1% proof strength.
characteristics of the shell. The lining
(3) The values of yield strength or
of every shell, shell fittings and piping
proof strength must be the values acmust be continuous and must extend
cording to recognized material standaround the face of any flange. Where
ards. When austenitic steels are used,
external fittings are welded to the
the specified minimum values of yield
tank, the lining must be continuous
strength or proof strength according to
through the fitting and around the face
the material standards may be inof external flanges. Joints and seams in
creased by up to 15% for portable tanks
the lining must be made by fusing the
used for liquid and solid hazardous mamaterial together or by other equally
terials, other than toxic by inhalation
effective means.
liquids meeting the criteria of Hazard
(5) Contact between dissimilar met-
Zone A or Hazard Zone B (see § 173.133
als which could result in damage by
of this subchapter), when these greater
galvanic action must be prevented by
values are attested in the material inappropriate measures.
spection certificate.
928
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.274
(4) Portable tanks must be capable of
the construction of welded shells. The
being electrically grounded to prevent
values of Re and Rm to be used in dedangerous electrostatic discharge when
termining this ratio must be the values
they are used for Class 2 flammable
specified in the material inspection
gases or Class 3 flammable liquids, incertificate.
cluding elevated temperature mate-
(10) Steels used in the construction of
rials transported at or above their
shells must have an elongation at fracflash point.
ture, in percentage, of not less than
(5) For shells of portable tanks used
10,000/Rm with an absolute minimum of
for liquefied compressed gases, the
16% for fine grain steels and 20% for
shell must consist of a circular cross
other steels.
section. Shells must be of a design ca-
(11) For the purpose of determining
pable of being stress-analyzed matheactual values for materials for sheet
matically or experimentally by resistmetal, the axis of the tensile test speciance strain gauges as specified in UGmen must be at right angles (trans-
101 of Section VIII of the ASME Code,
versely) to the direction of rolling. The
or other methods approved by the Aspermanent elongation at fracture must
sociate Administrator.
be measured on test specimens of rec-
(6) Shells must be designed and contangular cross sections in accordance
structed to withstand a hydraulic test
with ISO 6892 (IBR, see $171.7 of this
pressure of not less than 1.5 times the
subchapter), using a 50 mm gauge
design pressure for portable tanks used
length.
for liquids and 1.3 times the design
(d) Minimum shell thickness. (1) The
pressure for portable tanks used for liqminimum shell thickness must be the
uefied compressed gases. Specific regreatest thickness of the following:
quirements are provided for each haz-
(i) the minimum thickness deterardous material in the applicable T
mined in accordance with the require-
Code or portable tank special provision
ments of paragraphs (d)(2) through
specified in the $172.101 Table of this
(d)(7) of this section;
subchapter. The minimum shell thick-
(ii) the minimum thickness deterness requirements must also be taken
mined in accordance with Section VIII
into account.
of the ASME Code or other approved
(7) For metals exhibiting a clearly
pressure vessel code: or
defined yield point or characterized by
(iii) the minimum thickness specified
a guaranteed proof strength (0.2% proof
in the applicable T code or portable
strength, generally, or 1% proof
tank special provision indicated for
strength for austenitic steels). the prieach hazardous material in the $172.101
mary membrane stress σ (sigma) in the
Table of this subchapter.
shell must not exceed 0.75 Re or 0.50
(2) Shells (cylindrical portions, heads
Rm, whichever is lower, at the test
and manhole covers) not more than 1.80
pressure, where:
m in diameter may not be less than 5
mm thick in the reference steel or of
Re = yield strength in N/mm2, or 0.2%
proof strength or, for austenitic
equivalent thickness in the metal to be
used. Shells more than 1.80 m in diamesteels, 1% proof strength;
Rm = minimum tensile strength in N/
ter may not be less than 6 mm (0.2
inches) thick in the reference steel or
mm².
of equivalent thickness in the metal to
(8) The values of Re and Rm to be
be used. For portable tanks used only
used must be the specified minimum
for the transportation of powdered or
values according to recognized mategranular solid hazardous materials of
rial standards. When austenitic steels
Packing Group II or III, the minimum
are used, the specified minimum values
thickness requirement may be reduced
for Re and Rm according to the mateto 5 mm in the reference steel or of
rial standards may be increased by up
equivalent thickness in the metal to be
to 15% when greater values are atused regardless of the shell diameter.
tested in the material inspection cer-
For vacuum-insulated tanks, the agtificate.
gregate thickness of the jacket and the
(9) Steels which have a Re/Rm ratio
shell must correspond to the minimum
of more than 0.85 are not allowed for
thickness prescribed in this paragraph,
929
§ 178.274
49 CFR Ch. I (10-1-06 Edition)
with the thickness of the shell itself
(d)(3) and (d)(4) of this section. This
not less than the minimum thickness
thickness must be exclusive of any corprescribed in paragraph (d)(3) of this
rosion allowance.
section.
(7) There must be no sudden change
(3) When additional protection
of plate thickness at the attachment of
against shell damage is provided in the
the heads to the cylindrical portion of
case of portable tanks used for liquid
the shell.
and solid hazardous materials requir-
(e) Service equipment. (1) Service
ing test pressures less than 2.65 bar
equipment must be arranged so that it
(265.0 kPa), subject to certain limitais protected against the risk of metions specified in the UN Recommendachanical damage by external forces
tions (IBR, see $171.7 of this subduring handling and transportation.
chapter), the Associate Administrator
When the connections between the
may approve a reduced minimum shell
frame and the shell allow relative
thickness.
movement between the sub-assemblies,
(4) The cylindrical portions, heads
the equipment must be fastened to
and manhole covers of all shells must
allow such movement without risk of
not be less than 3 mm (0.1 inch) thick
damage to any working part. The exregardless of the material of constructernal discharge fittings (pipe sockets,
tion, except for portable tanks used for
shut-off devices) and the internal stopliquefied compressed gases where the
valve and its seating must be protected
cylindrical portions, ends (heads) and
manhole covers of all shells must not
against mechanical damage by external forces (for example, by using shear
be less than 4 mm (0.2 inch) thick regardless of the material of construcsections). Each internal self-closing
tion.
stop-valve must be protected by a
shear section or sacrificial device lo-
(5) When steel is used, that has charcated outboard of the valve. The shear
acteristics other than that of reference
section or sacrificial device must break
steel, the equivalent thickness of the
at no more than 70% of the load that
shell and heads must be determined acwould cause failure of the Internal selfcording to the following formula:
closing stop valve. The filling and dis-
21.4e₀d₁
charge devices (including flanges or
e₁
=
threaded plugs) and any protective
X
A1
caps must be capable of being secured
Where:
against unintended opening.
e₁ = required equivalent thickness (in mm) of
(2) Each filling or discharge opening
the metal to be used;
of a portable tank must be clearly
eo = minimum thickness (in mm) of the refmarked to indicate its function.
erence steel specified in the applicable T
(3) Each stop-valve or other means of
code or portable tank special provision inclosure must be designed and condicated for each material in the $172.101
structed to a rated pressure not less
Table of this subchapter;
di = 1.8m, unless the formula is used to dethan the MAWP of the shell taking
termine the equivalent minimum thickinto account the temperatures exness for a portable tank shell that is repected during transport. All stopquired to have a minimum thickness of
valves with screwed spindles must
8mm or 10mm according to the applicable
close by a clockwise motion of the
T code indicated in the $172.101 Table of
handwheel. For other stop-valves, the
this subchapter. When reference steel
position (open and closed) and directhicknesses of 8mm or 10mm are specified,
d, is equal to the actual diameter of the
tion of closure must be clearly indishell but not less than 1.8m;
cated. All stop-valves must be designed
Rm, = guaranteed minimum tensile strength
to prevent unintentional opening.
(in N/mm²) of the metal to be used;
(4) Piping must be designed, con-
A, = guaranteed minimum elongation at
structed and installed to avoid the risk
fracture (in %) of the metal to be used acof damage due to thermal expansion
cording to recognized material standards.
and contraction, mechanical shock and
(6) The wall and all parts of the shell
vibration. All piping must be of a suitmay not have a thickness less than
able metallic material. Welded pipe
that prescribed in paragraphs (d)(2),
joints must be used wherever possible.
930
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.274
(5) Joints in copper tubing must be
use. There must be no obstruction in
brazed or have an equally strong metal
an opening leading to a vent or presunion. The melting point of brazing
sure relief device which might restrict
materials must be no lower than 525 °C
or cut-off the flow from the shell to
(977 °F). The joints must not decrease
that device. Vents or pipes from the
the strength of the tubing, such as may
pressure relief device outlets, when
happen when cutting threads. Brazed
used, must deliver the relieved vapor or
joints are not authorized for portable
liquid to the atmosphere in conditions
tanks intended for refrigerated liqueof minimum back-pressure on the refied gases.
lieving devices.
(6) The burst pressure of all piping
(3) Location of pressure relief devices.
and pipe fittings must be greater than
(i) Each pressure relief device inlet
the highest of four times the MAWP of
must be situated on top of the shell in
the shell or four times the pressure to
a position as near the longitudinal and
which it may be subjected in service by
transverse center of the shell as reathe action of a pump or other device
sonably practicable. All pressure relief
(except pressure relief devices).
device inlets must, under maximum
(7) Ductile metals must be used in
filling conditions, be situated in the
the construction of valves and accesvapor space of the shell and the devices
sories.
must be so arranged as to ensure that
(f) Pressure relief devices-(1) Marking
any escaping vapor is not restricted in
of pressure relief devices. Every pressure
any manner. For flammable hazardous
relief device must be clearly and permaterials, the escaping vapor must be
manently marked with the following:
directed away from the shell in such a
(i) the pressure (in bar or kPa) or
manner that it cannot impinge upon
temperature for fusible elements (in
the shell. For refrigerated liquefied
°C) at which it is set to discharge;
gases, the escaping vapor must be di-
(ii) the allowable tolerance at the
rected away from the tank and in such
discharge pressure for reclosing de-
a manner that it cannot impinge upon
vices;
the tank. Protective devices which de-
(iii) the reference temperature corflect the flow of vapor are permissible
responding to the rated pressure for
provided the required relief-device cafrangible discs;
pacity is not reduced.
(iv) the allowable temperature toler-
(ii) Provisions must be implemented
ance for fusible elements;
to prevent unauthorized persons from
(v) The rated flow capacity of the
access to the pressure relief devices
spring loaded pressure relief devices,
and to protect the devices from damage
frangible disc or fusible elements in
caused by the portable tank overstandard cubic meters of air per second
turning.
