SERVICE UTILITIES
Length: 27,460 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-113 dup2
[A]113.1 Authority to disconnect service utilities. The fire code official shall have the authority
to authorize disconnection of utility service to the building, structure or system in order to safely
execute emergency operations or to eliminate an immediate hazard. The fire code official shall
notify the and the government agencies with jurisdiction and, where possible, the owner or the
owner's authorized agent and the occupant of the building, structure or service system of the
decision to disconnect prior to taking such action. If not notified prior to disconnection, then the
owner, the owner's authorized agent or occupant of the building, structure or service system shall
be notified in writing as soon as practical thereafter.
CHAPTER 2 - DEFINITIONS
SECTION 201 GENERAL
201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the
purposes of this code, have the meanings shown in this chapter.
201.2 Interchangeability. Words used in the present tense include the future; words stated in the
masculine gender include the feminine and neuter; the singular number includes the plural and
the plural, the singular.
201.3 Terms defined in other codes. Where terms are not defined in this code and are defined in
the Puerto Rico Building Code, Puerto Rico Fuel Gas Code, Puerto Rico Mechanical Code or
Puerto Rico Plumbing Code, such terms shall have the meanings ascribed to them as in those
codes.
201.4 Terms not defined. Where terms are not defined through the methods authorized by this
section, such terms shall have ordinarily accepted meanings such as the context implies.
Merriam Webster's Collegiate Dictionary, 11th Edition, shall be considered as providing
ordinarily accepted meanings.
653
SECTION 202 GENERAL DEFINITIONS
[BG] 24-HOUR BASIS. The actual time that a person is an occupant within a facility for the
purpose of receiving care. It shall not include a facility that is open for 24 hours and is capable of
providing care to someone visiting the facility during any segment of the 24 hours.
[M]ACCESS (TO). That which enables a device, appliance or equipment to be reached by ready
access or by a means that first requires the removal or movement of a panel, door or similar
obstruction [see also "Ready access (to)"].
[BE] ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress
travel from any accessible point in a building or facility to a public way.
[BE] ACCESSIBLE ROUTE. A continuous, unobstructed path that complies with Chapter 11
of the Puerto Rico Building Code.
[AJADMINISTRATIVE JUDGE. The director of the Administrative Revisions Division, as
establish by Act 161-2009, as amended.
AEROSOL CONTAINER. A metal can or plastic container up to a maximum size of 33.8 fluid
ounces (1000 ml) or a glass bottle up to a maximum size of 4 fluid ounces (118 ml) designed and
intended to dispense an aerosol.
AEROSOL COOKING SPRAY PRODUCTS. Aerosol cooking spray products are those
aerosol products designed to deliver a vegetable oil or a solid or nonflammable liquid to reduce
sticking on cooking and baking surfaces, or to be applied to food, or both. These products have a
chemical heat of combustion that is greater than 8600 Btu/lb. (20 kJ/g) and contain no more than
18 percent by weight of flammable propellant.
AEROSOL PRODUCT. A combination of a container, a propellant and a material that is
dispensed. Aerosol products shall be classified by means of the calculation of their chemical heats
of combustion and shall be designated Level 1, Level 2 or Level 3.
Level 1 aerosol products. Those with a total chemical heat of combustion that is less than
or equal to 8,600 British thermal units per pound (Btu/lb) (20 kJ/g).
Level 2 aerosol products. Those with a total chemical heat of combustion that is greater
than 8,600 Btu/lb (20 but less than or equal to 13,000 Btu/lb (30 kJ/g).
Level 3 aerosol products. Those with a total chemical heat of combustion that is greater
than 13,000 Btu/lb (30 kJ/g).
AEROSOL PRODUCT WAREHOUSE. A building used for warehousing aerosol products.
AGENCY. Any emergency responder department within the jurisdiction that utilizes radio
frequencies for communication. This could include, but not be limited to, various public safety
654
agencies such as fire departments, emergency medical services and law enforcement.
AGENT. A person who shall have charge, care or control of any structure as owner, or agent of
the owner, or as executor, executrix, administrator, administratrix, trustee or guardian of the estate
of the owner. Any such person representing the actual owner shall be bound to comply with the
provisions of this code to the same extent as if that person was the owner.
[BG] AGRICULTURAL BUILDING. A structure designed and constructed to house farm
implements, hay, grain, poultry, livestock or other horticultural products. This structure shall not
be a place of human habitation or a place of employment where agricultural products are
processed, treated or packaged, nor shall it be a place used by the public.
AGRO-INDUSTRIAL. A facility, or portion thereof, housing operations involving the
transforming of raw agricultural products into intermediate or consumable products.
[BG] AIR-INFLATED STRUCTURE. A structure that uses air-pressurized membrane beams,
arches or other elements to enclose space. Occupants of such a structure do not occupy the
pressurized areas used to support the structure.
[BG] AIR-SUPPORTED STRUCTURE. A structure wherein the shape of the structure is
attained by air pressure, and occupants of the structure are within the elevated pressure area. Air
supported structures are of two basic types:
Double skin. Similar to a single skin, but with an attached liner that is separated from the
outer skin and provides an airspace which serves for insulation, acoustic, aesthetic or
similar purposes.
Single skin. Where there is only the single outer skin and the air pressure is directly against
that skin.
AIRCRAFT MOTOR-VEHICLE FUEL-DISPENSING FACILITY. That portion of
property where flammable or combustible liquids or gases used as motor fuels are stored and
dispensed from fixed automotive-type equipment into the fuel tanks of aircraft.
AIRCRAFT OPERATION AREA (AOA). Any area used or intended for use for the parking,
taxiing, takeoff, landing or other ground-based aircraft activity.
AIRPORT. An area of land or structural surface that is used, or intended for use, for the landing
and taking off of aircraft with an overall length greater than 39 feet (11 887 mm) and an overall
exterior fuselage width greater than 6.6 feet (2012 mm), and any appurtenant areas that are used
or intended for use for airport buildings and other airport facilities.
[BE] AISLE. An unenclosed exit access component that defines and provides a path of egress
travel.
[BE] AISLE ACCESSWAY. That portion of an exit access that leads to an aisle.
655
ALARM, NUISANCE. See "Nuisance alarm."
ALARM DEVICE, MULTIPLE STATION. See "Multiple-station alarm device."
ALARM NOTIFICATION APPLIANCE. A fire alarm system component such as a bell, horn,
speaker, light or text display that provides audible, tactile or visible outputs, or any combination
thereof. See also "Audible alarm notification appliance" or "Visible alarm notification appliance."
ALARM SIGNAL. A signal indicating an emergency requiring immediate action, such as a signal
indicative of fire.
ALARM VERIFICATION FEATURE. A feature of automatic fire detection and alarm
systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a
minimum period of time, or confirm alarm conditions within a given time period, after being
automatically reset, in order to be accepted as a valid alarm-initiation signal.
ALCOHOL-BASED HAND RUB. An alcohol-containing preparation designed for application
to the hands for reducing the number of viable microorganisms on the hands and containing
ethanol or isopropanol in an amount not exceeding 95-percent by volume.
ALCOHOL-BLENDED FUELS. Flammable liquids consisting of greater than 10 percent, by
volume, ethanol or other alcohols blended with gasoline.
[A] ALTERATION. Any construction or renovation to an existing structure other than a repair
or addition.
[BE] ALTERNATING TREAD DEVICE. A device that has a series of steps between 50 and
70 degrees (0.87 and 1.22 rad) from horizontal, usually attached to a center support rail in an
alternating manner so that the user does not have both feet on the same level at the same time.
[BG] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide
medical, surgical, psychiatric, nursing or similar care on a less-than-24-hour basis to persons
who are rendered incapable of self-preservation by the services provided or staff has accepted
responsibility for care recipients already incapable.
AMMONIUM NITRATE. A chemical compound represented by the formula NH4NO3.
ANNUNCIATOR. A unit containing one or more indicator lamps, alphanumeric displays or
other equivalent means in which each indication provides status information about a circuit,
condition or location.
[A] APPROVED. Acceptable to the fire code official.
BG] AREA, BUILDING. The area included within surrounding exterior walls (or exterior walls
and fire walls) exclusive of vent shafts and courts. Areas of the building not provided with
656
surrounding walls shall be included in the building area if such areas are included within the
horizontal projection of the roof or floor above.
[BE] AREA OF REFUGE. An area where persons unable to use stairways can remain temporarily
to await instructions or assistance during emergency evacuation.
ARRAY. The configuration of storage. Characteristics considered in defining an array include
the type of packaging, flue spaces, height of storage and compactness of storage.
ARRAY, CLOSED. A storage configuration having a 6-inch (152 mm) or smaller width vertical
flue space that restricts air movement through the stored commodity.
[BG] ATRIUM. An opening connecting two or more stories other than enclosed stairways,
elevators, hoistways, escalators, plumbing, electrical, air-conditioning or other equipment, which
is closed at the top and not defined as a mall. Stories, as used in this definition, do not include
balconies within assembly groups or mezzanines that comply with Section 505 of the Puerto Rico
Building Code.
[BG] ATTIC. The space between the ceiling framing of the top story and the underside of the
roof.
AUDIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by
the sense of hearing.
AUTOMATED RACK STORAGE. Automated rack storage is a stocking method whereby the
movement of pallets, products, apparatus or systems are automatically controlled by mechanical
or electronic devices.
AUTOMATIC. As applied to fire protection devices, a device or system providing an
emergency function without the necessity for human intervention and activated as a result of a
predetermined temperature rise, rate of temperature rise or combustion products.
AUTOMATIC FIRE-EXTINGUISHING SYSTEM. An approved system of devices and
equipment which automatically detects a fire and discharges an approved fire-extinguishing agent
onto or in the area of a fire.
AUTOMATIC SMOKE DETECTION SYSTEM. A fire alarm system that has initiation
devices that utilize smoke detectors for protection of an area such as a room or space with
detectors to provide early warning of fire.
AUTOMATIC SPRINKLER SYSTEM. An automatic sprinkler system, for fire protection
purposes, is an integrated system of underground and overhead piping designed in accordance with
fire protection engineering standards. The system includes a suitable water supply. The portion of
the system above the ground is a network of specially sized or hydraulically designed piping
installed in a structure or area, generally overhead, and to which automatic sprinklers are connected
in a systematic pattern. The system is usually activated by heat from a fire and discharges water over
657
the fire area.
AUTOMATIC WATER MIST SYSTEM. A system consisting of a water supply, a pressure
source and a distribution piping system with attached nozzles which, at or above a minimum
operating pressure, defined by its listing, discharges water in fine droplets meeting the
requirements of NFPA 750 for the purpose of the control, suppression or extinguishment of a fire.
Such systems include wet-pipe, drypipe and pre-action types. The systems are designed as
engineered, preengineered, local-application or total flooding systems.
AUTOMOTIVE MOTOR FUEL-DISPENSING FACILITY. That portion of property where
flammable or combustible liquids or gases used as motor fuels are stored and dispensed from fixed
equipment into the fuel tanks of motor vehicles.
AVERAGE AMBIENT SOUND LEVEL. The root mean square, A-weighted sound pressure
level measured over a 24hour period, or the time any person is present, whichever time period is
less.
