Regl. 9049, art. 107-1020
CORRIDORS
Length: 183 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-1020
TABLE 1020.1
CORRIDOR FIRE-RESISTANCE RATING
REQUIRED FIRE-RESISTANCE
OCCUPANT LOAD SERVED
RATING (hours)
OCCUPANCY
BY CORRIDOR
Without sprinkler
With sprinkler
system
system
H-1, H-2, H-3
All
Not Permitted
1
H-4, H-5
Greater than 30
Not Permitted
1
A, B, E, F, M, S,
Greater than 30
1
0
U
R-1, R-4
Greater than 10
Not Permitted
0.5c/1ᵃ
R2
Less than 30
1
0.5c/1ᵃ
R2
Greater than 30
Not Permitted
0.5%/1ᵃ
R3
Less than 16
1
0.5c/1ᵃ
I-2ª
All
Not Permitted
0
I-1, I-3
All
Not Permitted
1ᵇ
I-4
Al
1
0
a.
For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3.
b.
For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8.
c.
Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed.
d.
Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems
are permitted in accordance with Section 903.3.1.3.