(m³/s). For spring loaded pressure relief
(g) Gauging devices. Unless a portable
device the rated flow capacity shall be
tank is intended to be filled by weight,
determined according to ISO 4126-1
it must be equipped with one or more
(IBR, see § 171.7 of this subchapter); and
gauging devices. Glass level-gauges and
(vi) when practicable, the device
gauges made of other fragile material,
must show the manufacturer's name
which are in direct communication
and product number.
with the contents of the tank are pro-
(2) Connections to pressure relief dehibited. A connection for a vacuum
vices. Connections to pressure relief degauge must be provided in the jacket of
vices must be of sufficient size to en-
a vacuum-insulated portable tank.
able the required discharge to pass un-
(h) Portable tank supports, frameworks,
restricted to the safety device. No stoplifting and tie-down attachments. (1)
valve may be installed between the
Portable tanks must be designed and
shell and the pressure relief devices exconstructed with a support structure to
cept where duplicate devices are proprovide a secure base during transport.
vided for maintenance or other reasons
The forces and safety factors specified
and the stop-valves serving the devices
in paragraphs (c)(1) and (c)(2) of this
actually in use are locked open or the
section, respectively, must be taken
stop-valves are interlocked so that at
into account in this aspect of the deleast one of the devices is always in
sign. Skids, frameworks, cradles or
931
$ 178.274
49 CFR Ch. I (10-1-06 Edition)
other similar structures are acceptof reinforcement rings or bars fixed
able.
across the frame;
(2) The combined stresses caused by
(iii) Protection against rear impact
portable tank mountings (for example,
which may consist of a bumper or
cradles, framework, etc.) and portable
frame;
tank lifting and tie-down attachments
(iv) Protection of the shell against
must not cause stress that would damdamage from impact or overturning by
age the shell in a manner that would
use of an ISO frame in accordance with
compromise its lading retention capa-
ISO 1496-3 (IBR, see § 171.7 of this subbility. Permanent lifting and tie-down
chapter); and
attachments must be fitted to all port-
(v) Protection of the portable tank
able tanks. Preferably they should be
from impact or damage that may refitted to the portable tank supports
sult from overturning by an insulation
but may be secured to reinforcing
jacket.
plates located on the shell at the
(i) Marking. (1) Every portable tank
points of support. Each portable tank
must be fitted with a corrosion resistmust be designed so that the center of
ant metal plate permanently attached
gravity of the filled tank is approxito the portable tank in a conspicuous
mately centered within the points of
place and readily accessible for inspecattachment for lifting devices.
tion. When the plate cannot be perma-
(3) In the design of supports and
nently attached to the shell, the shell
frameworks, the effects of environmust be marked with at least the informental corrosion must be taken into
mation required by Section VIII of the
account.
ASME Code. At a minimum, the fol-
(4) Forklift pockets must be capable
lowing information must be marked on
of being closed off. The means of closthe plate by stamping or by any other
ing forklift pockets must be a permaequivalent method:
nent part of the framework or perma-
Country of manufacture
nently attached to the framework. Sin-
UN
gle compartment portable tanks with a
Approval Country
length less than 3.65 m (12 ft.) need not
Approval Number
have forklift pockets that are capable
Alternative Arrangements (see $178.274(a)(2))
of being closed off provided that:
"AA"
Manufacturer's name or mark
(i) The shell, including all the fit-
Manufacturer's serial number
tings, are well protected from being hit
Approval Agency (Authorized body for the
by the forklift blades; and
design approval)
(ii) The distance between forklift
Owner's registration number
pockets (measured from the center of
Year of manufacture
each pocket) is at least half of the
Pressure vessel code to which the shell is demaximum length of the portable tank.
signed
(5) During transport, portable tanks
Test pressure
bar gauge.
MAWP
bar gauge.
must be adequately protected against
External design pressure (not required for
damage to the shell, and service equipportable tanks used for refrigerated liquement resulting from lateral and longified gases)
bar gauge.
tudinal impact and overturning, or the
Design temperature range
°C
shell and service equipment must be
to
°C. (For portable tanks used for
constructed to withstand the forces rerefrigerated liquefied gases, the minimum
sulting from impact or overturning.
design temperature must be marked.)
Water capacity at 20 °C/
liters.
External fittings must be protected so
Water capacity of each compartment at 20
as to preclude the release of the shell
°C
liters.
contents upon impact or overturning of
Initial pressure test date and witness identithe portable tank on its fittings. Exfication.
amples of protection include:
MAWP for heating/cooling system
bar
(i) Protection against lateral impact
gauge.
which may consist of longitudinal bars
Shell material(s) and material standard reference(s).
protecting the shell on both sides at
Equivalent
thickness
in
reference
the level of the median line;
steel
mm.
(ii) Protection of the portable tank
Lining material (when applicable).
against overturning which may consist
Date and type of most recent periodic test(s).
932
Pipeline and Hazardous Materials Safety Admin., DOT
$ 178.274
Month
Year
Test
(5) A test of the satisfactory operpressure
bar gauge.
ation of all service equipment includ-
Stamp of approval agency that performed or
ing pressure relief devices must also be
witnessed the most recent test.
performed. When the shell and its fit-
For portable tanks used for refrigerated
tings have been pressure-tested sepaliquefied gases:
rately, they must be subjected to a
Either "thermally insulated" or "vacuum inleakage test after reassembly. All
sulated"
welds, subject to full stress level in the
Effectiveness of the insulation system (heat
influx)
Watts (W).
shell, must be inspected during the ini-
Reference holding time
days or hours
tial test by radiographic, ultrasonic, or
and initial pressure
bar/kPa gauge
another suitable non-destructive test
and degree of filling
in kg for each
method. This does not apply to the
refrigerated liquefied gas permitted for
jacket.
transportation.
(6) A UN portable tank that meets
the definition of "container" in the
(2) The following information must
be marked either on the portable tank
CSC (see 49 CFR 450.3(a) must be
itself or on a metal plate firmly sesubjected to an impact test using a
cured to the portable tank:
prototype representing each design
type. The prototype portable tank
Name of the operator.
must be shown to be capable of absorb-
Name of hazardous materials being transing the forces resulting from an impact
ported and maximum mean bulk temperanot less than 4 times (4 g) the maxture (except for refrigerated liquefied
imum permissible gross mass of the
gases, the name and temperature are only
required when the maximum mean bulk
fully loaded portable tank at a duratemperature is higher than 50 °C).
tion typical of the mechanical shocks
Maximum
permissible
gross
mass
experienced in rail transportation. A
(MPGM)
kg.
listing of standards describing methods
Unladen (tare) mass
kg.
acceptable for performing the impact
test are provided in the UN Rec-
NOTE TO PARAGRAPH (1)(2): For the identification of the hazardous materials being
ommendations. UN portable tanks used
transported refer to part 172 of this subfor the dedicated transportation of
chapter.
"Helium, refrigerated liquid," UN1963
and "Hydrogen, refrigerated liquid,"
(3) If a portable tank is designed and
UN1966 that are marked "NOT FOR
approved for open seas operations, such
RAIL TRANSPORT" in letters of a
as offshore oil exploration, in accordminimum height of 10 cm (4 inches) on
ance with the IMDG Code, the words
at least two sides of the portable tank
"OFFSHORE PORTABLE TANK" must
are excepted from the 4 g impact test.
be marked on the identification plate.
(7) The following tests must be com-
(j) Initial inspection and test. The inipleted on a portable tank or a series of
tial inspection and test of a portable
portable tanks designed and contank must include the following:
structed to a single design type that is
(1) A check of the design characterisalso a CSC container without leakage
tics.
or deformation that would render the
(2) An internal and external examinaportable tank unsafe for transportation
tion of the portable tank and its fitand use:
tings, taking into account the haz-
(i) Longitudinal Inertia. The portable
ardous materials to be transported. For
tank loaded to its maximum gross
UN portable tanks used for refrigerated
weight must be positioned with its lonliquefied gases, a pressure test using an
gitudinal axis vertical. It shall be held
inert gas may be conducted instead of
in this position for five minutes by sup-
a hydrostatic test. An internal inspecport at the lower end of the base struction is not required for a portable tank
ture providing vertical and lateral reused for the dedicated transportation
straint and by support at the upper end
of refrigerated liquefied gases that are
of the base structure providing lateral
not filled with an inspection opening.
restraint only.
(3) A pressure test as specified in
(ii) Lateral inertia. The portable tank
paragraph (i) of this section.
loaded to its maximum gross weight
(4) A leakage test.
must be positioned for five minutes
933
§ 178.275
49 CFR Ch. I (10-1-06 Edition)
with its transverse axis vertical. It
(i) The maximum effective gauge
shall be held in this position for five
pressure allowed in the shell during
minutes by support at the lower side of
filling or discharge; or
the base structure providing vertical
(ii) The maximum effective gauge
and lateral restraint and by support at
pressure to which the shell is designed
the upper side of the base structure
which must be not less than the design
providing lateral restraint only.
pressure.
[66 FR 33440, June 21, 2001, as amended at 67
(c) Service equipment. (1) In addition
FR 15744, Apr. 3, 2002; 68 FR 45041, July 31.
to the requirements specified in
2003; 68 FR 57633, Oct. 6, 2003; 68 FR 75751,
$178.274, for service equipment, all
Dec. 31, 2003; 69 FR 76185, Dec. 20, 2004; 70 FR
openings in the shell, intended for fill-
34399. June 14, 2005]
ing or discharging the portable tank
EDITORIAL NOTE: At 68 FR 57633, Oct. 6,
must be fitted with a manually oper-
2003, $178.274 was amended in paragraph
ated stop-valve located as close to the
(b)(1); however, the amendment could not be
shell as reasonably practicable. Other
incorporated due to inaccurate amendatory
openings, except for openings leading
instruction.
to venting or pressure relief devices,
must be equipped with either a stop-
§ 178.275 Specification for UN Portable
valve or another suitable means of clo-
Tanks intended for the transporsure located as close to the shell as
tation of liquid and solid hazardous
materials.
reasonably practicable.
(2) All portable tanks must be fitted
(a) In addition to the requirements of
with a manhole or other inspection
$178.274, this section sets forth definiopenings of a suitable size to allow for
tions and requirements that apply to
internal inspection and adequate ac-
UN portable tanks intended for the
cess for maintenance and repair of the
transportation of liquid and solid hazinterior. Compartmented portable
ardous materials.
tanks must have a manhole or other
(b) Definitions and requirements-(1)
inspection openings for each compart-
Design pressure means the pressure to
ment.
be used in calculations required by the
(3) For insulated portable tanks, top
recognized pressure vessel code. The
fittings must be surrounded by a spill
design pressure must not be less than
collection reservoir with suitable
the highest of the following pressures:
drains.
(i) The maximum effective gauge
(4) Piping must be designed, conpressure allowed in the shell during
structed and installed to avoid the risk
filling or discharge; or
of damage due to thermal expansion
(ii) The sum ofand contraction, mechanical shock and
(A) The absolute vapor pressure (in
vibration. All piping must be of a suitbar) of the hazardous material at 65 °C,
able metallic material. Welded pipe
minus 1 bar (149 °F, minus 100 kPa);
joints must be used wherever possible.
(B) The partial pressure (in bar) of
(d) Bottom openings. (1) Certain hazair or other gases in the ullage space,
ardous materials may not be transresulting from their compression durported in portable tanks with bottom
ing filling without pressure relief by a
openings. When the applicable T code
maximum ullage temperature of 65 °C
or portable tank special provision, as
(149 °F) and a liquid expansion due to
referenced for materials in the $172.101
an increase in mean bulk temperature
Table of this subchapter, specifies that
of 35 °C (95 °F); and
bottom openings are prohibited, there
(C) A head pressure determined on
must be no openings below the liquid
the basis of the forces specified in
level of the shell when it is filled to its
$ 178.274(c) of this subchapter, but not
maximum permissible filling limit.
less than 0.35 bar (35 kPa).
When an existing opening is closed, it
(2) Maximum allowable working presmust be accomplished by internally
sure (MAWP) means a pressure that
and externally welding one plate to the
must not be less than the highest of
shell.
the following pressures measured at
(2) Bottom discharge outlets for portthe top of the shell while in operating
able tanks carrying certain solid, crysposition:
tallizable or highly viscous hazardous
934
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.275
materials must be equipped with at
6.1, PG I or II, the remote means of cloleast two serially fitted and mutually
sure must be capable of thermal actiindependent shut-off devices. Use of
vation. The thermal means of activaonly two shut-off devices is only aution must activate at a temperature of
thorized when this paragraph is refnot more than 250 °F (121 °C).
erenced in the applicable T Code indi-
(e) Pressure relief devices. All portable
cated for each hazardous material in
tanks must be fitted with at least one
the $172.101 Table of this subchapter.
pressure relief device. All relief devices
The design of the equipment must be to
must be designed, constructed and
the satisfaction of the approval agency
marked in accordance with the requireand must include:
ments of this subchapter.
(i) An external stop-valve fitted as
(f) Vacuum-relief devices. (1) A shell
close to the shell as reasonably pracwhich is to be equipped with a vacuumticable; and
relief device must be designed to with-
(ii) A liquid tight closure at the end
stand, without permanent deformation,
of the discharge pipe, which may be a
an external pressure of not less than
bolted blank flange or a screw cap.