[BG] AWNING. An architectural projection that provides weather protection, identity or
decoration and is partially or wholly supported by the building to which it is attached. An awning
is comprised of a lightweight frame structure over which a covering is attached.
[BE] BALANCED DOOR. A door equipped with doublepivoted hardware so designed as to
cause a semicounter balanced swing action when opening.
BALED COTTON. See "Cotton."
BALED COTTON, DENSELY PACKED. See "Cotton."
BARRICADE. A structure that consists of a combination of walls, floor and roof, which is
designed to withstand the rapid release of energy in an explosion and which is fully confined,
partially vented or fully vented; or other effective method of shielding from explosive materials
by a natural or artificial barrier.
Artificial barricade. An artificial mound or revetment with a minimum thickness of 3 feet
(914 mm).
Natural barricade. Natural features of the ground, such as hills, or timber of sufficient
density that the surrounding exposures that require protection cannot be seen from the
magazine or building containing explosives when the trees are bare of leaves.
BARRICADED. The effective screening of a building containing explosive materials from the
magazine or other building, railway or highway by a natural or an artificial barrier. A straight line
from the top of any sidewall of the building containing explosive materials to the eave line of any
magazine or other building or to a point 12 feet (3658 mm) above the center of a railway or
highway shall pass through such barrier.
658
[BG] BASEMENT. A story that is not a story above grade plane.
BATTERY SYSTEM, STATIONARY STORAGE. A rechargeable energy storage system
consisting of electrochemical storage batteries, battery chargers, controls and associated electrical
equipment designed to provide electrical power to a building. The system is typically used to
provide standby or emergency power, an uninterruptable power supply, load shedding, load
sharing or similar capabilities.
BATTERY TYPES.
Flow battery. A type of storage battery that includes chemical components dissolved in
two different liquids. Ion exchange, which provides the flow of electrical current, occurs
through the membrane while both liquids circulate in their respective spaces.
Lead-acid battery. A storage battery that is comprised of lead electrodes immersed in
sulphuric acid electrolyte.
Lithium-ion battery. A storage battery with lithium ions serving as the charge carriers of
the battery. The electrolyte is a polymer mixture of carbonates with an inorganic salt and
can be in a liquid or a gelled polymer form. Lithiated metal oxide is typically a cathode
and forms of carbon or graphite typically form the anode.
Nickel-cadmium (Ni-Cd) battery. An alkaline storage battery in which the positive
active material is nickel oxide, the negative contains cadmium and the electrolyte is
potassium hydroxide.
Preengineered stationary storage battery system. An energy storage system consisting
of batteries, a battery management system, components and modules that are produced in
a factory, designed to comprise the system when assembled on the job site.
Prepackaged stationary storage battery system. An energy storage system consisting
of batteries, a battery management system, components and modules that is factory
assembled and shipped as a complete unit for installation at the job site.
Sodium-beta storage battery. A storage battery, also referred to as a Na-beta battery or
NBB, which uses a solid beta-alumina electrolyte membrane that selectively allows sodium
ion transport between a positive electrode such as metal halide and a negative sodium
electrode.
Stationary storage battery. A group of electrochemical cells interconnected to supply
a nominal voltage of DC power to a suitably connected electrical load, designed for
service in a permanent location.
BIN BOX. A five-sided container with the open side facing an aisle. Bin boxes are self-supporting
or supported by a structure designed so that little or no horizontal or vertical space exists around
the boxes.
659
BIOMASS. Plantor animal-based material of biological origin excluding material embedded in
geologic formations or transformed into fossils.
BLAST AREA. The area including the blast site and the immediate adjacent area within the
influence of flying rock, missiles and concussion.
BLAST SITE. The area in which explosive materials are being or have been loaded and which
includes all holes loaded or to be loaded for the same blast and a distance of 50 feet (15 240 mm)
in all directions.
BLASTER. A person qualified in accordance with Section 3301.4 to be in charge of and
responsible for the loading and firing of a blast.
BLASTING AGENT. A material or mixture consisting of fuel and oxidizer, intended for
blasting provided that the finished product, as mixed for use or shipment, cannot be detonated by
means of a No. 8 test detonator when unconfined. Blasting agents are labeled and placarded as
Class 1.5 material by US DOTn.
[BE] BLEACHERS. Tiered seating supported on a dedicated structural system and two or more
rows high and is not a building element (see "Grandstand").
[BG] BOARDING HOUSE. A building arranged or used for lodging for compensation, with or
without meals, and not occupied as a single-family unit.
BOILING POINT. The temperature at which the vapor pressure of a liquid equals the
atmospheric pressure of 14.7 pounds per square inch absolute (psia) (101 kPa) or 760 mm of
mercury. Where an accurate boiling point is unavailable for the material in question, or for
mixtures which do not have a constant boiling point, for the purposes of this classification, the
20-percent evaporated point of a distillation performed in accordance with ASTM D86 shall be
used as the boiling point of the liquid.
BONFIRE. An outdoor fire utilized for ceremonial purposes.
[BE] BREAKOUT. For revolving doors, a process whereby wings or door panels can be pushed
open manually for means of egress travel.
BRITISH THERMAL UNIT (BTU). The heat necessary to raise the temperature of 1 pound
(0.454 kg) of water by 1°F (0.5565°C).
[A] BUILDING. Any structure utilized or intended for supporting or sheltering any occupancy.
BUILDING AREA. See "Area, building."
BUILDING HEIGHT. See "Height, building."
660
[A] BUILDING OFFICIAL. The officer or other designated authority charged with the
administration and enforcement of the Puerto Rico Building Code, or a duly authorized
representative.
BULK OXYGEN SYSTEM. An assembly of equipment, such as oxygen storage containers,
pressure regulators, safety devices, vaporizers, manifolds and interconnecting piping, that has a
storage capacity of more than 20,000 cubic feet (566 m³) of oxygen at normal temperature and
pressure (NTP) including unconnected reserves on hand at the site. The bulk oxygen system
terminates at the point where oxygen at service pressure first enters the supply line. The oxygen
containers can be stationary or movable, and the oxygen can be stored as a gas or liquid.
BULK PLANT OR TERMINAL. That portion of a property where flammable or combustible
liquids are received by tank vessel, pipelines, tank car or tank vehicle and are stored or blended in
bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle,
portable tank or container.
BULK TRANSFER. The loading or unloading of flammable or combustible liquids from or
between tank vehicles, tank cars or storage tanks.
BULLET RESISTANT. Constructed so as to resist penetration of a bullet of 150-grain M2 ball
ammunition having a nominal muzzle velocity of 2,700 feet per second (fps) (824 mps) when
fired from a 30-caliber rifle at a distance of 100 feet (30 480 mm), measured perpendicular to the
target.
CANOPY. A structure or architectural projection of rigid construction over which a covering is
attached that provides weather protection, identity or decoration, and may be structurally
independent or supported by attachment to a building on one end and by not less than one
stanchion on the outer end.
CAPACITOR ARRAY. An arrangement of individual capacitor modules in close proximity to
each other, mounted on storage racks or in cabinets or other enclosures.
CAPACITOR ENERGY STORAGE SYSTEM. A stationary, rechargeable energy storage
system consisting of capacitors, chargers, controls and associated electrical equipment designed
to provide electrical power to a building or facility. The system is typically used to provide standby
or emergency power, an uninterruptable power supply, load shedding, load sharing or similar
capabilities.
Preengineered capacitor energy storage system. A capacitor energy storage system
consisting of capacitors, an energy management system, components and modules that are
produced in a factory, designed to comprise the system when assembled on the job site.
Prepackaged capacitor energy storage system. A capacitor energy storage system
consisting of capacitors, an energy management system, components and modules that is
661
factory assembled and then shipped as a complete unit for installation at the job site.
CARBON DIOXIDE ENRICHMENT SYSTEM. A system where carbon dioxide gas is
intentionally introduced into an indoor environment, typically for the purpose of stimulating plant
growth.
CARBON DIOXIDE EXTINGUISHING SYSTEM. A system supplying carbon dioxide (COâ‚‚)
from a pressurized vessel through fixed pipes and nozzles. The system includes a manual or
automatic-actuating mechanism.
CARBON MONOXIDE ALARM. A single or multiple station alarm intended to detect carbon
monoxide gas and alert occupants by a distinct audible signal. It incorporates a sensor, control
components and an alarm notification appliance in a single unit.
CARBON MONOXIDE DETECTOR. A device with an integral sensor to detect carbon
monoxide gas and transmit an alarm signal to a connected alarm control unit.
[BG] CARE SUITE. In Group I-2 occupancies, a group of treatment rooms, care recipient
sleeping rooms and the support rooms or spaces and circulation space within the suite where
staff are in attendance for supervision of all care recipients within the suite, and the suite is in
compliance with the requirements of Section 407.4.4 of the Puerto Rico Building Code.
CARTON. A cardboard or fiberboard box enclosing a product.
CEILING LIMIT. The maximum concentration of an airborne contaminant to which one may
be exposed. The ceiling limits utilized are those published in DOL 29 CFR Part 1910.1000. The
ceiling Recommended Exposure Limit (REL-C) concentrations published by the U.S. National
Institute for Occupational Safety and Health (NIOSH), Threshold Limit Value-Ceiling (TLV-C)
concentrations published by the American Conference of Governmental Industrial Hygienists
(ACGIH), Ceiling Workplace Environmental Exposure Level (WEEL-Ceiling) Guides published
by the American Industrial Hygiene Association (AIHA), and other approved, consistent
measures are allowed as surrogates for hazardous substances not listed in DOL 29 CFR Part
1910.1000.
[A] CHANGE OF OCCUPANCY. A change in the use of a building or a portion of a building
that results in any of the following:
1. A change of occupancy classification.
2. A change from one group to another group within an occupancy classification.
3. Any change in use within a group for which there is a change in the application of the
requirements of this code.
CHEMICAL. An element, chemical compound or mixture of elements or compounds or both.
CHEMICAL FUME HOOD. A ventilated enclosure designed to contain and exhaust fumes,
gases, vapors, mists and particulate matter generated within the hood.
662
CHEMICAL NAME. The scientific designation of a chemical in accordance with the
nomenclature system developed by the Puerto Rico Union of Pure and Applied Chemistry, the
Chemical Abstracts Service rules of nomenclature, or a name which will clearly identify a
chemical for the purpose of conducting an evaluation.
[M] CHIMNEY. A primarily vertical structure containing one or more flues for the purpose of
carrying gaseous products of combustion and air from a fuel-burning appliance to the outdoor
atmosphere.
Factory-built chimney. A listed and labeled chimney composed of factory-made
components, assembled in the field in accordance with manufacturer's instructions and
the conditions of the listing.
Masonry chimney. A field-constructed chimney composed of solid masonry units, bricks,
stones, or concrete.
Metal chimney. A field-constructed chimney of metal.
CLEAN AGENT. Electrically nonconducting, volatile or gaseous fire extinguishant that does not
leave a residue upon evaporation.
[BG] CLINIC, OUTPATIENT. Buildings or portions thereof used to provide medical care on a
less-than-24-hour basis to persons who are not rendered incapable of self-preservation by the
services provided.
