Regl. 9049, art. 107-106
FLOOR AND ROOF DESIGN LOADS
Length: 132 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-106
[A]106.1 Live loads posted. In commercial or industrial buildings, for each floor or portion
thereof designed for live loads exceeding 50 psf (2.40 kN/m2), such design live loads shall be
conspicuously posted by the owner or the owner's authorized agent in that part of each story in
which they apply, using durable signs. It shall be unlawful to remove or deface such notices.
[A]106.2 Issuance of certificate of occupancy. A certificate of occupancy required by Section
111 shall not be issued until the floor load signs, required by Section 106.1, have been installed.
36
[A]106.3 Restrictions on loading. It shall be unlawful to place, or cause or permit to be placed,
on any floor or roof of a building, structure or portion thereof, a load greater than is permitted by
this code.