0.21 bar (21.0 kPa). The vacuum-relief
(3) Except as provided in paragraph
device must be set to relieve at a vacu-
(c) (2) of this section, every bottom disum setting not greater than -0.21 bar (-
charge outlet must be equipped with
21.0 kPa) unless the shell is designed
three serially fitted and mutually indefor a higher external over pressure, in
pendent shut-off devices. The design of
which case the vacuum-relief pressure
the equipment must include:
of the device to be fitted must not be
(i) A self-closing internal stop-valve,
greater than the tank design vacuum
which is a stop-valve within the shell
pressure. A shell that is not fitted with
or within a welded flange or its com-
a vacuum-relief device must be depanion flange, such that:
signed to withstand, without perma-
(A) The control devices for the opernent deformation, an external pressure
ation of the valve are designed to preof not less than 0.4 bar (40.0 kPa).
vent any unintended opening through
(2) Vacuum-relief devices used on
impact or other inadvertent act;
portable tanks intended for the trans-
(B) The valve is operable from above
portation of hazardous materials meetor below;
ing the criteria of Class 3. including
(C) If possible, the setting of the
elevated temperature hazardous matevalve (open or closed) must be capable
rials transported at or above their
of being verified from the ground;
flash point, must prevent the imme-
(D) Except for portable tanks having
diate passage of flame into the shell or
a capacity less than 1,000 liters (264.2
the portable tank must have a shell cagallons), it must be possible to close
pable of withstanding, without leakthe valve from an accessible position
age, an internal explosion resulting
on the portable tank that is remote
from the passage of flame into the
from the valve itself within 30 seconds
shell.
of actuation: and
(g) Pressure relief devices. (1) Each
(E) The valve must continue to be efportable tank with a capacity not less
fective in the event of damage to the
than 1,900 liters (501.9 gallons) and
external device for controlling the opevery independent compartment of a
eration of the valve;
portable tank with a similar capacity,
(ii) An external stop-valve fitted as
must be provided with one or more
close to the shell as reasonably pracpressure relief devices of the reclosing
ticable;
type. Such portable tanks may, in ad-
(iii) A liquid tight closure at the end
dition, have a frangible disc or fusible
of the discharge pipe, which may be a
element in parallel with the reclosing
bolted blank flange or a screw cap; and
devices, except when the applicable T
(iv) For UN portable tanks, with botcode assigned to a hazardous material
tom outlets, used for the transporrequires that the frangible disc precede
tation of liquid hazardous materials
the pressure relief device, according to
that are Class 3, PG I or II, or PG III
paragraph (g)(3) of this section, or
with a flash point of less than 100 °F (38
when no bottom openings are allowed.
°C); Division 5.1, PG I or II; or Division
The pressure relief devices must have
935
$ 178.275
49 CFR Ch. I (10-1-06 Edition)
sufficient capacity to prevent rupture
temperature. The shell must not be
of the shell due to over pressurization
subject to undue fluctuations of presor vacuum resulting from filling, dissure during normal conditions of transcharging, heating of the contents or
portation.
fire.
(ii) The required pressure relief de-
(2) Pressure relief devices must be device must be set to start to discharge
signed to prevent the entry of foreign
at a nominal pressure of five-sixths of
matter, the leakage of liquid and the
the test pressure for shells having a
development of any dangerous excess
test pressure of not more than 4.5 bar
pressure.
(450 kPa) and 110% of two-thirds of the
(3) When required for certain haztest pressure for shells having a test
ardous materials by the applicable T
pressure of more than 4.5 bar (450 kPa).
code or portable tank special provision
A self-closing relief device must close
specified for a hazardous material in
at a pressure not more than 10% below
the $172.101 Table of this subchapter,
the pressure at which the discharge
portable tanks must have a pressure
starts. The device must remain closed
relief device consistent with the reat all lower pressures. This requirequirements of this subchapter. Except
ment does not prevent the use of vacufor a portable tank in dedicated service
um-relief or combination pressure rethat is fitted with an approved relief
lief and vacuum-relief devices.
device constructed of materials com-
(h) Fusible elements. Fusible elements
patible with the hazardous material,
must operate at a temperature between
the relief device system must include a
110 °C (230 °F) and 149 °C (300.2 °F) profrangible disc preceding (such as, bevided that the pressure in the shell at
tween the lading and the reclosing
the fusing temperature will not exceed
pressure relief device) a reclosing presthe test pressure. They must be placed
sure relief device. A pressure gauge or
at the top of the shell with their inlets
suitable tell-tale indicator for the dein the vapor space and in no case may
tection of disc rupture, pin-holing or
they be shielded from external heat.
leakage must be provided in the space
Fusible elements must not be utilized
between the frangible disc and the
on portable tanks with a test pressure
pressure relief device to allow the portwhich exceeds 2.65 bar (265.0 kPa). Fusiable tank operator to check to deterble elements used on portable tanks inmine if the disc is leak free. The frantended for the transport of elevated
gible disc must rupture at a nominal
temperature hazardous materials must
pressure 10% above the start-to-disbe designed to operate at a temperacharge pressure of the reclosable presture higher than the maximum temsure relief device.
perature that will be experienced dur-
(4) Every portable tank with a capacing transport and must be designed to
ity less than 1,900 liters (501.9 gallons)
the satisfaction of the approval agency.
must be fitted with a pressure relief de-
(i) Capacity of pressure relief devices.
vice which, except as provided in para-
(1) The reclosing pressure relief device
graph (g)(3) of this section, may be a
required by paragraph (g)(1) of this secfrangible disc when this disc is set to
tion must have a minimum cross secrupture at a nominal pressure equal to
tional flow area equivalent to an orithe test pressure at any temperature
fice of 31.75 mm (1.3 inches) diameter.
within the design temperature range.
Vacuum-relief devices, when used.
(5) When the shell is fitted for presmust have a cross sectional flow area
sure discharge, a suitable pressure renot less than 284 mm² (11.2 inches2).
lief device must provide the inlet line
(2) The combined delivery capacity of
to the portable tank and set to operate
the pressure relief system (taking into
at a pressure not higher than the
account the reduction of the flow when
MAWP of the shell, and a stop-valve
the portable tank is fitted with franmust be fitted as close to the shell as
gible-discs preceding spring-loaded
practicable to minimize the potential
pressure-relief devices or when the
for damage.
spring-loaded pressure-relief devices
(6) Setting of pressure relief devices. (i)
are provided with a device to prevent
Pressure relief devices must operate
the passage of the flame), in condition
only in conditions of excessive rise in
of complete fire engulfment of the
936
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.276
portable tank must be sufficient to
(A) Without insulation or sun shield:
limit the pressure in the shell to 20%
60 °C (140 °F);
above the start to discharge pressure
(B) With sun shield: 55 °C (131 °F); and
limiting device (pressure relief device).
(C) With insulation: 50 °C (122 °F).
The total required capacity of the re-
(3) Filling density means the average
lief devices may be determined using
mass of liquefied compressed gas per
the formula in paragraph (i)(2)(i)(A) of
liter of shell capacity (kg/1).
this section or the table in paragraph
(4) Maximum allowable working pres-
(i)(2)(iii) of this section.
sure (MAWP) means a pressure that
(j) Approval, inspection and testing.
must be not less than the highest of
Approval procedures for UN portable
the following pressures measured at
tanks are specified in $178.273. Inspecthe top of the shell while in operating
tion and testing requirements are specposition, but in no case less than 7 bar
ified in § 180.605 of this subchapter.
(700 kPa):
[66 FR 33445, June 21, 2001, as amended at 68
(i) The maximum effective gauge
FR 32414, May 30, 2003; 69 FR 76185, Dec. 20,
pressure allowed in the shell during
2004)
filling or discharge; or
(ii) The maximum effective gauge
§ 178.276 Requirements for the design,
pressure to which the shell is designed,
construction, inspection and testing
which must be:
of portable tanks intended for the
(A) Not less than the pressure specitransportation of non-refrigerated
fied for each liquefied compressed gas
liquefied compressed gases.
listed in the UN Portable Tank Table
(a) In addition to the requirements of
for Liquefied Compressed Gases in
§ 178.274 applicable to UN portable
§ 173.313; and
tanks, the following requirements
(B) Not less than the sum of:
apply to UN portable tanks used for
(1) The absolute vapor pressure (in
non-refrigerated liquefied compressed
bar) of the liquefied compressed gas at
gases. In addition to the definitions in
the design reference temperature
$178.274, the following definitions
minus 1 bar; and
apply:
(2) The partial pressure (in bar) of air
(1) Design pressure means the pressure
or other gases in the ullage space
to be used in calculations required by
which is determined by the design refthe ASME Code, Section VIII (IBR, see
erence temperature and the liquid
$171.7 of this subchapter). The design
phase expansion due to the increase of
pressure must be not less than the
the mean bulk temperature of (t,
highest of the following pressures:
= filling temperature, usually 15 °C, t, =
(i) The maximum effective gauge
50 °C maximum mean bulk temperapressure allowed in the shell during
ture).
filling or discharge; or
(b) General design and construction re-
(ii) The sum of:
quirements. (1) Shells must be of seam-
(A) The maximum effective gauge
less or welded steel construction, or
pressure to which the shell is designed
combination of both, and have a water
as defined in this paragraph under
capacity greater than 450 liters (118.9
"MAWP"; and
gallons). Shells must be designed. con-
(B) A head pressure determined on
structed, certified and stamped in acthe basis of the dynamic forces specicordance with the ASME Code, Section
fied in paragraph (h) of this section,
VIII.
but not less than 0.35 bar (35 kPa).
(2) Portable tanks must be postweld
(2) Design reference temperature means
heat-treated and radiographed as prethe temperature at which the vapor
scribed in Section VIII of the ASME
pressure of the contents is determined
Code, except that each portable tank
for the purpose of calculating the
constructed in accordance with part
MAWP. The value for each portable
UHT of the ASME Code must be
tank type is as follows:
postweld heat-treated. Where postweld
(i) Shell with a diameter of 1.5 meters
heat treatment is required, the port-
(4.9 ft.) or less: 65 °C (149 °F); or
able tank must be treated as a unit
(ii) Shell with a diameter of more
after completion of all the welds in
than 1.5 meters (4.9 ft.):
and/or to the shell and heads. The
937
§ 178.276
49 CFR Ch. I (10-1-06 Edition)
method must be as prescribed in the
must satisfy the following require-
ASME Code. Welded attachments to
ments:
pads may be made after postweld heat
(1) consist of a shield covering not
treatment is made. A portable tank
less than the upper third, but not more
used for anhydrous ammonia must be
than the upper half of the surface of
postweld heat-treated. The postweld
the shell, and separated from the shell
heat treatment must be as prescribed
by an air space of approximately 40 mm
in the ASME Code, but in no event at
(1.7 inches) across; or
less than 1050 °F tank metal tempera-
(ii) consist of a complete cladding of
ture. Additionally, portable tanks coninsulating materials. The insulation
structed in accordance with part UHT
must be of adequate thickness and conof the ASME Code must conform to the
structed to prevent the ingress of moisfollowing requirements:
ture and damage to the insulation. The
(i) Welding procedure and welder perinsulation and cladding must have a
formance tests must be made annually
thermal conductance of not more than
in accordance with Section IX of the
0.67 (W.m⁻².K⁻¹) under normal condi-
ASME Code. In addition to the essentions of transportation.
tial variables named therein, the fol-
(c) Service equipment. (1) Each opening
lowing must be considered to be essenwith a diameter of more than 1.5 mm
tial variables: number of passes, thick-
(0.1 inch) in the shell of a portable
ness of plate, heat input per pass, and
tank, except openings for pressure-remanufacturer's identification of rod
lief devices, inspection openings and
and flux. The number of passes, thickclosed bleed holes, must be fitted with
ness of plate and heat input per pass
at least three mutually independent
may not vary more than 25 percent
shut-off devices in series: the first
from the qualified procedure. Records
being an internal stop-valve, excess
of the qualification must be retained
flow valve, integral excess flow valve,
for at least 5 years by the portable
or excess flow feature (see $178.337-
tank manufacturer or his designated
1(g)), the second being an external
agent and, upon request, made availstop-valve and the third being a blank
able to a representative of the Departflange. thread cap, plug or equivalent
ment of Transportation or the owner of
tight liquid closure device.
the tank.