CLOSED CONTAINER. A container sealed by means of a lid or other device such that liquid,
vapor or dusts will not escape from it under ordinary conditions of use or handling.
CLOSED SYSTEM. The use of a solid or liquid hazardous material involving a closed vessel or
system that remains closed during normal operations where vapors emitted by the product are not
liberated outside of the vessel or system and the product is not exposed to the atmosphere during
normal operations; and all uses of compressed gases. Examples of closed systems for solids and
liquids include product conveyed through a piping system into a closed vessel, system or piece of
equipment.
COLD DECK. A pile of unfinished cut logs.
COMBUSTIBLE DUST. Finely divided solid material which is 420 microns or less in diameter
and which, when dispersed in air in the proper proportions, could be ignited by a flame, spark or
other source of ignition. Combustible dust will pass through a U.S. No. 40 standard sieve.
COMBUSTIBLE FIBERS. Readily ignitable and free-burning materials in a fibrous or
shredded form, such as cocoa fiber, cloth, cotton, excelsior, hay, hemp, henequen, istle, jute,
kapok, oakum, rags, sisal, Spanish moss, straw, tow, wastepaper, certain synthetic fibers or other
like materials. This definition does not include densely packed baled cotton.
663
COMBUSTIBLE GAS DETECTOR. An instrument that samples the local atmosphere and
indicates the presence of ignitable vapors or gases within the flammable or explosive range
expressed as a volume percent in air.
COMBUSTIBLE LIQUID. A liquid having a closed cup flash point at or above 100°F (38°C).
Combustible liquids shall be subdivided as follows:
Class II. Liquids having a closed cup flash point at or above 100°F (38°C) and below
140°F (60°C).
Class IIIA. Liquids having a closed cup flash point at or above 140°F (60°C) and below
200°F (93°C).
Class IIIB. Liquids having closed cup flash points at or above 200°F (93°C).
The category of combustible liquids does not include compressed gases or cryogenic fluids.
[M] COMMERCIAL COOKING APPLIANCES. Appliances used in a commercial food
service establishment for heating or cooking food and which produce grease vapors, steam,
fumes, smoke or odors that are required to be removed through a local exhaust ventilation system.
Such appliances include deep fat fryers, upright broilers, griddles, broilers, steam-jacketed kettles,
hot-top ranges, under-fired broilers (charbroilers), ovens, barbecues, rotisseries, and similar
appliances. For the purpose of this definition, a food service establishment shall include any
building or a portion thereof used for the preparation and serving of food.
COMMERCIAL MOTOR VEHICLE. A motor vehicle used to transport passengers or
property where the motor vehicle:
1. Has a gross vehicle weight rating of 10,000 pounds (454 kg) or more; or
2. Is designed to transport 16 or more passengers, including the driver.
COMMODITY. A combination of products, packing materials and containers.
[BE] COMMON PATH OF EGRESS TRAVEL. That portion of exit access travel distance
measured from the most remote point of each room, area or space to that point where the
occupants have separate and distinct access to two exits or exit access doorways.
[BE] COMMON USE. Interior or exterior circulation paths, rooms, spaces or elements that are
not for public use and are made available for the shared use of two or more people.
COMPRESSED GAS. A material, or mixture of materials that:
1. Is a gas at 68°F (20°C) or less at 14.7 psia (101 kPa) of pressure; and
2. Has a boiling point of 68°F (20°C) or less at 14.7 psia (101 kPa) which is either
liquefied, nonliquefied or in solution, except those gases which have no other health or
664
physical-hazard properties are not considered to be compressed until the pressure in the
packaging exceeds 41 psia (282 kPa) at 68°F (20°C).
The states of a compressed gas are categorized as follows:
1. Nonliquefied compressed gases are gases, other than those in solution, which are in a
packaging under the charged pressure and are entirely gaseous at a temperature of 68°F
(20°C).
2. Liquefied compressed gases are gases that, in a packaging under the charged pressure,
are partially liquid at a temperature of 68°F (20°C).
3. Compressed gases in solution are nonliquefied gases that are dissolved in a solvent.
4. Compressed gas mixtures consist of a mixture of two or more compressed gases
contained in a packaging, the hazard properties of which are represented by the properties
of the mixture as a whole.
COMPRESSED GAS CONTAINER. A pressure vessel designed to hold compressed gases at
pressures greater than one atmosphere at 68°F (20°C) and includes cylinders, containers and tanks.
COMPRESSED GAS SYSTEM. An assembly of equipment designed to contain, distribute or
transport compressed gases. It can consist of a compressed gas container or containers, reactors
and appurtenances, including pumps, compressors and connecting piping and tubing.
[BG] CONGREGATE LIVING FACILITIES. A building or part thereof that contains
sleeping units where residents share bathroom and/or kitchen facilities.
CONSTANTLY ATTENDED LOCATION. A designated location at a facility staffed by
trained personnel on a continuous basis where alarm or supervisory signals are monitored and
facilities are provided for notification of the fire department or other emergency services.
[A] CONSTRUCTION DOCUMENTS. The written, graphic and pictorial documents prepared
or assembled for describing the design, location and physical characteristics of the elements of the
project necessary for obtaining a permit.
CONTAINER. A vessel of 60 gallons (227 L) or less in capacity used for transporting or storing
hazardous materials. Pipes, piping systems, engines and engine fuel tanks are not considered to
be containers.
CONTAINMENT SYSTEM. A gas-tight recovery system comprised of equipment or devices
which can be placed over a leak in a compressed gas container, thereby stopping or controlling
the escape of gas from the leaking container.
CONTAINMENT VESSEL. A gas-tight recovery vessel designed so that a leaking compressed
gas container can be placed within its confines thereby encapsulating the leaking container.
CONTROL AREA. Spaces within a building where quantities of hazardous materials not
665
exceeding the maximum allowable quantities per control area are stored, dispensed, used or
handled. See also the definition of "Outdoor control area."
[BE] CORRIDOR. An enclosed exit access component that defines and provides a path of egress
travel.
CORRIDOR, OPEN-ENDED. See "Open-ended corridor."
CORROSIVE. A chemical that causes visible destruction of, or irreversible alterations in, living
tissue by chemical action at the point of contact. A chemical shall be considered corrosive if, when
tested on the intact skin of albino rabbits by the method described in DOTn 49 CFR 173.137, such
chemical destroys or changes irreversibly the structure of the tissue at the point of contact
following an exposure period of 4 hours. This term does not refer to action on inanimate surfaces.
COTTON.
Baled cotton. A natural seed fiber wrapped in and secured with industry-accepted
materials, usually consisting of burlap, woven polypropylene, polyethylene or cotton or
sheet polyethylene, and secured with steel, synthetic or wire bands, or wire; also includes
linters (lint removed from the cottonseed) and motes (residual materials from the ginning
process).
Baled cotton, densely packed. Cotton, made into banded bales, with a packing density of
not less than 22 pounds per cubic foot (360 kg/m³), and dimensions complying with the
following: a length of 55 inches (1397 mm), a width of 21 inches (533.4 mm) and a height
of 27.6 to 35.4 inches (701 to 899 mm).
Seed cotton. Perishable raw agricultural commodity consisting of cotton fiber (lint)
attached to the seed of the cotton plant, which requires ginning to become a commercial
product.
[BG] COURT. An open, uncovered space, unobstructed to the sky, bounded on three or more
sides by exterior building walls or other enclosing devices.
[BG] COVERED MALL BUILDING. A single building enclosing a number of tenants and
occupants such as retail stores, drinking and dining establishments, entertainment and amusement
facilities, passenger transportation terminals, offices, and other similar uses wherein two or more
tenants have a main entrance into one or more malls. Anchor buildings shall not be considered as
a part of the covered mall building. The term "covered mall building" shall include open mall
buildings as defined below.
Mall. A roofed or covered common pedestrian area within a covered mall building that
serves as access for two or more tenants and not to exceed three levels that are open to
each other. The term "mall" shall include open malls as defined below.
Open mall. An unroofed common pedestrian way serving a number of tenants not
666
exceeding three levels. Circulation at levels above grade shall be permitted to include
open exterior balconies leading to exits discharging at grade.
Open mall building. Several structures housing a number of tenants such as retail stores,
drinking and dining establishments, entertainment and amusement facilities, offices, and
other similar uses wherein two or more tenants have a main entrance into one or more open
malls. Anchor buildings are not considered as a part of the open mall building.
CRITICAL CIRCUIT. A circuit that requires continuous operation to ensure safety of the
structure and occupants.
CRYOGENIC CONTAINER. A cryogenic vessel of any size used for the transportation,
handling or storage of cryogenic fluids.
CRYOGENIC FLUID. A fluid having a boiling point lower than -130°F (-89.9°C) at 14.7 pounds
per square inch atmosphere (psia) (an absolute pressure of 101.3 kPa).
CRYOGENIC VESSEL. A pressure vessel, low-pressure tank or atmospheric tank designed
to contain a cryogenic fluid on which venting, insulation, refrigeration or a combination of these
is used in order to maintain the operating pressure within the design pressure and the contents in
a liquid phase.
[BG] CUSTODIAL CARE. Assistance with day-to-day living tasks; such as assistance with
cooking, taking medication, bathing, using toilet facilities and other tasks of daily living. Custodial
care includes persons receiving care who have the ability to respond to emergency situations and
evacuate at a slower rate and/or who have mental and psychiatric complications.
CYLINDER. A pressure vessel designed for pressures higher than 40 psia (275.6 kPa) and having
a circular cross section. It does not include a portable tank, multiunit tank car tank, cargo tank or
tank car.
DAMPER. See "Fire damper" and "Smoke damper."
DAY BOX. A portable magazine designed to hold explosive materials and constructed in
accordance with the requirements for a Type 3 magazine as defined and classified in Chapter 56.
DECORATIVE MATERIALS. All materials applied over the building interior finish for
decorative, acoustical or other effect including, but not limited to, curtains, draperies, fabrics,
streamers and all other materials utilized for decorative effect including, but not limited to, bulletin
boards, artwork, posters, photographs, paintings, batting, cloth, cotton, hay, stalks, straw, vines,
leaves, trees, moss and similar items, foam plastics and materials containing foam plastics.
Decorative materials do not include wall coverings, ceiling coverings, floor coverings, ordinary
window shades, interior finish and materials 0.025 inch (0.64 mm) or less in thickness applied
directly to and adhering tightly to a substrate.
667
DEFLAGRATION. An exothermic reaction, such as the extremely rapid oxidation of a
flammable dust or vapor in air, in which the reaction progresses through the unburned material at
a rate less than the velocity of sound. A deflagration can have an explosive effect.
DELUGE SYSTEM. A sprinkler system employing open sprinklers attached to a piping system
connected to a water supply through a valve that is opened by the operation of a detection system
installed in the same area as the sprinklers. When this valve opens, water flows into the piping
system and discharges from all sprinklers attached thereto.
DESIGN PRESSURE. The maximum gauge pressure that a pressure vessel, device, component
or system is designed to withstand safely under the temperature and conditions of use expected.
DESOLVENTIZING. The act of removing a solvent from a material.
