Regl. 1279, art. 205.8b dup2
Reglamento General de Seguridad e Higiene Industrial, Cap. VI -- Montacargas de Trabajadores. No incluido en el Ãndice bajo la Ley Núm. 149 de 12 dic, 2005
Cite as Reglamento Núm. 1279, Art. 205.8b dup2
supported and guided below the car frame that the
clearance specified in Rule 205.10 for the safety
parts are maintained during normal operation.
The auxiliary safety plank shall be so designed
that the maximum stresses in the plank shall not
exceed those specified for similar car frame members
in Section 203.
6. The rail-gripping device of auxiliary safety
plank shall be so arranged and connected as to prevent the plank from being out of level more than onehalf (1/2) inch in the length of the plank when the
safety is operated to stop the car.
7. An electric switch shall be provided and
so arranged and connected that the elevator cannot
be operated by means of the normal operating device
if any buffer is compressed more than ten (10) per
cent of its stroke.
8. Means shall be provided to prevent operation
of the elevator by means of the normal operating
device if the oil level in any buffer is below the
minimum allowable level (See also Part 1, Section 107,
Rule 107.1a).
USAS, A17.1
-SECTION 212-