(2) When a portable tank is fitted
(ii) Impact tests must be made on a
with an excess flow valve, the excess
lot basis. A lot is defined as 100 tons or
flow valve must be so fitted that its
less of the same heat and having a
seating is inside the shell or inside a
thickness variation no greater than
welded flange or, when fitted exterplus or minus 25 percent. The minimum
nally, its mountings must be designed
impact required for full-sized speciso that in the event of impact it mainmens shall be 20 foot-pounds (or 10
tains its effectiveness. The excess flow
foot-pounds for half-sized specimens) at
valves must be selected and fitted so as
0 °F (-17.8 °F) Charpy V-Notch in both
to close automatically when the rated
the longitudinal and transverse direcflow, specified by the manufacturer, is
tion. If the lot test does not pass this
reached. Connections and accessories
requirement, individual plates may be
leading to or from such a valve must
accepted if they individually meet this
have a capacity for a flow more than
impact requirement.
the excess flow valve's rated flow.
(3) When the shells intended for the
(3) For filling and discharge openings
transportation of non-refrigerated liqthat are located below the liquid level,
uefied compressed gases are equipped
the first shut-off device must be an inwith thermal insulation, a device must
ternal stop-valve and the second must
be provided to prevent any dangerous
be a stop-valve placed in an accessible
pressure from developing in the insuposition on each discharge and filling
lating layer in the event of a leak,
pipe.
when the protective covering is closed
(4) For filling and discharge openings
it must be gas tight. The thermal insulocated below the liquid level of portlation must not inhibit access to the
able tanks intended for the transporfittings and discharge devices. In additation of flammable and/or toxic liquetion, the thermal insulation systems
fied compressed gases, the internal
938
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.276
stop-valve must be a self-closing safety
(ii) One plugged opening of 2-inch Nadevice that fully closes automatically
tional Pipe Thread or less provided for
during filling or discharge in the event
maintenance purposes may be located
of fire engulfment. The device shall
elsewhere;
fully close within 30 seconds of actu-
(iii) An opening of 3-inch National
ation and the thermal means of closure
Pipe Size or less may be provided at
must actuate at a temperature of not
another location, when necessary, to
more than 121 °C (250 °F). Except for
facilitate installation of condensing
portable tanks having a capacity less
coils.
than 1,000 liters (264.2 gallons), this de-
(9) Filling and discharge connections
vice must be operable by remote conare not required to be grouped and may
trol.
be installed below the normal liquid
(5) In addition to filling, discharge
level of the tank if:
and gas pressure equalizing orifices,
(i) The portable tank is permanently
shells may have openings in which
mounted in a full framework for congauges, thermometers and manometers
tainerized transport;
can be fitted. Connections for such in-
(ii) For each portable tank design, a
struments must be made by suitable
prototype portable tank, meets the rewelded nozzles or pockets and may not
be connected by screwed connections
quirements of parts 450 through 453 of
this title for compliance with the rethrough the shell.
(6) All portable tanks must be fitted
quirements of Annex II of the International Convention for Safe Conwith manholes or other inspection
tainers; and
openings of suitable size to allow for
internal inspection and adequate ac-
(iii) Each filling and discharge outlet
cess for maintenance and repair of the
meets the requirements of paragraph
interior.
(c)(4) of this section.
(7) Inlets and discharge outlets on chlo-
(d) Bottom openings. Bottom openings
rine portable tanks. The inlet and disare prohibited on portable tanks when
charge outlets on portable tanks used
the UN Portable Tank Table for Liqueto transport chlorine must meet the refied Compressed Gases in $173.313 of
quirements of § 178.337-1(c)(2) and must
this subchapter indicates that bottom
be fitted with an internal excess flow
openings are not allowed. In this case,
valve. In addition to the internal exthere may be no openings located
cess flow valve, the inlet and discharge
below the liquid level of the shell when
outlets must be equipped with an exit is filled to its maximum permissible
ternal stop valve (angle valve). Excess
filling limit.
flow valves must conform to the stand-
(e) Pressure relief devices. (1) Portable
ards of The Chlorine Institute, Inc.
tanks must be provided with one or
(IBR, see $171.7 of this subchapter) as
more reclosing pressure relief devices.
follows:
The pressure relief devices must open
(i) A valve conforming to Drawing
automatically at a pressure not less
101-7, dated July 1993, must be installed
than the MAWP and be fully open at a
under each liquid angle valve.
pressure equal to 110% of the MAWP.
(ii) A valve conforming to Drawing
These devices must, after discharge,
106-6, dated July 1993, must be installed
close at a pressure not less than 10%
under each gas angle valve. For portbelow the pressure at which discharge
able tanks used to transport non-restarts and must remain closed at all
frigerated liquefied gases.
lower pressures. The pressure relief de-
(8) External fittings must be grouped
vices must be of a type that will resist
together as close as reasonably pracdynamic forces including liquid surge.
ticable. The following openings may be
A frangible disc may only be used in seinstalled at locations other than on the
ries with a reclosing pressure relief detop or end of the tank:
vice.
(i) The openings for liquid level gaug-
(2) Pressure relief devices must be deing devices, pressure gauges, or for
signed to prevent the entry of foreign
safety devices, may be installed sepamatter, the leakage of gas and the derately at the other location or in the
velopment of any dangerous excess
side of the shell;
pressure.
939
§ 178.277
49 CFR Ch. I (10-1-06 Edition)
(3) A portable tank intended for the
ery capacity must consider the additransportation of certain liquefied
tional thermodynamic properties of the
compressed gases identified in the UN
gas, for example see CGA S-1.2 (IBR,
Portable Tank Table for Liquefied
see § 171.7 of this subchapter).
Compressed Gases in $173.313 of this
subchapter must have a pressure relief
[66 FR 33448, June 21, 2001, as amended at 68
FR 75748, 75752, Dec. 31, 2003; 69 FR 54046,
device which conforms to the require-
Sept. 7, 2004; 69 FR 76185, Dec. 20, 2004)
ments of this subchapter. Unless a
portable tank, in dedicated service, is
§ 178.277 Requirements for the design,
fitted with a relief device constructed
construction, inspection and testing
of materials compatible with the hazof portable tanks intended for the
ardous material, the relief device must
transportation of refrigerated liquebe comprised of a frangible disc prefied gases.
ceded by a reclosing device. The space
(a) In addition to the requirements of
between the frangible disc and the de-
§ 178.274 applicable to UN portable
vice must be provided with a pressure
tanks, the following requirements and
gauge or a suitable tell-tale indicator.
definitions apply to UN portable tanks
This arrangement must facilitate the
used for refrigerated liquefied gases:
detection of disc rupture, pinholing or
Design pressure For the purpose of
leakage which could cause a malfuncthis section the term "design pressure"
tion of the pressure relief device. The
is consistent with the definition for defrangible disc must rupture at a nomisign pressure in the ASME Code, Secnal pressure 10% above the start-to-distion VIII (IBR, see $171.7 of this subcharge pressure of the relief device.
(4) In the case of portable tanks used
chapter).
for more than one gas, the pressure re-
Holding time is the time, as deterlief devices must open at a pressure inmined by testing, that will elapse from
dicated in paragraph (e)(1) of this secloading until the pressure of the contion for the gas having the highest
tents, under equilibrium conditions,
maximum allowable pressure of the
reaches the lowest set pressure of the
gases allowed to be transported in the
pressure limiting device(s) (for examportable tank.
ple, pressure control valve or pressure
(f) Capacity of relief devices. The comrelief device). Holding time must be debined delivery capacity of the relief determined as specified in § 178.338-9.
vices must be sufficient so that, in the
Maximum allowable working pressure
event of total fire engulfment, the
(MAWP) means the maximum effective
pressure inside the shell cannot exceed
gauge pressure permissible at the top
120% of the MAWP. Reclosing relief deof the shell of a loaded portable tank in
vices must be used to achieve the full
its operating position including the
relief capacity prescribed. In the case
highest effective pressure during filling
of portable tanks used for more than
and discharge;
gas, the combined delivery capacity of
Minimum design temperature means
the pressure relief devices must be
the temperature which is used for the
taken for the liquefied compressed gas
design and construction of the shell
which requires the highest delivery canot higher than the lowest (coldest)
pacity of the liquefied compressed
service temperature of the contents
gases allowed to be transported in the
during normal conditions of filling, disportable tank. The total required cacharge and transportation.
pacity of the relief devices must be de-
Shell means the part of the portable
termined according to the requiretank which retains the refrigerated liqments in § 178.275(i). These requireuefied gas intended for transport, inments apply only to liquefied comcluding openings and their closures,
pressed gases which have critical tembut does not include service equipment
peratures well above the temperature
or external structural equipment.
at the accumulating condition. For
Tank means a construction which
gases that have critical temperatures
normally consists of either:
near or below the temperature at the
(1) A jacket and one or more Inner
accumulating condition, the calculashells where the space between the
tion of the pressure relief device delivshell(s) and the jacket is exhausted of
940
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.277
air (vacuum insulation) and may incorto be sufficient. In choosing the mateporate a thermal insulation system; or
rial, the minimum design temperature
(2) A jacket and an inner shell with
must be taken into account with rean intermediate layer of solid therspect to risk of brittle fracture, to hymally insulating material (for examdrogen embrittlement, to stress corrople, solid foam).
sion cracking and to resistance to im-
(b) General design and construction repact.
quirements. (1) Portable tanks must be
(5) Any part of a portable tank, inof seamless or welded steel construccluding fittings, gaskets and pipetion and have a water capacity of more
work, which can be expected normally
than 450 liters (118.9 gallons). Portable
to come into contact with the refrigtanks must be designed, constructed,
erated liquefied gas transported must
certified and stamped in accordance
be compatible with that refrigerated
with Section VIII of the ASME Code.
liquefied gas.