DETACHED BUILDING. A separate single-story building, without a basement or crawl space,
used for the storage or use of hazardous materials and located an approved distance from all
structures.
DETEARING. A process for rapidly removing excess wet coating material from a dipped or
coated object or material by passing it through an electrostatic field.
DETECTOR, HEAT. A fire detector that senses heat, either abnormally high temperature or rate
of rise, or both.
DETONATING CORD. A flexible cord containing a center core of high explosive used to initiate
other explosives.
DETONATION. An exothermic reaction characterized by the presence of a shock wave in the
material which establishes and maintains the reaction. The reaction zone progresses through the
material at a rate greater than the velocity of sound. The principal heating mechanism is one of
shock compression. Detonations have an explosive effect.
DETONATOR. A device containing any initiating or primary explosive that is used for
initiating detonation. A detonator shall not contain more than 154.32 grains (10 grams) of total
explosives by weight, excluding ignition or delay charges. The term includes, but is not limited
to, electric blasting caps of instantaneous and delay types, blasting caps for use with safety fuses,
detonating cord delay connectors, and noninstantaneous and delay blasting caps which use
detonating cord, shock tube or any other replacement for electric leg wires. All types of detonators
in strengths through No. 8
DRAFT CURTAIN. A structure arranged to limit the spread of smoke and heat along the
underside of the ceiling or roof.
[BF] DRAFTSTOP. A material, device or construction installed to restrict the movement of air
668
within open spaces of concealed areas of building components such as crawl spaces, floor/ceiling
assemblies, roof/ceiling assemblies and attics.
DRY-CHEMICAL EXTINGUISHING AGENT. A powder composed of small particles,
usually of sodium bicarbonate, potassium bicarbonate, urea-potassium-based bicarbonate,
potassium chloride or monoammonium phosphate, with added particulate material supplemented
by special treatment to provide resistance to packing, resistance to moisture absorption (caking)
and the proper flow capabilities.
DRY CLEANING. The process of removing dirt, grease, paints and other stains from such items
as wearing apparel, cap should be rated at 1 1/2 pounds (0.68 kg) of explosives per textiles, fabrics
and rugs by use of nonaqueous liquids (sol-1,000 caps. For strengths higher than No. 8 cap, consult
the manufacturer.
[BG] DETOXIFICATION FACILITIES. Facilities that provide treatment for substance abuse
serving care recipients who are incapable of self-preservation or who are harmful to themselves
or others.
DIP TANK. A tank, vat or container of flammable or combustible liquid in which articles or
materials are immersed for the purpose of coating, finishing, treating and similar processes.
DISCHARGE SITE. The immediate area surrounding the fireworks mortars used for an outdoor
fireworks display.
DISPENSING. The pouring or transferring of any material from a container, tank or similar
vessel, whereby vapors, dusts, fumes, mists or gases are liberated to the atmosphere.
DISPENSING DEVICE, OVERHEAD TYPE. A dispensing device that consists of one or more
individual units intended for installation in conjunction with each other, mounted above a
dispensing area typically within the motor fuel-dispensing facility canopy structure, and
characterized by the use of an overhead hose reel.
DISPLAY SITE. The immediate area where a fireworks display is conducted. The display area
includes the discharge site, the fallout area and the required separation distance from the mortars
to spectator viewing areas. The display area does not include spectator viewing areas or vehicle
parking areas.
DOOR, BALANCED. See "Balanced door."
DOOR, DUTCH. See "Dutch door."
DOOR, LOW ENERGY POWER-OPERATED. See "Low energy power-operated door."
DOOR, POWER-ASSISTED. See "Power-assisted door."
DOOR, POWER-OPERATED. See "Power-operated door."
669
DOORWAY, EXIT ACCESS. See "Exit access doorway."
[BG] DORMITORY. A space in a building where group sleeping accommodations are
provided in one room, or in a series of closely associated rooms, for persons not members of the
same family group, under joint occupancy and single management, as in college dormitories or
fraternity houses. vents).
DRY CLEANING PLANT. A facility in which dry cleaning and associated operations are
conducted, including the office, receiving area and storage rooms.
DRY CLEANING ROOM. An occupiable space within a building used for performing dry
cleaning operations, the installation of solvent-handling equipment or the storage of dry cleaning
solvents.
DRY CLEANING SYSTEM. Machinery or equipment in which textiles are immersed or
agitated in solvent or in which dry cleaning solvent is extracted from textiles.
DUTCH DOOR. A door divided horizontally so that the top can be operated independently from
the bottom.
[BG] DWELLING. A building that contains one or two dwelling units used, intended or designed
to be used, rented, leased, let or hired out to be occupied for living purposes.
[BG] DWELLING UNIT. A single unit providing complete, independent living facilities for one
or more persons, including permanent provisions for living, sleeping, eating, cooking and
sanitation.
EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER. A sprinkler listed for
early suppression fastresponse performance.
[BE] EGRESS COURT. A court or yard which provides access to a public way for one or more
exits.
ELECTROSTATIC FLUIDIZED BED. A container holding powder coating material that is
aerated from below so as to form an air-supported expanded cloud of such material that is
electrically charged with a charge opposite to that of the object to be coated. Such object is
transported through the container immediately above the charged and aerated materials in order
to be coated.
ELEVATOR GROUP. A grouping of elevators in a building located adjacent or directly across
from one another that respond to a common hall call button(s).
EMERGENCY ALARM SYSTEM. A system to provide indication and warning of emergency
situations involving hazardous materials.
670
EMERGENCY CONTROL STATION. An approved location on the premises where signals
from emergency equipment are received and which is staffed by trained personnel.
[BE] EMERGENCY ESCAPE AND RESCUE OPENING. An operable window, door or other
similar device that provides for a means of escape and access for rescue in the event of an
emergency.
EMERGENCY EVACUATION DRILL. An exercise performed to train staff and occupants
and to evaluate their efficiency and effectiveness in carrying out emergency evacuation
procedures.
EMERGENCY POWER SYSTEM. A source of automatic electric power of a required capacity
and duration to operate required life safety, fire alarm, detection and ventilation systems in the
event of a failure of the primary power. Emergency power systems are required for electrical
loads where interruption of the primary power could result in loss of human life or serious injuries.
EMERGENCY SHUTOFF VALVE. A valve designed to shut off the flow of gases or liquids.
EMERGENCY SHUTOFF VALVE, AUTOMATIC. A fail-safe automatic-closing valve
designed to shut off the flow of gases or liquids initiated by a control system that is activated by
automatic means.
EMERGENCY SHUTOFF VALVE, MANUAL. A manually operated valve designed to shut
off the flow of gases or liquids.
EMERGENCY VOICE/ALARM COMMUNICATIONS. Dedicated manual or automatic
facilities for originating and distributing voice instructions, as well as alert and evacuation signals
pertaining to a fire emergency, to the occupants of a building.
[BG] EMPLOYEE WORK AREA. All or any portion of a space used only by employees and
only for work. Corridors, toilet rooms, kitchenettes and break rooms are not employee work areas.
ENERGY MANAGEMENT SYSTEMS. An electronic system that protects stationary storage
batteries from operating outside their safe operating parameters, and generates an alarm and
trouble signal for off normal conditions.
[BG] EQUIPMENT PLATFORM. An unoccupied, elevated platform used exclusively for
mechanical systems or industrial process equipment, including the associated elevated walkways,
stairways, alternating tread devices and ladders necessary to access the platform (see Section
505.3 of the International Building Code).
EXCESS FLOW CONTROL. A fail-safe system or other approved means designed to shut off
flow caused by a rupture in pressurized piping systems.
EXCESS FLOW VALVE. A valve inserted into a compressed gas cylinder, portable tank or
671
stationary tank that is designed to positively shut off the flow of gas in the event that its
predetermined flow is exceeded.
EXHAUSTED ENCLOSURE. An appliance or piece of equipment which consists of a top, a
back and two sides providing a means of local exhaust for capturing gases, fumes, vapors and
mists. Such enclosures include laboratory hoods, exhaust fume hoods and similar appliances and
equipment used to retain and exhaust locally the gases, fumes, vapors and mists that could be
released. Rooms or areas provided with general ventilation, in themselves, are not exhausted
enclosures.
EXISTING. Buildings, facilities or conditions that are already in existence, constructed or
officially authorized prior to the adoption of this code.
[BE] EXIT. That portion of a means of egress system between the exit access and the exit
discharge or public way. Exit components include exterior exit doors at the level of exit discharge,
interior exit stairways and ramps, exit passageways, exterior exit stairways and ramps and
horizontal exits.
[BE] EXIT ACCESS. That portion of a means of egress system that leads from any occupied
portion of a building or structure to an exit.
[BE] EXIT ACCESS DOORWAY. A door or access point along the path of egress travel from
an occupied room, area or space where the path of egress enters an intervening room, corridor,
exit access stairway or ramp.
[BE] EXIT ACCESS RAMP. A ramp within the exit access portion of the means of egress
system.
[BE] EXIT ACCESS STAIRWAY. A stairway within the exit access portion of the means of
egress system.
[BE] EXIT DISCHARGE. That portion of a means of egress system between the termination of
an exit and a public way.
[BE] EXIT DISCHARGE, LEVEL OF. The story at the point at which an exit terminates and
an exit discharge begins.
[BE] EXIT PASSAGEWAY. An exit component that is separated from other interior spaces of a
building or structure by fire-resistance-rated construction and opening protectives, and provides
for a protected path of egress travel in a horizontal direction to the exit discharge.
EXPANDED PLASTIC. A foam or cellular plastic material having a reduced density based on
the presence of numerous small cavities or cells dispersed throughout the material.
EXPLOSION. An effect produced by the sudden violent expansion of gases, which may be
accompanied by a shock wave or disruption, or both, of enclosing materials or structures. An
672
explosion could result from any of the following:
1. Chemical changes such as rapid oxidation, deflagration or detonation, decomposition
of molecules and runaway polymerization (usually detonations).
2. Physical changes such as pressure tank ruptures.
3. Atomic changes (nuclear fission or fusion).
EXPLOSIVE. A chemical compound, mixture or device, the primary or common purpose of
which is to function by explosion. The term includes, but is not limited to, dynamite, black powder,
pellet powder, initiating explosives, detonators, safety fuses, squibs, detonating cord, igniter cord
and igniters.
The term "Explosive" includes any material determined to be within the scope of USC Title 18:
Chapter 40 and also includes any material classified as an explosive by the hazardous materials
regulations of DOTn 49 CFR Parts 100-185.
High explosive. Explosive material, such as dynamite, which can be caused to detonate
by means of a No. 8 test blasting cap where unconfined.
Low explosive. Explosive material that will burn or deflagrate when ignited. It is
characterized by a rate of reaction that is less than the speed of sound. Examples of low
explosives include, but are not limited to, black powder, safety fuse, igniters, igniter cord,
fuse lighters, fireworks and propellants, 1.3C.