(2) Portable tanks must be postweld
(6) The thermal insulation system
heat treated and radiographed as premust include a complete covering of
scribed in Sections V and VIII of the
the shell with effective insulating ma-
ASME Code except that each tank conterials. External insulation must be
structed in accordance with part UHT
protected by a jacket so as to prevent
in Section VIII of the ASME Code must
the ingress of moisture and other dambe postweld heat treated. Where
age under normal transport conditions.
postweld heat treatment is required,
(7) When a jacket is so closed as to be
the tank must be treated as a unit
gas-tight, a device must be provided to
after completion of all the welds to the
prevent any dangerous pressure from
shell and heads. The method must be as
developing in the insulation space.
prescribed in the ASME Code. Welded
(8) Materials which may react with
attachments to pads may be made after
oxygen
or
oxygen
enriched
postweld heat treatment is made. The
atmospheres in a dangerous manner
postweld heat treatment must be as
may not be used in portable tanks inprescribed in Section VIII of the ASME
tended for the transport of refrigerated
Code, but in no event at less than 1,050
liquefied gases having a boiling point
°F tank metal temperature.
below minus 182 °C at atmospheric
(3) Welding procedure and welder perpressure in locations with the thermal
formance tests must be made annually
insulation where there is a risk of conin accordance with Section IX of the
tact with oxygen or with oxygen en-
ASME Code (IBR, see § 171.7 of this subriched fluid.
chapter). In addition to the essential
variables named in the ASME Code, the
(9) Insulating materials must not deteriorate to an extent that the effecfollowing must be considered as essentiveness of the insulation system, as
tial variables: number of passes, thickness of plate. heat input per pass, and
determined in accordance with parathe specified rod and flux. The number
graph (b)(11) of this section, would be
reduced in service.
of passes, thickness of plate and heat
input per pass may not vary more than
(10) A reference holding time must be
25% from the procedure qualification.
determined for each refrigerated lique-
Records of the qualification must be
fied gas intended for transport in a
retained for at least 5 years by the
portable tank. The reference holding
portable tank manufacturer and made
time must be determined by testing in
available to the approval agency and
accordance with the requirements of
the owner of the portable tank as spec-
§ 178.338-9, considering the following
ified in § 178.273.
factors:
(4) Shells and jackets must be made
(i) The effectiveness of the insulation
of metallic materials suitable for formsystem, determined in accordance with
ing. Jackets must be made of steel.
paragraph (b)(11) of this section;
Non-metallic materials may be used
(ii) The lowest set pressure of the
for the attachments and supports bepressure limiting device;
tween the shell and jacket, provided
(iii) The initial filling conditions;
their material properties at the min-
(iv) An assumed ambient temperaimum design temperature are proven
ture of 30 °C (86 °F);
941
§ 178.277
49 CFR Ch. I (10-1-06 Edition)
(v) The physical properties of the inclosest to the jacket must be a selfdividual refrigerated liquefied gas inclosing device, which is capable of
tended to be transported.
being closed from an accessible posi-
(11) The effectiveness of the insulation on the portable tank that is retion system (heat influx in watts) may
mote from the valve within 30 seconds
be determined by type testing the portof actuation. This device must actuate
able tank in accordance with a proceat a temperature of not more than 121
dure specified in 178.338-9(c) or by
°C (250 °F).
using the holding time test in § 178.338-
(2) Each filling and discharge opening
9(b). This test must consist of either:
in portable tanks used for the trans-
(i) A constant pressure test (for export of non-flammable refrigerated liqample, at atmospheric pressure) when
uefied gases must be fitted with at
the loss of refrigerated liquefied gas is
least two mutually independent shutmeasured over a period of time; or
off devices in series: the first being a
(ii) A closed system test when the
stop-valve situated as close as reasonrise in pressure in the shell is measured
ably practicable to the jacket and the
over a period of time.
(12) When performing the constant
second a blank flange or equivalent device.
pressure test, variations in atmospheric pressure must be taken into ac-
(3) For sections of piping which can
count. When performing either test,
be closed at both ends and where liquid
corrections must be made for any variproduct can be trapped, a method of
ation of the ambient temperature from
automatic pressure relief must be prothe assumed ambient temperature refvided to prevent excess pressure builderence value of 30 °C (86 °F).
up within the piping.
(13) The jacket of a vacuum-insulated
(4) Each filling and discharge opening
double-wall tank must have either an
on a portable tank must be clearly
external design pressure not less than
marked to indicate its function.
100 kPa (1 bar) gauge pressure cal-
(5) When pressure-building units are
culated in accordance with Section
used, the liquid and vapor connections
VIII of the ASME Code or a calculated
to that unit must be provided with a
critical collapsing pressure of not less
valve as close to the jacket as reasonthan 200 kPa (2 bar) gauge pressure. Inably practicable to prevent the loss of
ternal and external reinforcements
contents in case of damage to the presmay be included in calculating the
sure-building unit. A check valve may
ability of the jacket to resist the exterbe used for this purpose if it is located
nal pressure.
on the vapor side of the pressure build-
NOTE TO PARAGRAPH (b): For the deterup coil.
mination of the actual holding time, as indi-
(6) The materials of construction of
cated by paragraphs (b)(10), (11), (12), and
valves and accessories must have satis-
(13). before each journey. refer to $178.338-
factory properties at the lowest oper-
9(b).
ating temperature of the portable
(c) Design criteria. For shells with
tank.
vacuum insulation, the test pressure
(7) Vacuum insulated portable tanks
must not be less than 1.3 times the sum
are not required to have an inspection
of the MAWP and 100 kPa (1 bar). In no
opening.
case may the test pressure be less than
(e) Pressure relief devices. (1) Every
300 kPa (3 bar) gauge pressure.
shell must be provided with not less
(d) Service equipment. (1) Each filling
than two independent reclosing presand discharge opening in portable
sure relief devices. The pressure relief
tanks used for the transport of flamdevices must open automatically at a
mable refrigerated liquefied gases must
pressure not less than the MAWP and
be fitted with at least three mutually
be fully open at a pressure equal to
independent shut-off devices in series:
110% of the MAWP. These devices
the first being a stop-valve situated as
must, after discharge, close at a presclose as reasonably practicable to the
sure not lower than 10% below the presjacket, the second being a stop-valve
sure at which discharge starts and
and the third being a blank flange or
must remain closed at all lower presequivalent device. The shut-off device
sures. The pressure relief devices must
942
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.318-2
be of the type that will resist dynamic
§ 178.318 Specification MC 201; conforces including surge.
tainer for detonators and percus-
(2) Except for portable tanks used for
sion caps.
oxygen, portable tanks for non-flam-
§ 178.318-1 Scope.
mable refrigerated liquefied gases (except oxygen) and hydrogen may in ad-
(a) This specification pertains to a
dition have frangible discs in parallel
container to be used for the transporwith the reclosing devices as specified
tation of detonators and percussion
in paragraphs (e)(4)(ii) and (e)(4)(iii) of
caps in connection with the transporthis section.
tation of liquid nitroglycerin, desen-
(3) Pressure relief devices must be desitized liquid nitroglycerin or
signed to prevent the entry of foreign
diethylene glycol dinitrate, where any
matter, the leakage of gas and the deor all of such types of caps may be used
velopment of any dangerous excess
for the detonation of liquid nitroglycerin, desentitized liquid nitroglycerin
pressure.
or diethylene glycol dinitrate in blast-
(4) Capacity and setting of pressure relief devices. (i) In the case of the loss of
ing operations. This specification is
not intended to take the place of any
vacuum in a vacuum-insulated tank or
shipping or packing requirements of
of loss of 20% of the insulation of a
this Department where the caps in
portable tank insulated with solid maquestion are themselves articles of
terials, the combined capacity of all
commerce.
pressure relief devices installed must
(b) [Reserved]
be sufficient so that the pressure (including accumulation) inside the shell
[29 FR 18975, Dec. 29, 1964. Redesignated at 32
does not exceed 120% of the MAWP.
FR 5606, Apr. 5, 1967. and amended by Amdt.
178-60, 44 FR 70733, Dec. 10. 1979]
(ii) For non-flammable refrigerated
liquefied gases (except oxygen) and hy-
§ 178.318-2 Container.
drogen, this capacity may be achieved
by the use of frangible discs in parallel
(a) Every container for detonators
with the required safety-relief devices.
and percussion caps coming within the
Frangible discs must rupture at nomiscope of this specification shall be constructed entirely of hard rubber,
nal pressure equal to the test pressure
of the shell.
phenolresinous or other resinous material, or other nonmetallic, nonsparking
(iii) Under the circumstances dematerial, except that metal parts may
scribed in paragraphs (e)(4)(i) and
be used in such locations as not in any
(e)(4)(ii) of this section, together with
event to come in contact with any of
complete fire engulfment, the comthe caps. Space shall be provided so
bined capacity of all pressure relief dethat each detonator of whatever nature
vices installed must be sufficient to
may be inserted in an individual cell in
limit the pressure in the shell to the
the body of the container, into which
test pressure.
each such cap shall snugly fit. There
(iv) The required capacity of the reshall be provided no more than twenty
lief devices must be calculated in ac-
(20) such cellular spaces. Space may be
cordance with CGA Pamphlet S-1.2
provided into which a plurality of per-
(IBR, see § 171.7 of this subchapter).
cussion caps may be carried, provided
[66 FR 33450, June 21, 2001, as amended at 68
that such space may be closed with a
FR 75748, 75752, Dec. 31, 2003]
screw cap, and further provided that
each or any such space is entirely sepa-
Subpart I [Reserved]
rate from any space provided for any
detonator. Each cellular space into
which a detonator is to be inserted and
Subpart J-Specifications for Concarried shall be capable of being covtainers for Motor Vehicle
ered by a rotary cover so arranged as
Transportation
to expose not more than one cell at any
time, and capable of rotation to such a
SOURCE: 29 FR 18975, Dec. 29, 1964, unless
place that all cells will be covered at
otherwise noted. Redesignated at 32 FR 5606,
the same time, at which place means
Apr. 5, 1967.
shall be provided to lock the cover in
943
§ 178.318-2
49 CFR Ch. I (10-1-06 Edition)
place. Means shall be provided to lock
tion of moisture, such treatment shall
in place the cover for the cells provided
be applied as shall be necessary in
for the carrying of detonators. The reorder to provide against the penetraquirement that not more than one cell
tion of water by permeation. A suitable
be exposed at one time need not apply
carrying handle shall be provided, exin the case of detonators, although
cept for which handle no part of the
spaces for such caps and detonators
container may project beyond the exteshall be separate. Sufficient annular
rior of the body.
space shall be provided inside the cover
(b) Exhibited in plates I and II are
for such detonators that, when the
line drawings of a container for detocover is closed, there will be sufficient
nators and percussion caps, illustrative
space to accommodate the wires cusof the requirements set forth in
tomarily attached to such caps. If the
$178.318-2(a). These plates shall not be
material is of such a nature as to reconstrued as a part of this specificaquire treatment to prevent the absorption.
944
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.320
Fuse cop container end
Electric cop container end
Section A-B-C
BLASTING CAP CONTAINER
PLATE 1
Spot for index button of close position "F"
Spot for center holes at "G"
C
2020
F
Engrave and
fill in white
C
E
Percussion cap
pocket
2 required
Section E-E
PLAN
Handie removed
PLATE Il
[29 FR 18975, Dec. 29, 1964. Redesignated at 32 FR 5606, Apr. 5, 1967, and amended by Amdt.
178-60, 44 FR 70733, Dec. 10, 1979)
§ 178.318-3 Marking.
tention or containment function and
Each container must be marked as
provides no structural support to the
prescribed in $178.2(b).
cargo tank.
Baffle means a non-liquid-tight trans-
[Amdt. 178-40, 41 FR 38181, Sept. 9, 1976. as
verse partition device that deflects,
amended at 66 FR 45185, Aug. 28, 2001]
checks or regulates fluid motion in a
tank.
§ 178.320 General requirements appli-
Bulkhead means a liquid-tight transcable to all DOT specification cargo
verse closure at the ends of or between
tank motor vehicles.
cargo tanks.
(a) Definitions. For the purpose of this
Cargo tank means a bulk packaging
subchapter:
that:
Appurtenance means any attachment
(1) Is a tank intended primarily for
to a cargo tank that has no lading rethe carriage of liquids, gases, solids, or
945
§ 178.320
49 CFR Ch. I (10-1-06 Edition)
semi-solids and includes appurvariations in piping that do not affect
tenances, reinforcements, fittings, and
the lading retention capability of the
closures (for tank, see SS 178.337-1,
cargo tank;
178.338-1, or 178.345-1, as applicable);
(4) Of the same materials of construc-
(2) Is permanently attached to or
tion;
forms a part of a motor vehicle, or is
(5) To the same cross-sectional dinot permanently attached to a motor
mensions;
vehicle but that, by reason of its size,
(6) To a length varying by no more
construction, or attachment to a
than 5 percent;
motor vehicle, is loaded or unloaded
(7) With the volume varying by no
without being removed from the motor
more than 5 percent (due to a change in
vehicle; and
length only); and
(3) Is not fabricated under a speci-
(8) For the purposes of § 178.338 only,
fication for cylinders, intermediate
with the same insulation system.
bulk containers, multi-unit tank car
External self-closing stop valve means a
tanks, portable tanks, or tank cars.
self-closing stop valve designed so that
Cargo tank motor vehicle means a
the self-stored energy source is located
motor vehicle with one or more cargo
tanks permanently attached to or
outside the cargo tank and the welded
forming an integral part of the motor
flange.
vehicle.
Extreme dynamic loading means the
Cargo tank wall means those parts of
maximum loading a cargo tank motor
the cargo tank that make up the privehicle may experience during its exmary lading retention structure, inpected life, excluding accident loadings
cluding shell, bulkheads, and fittings
resulting from an accident, such as
overturn or collision.
and, when closed, yield the minimum
volume of the cargo tank assembly.
Flange means the structural ring for
Charging line means a hose, tube,
guiding or attachment of a pipe or fitpipe, or a similar device used to presting with another flange (companion
surize a tank with material other than
flange), pipe, fitting or other attachment.
the lading.
Companion flange means one of two
Inspection pressure means the presmating flanges where the flange faces
sure used to determine leak tightness
are in contact or separated only by a
of the cargo tank when testing with
thin leak-sealing gasket and are sepneumatic pressure.
cured to one another by bolts or
Internal self-closing stop valve means a
clamps.
self-closing stop valve designed so that
Connecting structure means the structhe self-stored energy source is located
ture joining two cargo tanks.
inside the cargo tank or cargo tank
Constructed and certified in accordance
sump, or within the welded flange, and
with the ASME Code means a cargo
the valve seat is located within the
tank is constructed and stamped in accargo tank or within one inch of the
cordance with Section VIII of the
external face of the welded flange or
ASME Code (IBR, see $171.7 of this subsump of the cargo tank.
chapter), and is inspected and certified
Lading means the hazardous material
by an Authorized Inspector.
contained in a cargo tank.
Constructed in accordance with the
Loading/unloading connection means
ASME Code means a cargo tank is conthe fitting in the loading/unloading
structed in accordance with Section
line farthest from the loading/unload-
VIII of the ASME Code with authorized
ing outlet to which the loading/unloadexceptions (see $178.346 through
ing hose, pipe, or device is attached.
178.348) and is inspected and certified
Loading/unloading outlet means a
by a Registered Inspector.
cargo tank outlet used for normal load-
Design type means one or more cargo
ing/unloading operations.
tanks that are made-
Loading/unloading stop valve means
(1) To the same specification:
the stop valve farthest from the cargo
(2) By the same manufacturer;
tank loading/unloading outlet to which
(3) To the same engineering drawings
the loading/unloading connection is atand calculations, except for minor
tached.
946
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.320
Manufacturer means any person enfabricated to more than one cargo tank
gaged in the manufacture of a DOT
specification.
specification cargo tank, cargo tank
Normal operating loading means the
motor vehicle, or cargo tank equiploading a cargo tank motor vehicle
ment that forms part of the cargo tank
may be expected to experience rouwall. This term includes attaching a
tinely in operation.
cargo tank to a motor vehicle or to a
Nozzle means a subassembly conmotor vehicle suspension component
sisting of a pipe or tubular section with
that involves welding on the cargo
or without a welded or forged flange on
tank wall. A manufacturer must regone end.
ister with the Department in accord-
Outlet means any opening in the shell
ance with subpart F of part 107 in subor head of a cargo tank, (including the
part A of this chapter.
means for attaching a closure), except
Maximum allowable working pressure
that the following are not outlets: a
or MAWP means the maximum presthreaded opening securely closed dursure allowed at the top of the tank in
ing transportation with a threaded
its normal operating position. The
plug or a threaded cap. a flanged open-
MAWP must be calculated as preing securely closed during transporscribed in Section VIII of the ASME
tation with a bolted or welded blank
Code. In use, the MAWP must be greatflange, a manhole, a gauging device, a
er than or equal to the maximum ladthermometer well, or a pressure relief
ing pressure conditions prescribed in
device.
$173.33 of this subchapter for each ma-
Outlet stop valve means the stop valve
terial transported.
at a cargo tank loading or unloading
Maximum
lading
pressure.
See
outlet.
173.33(c).
Pipe coupling means a fitting with in-
Minimum thickness means the minternal threads on both ends.
imum required shell and head (and baf-
Rear bumper means the structure defle and bulkhead when used as tank resigned to prevent a vehicle or object
inforcement) thickness needed to meet
from under-riding the rear of another
the specification. The minimum thickmotor vehicle. See $393.86 of this title.
ness is the greatest of the following val-
Rear-end tank protection device means
ues: (1)(i) For MC 330, MC 331, and MC
the structure designed to protect a
338 cargo tanks, the specified minimum
cargo tank and any lading retention
thickness found the applicable specipiping or devices in case of a rear end
fication(s): or
collision.
(ii) For DOT 406, DOT 407 and DOT
Self-closing stop valve means a stop
412 cargo tanks, the specified minimum
valve held in the closed position by
thickness found in Tables I and II of
means of self-stored energy, that opens
the applicable specification(s); or
only by application of an external force
(iii) For MC 300, MC 301, MC 302, MC
and that closes when the external force
303, MC 304, MC 305, MC 306, MC 307, MC
is removed.
310, MC 311, and MC 312 cargo tanks,
Shell means the circumferential porthe in-service minimum thickness pretion of a cargo tank defined by the
scribed in Tables I and II of
basic design radius or radii excluding
$ 180.407(i)(5) of this subchapter, for the
the bulkheads.
minimum thickness specified by Tables
Stop valve means a valve that stops
I and Il of the applicable specificathe flow of lading.
tion(s); or
Sump means a protrusion from the
(2) The thickness necessary to meet
bottom of a cargo tank shell designed
with the structural integrity and accito facilitate complete loading and undent damage requirements of the appliloading of lading.
cable specification(s); or
Tank means a container, consisting
(3) The thickness as computed per
of a shell and heads, that forms a presthe ASME Code requirements (if applisure tight vessel having openings decable).
signed to accept pressure tight fittings
Multi-specification cargo tank motor veor closures, but excludes any appurhicle means a cargo tank motor vehicle
tenances, reinforcements. fittings, or
equipped with two or more cargo tanks
closures.
947
§ 178.337
49 CFR Ch. I (10-1-06 Edition)
Test pressure means the pressure to
compliance with certain paragraphs of
which a tank is subjected to determine
the ASME Code, compliance with those
structural integrity.
paragraphs is not prohibited.
Toughness of material means the capa-
[Amdt. 178-89, 55 FR 37055, Sept. 7. 1990, as
bility of a material to absorb energy
amended by Amdt. 178-98, 58 FR 33306, June
represented by the area under a stress
16, 1993; Amdt. 178-118, 61 FR 51339, Oct. 1.
strain curve (indicating the energy ab-
1996: 68 FR 19277, Apr. 18, 2003; 68 FR 52370,
sorbed per unit volume of the material)
Sept. 3, 2003: 68 FR 75752, Dec. 31, 2003)
up to the point of rupture.
Vacuum cargo tank means a cargo
§ 178.337 Specification MC 331; cargo
tank that is loaded by reducing the
tank motor vehicle primarily for
transportation of compressed gases
pressure in the cargo tank to below atas defined in subpart G of part 173
mospheric pressure.
of this subchapter.
Variable specification cargo tank
means a cargo tank that is constructed
§ 178.337-1 General requirements.
in accordance with one specification,
(a) ASME Code construction. Tanks
but that may be altered to meet anmust beother specification by changing relief
(1) Seamless or welded construction,
device, closures, lading discharge deor a combination of both;
vices, and other lading retention de-
(2) Designed, constructed, certified,
vices.
and stamped in accordance with Sec-
Void means the space between tank
tion VIII of the ASME Code (IBR, see
heads or bulkheads and a connecting
$171.7 of this subchapter);
structure.
(3) Made of steel or aluminum; how-
Welded flange means a flange atever, if aluminum is used, the cargo
tached to the tank by a weld joining
tank must be insulated and the hazthe tank shell to the cylindrical outer
ardous material to be transported must
surface of the flange, or by a fillet weld
be compatible with the aluminum (see
joining the tank shell to a flange
§§ 178.337-1(e)(2), 173.315(a) table, and
shaped to fit the shell contour.
178.337-2(a)(1) of this subchapter); and
(b) Design certification. (1) Each cargo
(4) Covered with a steel jacket if the
tank or cargo tank motor vehicle decargo tank is insulated and used to
sign type, including its required accitransport a flammable gas (see
dent damage protection device, must
$ 173.315(a) table Note 11 of this subbe certified to conform to the specificachapter).
tion requirements by a Design Certi-
(b) Design pressure. The design presfying Engineer who is registered in acsure of a cargo tank authorized under
cordance with subpart F of part 107 of
this specification shall be not less than
this title. An accident damage protecthe vapor pressure of the commodity
tion device is a rear-end protection,
contained therein at 115 °F. or as preoverturn protection, or piping protecscribed for a particular commodity in
tion device.
$173.315(a) of this subchapter, except
(2) The Design Certifying Engineer
that in no case shall the design presshall furnish to the manufacturer a
sure of any cargo tank be less than 100
certificate to indicate compliance with
p.s.i.g. nor more than 500 p.s.i.g.
the specification requirements. The
certificate must include the sketches,
NOTE 1: The term design pressure as used in
drawings, and calculations used for certhis specification. is identical to the term
MAWP as used in the ASME Code.
tification. Each certificate, including
sketches, drawings, and calculations,
(c) Openings. (1) Excess pressure relief
shall be signed by the Design Certivalves shall be located in the top of the
fying Engineer.
cargo tank or heads.
(3) The manufacturer shall retain the
(2) A chlorine cargo tank shall have
design certificate at his principal place
only one opening. That opening shall
of business for as long as he manufacbe in the top of the cargo tank and
tures DOT specification cargo tanks.
shall be fitted with a nozzle that meets
(c) Exceptions to the ASME Code. Unthe following requirements:
less otherwise specified, when excep-
(i) On a cargo tank manufactured on
tions are provided in this subpart from
or before December 31, 1974, the nozzle
948
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.337-1
shall be protected by a dome cover
as a unit after completion of all the
plate which conforms to either the
welds in and/or to the shells and heads.
standard of The Chlorine Institute,
The method must be as prescribed in
Inc., Dwg. 103-3, dated January 23, 1958,
Section VIII of the ASME Code. Welded
or to the standard specified in paraattachments to pads may be made after
graph (c) (2) (ii) of this section.
postweld heat treatment. A cargo tank
(ii) On a cargo tank manufactured on
used for anhydrous ammonia must be
or after January 1, 1975. the nozzle
postweld heat treated. The postweld
shall be protected by a manway cover
heat treatment must be as prescribed
which conforms to the standard of The
in Section VIII of the ASME Code, but
Chlorine Institute, Inc., Dwg. 103-4,
in no event at less than 1,050 SF cargo
dated September 1, 1971.
tank metal temperature.