Mass-detonating explosives. Division 1.1, 1.2 and 1.5 explosives alone or in combination,
or loaded into various types of ammunition or containers, most of which can be expected
to explode virtually instantaneously when a small portion is subjected to fire, severe
concussion, impact, the impulse of an initiating agent or the effect of a considerable
discharge of energy from without. Materials that react in this manner represent a mass
explosion hazard. Such an explosive will normally cause severe structural damage to
adjacent objects. Explosive propagation could occur immediately to other items of
ammunition and explosives stored sufficiently close to and not adequately protected from
the initially exploding pile with a time interval short enough so that two or more quantities
must be considered as one for quantity-distance purposes.
UN/DOTn Class 1 explosives. The former classification system used by DOTn included
the terms "high" and "low" explosives as defined herein. The following terms further
define explosives under the current system applied by DOTn for all explosive materials
defined as hazard Class 1 materials. Compatibility group letters are used in concert with
the division to specify further limitations on each division noted (for example, the letter G
identifies the material as a pyrotechnic substance or article containing a pyrotechnic
substance and similar materials).
Division 1.1. Explosives that have a mass explosion hazard. A mass explosion is one
which affects almost the entire load instantaneously.
673
Division 1.2. Explosives that have a projection hazard but not a mass explosion hazard.
Division 1.3. Explosives that have a fire hazard and either a minor blast hazard or a
minor projection hazard or both, but not a mass explosion hazard.
Division 1.4. Explosives that pose a minor explosion hazard. The explosive effects
are largely confined to the package and no projection of fragments of appreciable size
or range is to be expected. An external fire must not cause virtually instantaneous
explosion of almost the entire contents of the package.
Division 1.5. Very insensitive explosives. This division is comprised of substances that
have a mass explosion hazard but which are so insensitive that there is very little
probability of initiation or of transition from burning to detonation under normal
conditions of transport.
Division 1.6. Extremely insensitive articles which do not have a mass explosion
hazard. This division is comprised of articles that contain only extremely insensitive
detonating substances and which demonstrate a negligible probability of accidental
initiation or propagation.
EXPLOSIVE MATERIAL. The term "explosive" material means explosives, blasting agents and
detonators.
[BE] EXTERIOR EXIT RAMP. An exit component that serves to meet one or more means of
egress design requirements, such as required number of exits or exit access travel distance, and is
open to yards, courts or public ways.
[BE] EXTERIOR EXIT STAIRWAY. An exit component that serves to meet one or more
means of egress design requirements, such as required number of exits or exit access travel
distance, and is open to yards, courts or public ways.
[BF] EXTERIOR WALL. A wall, bearing or nonbearing, that is used as an enclosing wall for
a building, other than a fire wall, and that has a slope of 60 degrees (1.05 rad) or greater with the
horizontal plane.
EXTRA-HIGH-RACK COMBUSTIBLE STORAGE. Storage on racks of Class I, II, III or
IV commodities that exceed 40 feet (12 192 mm) in height and storage on racks of high-hazard
commodities that exceed 30 feet (9144 mm) in height.
FABRICATION AREA. An area within a semiconductor fabrication facility and related
research and development areas in which there are processes using hazardous production
materials. Such areas are allowed to include ancillary rooms or areas such as dressing rooms and
offices that are directly related to the fabrication area processes.
[A] FACILITY. A building or use in a fixed location including exterior storage areas for
flammable and combustible substances and hazardous materials, piers, wharves, tank farms and
674
similar uses. This term includes recreational vehicles, mobile home and manufactured housing
parks, sales and storage lots.
FAIL-SAFE. A design condition incorporating a feature for automatically counteracting the
effect of an anticipated possible source of failure; also, a design condition eliminating or
mitigating a hazardous condition by compensating automatically for a failure or malfunction.
FALLOUT AREA. The area over which aerial shells are fired. The shells burst over the area,
and unsafe debris and malfunctioning aerial shells fall into this area. The fallout area is the
location where a typical aerial shell dud falls to the ground depending on the wind and the angle of
mortar placement.
FALSE ALARM. The willful and knowing initiation or transmission of a signal, message or
other notification of an event of fire when no such danger exists.
FINES. Small pieces or splinters of wood byproducts that will pass through a 0.25-inch (6.4 mm)
screen.
FIRE ALARM. The giving, signaling or transmission to any public fire station, or company or to
any officer or employee thereof, whether by telephone, spoken word or otherwise, of information
to the effect that there is a fire at or near the place indicated by the person giving, signaling or
transmitting such information.
FIRE ALARM BOX, MANUAL. See "Manual fire alarm box."
FIRE ALARM CONTROL UNIT. A system component that receives inputs from automatic
and manual fire alarm devices and may be capable of supplying power to detection devices and
transponder(s) or off-premises transmitter(s). The control unit may be capable of providing a
transfer of power to the notification appliances and transfer of condition to relays or devices.
FIRE ALARM SIGNAL. A signal initiated by a fire alarminitiating device such as a manual fire
alarm box, automatic fire detector, waterflow switch or other device whose activation is indicative
of the presence of a fire or fire signature.
FIRE ALARM SYSTEM. A system or portion of a combination system consisting of
components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory
signal-initiating devices and to initiate the appropriate response to those signals.
FIRE APPARATUS ACCESS ROAD. A road that provides fire apparatus access from a fire
station to a facility, building or portion thereof. This is a general term inclusive of all other terms
such as fire lane, public street, private street, parking lot lane and access roadway.
[BF] FIRE AREA. The aggregate floor area enclosed and bounded by fire walls, fire barriers,
exterior walls or horizontal assemblies of a building. Areas of the building not provided with
surrounding walls shall be included in the fire area if such areas are included within the horizontal
675
projection of the roof or floor next above.
[BF] FIRE BARRIER. A fire-resistance-rated wall assembly of materials designed to restrict
the spread of fire in which continuity is maintained.
FIRE CHIEF. The chief officer of the fire department serving the jurisdiction, or a duly
authorized representative.
FIRE CODE OFFICIAL. The fire chief or other designated authority charged with the
administration and enforcement of the code, or a duly authorized representative.
FIRE COMMAND CENTER. The principal attended or unattended location where the status of
detection, alarm communications and control systems is displayed, and from which the system(s)
can be manually controlled.
[BF] FIRE DAMPER. A listed device installed in ducts and air transfer openings designed to
close automatically upon detection of heat and resist the passage of flame. Fire dampers are
classified for use in either static systems that will automatically shut down in the event of a fire, or
in dynamic systems that continue to operate during a fire. A dynamic fire damper is tested and
rated for closure under elevated temperature airflow.
FIRE DEPARTMENT MASTER KEY. A limited issue key of special or controlled design
to be carried by fire department officials in command which will open key boxes on specified
properties.
FIRE DETECTOR, AUTOMATIC. A device designed to detect the presence of a fire signature
and to initiate action.
[BF] FIRE DOOR. The door component of a fire door assembly.
[BF] FIRE DOOR ASSEMBLY. Any combination of a fire door, frame, hardware and other
accessories that together provide a specific degree of fire protection to the opening.
[BF] FIRE EXIT HARDWARE. Panic hardware that islisted for use on fire door assemblies.
FIRE LANE. A road or other passageway developed to allow the passage of fire apparatus. A
fire lane is not necessarily intended for vehicular traffic other than fire apparatus.
[BF] FIRE PARTITION. A vertical assembly of materials designed to restrict the spread of fire
in which openings are protected.
FIRE POINT. The lowest temperature at which a liquid will ignite and achieve sustained burning
when exposed to a test flame in accordance with ASTM D92.
[BF] FIRE PROTECTION RATING. The period of time that an opening protective assembly
676
will maintain the ability to confine a fire as determined by tests prescribed in Section
716 of the Puerto Rico Building Code. Ratings are stated in hours or minutes.
FIRE PROTECTION SYSTEM. Approved devices, equipment and systems or combinations of
systems used to detect a fire, activate an alarm, extinguish or control a fire, control or manage
smoke and products of a fire or any combination thereof.
[BF] FIRE RESISTANCE. That property of materials or their assemblies that prevents or retards
the passage of excessive heat, hot gases or flames under conditions of use.
FIRE SAFETY FUNCTIONS. Building and fire control functions that are intended to increase
the level of life safety for occupants or to control the spread of the harmful effects of fire.
[BF] FIRE SEPARATION DISTANCE. The distance measured from the building face to one of
the following:
1. The closest interior lot line.
2. To the centerline of a street, an alley or public way.
3. To an imaginary line between two buildings on the lot. The distance shall be measured
at right angles from the face of the wall.
[BF] FIRE WALL. A fire-resistance-rated wall having protected openings, which restricts the
spread of fire and extends continuously from the foundation to or through the roof, with sufficient
structural stability under fire conditions to allow collapse of construction on either side without
collapse of the wall.
FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance
of a building or portion thereof by one or more qualified individuals for the purposes of
identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of
fire and notifying the fire department.
[BF] FIREBLOCKING. Building materials, or materials approved for use as fireblocking,
installed to resist the free passage of flame to other areas of the building through concealed spaces.
[BF] FIRE-RESISTANCE RATING. The period of time a building element, component or
assembly maintains the ability to confine a fire, continues to perform a given structural function,
or both, as determined by the tests, or the methods based on tests, prescribed in Section 703 of the
Puerto Rico Building Code.
[BF] FIRE-RESISTANT JOINT SYSTEM. An assemblage of specific materials or products
that are designed, tested and fire-resistance rated in accordance with either ASTM E1966 or UL
2079 to resist for a prescribed period of time the passage of fire through joints made in or
between fire-resistance-rated assemblies.
677
FIREWORKS. Any composition or device for the purpose of producing a visible or an audible
effect for entertainment purposes by combustion, deflagration or detonation that meets the
definition of 1.3G fireworks or 1.4G fireworks.
Fireworks, 1.3G. Large fireworks devices, which are explosive materials, intended for use in
fireworks displays and designed to produce audible or visible effects by combustion,
deflagration or detonation. Such 1.3G fireworks include, but are not limited to, firecrackers
containing more than 130 milligrams (2 grains) of explosive composition, aerial shells
containing more than 40 grams of pyrotechnic composition and other display pieces which
exceed the limits for classification as 1.4G fireworks. Such 1.3G fireworks are also described
as Fireworks, UN 0335 by the DOTn.
Fireworks, 1.4G. Small fireworks devices containing restricted amounts of pyrotechnic
composition designed primarily to produce visible or audible effects by combustion or
deflagration that complies with the construction, chemical composition and labeling
regulations of the DOTn for Fireworks, UN 0336, and the U.S. Consumer Product Safety
Commission as set forth in CPSC 16 CFR Parts 1500 and 1507.
FIREWORKS DISPLAY. A presentation of fireworks for a public or private gathering.
[BG] FIXED BASE OPERATOR (FBO). A commercial business granted the right by the airport
sponsor to operate on an airport and provide aeronautical services such as fueling, hangaring, tiedown and parking, aircraft rental, aircraft maintenance and flight instruction.
[BE] FIXED SEATING. Furniture or fixtures designed and installed for the use of sitting and
secured in place including bench-type seats and seats with or without back or arm rests.
[BF] FLAME SPREAD. The propagation of flame over a surface.
[BF] FLAME SPREAD INDEX. A comparative measure, expressed as a dimensionless
number, derived from visual measurements of the spread of flame versus time for a material tested
in accordance with ASTM E84 or UL 723.
FLAMMABLE CRYOGENIC FLUID. A cryogenic fluidthat is flammable in its vapor state.
FLAMMABLE FINISHES. Coatings to articles or materials in which the material being applied
is a flammable liquid, combustible liquid, combustible powder, fiberglass resin or flammable or
combustible gel coating.
FLAMMABLE GAS. A material which is a gas at 68°F (20°C) or less at 14.7 pounds per square
inch atmosphere (psia) (101 kPa) of pressure [a material that has a boiling point of 68°F (20°C)
or less at 14.7 psia (101 kPa)] which:
678
1. Is ignitable at 14.7 psia (101 kPa) when in a mixture of 13 percent or less by volume
with air; or
2. Has a flammable range at 14.7 psia (101 kPa) with air of not less than 12 percent,
regardless of the lower limit.
The limits specified shall be determined at 14.7 psi (101 kPa) of pressure and a temperature of
68°F (20°C) in accordance with ASTM E681.
FLAMMABLE LIQUEFIED GAS. A liquefied compressed gas which, under a charged
pressure, is partially liquid at a temperature of 68°F (20°C) and which is flammable.
FLAMMABLE LIQUID. A liquid having a closed cup flash point below 100°F (38°C).
Flammable liquids are further categorized into a group known as Class I liquids. The Class I
category is subdivided as follows:
Class IA. Liquids having a flash point below 73°F (23°C) and having a boiling point below
100°F (38°C).
Class IB. Liquids having a flash point below 73°F (23°C) and having a boiling point at or
above 100°F (38°C).
Class IC. Liquids having a flash point at or above 73°F (23°C) and below 100°F (38°C).
The category of flammable liquids does not include compressed gases or cryogenic fluids.
FLAMMABLE MATERIAL. A material capable of being readily ignited from common sources
of heat or at a temperature of 600°F (316°C) or less.
FLAMMABLE SOLID. A solid, other than a blasting agent or explosive, that is capable of
causing fire through friction, absorption of moisture, spontaneous chemical change or retained
heat from manufacturing or processing, or which has an ignition temperature below 212°F (100°C)
or which burns so vigorously and persistently when ignited as to create a serious hazard. A
chemical shall be considered a flammable solid as determined in accordance with the test method
of CPSC 16 CFR Part 1500.44, if it ignites and burns with a self-sustained flame at a rate
greater than 0.0866 inch (2.2 mm) per second along its major axis.
FLAMMABLE VAPOR AREA. An area in which the concentration of flammable constituents
(vapor, gas, fume, mist or dust) in air exceeds 25 percent of their lower flammable limit (LFL)
because of the flammable finish processes operation. It shall include:
1. The interior of spray booths.
2. The interior of ducts exhausting from spraying processes.
3. Any area in the direct path of spray or any area containing dangerous quantities of airsuspended powder, combustible residue, dust, deposits, vapor or mists as a result of
spraying operations.
4. The area in the vicinity of dip tanks, drain boards or associated drying, conveying or
679
other equipment during operation or shutdown periods.
The fire code official is authorized to determine the extent of the flammable vapor area, taking
into consideration the material characteristics of the flammable materials, the degree of sustained
ventilation and the nature of the operations.
FLUE SPACES.
Longitudinal flue space. The flue space between rows of storage perpendicular to the
direction of loading.
Transverse flue space. The space between rows of storage parallel to the direction of
loading.
FLUIDIZED BED. A container holding powder coating material that is aerated from below so
as to form an air-supported expanded cloud of such material through which the preheated object
to be coated is immersed and transported.
FOAM-EXTINGUISHING SYSTEM. A special system discharging a foam made from
concentrates, either mechanically or chemically, over the area to be protected.
[BE] FOLDING AND TELESCOPIC SEATING. Tiered seating having an overall shape and
size that is capable of being reduced for purposes of moving or storing and is not a building
element.
[BG] FOSTER CARE FACILITIES. Facilities that provideᵃʳᵉ to more than five children, 2¹/2
years of age or less.
FLAMMABLE VAPORS OR FUMES. The concentration of flammable constituents in air
that exceeds 25 percent of their lower flammable limit (LFL).
FLASH POINT. The minimum temperature in degrees Fahrenheit at which a liquid will give off
sufficient vapors to form an ignitable mixture with air near the surface or in the container, but will
not sustain combustion. The flash point of a liquid shall be determined by appropriate test
procedure and apparatus as specified in ASTM D56, ASTM D93 or ASTM D3278.
FLEET VEHICLE MOTOR FUEL-DISPENSING FACILITY. That portion of a commercial,
industrial, governmental or manufacturing property where liquids used as fuels are stored and
dispensed into the fuel tanks of motor vehicles that are used in connection with such businesses,
by persons within the employ of such businesses.
[BE] FLIGHT. A continuous run of rectangular treads, winders or combination thereof from one
landing to another.
FLOAT. A floating structure normally used as a point of transfer for passengers and goods, or
both, for mooring purposes.
680
[BE] FLOOR AREA, GROSS. The floor area within the inside perimeter of the exterior walls
of the building under consideration, exclusive of vent shafts and courts, without deduction for
corridors, stairways, ramps, closets, the thickness of interior walls, columns or other features.
The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall
be the usable area under the horizontal projection of the roof or floor above. The gross floor area
shall not include shafts with no openings or interior courts.
[BE] FLOOR AREA, NET. The actual occupied area not including unoccupied accessory areas
such as corridors, stairways, ramps, toilet rooms, mechanical rooms and closets.
FUEL CELL POWER SYSTEM, STATIONARY. A stationary energy generation system that
converts the chemical energy of a fuel and oxidant to electric energy (DC or AC electricity) by
an electrochemical process.
Field-fabricated fuel cell power system. A stationary fuel cell power system that is
assembled at the job site and is not a preengineered or prepackaged factory-assembled fuel
cell power system.
Preengineered fuel cell power system. A stationary fuel cell power system consisting of
components and modules that are produced in a factory, and shipped to the job site for
assembly.
Prepackaged fuel cell power system. A stationary fuel cell power system that is factory
assembled as a single, complete unit and shipped as a complete unit for installation at the job
site.
FUEL LIMIT SWITCH. A mechanism, located on a tank vehicle, that limits the quantity of
product dispensed at one time.
FUMIGANT. A substance which by itself or in combination with any other substance emits or
liberates a gas, fume or vapor utilized for the destruction or control of insects, fungi, vermin,
germs, rats or other pests, and shall be distinguished from insecticides and disinfectants which are
essentially effective in the solid or liquid phases. Examples are methyl bromide, ethylene
dibromide, hydrogen cyanide, carbon disulfide and sulfuryl fluoride.
FUMIGATION. The utilization within an enclosed space of a fumigant in concentrations that
are hazardous or acutely toxic to humans.
FURNACE CLASS A. An oven or furnace that has heat utilization equipment operating at
approximately atmospheric pressure wherein there is a potential explosion or fire hazard that could
be occasioned by the presence of flammable volatiles or combustible materials processed or
heated in the furnace.
Note: Such flammable volatiles or combustible materials can, for instance, originate from
the following:
1. Paints, powders, inks, and adhesives from finishing processes, such as dipped, coated,
681
sprayed and impregnated materials.
2. The substrate material.
3. Wood, paper and plastic pallets, spacers or packaging materials.
4. Polymerization or other molecular rearrangements. Potentially flammable materials,
such as quench oil, waterborne finishes, cooling oil or cooking oils, that present a hazard
are ventilated according to Class A standards.
FURNACE CLASS B. An oven or furnace that has heat utilization equipment operating at
approximately atmospheric pressure wherein there are no flammable volatiles or combustible
materials being heated.
FURNACE CLASS C. An oven or furnace that has a potential hazard due to a flammable or
other special atmosphere being used for treatment of material in process. This type of furnace
can use any type of heating system and includes a special atmosphere supply system. Also
included in the Class C classification are integral quench furnaces and molten salt bath furnaces.
FURNACE CLASS D. An oven or furnace that operates at temperatures from above ambient to
over 5,000°F (2760°C) and at pressures normally below atmospheric using any type of heating
system. These furnaces can include the use of special processing atmospheres.
GAS CABINET. A fully enclosed, ventilated, noncombustible enclosure used to provide an
isolated environment for compressed gas cylinders in storage or use. Doors and access ports for
exchanging cylinders and accessing pressure-regulating controls are allowed to be included.
GAS DETECTION SYSTEM. A system or portion of a combination system that utilizes one or
more stationary sensors to detect the presence of a specified gas at a specified concentration and
initiate one or more responses required by this code, such as notifying a responsible person,
activating an alarm signal, or activating or deactivating equipment. A self-contained gas detection
and alarm device is not classified as a gas detection system.
GAS ROOM. A separately ventilated, fully enclosed room in which only compressed gases and
associated equipment and supplies are stored or used.
GAS ROOM, HYDROGEN FUEL. See "Hydrogen fuel gas room."
GASEOUS HYDROGEN SYSTEM. An assembly of piping, devices and apparatus designed to
generate, store, contain, distribute or transport a nontoxic, gaseous hydrogencontaining mixture
having not less than 95-percent hydrogen gas by volume and not more than 1-percent oxygen by
volume. Gaseous hydrogen systems consist of items such as compressed gas containers, reactors
and appurtenances, including pressure regulators, pressure relief devices, manifolds, pumps,
compressors and interconnecting piping and tubing and controls.
GLOVE BOX. A sealed enclosure in which items inside the box are handled exclusively using
long gloves sealed to ports in the enclosure.
[BG] GRADE FLOOR OPENING. A window or other opening located such that the sill height
682
of the opening is not more than 44 inches (1118 mm) above or below the finished ground level
adjacent to the opening.
[BG] GRADE PLANE. A reference plane representing the average of finished ground level
adjoining the building at exterior walls. Where the finished ground level slopes away from the
exterior walls, the reference plane shall be established by the lowest points within the area
between the building and the lot line or, where the lot line is more than 6 feet (1829 mm) from the
building, between the building and a point 6 feet (1829 mm) from the building.
[BE] GRANDSTAND. Tiered seating supported on a dedicated structural system and two or
more rows high and is not a building element (see "Bleachers").
[BG] GROUP HOME. A facility for social rehabilitation, substance abuse or mental health
problems that contains a group housing arrangement that provides custodial care but does not
provide medical care.
[BE] GUARD. A building component or a system of building components located at or near the
open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking
surface to a lower level.
[BG] GUESTROOM. A room used or intended to be used by one or more guests for living or
sleeping purposes.
[BS] GYPSUM BOARD. Gypsum wallboard, gypsum sheathing, gypsum base for gypsum
veneer plaster, exterior gypsum soffit board, predecorated gypsum board or waterresistant
gypsum backing board complying with the standards listed in Tables 2506.2 and 2507.2 and
Chapter 35 of the Puerto Rico Building Code.
[BG] HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking.
Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not
considered habitable spaces.
HALOGENATED EXTINGUISHING SYSTEM. A fireextinguishing system using one or
more atoms of an element from the halogen chemical series: fluorine, chlorine, bromine and
iodine.
HANDLING. The deliberate transport by any means to a point of storage or use.