(d) Reflective design. Every
(g) Definitions. The following definiuninsulated cargo tank permanently
tions apply to §§ 178.337-1 through
attached to a cargo tank motor vehicle
178.337-18:
shall, unless covered with a jacket
Emergency discharge control means the
made of aluminum, stainless steel, or
ability to stop a cargo tank unloading
other bright nontarnishing metal, be
operation in the event of an unintenpainted a white, aluminum or similar
tional release. Emergency discharge
reflecting color on the upper two-thirds
control can utilize passive or off-truck
of area of the cargo tank.
remote means to stop the unloading
(e) Insulation. (1) Each cargo tank reoperation. A passive means of emerquired to be insulated must conform
gency discharge control automatically
with the use and performance requireshuts off the flow of product without
ments contained in 173.315(a) table
the need for human intervention withand 178.337-1 (a)(3) and (e)(2) of this
in 20 seconds of an unintentional resubchapter.
lease caused by a complete separation
(2) Each cargo tank intended for
of the liquid delivery hose. An offchlorine; carbon dioxide, refrigerated
truck remote means of emergency disliquid; or nitrous oxide, refrigerated
charge control permits a qualified perliquid service must have suitable insuson attending the unloading operation
lation of such thickness that the overto close the cargo tank's internal selfall thermal conductance is not more
closing stop valve and shut off all mothan 0.08 Btu per square foot per °F diftive and auxiliary power equipment at
ferential per hour. The conductance
a distance from the cargo tank motor
must be determined at 60 °F. Insulation
vehicle.
material used on cargo tanks for ni-
Excess flow valve, integral excess flow
trous oxide, refrigerated liquid must be
valve, or excess flow feature means a
noncombustible. Insulating material
component that will close automatiused on cargo tanks for chlorine must
cally if the flow rate of a gas or liquid
be corkboard or polyurethane foam,
through the component reaches or exwith a minimum thickness of 4 inches,
ceeds the rated flow of gas or liquid
or 2 inches minimum thickness of cespecified by the original valve manuramic fiber/fiberglass of 4 pounds per
facturer when piping mounted directly
cubic foot minimum density covered by
on the valve is sheared off before the
2 inches minimum thickness of fiber.
first valve, pump, or fitting down-
(f) Postweld heat treatment. Postweld
stream from the valve.
heat treatment must be as prescribed
Internal self-closing stop valve means a
in the ASME Code except that each
primary shut off valve installed in a
cargo tank constructed in accordance
product discharge outlet of a cargo
with Part UHT of Section VIII of the
tank and designed to be kept closed by
ASME Code must be postweld heat
self-stored energy.
treated. Each chlorine cargo tank must
Primary discharge control system
be fully radiographed and postweld
means a primary shut-off installed at a
heat treated in accordance with the
product discharge outlet of a cargo
provisions in Section VIII of the ASME
tank consisting of an Internal self-clos-
Code under which it is constructed.
ing stop valve that may include an in-
Where postweld heat treatment is retegral excess flow valve or an excess
quired, the cargo tank must be treated
flow feature, together with linkages
949
§ 178.337-2
49 CFR Ch. I (10-1-06 Edition)
that must be installed between the
ferential orientation of the cargo tank
valve and remote actuator to provide
shell.
manual and thermal on-truck remote
(b) For a chlorine cargo tank. Plates,
means of closure.
the manway nozzle, and anchorage
[Order 59-B. 30 FR 579, Jan. 16, 1965. Redesigshall be made of carbon steel which
nated at 32 FR 5606, Apr. 5. 1967]
meets the following requirements:
(1) For a cargo tank manufactured on
EDITORIAL NOTE: For FEDERAL REGISTER cltations affecting 178.337-1, see the List of
or before December 31, 1974-
CFR Sections Affected which appears in the
(i) Material shall conform to ASTM A
Finding Aids section of the printed volume
300, "Steel Plates for Pressure Vessels
and on GPO Access.
for Service at Low Temperatures"
(IBR, see § 171.7 of this subchapter);
§ 178.337-2 Material.
(ii) Material shall be Class 1, Grade
(a) General. (1) All material used for
A, flange or firebox quality:
construction of the cargo tank and ap-
(iii) Plate impact test specimens, as
purtenances must be suitable for use
required under paragraph (a) of this
with the commodities to be transsection, shall be of the Charpy keyhole
ported therein and must conform to
notch type; and
the requirements in Section II of the
(iv) Plate impact test specimens
ASME Code (IBR, see $171.7 of this subshall meet the impact test requirechapter) and/or requirements of the
ments in paragraph (a) of this section
American Society for Testing and Main both the longitudinal and transverse
terials in all respects.
directions of rolling at a temperature
(2) Impact tests are required on steel
of minus 45.5 C. °F.).
used in the fabrication of each cargo
(2) For a cargo tank manufactured on
tank constructed in accordance with
or after January 1, 1975-
part UHT in Section VIII of the ASME
(i) Material shall conform to ASTM A
Code. The tests must be made on a lot
612 (IBR, see $171.7 of this subchapter),
basis. A lot is defined as 100 tons or less
Grade B or A 516/A 516M (IBR, see 171.7
of the same heat treatment processing
of this subchapter), Grade 65 or 70;
lot having a thickness variation no
(ii) Material shall meet the Charpy
greater than plus or minus 25 percent.
V-notch test requirements of ASTM A
The minimum impact required for full
20/A 20M (IBR, see $171.7 of this subsize specimens must be 20 foot-pounds
chapter); and
in the longitudinal direction at -30
(iii) Plate impact test specimens
°F., Charpy V-Notch and 15 foot-pounds
shall meet the impact test requirein the transverse direction at -30 °F.,
ments in paragraph (a) of this section
Charpy V-Notch. The required values
in both the longitudinal and transverse
for subsize specimens must be reduced
directions of rolling at a temperature
in direct proportion to the cross-secof minus 40 °C. (-40 °F.).
tional area of the specimen beneath the
(c) A cargo tank in anhydrous ammonotch. If a lot does not meet this renia service must be constructed of
quirement, individual plates may be
steel. The use of copper, silver, zinc or
accepted if they individually meet this
their alloys is prohibited. Baffles made
requirement.
from aluminum may be used only if
(3) The fabricator shall record the
joined to the cargo tank by a process
heat, and slab numbers, and the ceΓ-
not requiring postweld heat treatment
tified Charpy impact values, where reof the cargo tank.
quired, of each plate used in each cargo
[Order 59-B, 30 FR 579, Jan. 16. 1965. Redesigtank on a sketch showing the location
nated at 32 FR 5606, Apr. 5, 1967]
of each plate in the shell and heads of
EDITORIAL NOTE: For FEDERAL REGISTER cithe cargo tank. Copies of each sketch
tations affecting $178.337-2, see the List of
shall be provided to the owner and re-
CFR Sections Affected which appears in the
tained for at least five years by the
Finding Aids section of the printed volume
fabricator and made available to duly
and on GPO Access.
identified representatives of the Department of Transportation.
$ 178.337-3 Structural integrity.
(4) The direction of final rolling of
(a) General requirements and acceptthe shell material shall be the circumance criteria. (1) Except as provided in
950
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.337-3
paragraph (d) of this section, the maxthroughout the cargo tank motor vehiimum calculated design stress at any
cle. The vertical, longitudinal, and latpoint in the cargo tank may not exceed
eral normal operating loadings can
the maximum allowable stress value
occur simultaneously and must be
prescribed in Section VIII of the ASME
combined. The vertical, longitudinal
Code (IBR, see $171.7 of this suband lateral extreme dynamic loadings
chapter), or 25 percent of the tensile
occur separately and need not be comstrength of the material used.
bined.
(2) The relevant physical properties
(1) Normal operating loadings. The folof the materials used in each cargo
lowing procedure addresses stress in
tank may be established either by a
the tank shell resulting from normal
certified test report from the material
operating loadings. The effective stress
manufacturer or by testing in conform-
(the maximum principal stress at any
ance with a recognized national standpoint) must be determined by the folard. In either case, the ultimate tensile
lowing formula:
strength of the material used in the de-
S = 0.5(S, + Sx) ±[0.25(Sy - Sx)2 + S,2]0.5
sign may not exceed 120 percent of the
ultimate tensile strength specified in
Where:
either the ASME Code or the ASTM
(i) S = effective stress at any given
standard to which the material is manpoint under the combination of static
ufactured.
and normal operating loadings that can
(3) The maximum design stress at
occur at the same time, in psi.
any point in the cargo tank must be
(ii) S, = circumferential stress gencalculated separately for the loading
erated by the MAWP and external presconditions described in paragraphs (b).
sure, when applicable, plus static head,
(c), and (d) of this section. Alternate
in psi.
test or analytical methods, or a com-
(iii) Sx = The following net longitubination thereof, may be used in place
dinal stress generated by the following
of the procedures described in parastatic and normal operating loading
graphs (b), (c), and (d) of this section, if
conditions, in psi:
the methods are accurate and
(A) The longitudinal stresses resultverifiable.
ing from the MAWP and external pres-
(4) Corrosion allowance material may
sure, when applicable, plus static head,
not be included to satisfy any of the
in combination with the bending stress
design calculation requirements of this
generated by the static weight of the
section.
fully loaded cargo tank motor vehicle,
(b) Static design and construction. (1)
all structural elements, equipment and
The static design and construction of
appurtenances supported by the cargo
each cargo tank must be in accordance
tank wall;
with Section VIII of the ASME Code.
(B) The tensile or compressive stress
The cargo tank design must include
resulting from normal operating longicalculation of stresses generated by detudinal acceleration or deceleration. In
sign pressure, the weight of lading, the
each case, the forces applied must be
weight of structure supported by the
0.35 times the vertical reaction at the
cargo tank wall, and the effect of temsuspension assembly, applied at the
perature gradients resulting from ladroad surface, and as transmitted to the
ing and ambient temperature extremes.
cargo tank wall through the suspension
When dissimilar materials are used,
assembly of a trailer during deceleratheir thermal coefficients must be used
tion; or the horizontal pivot of the
in calculation of thermal stresses.
truck tractor or converter dolly fifth
(2) Stress concentrations in tension,
wheel, or the drawbar hinge on the
bending and torsion which occur at
fixed dolly during acceleration; or anpads, cradles, or other supports must
choring and support members of a
be considered in accordance with aptruck during acceleration and decelerapendix G in Section VIII of the ASME
tion, as applicable. The vertical reac-
Code.
tion must be calculated based on the
(c) Shell design. Shell stresses resultstatic weight of the fully loaded cargo
ing from static or dynamic loadings, or
tank motor vehicle, all structural elecombinations thereof, are not uniform
ments, equipment and appurtenances
951
$ 178.337-3
49 CFR Ch. I (10-1-06 Edition)
supported by the cargo tank wall. The
sembly of a trailer, applied at the road
following loadings must be included:
surface, and as transmitted to the
(1) The axial load generated by a
cargo tank wall through the suspension
decelerative force;
assembly of a trailer, and the hori-
(2) The bending moment generated by
zontal pivot of the upper coupler (fifth
a decelerative force;
wheel) or turntable; or anchoring and
(3) The axial load generated by an acsupport members of a truck, as applicacelerative force; and
ble. The vertical reaction must be cal-
(4) The bending moment generated by
culated based on the static weight of
an accelerative force; and
the fully loaded cargo tank motor vehi-
(C) The tensile or compressive stress
cle, all structural elements, equipment
generated by the bending moment reand appurtenances supported by the
sulting from normal operating vertical
cargo tank wall; and
accelerative force equal to 0.35 times
(D) The torsional shear stress genthe vertical reaction at the suspension
erated by the same lateral forces as deassembly of a trailer; or the horizontal
scribed in paragraph (c)(1)(iv)(C) of this
pivot of the upper coupler (fifth wheel)
section.
or turntable; or anchoring and support
(2) Extreme dynamic loadings. The folmembers of a truck, as applicable. The
lowing procedure addresses stress in
vertical reaction must be calculated
the tank shell resulting from extreme
based on the static weight of the fully
dynamic loadings. The effective stress
loaded cargo tank motor vehicle, all
(the maximum principal stress at any
structural elements, equipment and appoint) must be determined by the folpurtenances supported by the cargo
lowing formula:
tank wall.