[BE] HANDRAIL. A horizontal or sloping rail intended for grasping by the hand for guidance or
support.
HAZARDOUS MATERIALS. Those chemicals or substances which are physical hazards or
health hazards as defined and classified in this chapter, whether the materials are in usable or
waste condition.
683
HAZARDOUS PRODUCTION MATERIAL (HPM). A solid, liquid or gas associated with
semiconductor manufacturing that has a degree-of-hazard rating in health, flammability or
instability of Class 3 or 4 as ranked by NFPA 704 and which is used directly in research,
laboratory or production processes which have, as their end product, materials that are not
hazardous.
HEALTH HAZARD. A classification of a chemical for which there is statistically significant
evidence that acute or chronic health effects are capable of occurring in exposed persons. The
term "health hazard" includes chemicals that are toxic, highly toxic and corrosive.
HEAT DETECTOR. See "Detector, heat."
[BG] HEIGHT, BUILDING. The vertical distance from grade plane to the average height of the
highest roof surface.
HELIPORT. An area of land or water or a structural surface that is used, or intended for use, for
the landing and taking off of helicopters, and any appurtenant areas which are used, or intended
for use, for heliport buildings and other heliport facilities.
HELISTOP. The same as "Heliport," except that fueling, defueling, maintenance, repairs or
storage of helicopters is not permitted.
HI-BOY. A cart used to transport hot roofing materials on a roof.
HIGHER EDUCATION LABORATORY. Laboratories in Group B occupancies used for
educational purposes above the 12th grade. Storage, use and handling of chemicals in such
laboratories shall be limited to purposes related to testing, analysis, teaching, research or
developmental activities on a nonproduction basis.
HIGHLY TOXIC. A material which produces a lethal dose or lethal concentration which falls
within any of the following categories:
1. A chemical that has a median lethal dose (LD50) of 50 milligrams or less per kilogram
of body weight when administered orally to albino rats weighing between
200 and 300 grams each.
2. A chemical that has a median lethal dose (LD50) of 200 milligrams or less per kilogram
of body weight when administered by continuous contact for 24 hours (or less if death
occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3
kilograms each.
3. A chemical that has a median lethal concentration (LC50) in air of 200 parts per million
by volume or less of gas or vapor, or 2 milligrams per liter or less of mist, fume or dust,
when administered by continuous inhalation for one hour (or less if death occurs within 1
hour) to albino rats weighing between 200 and 300 grams each.
684
Mixtures of these materials with ordinary materials, such as water, might not warrant
classification as highly toxic. While this system is basically simple in application, any
hazard evaluation that is required for the precise categorization of this type of material
shall be performed by experienced, technically competent persons.
HIGHLY VOLATILE LIQUID. A liquefied compressed gas with a boiling point of less than
68°F (20°C).
HIGH-PILED COMBUSTIBLE STORAGE. Storage of combustible materials in closely
packed piles or combustible materials on pallets, in racks or on shelves where the top of storage
is greater than 12 feet (3658 mm) in height. Where required by the fire code official, high-piled
combustible storage also includes certain high-hazard commodities, such as rubber tires, Group
A plastics, flammable liquids, idle pallets and similar commodities, where the top of storage is
greater than 6 feet (1829 mm) in height.
HIGH-PILED STORAGE AREA. An area within a building which is designated, intended,
proposed or actually used for high-piled combustible storage, including operating aisles.
[BG] HIGH-RISE BUILDING. A building with an occupied floor located more than 75 feet
(22 860 mm) above the lowest level of fire department vehicle access.
HIGH-VOLTAGE TRANSMISSION LINE. An electrical power transmission line operating at
or above 66 kilovolts.
HIGHWAY. A public street, public alley or public road.
[A] HISTORIC BUILDINGS. Any building or structure that is one or more of the following:
1. Listed, or certified as eligible for listing by the state historic preservation officer or the
Keeper of the National Register of Historic Places, in the National Register of Historic
Places.
2. Designated as historic under an applicable state or local law.
3. Certified as a contributing resource within a national register, state designated or
locally designated historic district.
HOGGED MATERIALS. Wood waste materials produced from the lumber production process.
[M] HOOD. An air-intake device used to capture by entrapment, impingement, adhesion or
similar means, grease and similar contaminants before they enter a duct system.
Type I. A kitchen hood for collecting and removing grease vapors and smoke.
Type II. A general kitchen hood for collecting and removing steam vapor, heat, odors and
products of combustion.
685
[BF] HORIZONTAL ASSEMBLY. A fire-resistance-rated floor or roof assembly of materials
designed to restrict the spread of fire in which continuity is maintained.
[BE] HORIZONTAL EXIT. An exit component consisting of fire-resistance-rated construction
and opening protectives intended to compartmentalize portions of a building thereby creating
refuge areas that afford safety from fire and smoke from the area of fire origin.
[BG] HOSPITALS AND PSYCHIATRIC HOSPITALS. Facilities that provide care or
treatment for the medical, psychiatric, obstetrical, or surgical treatment of inpatient care recipients
that are incapable of self-preservation.
HOT WORK. Operations including cutting, welding, Thermit welding, brazing, soldering,
grinding, thermal spraying, thawing pipe, installation of torch-applied roof systems or any other
similar activity.
HOT WORK AREA. The area exposed to sparks, hot slag, radiant heat, or convective heat as a
result of the hot work.
HOT WORK EQUIPMENT. Electric or gas welding or cutting equipment used for hot work.
HOT WORK PERMITS. Permits issued by the responsible person at the facility under the hot
work permit program permitting welding or other hot work to be done in locations referred to in
Section 3503.3 and prepermitted by the fire code official.
HOT WORK PROGRAM. A permitted program, carried out by approved facilities-designated
personnel, allowing them to oversee and issue permits for hot work conducted by their personnel
or at their facility. The intent is to have trained, on-site, responsible personnel ensure that
required hot work safety measures are taken to prevent fires and fire spread.
HPM. See "Hazardous Production Material."
HPM FACILITY. See "Semiconductor fabrication facility."
HPM ROOM. A room used in conjunction with or serving a Group H-5 occupancy, where HPM
is stored or used and which is classified as a Group H-2, H-3 or H-4 occupancy.
HYDROGEN FUEL GAS ROOM. A room or space that is intended exclusively to house a
gaseous hydrogen system.
IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH). The concentration of
airborne contaminants that poses a threat of death, immediate or delayed permanent adverse
health effects, or effects that could prevent escape from such an environment. This contaminant
concentration level is established by the National Institute of Occupational Safety and Health
(NIOSH) based on both toxicity and flammability. It generally is expressed in parts per million
by volume (ppm v/v) or milligrams per cubic meter (mg/ m³). Where adequate data do not exist
for precise establishment of IDLH concentrations, an independent certified industrial hygienist,
686
industrial toxicologist, appropriate regulatory agency or other source approved by the fire code
official shall make such determination.
IMPAIRMENT COORDINATOR. The person responsible for the maintenance of a particular
fire protection system.
[BG] INCAPABLE OF SELF-PRESERVATION. Persons who, because of age, physical
limitations, mental limitations, chemical dependency or medical treatment, cannot respond as an
individual to an emergency situation.
INCOMPATIBLE MATERIALS. Materials that, when mixed, have the potential to react in a
manner which generates heat, fumes, gases or byproducts which are hazardous to life or property.
INERT GAS. A gas that is capable of reacting with other materials only under abnormal
conditions such as high temperatures, pressures and similar extrinsic physical forces. Within the
context of the code, inert gases do not exhibit either physical or health hazard properties as
defined (other than acting as a simple asphyxiant) or hazard properties other than those of a
compressed gas. Some of the more common inert gases include argon, helium, krypton, neon,
nitrogen and xenon.
INHABITED BUILDING. A building regularly occupied in whole or in part as a habitation for
people, or any place of religious worship, schoolhouse, railroad station, store or other structure
where people are accustomed to assemble, except any building or structure occupied in connection
with the manufacture, transportation, storage or use of explosive materials.
INITIATING DEVICE. A system component that originates transmission of a change-of-state
condition, such as in a smoke detector, manual fire alarm box, or supervisory switch.
INSECTICIDAL FOGGING. The utilization of insecticidal liquids passed through foggenerating units where, by means of pressure and turbulence, with or without the application of
heat, such liquids are transformed and discharged in the form of fog or mist blown into an area to
be treated.
INTEGRATED TESTING (FIRE PROTECTION AND LIFE SAFETY SYSTEM). A
testing procedure to establish the operational status, interaction and coordination of two or more
fire protection and safety systems.
[BE] INTERIOR EXIT RAMP. An exit component that serves to meet one or more means of
egress design requirements, such as required number of exits or exit access travel distance, and
provides for a protected path of egress travel to the exit discharge or public way.
[BE] INTERIOR EXIT STAIRWAY. An exit component that serves to meet one or more means
of egress design requirements, such as required number of exits or exit access travel distance, and
provides for a protected path of egress travel to the exit discharge or public way.
[BG] INTERIOR FINISH. Interior finish includes interior wall and ceiling finish and interior
687
floor finish.
[BG] INTERIOR FLOOR-WALL BASE. Interior floor finish trim used to provide a functional
or decorative border at the intersection of walls and floors.
[BG] INTERIOR WALL AND CEILING FINISH. The exposed interior surfaces of buildings,
including but not limited to: fixed or movable walls and partitions; toilet room privacy partitions;
columns; ceilings; and interior wainscoting, paneling or other finish applied structurally or for
decoration, acoustical correction, surface insulation, structural fire resistance or similar purposes,
but not including trim.
IRRITANT. A chemical which is not corrosive, but which causes a reversible inflammatory
effect on living tissue by chemical action at the site of contact. A chemical is a skin irritant if,
when tested on the intact skin of albino rabbits by the methods of CPSC 16 CFR Part 1500.41
for an exposure of four or more hours or by other appropriate techniques, it results in an empirical
score of 5 or more. A chemical is classified as an eye irritant if so determined under the procedure
listed in CPSC 16 CFR Part 1500.42 or other approved techniques.
[A] JURISDICTION. The governmental unit that has adopted this code.
KEY BOX. A secure device with a lock operable only by a fire department master key, and
containing building entry keys and other keys that may be required for access in an emergency.
[A] LABELED. Equipment, materials or products to which have been affixed a label, seal,
symbol or other identifying mark of a nationally recognized testing laboratory, approved agency
or other organization concerned with product evaluation that maintains periodic inspection of the
production of such labeled items and whose labeling indicates either that the equipment, material
or product meets identified standards or has been tested and found suitable for a specified purpose.
LABORATORY SUITE. A fire-rated enclosed laboratory area that will provide one or more
laboratory spaces, within a Group B educational occupancy, that are permitted to include ancillary
uses such as offices, bathrooms and corridors that are contiguous with the laboratory area, and are
constructed in accordance with Chapter 38.
LEVEL OF EXIT DISCHARGE. See "Exit discharge, level of."
LIMITED SPRAYING SPACE. An area in which operations for touch-up or spot painting of
a surface area of 9 square feet (0.84 m²) or less are conducted.
LIQUEFIED NATURAL GAS (LNG). A fluid in the liquid state composed predominantly of
methane and which may contain minor quantities of ethane, propane, nitrogen or other components
normally found in natural gas.