S = 0.5(Sy + Sx) ±[0.25(S, - Sx)2 + S,2]0.5
(iv) S, = The following shear stresses
generated by the following static and
Where:
normal operating loading conditions,
(i) S = effective stress at any given
in psi:
point under a combination of static
(A) The static shear stress resulting
and extreme dynamic loadings that can
from the vertical reaction at the susoccur at the same time, in psi.
pension assembly of a trailer, and the
(ii) Sy = circumferential stress genhorizontal pivot of the upper coupler
erated by MAWP and external pressure,
(fifth wheel) or turntable; or anchoring
when applicable, plus static head, in
and support members of a truck, as appsi.
plicable. The vertical reaction must be
(iii) Sx = the following net longitucalculated based on the static weight
dinal stress generated by the following
of the fully loaded cargo tank motor
static and extreme dynamic loading
vehicle, all structural elements, equipconditions, in psi:
ment and appurtenances supported by
(A) The longitudinal stresses resultthe cargo tank wall;
ing from the MAWP and external pres-
(B) The vertical shear stress gensure, when applicable, plus static head,
erated by a normal operating accelerain combination with the bending stress
tive force equal to 0.35 times the
generated by the static weight of the
vertical reaction at the suspension asfully loaded cargo tank motor vehicle,
sembly of a trailer; or the horizontal
all structural elements, equipment and
pivot of the upper coupler (fifth wheel)
appurtenances supported by the tank
or turntable; or anchoring and support
wall;
members of a truck, as applicable. The
(B) The tensile or compressive stress
vertical reaction must be calculated
resulting from extreme longitudinal
based on the static weight of the fully
acceleration or deceleration. In each
loaded cargo tank motor vehicle, all
case the forces applied must be 0.7
structural elements, equipment and aptimes the vertical reaction at the suspurtenances supported by the cargo
pension assembly, applied at the road
tank wall;
surface, and as transmitted to the
(C) The lateral shear stress generated
cargo tank wall through the suspension
by a normal operating lateral acceleraassembly of a trailer during decelerative force equal to 0.2 times the
tion; or the horizontal pivot of the
vertical reaction at each suspension astruck tractor or converter dolly fifth
952
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.337-3
wheel, or the drawbar hinge on the
loaded cargo tank motor vehicle, all
fixed dolly during acceleration; or the
structural elements, equipment and apanchoring and support members of a
purtenances supported by the cargo
truck during acceleration and deceleratank wall;
tion, as applicable. The vertical reac-
(C) The lateral shear stress generated
tion must be calculated based on the
by an extreme lateral accelerative
static weight of the fully loaded cargo
force equal to 0.4 times the vertical retank motor vehicle, all structural eleaction at the suspension assembly of a
ments, equipment and appurtenances
trailer, applied at the road surface, and
supported by the cargo tank wall. The
as transmitted to the cargo tank wall
following loadings must be included:
through the suspension assembly of a
(1) The axial load generated by a
trailer, and the horizontal pivot of the
decelerative force;
upper coupler (fifth wheel) or turn-
(2) The bending moment generated by
table; or anchoring and support mem-
a decelerative force;
bers of a truck, as applicable. The
(3) The axial load generated by an acvertical reaction must be calculated
celerative force; and
based on the static weight of the fully
(4) The bending moment generated by
loaded cargo tank motor vehicle, all
an accelerative force; and
structural elements, equipment and ap-
(C) The tensile or compressive stress
purtenances supported by the cargo
generated by the bending moment retank wall; and
sulting from an extreme vertical accel-
(D) The torsional shear stress generative force equal to 0.7 times the
erated by the same lateral forces as devertical reaction at the suspension asscribed in paragraph (c)(2)(iv)(C) of this
sembly of a trailer, and the horizontal
section.
pivot of the upper coupler (fifth wheel)
(d) In order to account for stresses
or turntable; or the anchoring and supdue to impact in an accident, the deport members of a truck, as applicable.
sign calculations for the cargo tank
The vertical reaction must be calshell and heads must include the load
culated based on the static weight of
resulting from the design pressure in
the fully loaded cargo tank motor vehicombination with the dynamic prescle, all structural elements, equipment
sure resulting from a longitudinal deand appurtenances supported by the
celeration of "2g". For this loading
cargo tank wall.
condition the stress value used may
(iv) Ss = The following shear stresses
not exceed the lesser of the yield
generated by static and extreme dystrength or 75 percent of the ultimate
namic loading conditions, in psi:
tensile strength of the material of con-
(A) The static shear stress resulting
struction. For cargo tanks constructed
from the vertical reaction at the susof stainless steel the maximum design
pension assembly of a trailer, and the
stress may not exceed 75 percent of the
horizontal pivot of the upper coupler
ultimate tensile strength of the type
(fifth wheel) or turntable: or anchoring
steel used.
and support members of a truck, as ap-
(e) The minimum metal thickness for
plicable. The vertical reaction must be
the shell and heads on tanks with a decalculated based on the static weight
sign pressure of 100 psig or more must
of the fully loaded cargo tank motor
be 4.75 mm (0.187 inch) for steel and 6.86
vehicle, all structural elements, equipmm (0.270 inch) for aluminum, except
ment and appurtenances supported by
for chlorine and sulfur dioxide tanks.
the cargo tank wall;
In all cases, the minimum thickness of
(B) The vertical shear stress genthe tank shell and head shall be detererated by an extreme vertical acceleramined using structural design requiretive force equal to 0.7 times the
ments in Section VIII of the ASME
vertical reaction at the suspension as-
Code or 25% of the tensile strength of
sembly of a trailer, and the horizontal
the material used. For a cargo tank
pivot of the upper coupler (fifth wheel)
used in chlorine or sulfur dioxide servor turntable; or anchoring and support
ice, the cargo tank must be made of
members of a truck, as applicable. The
steel. A corrosion allowance of 20 pervertical reaction must be calculated
cent or 2.54 mm (0.10 inch), whichever
based on the static weight of the fully
is less, must be added to the thickness
953
§ 178.337-4
49 CFR Ch. I (10-1-06 Edition)
otherwise required for sulfur dioxide
thickness of the mounting pad may not
and chlorine tank material. In chlorine
be less than that of the shell wall or
cargo tanks, the wall thickness must
head wall to which it is attached, and
be at least 1.59 cm (0.625 inch), includnot more than 1.5 times the shell or
ing corrosion allowance.
head thickness. However, a pad with a
(f) Where a cargo tank support is atminimum thickness of 0.25 inch may be
tached to any part of the cargo tank
used when the shell or head thickness
wall, the stresses imposed on the cargo
is over 0.25 inch. If weep holes or telltank wall must meet the requirements
tale holes are used, the pad must be
in paragraph (a) of this section.
drilled or punched at the lowest point
(g) The design, construction, and inbefore it is welded to the tank. Each
stallation of an attachment, appurpad musttenance to the cargo tank, structural
(i) Be fabricated from material detersupport member between the cargo
mined to be suitable for welding to
tank and the vehicle or suspension
both the cargo tank material and the
component, or accident protection dematerial of the appurtenance or strucvice must conform to the following retural support member; a Design Certiquirements:
fying Engineer must make this deter-
(1) Structural members, the suspenmination considering chemical and
sion sub-frame, accident protection
physical properties of the materials
structures, and external circumferenand must specify filler material contial reinforcement devices must be
forming to the requirements in Section
used as sites for attachment of appur-
VIII of the ASME Code (IBR, see $ 171.7
tenances and other accessories to the
of this subchapter).
cargo tank, when practicable.
(2) A lightweight attachment to the
(ii) Be preformed to an inside radius
cargo tank wall such as a conduit clip,
no greater than the outside radius of
brake line clip, skirting structure,
the cargo tank at the attachment location.
lamp mounting bracket, or placard
holder must be of a construction hav-
(iii) Extend at least 2 inches in each
ing lesser strength than the cargo tank
direction from any point of attachment
wall materials and may not be more
of an appurtenance or structural supthan 72 percent of the thickness of the
port member. This dimension may be
material to which it is attached. The
measured from the center of the atlightweight attachment may be setached structural member.
cured directly to the cargo tank wall if
(iv) Have rounded corners, or otherthe device is designed and installed in
wise be shaped in a manner to minisuch a manner that, if damaged, it will
mize stress concentrations on the shell
not affect the lading retention integor head.
rity of the tank. A lightweight attach-
(v) Be attached by continuous fillet
ment must be secured to the cargo
welding. Any fillet weld discontinuity
tank shell or head by a continuous
may only be for the purpose of preweld or in such a manner as to preclude
venting an intersection between the filformation of pockets which may belet weld and a tank or jacket seam
come sites for corrosion. Attachments
weld.
meeting the requirements of this para-
(Amdt. 178-89, 55 FR 37056, Sept. 7, 1990, as
graph are not authorized for cargo
amended by Amdt. 178-104, 59 FR 49135, Sept.
tanks constructed under part UHT in
26, 1994; Amdt. 178-105, 60 FR 17401. Apr. 5,
Section VIII of the ASME Code.
1995; Amdt. 178-118, 61 FR 51340. Oct. 1. 1996;
(3) Except as prescribed in para-
65 FR 58631, Sept. 29, 2000; 68 FR 19279, Apr.
graphs (g) (1) and (g)(2) of this section,
18, 2003; 68 FR 52370, Sept. 3, 2003; 68 FR 75753,
the welding of any appurtenance to the
Dec. 31, 2003]
cargo tank wall must be made by attachment of a mounting pad so that
§ 178.337-4 Joints.
there will be no adverse effect upon the
(a) Joints shall be as required in Seclading retention integrity of the cargo
tion VIII of the ASME Code (IBR, see
tank if any force less than that pre-
$171.7 of this subchapter), with all unscribed in paragraph (b)(1) of this secdercutting in shell and head material
tion is applied from any direction. The
repaired as specified therein.
954
Pipeline and Hazardous Materials Safety Admin., DOT
§ 178.337-8
(b) Welding procedure and welder per-
§ 178.337-6 Closure for manhole.
formance must be in accordance with
Section IX of the ASME Code. In addi-
(a) Each cargo tank marked or certion to the essential variables named
tified after April 21, 1994, must be protherein, the following must be considvided with a manhole conforming to
ered as essential variables: Number of
paragraph UG-46(g) (1) and other applipasses; thickness of plate; heat input
cable requirements in Section VIII of
the ASME Code (IBR, see § 171.7 of this
per pass; and manufacturer's identification of rod and flux. When fabricasubchapter), except that a cargo tank
tion is done in accordance with part
constructed of NQT steel having a ca-
UHT in Section VIII of the ASME Code,
pacity of 3,500 water gallons or less
filler material containing more than
may be provided with an inspection
0.08 percent vanadium must not be
opening conforming to paragraph UGused. The number of passes, thickness
46 and other applicable requirements of
the ASME Code instead of a manhole.
of plate, and heat input per pass may
not vary more than 25 percent from the
(b) The manhole assembly of cargo
tanks constructed after June 30, 1979,
procedure or welder qualifications.
Records of the qualifications must be
may not be located on the front head of
retained for at least 5 years by the
the cargo tank.
cargo tank manufacturer and must be
[Amdt. 178-7. 34 FR 18250, Nov. 14, 1969, as
made available to duly identified repamended by Amdt. 178-52, 43 FR 58820, Dec.
resentatives of the Department and the
18, 1978; Amdt. 178-89. 54 FR 25017. June 12,
owner of the cargo tank.
1989; 55 FR 21038, May 22, 1990; 56 FR 27876,
(c) All longitudinal shell welds shall
June 17, 1991; 58 FR 12905, March 8, 1993;
Amdt. 178-118, 61 FR 51340, Oct. 1, 1996; 68 FR
be located in the upper half of the
75753, Dec. 31, 2003]
cargo tank.
(d) Edge preparation of shell and
§ 178.337-7 Overturn protection.
head components may be by machine
(a) See § 178.337-10.
heat processes, provided such surfaces
(b) [Reserved]
are remelted in the subsequent welding
process. Where there will be no subse-
[Order 59-B, 30 FR 580, Jan. 16, 1965. Redesigquent remelting of the prepared surface
nated at 32 FR 5606, Apr. 5, 1967]
as in a tapered section, the final 0.050
inch of material shall be removed by
$ 178.337-8 Openings, inlets, and outlets.
mechanical means.
(e) The maximum tolerance for mis-
(a) General. The requirements in this
alignment and butting up shall be in
paragraph (a) apply to MC 331 cargo
accordance with the requirement in
tanks except for those used to trans-