LIQUEFIED PETROLEUM GAS (LP-gas). A material which is composed predominantly of
the following hydrocarbons or mixtures of them: propane, propylene, butane (normal butane or
688
isobutane) and butylenes.
LIQUID. A material having a melting point that is equal to or less than 68°F (20°C) and a boiling
point which is greater than 68°F (20°C) at 14.7 pounds per square inch absolute (psia) (101 kPa).
Where not otherwise identified, the term "liquid" includes both flammable and combustible
liquids.
LIQUID OXYGEN AMBULATORY CONTAINER. A container used for liquid oxygen not
exceeding 0.396 gallons (1.5 liters) specifically designed for use as a medical device as defined
by 21 USC Chapter 9 that is intended for portable therapeutic use and to be filled from its
companion base unit, a liquid oxygen home care container.
LIQUID OXYGEN HOME CARE CONTAINER. A container used for liquid oxygen not
exceeding 15.8 gallons (60 liters) specifically designed for use as a medical device as defined
by 21 USC Chapter 9 that is intended to deliver gaseous oxygen for therapeutic use in a home
environment.
LIQUID STORAGE ROOM. A room classified as a Group H-3 occupancy used for the storage
of flammable or combustible liquids in a closed condition.
LIQUID STORAGE WAREHOUSE. A building classified as a Group H-2 or H-3 occupancy
used for the storage of flammable or combustible liquids in a closed condition.
[A] LISTED. Equipment, materials, products or services included in a list published by an
organization acceptable to the fire code official and concerned with evaluation of products or
services that maintains periodic inspection of production of listed equipment or materials or
periodic evaluation of services and whose listing states either that the equipment, material,
product or service meets identified standards or has been tested and found suitable for a specified
purpose.
LOCKDOWN. An emergency situation, in other than a Group I-3 occupancy, requiring that the
occupants be sheltered and secured in place within a building when normal evacuation would put
occupants at risk.
[BG] LODGING HOUSE. A one-family dwelling where one or more occupants are primarily
permanent in nature and rent is paid for guestrooms.
LONGITUDINAL FLUE SPACE. See "Flue space-longitudinal."
[A]LOT. A portion or parcel of land considered as a unit.
[A] LOT LINE. A line dividing one lot from another, or from a street or any public place.
[BE] LOW ENERGY POWER-OPERATED DOOR. Swinging, sliding or folding door which
opens automatically upon an action by a pedestrian such as pressing a push plate or waving a hand
in front of a sensor. The door closes automatically, and operates with decreased forces and decreased
689
speeds. See also "Power-assisted door" and "Power-operated door."
LOWER EXPLOSIVE LIMIT (LEL). See "Lower flammable limit."
LOWER FLAMMABLE LIMIT (LFL). The minimum concentration of vapor in air at which
propagation of flame will occur in the presence of an ignition source. The LFL is sometimes
referred to as LEL or lower explosive limit.
LOW-PRESSURE TANK. A storage tank designed to withstand an internal pressure greater than
0.5 pound per square inch gauge (psig) (3.4 kPa) but not greater than 15 psig (103.4 kPa).
LP-GAS CONTAINER. Any vessel, including cylinders, tanks, portable tanks and cargo tanks,
used for transporting or storing LP-gases.
MAGAZINE. A building, structure or container, other than an operating building, approved for
storage of explosive materials.
Indoor. A portable structure, such as a box, bin or other container, constructed as required
for Type 2, 4 or 5 magazines in accordance with NFPA 495, NFPA 1124 or DOTy 27 CFR
Part 55 so as to be fire resistant and theft resistant.
Type 1. A permanent structure, such as a building or igloo, that is bullet resistant, fire
resistant, theft resistant, weather resistant and ventilated in accordance with the
requirements of NFPA 495, NFPA 1124 or DOTy 27 CFR Part 55.
Type 2. A portable or mobile structure, such as a box, skid-magazine, trailer or semitrailer,
constructed in accordance with the requirements of NFPA 495, NFPA 1124 or DOTy 27
CFR Part 55 that is fire resistant, theft resistant, weather resistant and ventilated. If used
outdoors, a Type 2 magazine is also bullet resistant.
Type 3. A fire resistant, theft resistant and weather resistant "day box" or portable
structure constructed in accordance with NFPA 495, NFPA 1124 or DOTy 27 CFR Part
55 used for the temporary storage of explosive materials.
Type 4. A permanent, portable or mobile structure such as a building, igloo, box,
semitrailer or other mobile container that is fire resistant, theft resistant and weather
resistant and constructed in accordance with NFPA 495, NFPA 1124 or DOTy 27 CFR Part
55.
Type 5. A permanent, portable or mobile structure such as a building, igloo, box, bin, tank,
semitrailer, bulk trailer, tank trailer, bulk truck, tank truck or other mobile container that
is theft resistant, which is constructed in accordance with NFPA 495, NFPA 1124 or DOTy
27 CFR Part 55.
MAGNESIUM. The pure metal and alloys, of which the major part is magnesium.
690
MALL. See "Covered mall building."
MANUAL FIRE ALARM BOX. A manually operated device used to initiate an alarm signal.
MANUAL STOCKING METHODS. Stocking methods utilizing ladders or other
nonmechanical equipment to move stock.
MARINA. Any portion of the ocean or inland water, either naturally or artificially protected, for
the mooring, servicing or safety of vessels and shall include artificially protected works, the public
or private lands ashore, and structures or facilities provided within the enclosed body of water
and ashore for the mooring or servicing of vessels or the servicing of their crews or passengers.
MARINE MOTOR FUEL-DISPENSING FACILITY. That portion of property where
flammable or combustible liquids or gases used as fuel for watercraft are stored and dispensed
from fixed equipment on shore, piers, wharves, floats or barges into the fuel tanks of watercraft
and shall include all other facilities used in connection therewith.
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA. The maximum amount of
a hazardous material allowed to be stored or used within a control area inside a building or an
outdoor control area. The maximum allowable quantity per control area is based on the material
state (solid, liquid or gas) and the material storage or use conditions.
[BE] MEANS OF EGRESS. A continuous and unobstructed path of vertical and horizontal egress
travel from any occupied portion of a building or structure to a public way. A means of egress
consists of three separate and distinct parts: the exit access, the exit and the exit discharge.
MECHANICAL STOCKING METHODS. Stocking methods utilizing motorized vehicles or
hydraulic jacks to move stock.
[BG] MEDICAL CARE. Care involving medical or surgical procedures, nursing or for
psychiatric purposes.
MEMBRANE STRUCTURE. An air-inflated, air-supported, cable or frame-covered structure
as defined by the Puerto Rico Building Code and not otherwise defined as a tent. See Chapter 31
of the Puerto Rico Building Code.
[BF] MEMBRANE-PENETRATION FIRESTOP SYSTEM. An assemblage consisting of a
fire-resistance-rated floor-ceiling, roof-ceiling or wall assembly, one or more penetrating items
installed into or passing through the breach in one side of the assembly and the materials or devices,
or both, installed to resist the spread of fire into the assembly for a prescribed period of time.
[BE] MERCHANDISE PAD. A merchandise pad is an area for display of merchandise
surrounded by aisles, permanent fixtures or walls. Merchandise pads contain elements such as
nonfixed and moveable fixtures, cases, racks, counters and partitions as indicated in Section
105.2 of the Puerto Rico Building Code from which customers browse or shop.
METAL HYDRIDE. A generic name for compounds composed of metallic element(s) and
691
hydrogen.
METAL HYDRIDE STORAGE SYSTEM. A closed system consisting of a group of
components assembled as a package to contain metal-hydrogen compounds for which there exists
an equilibrium condition where the hydrogenabsorbing metal alloy(s), hydrogen gas and the
metal-hydrogen compound(s) coexist and where only hydrogen gas is released from the system
in normal use.
[BG] MEZZANINE. An intermediate level or levels between the floor and ceiling of any story
and in accordance with Section 505 of the Puerto Rico Building Code.
MISCELLA. A mixture, in any proportion, of the extracted oil or fat and the extracting solvent.
MOBILE FOOD PREPARATION VEHICLES. Vehicles that contain cooking equipment that
produce smoke or grease-laden vapors for the purpose of preparing and serving food to the public.
Vehicles intended for private recreation shall not be considered mobile food preparation vehicles.
MOBILE FUELING. The operation of dispensing liquid fuels from tank vehicles into the fuel
tanks of motor vehicles. Mobile fueling may also be known by the terms "Mobile fleet fueling,"
"Wet fueling" and "Wet hosing."
MORTAR. A tube from which fireworks shells are fired into the air.
MULTIPLE-STATION ALARM DEVICE. Two or more single-station alarm devices that can
be interconnected such that actuation of one causes all integral or separate audible alarms to
operate. A multiple-station alarm device can consist of one single-station alarm device having
connections to other detectors or to a manual fire alarm box.
MULTIPLE-STATION SMOKE ALARM. Two or more single-station alarm devices that are
capable of interconnection such that actuation of one causes the appropriate alarm signal to
operate in all interconnected alarms.
NESTING. A method of securing flat-bottomed compressed gas cylinders upright in a tight mass
using a contiguous threepoint contact system whereby all cylinders within a group have not less
than three points of contact with other cylinders, walls or bracing.
NET EXPLOSIVE WEIGHT (net weight). The weight of explosive material expressed in
pounds. The net explosive weight is the aggregate amount of explosive material cotained within
buildings, magazines, structures or portions thereof, used to establish quantity-distance
relationships.
NORMAL TEMPERATURE AND PRESSURE (NTP). A temperature of 70°F (21°C) and a
pressure of 1 atmosphere [14.7 psia (101 kPa)].
[BE] NOSING. The leading edge of treads of stairs and of landings at the top of stairway flights.
NOTIFICATION ZONE. See "Zone, notification."
692
NUISANCE ALARM. An alarm caused by mechanical failure, malfunction, improper
installation or lack of proper maintenance, or an alarm activated by a cause that cannot be
determined.
[BG] NURSING HOMES. Facilities that provide care, including both intermediate care facilities
and skilled nursing facilities, where any of the persons are incapable of self-preservation.
OCCUPANCY CLASSIFICATION For the purposes of this code, certain occupancies are
defined as follows:
[BG] Assembly Group A. Assembly Group A occupancy includes, among others, the use of
a building or structure, or a portion thereof, for the gathering of persons for purposes such as
civic, social or religious functions; recreation, food or drink consumption; or awaiting
transportation.
[BG] Small buildings and tenant spaces. A building or tenant space used for assembly
purposes with an occupant load of less than 50 persons shall be classified as a Group B
occupancy.
[BG] Small assembly spaces. The following rooms and spaces shall not be classified as
assembly occupancies:
1. A room or space used for assembly purposes with an occupant load of less than 50
persons and accessory to another occupancy shall be classified as a Group B
occupancy or as part of that occupancy.
2. A room or space used for assembly purposes that is less than 750 square feet (70
m²) in area and accessory to another occupancy shall be classified as a Group B
occupancy or as part of that occupancy.
[BG] Associated with Group E occupancies. A room or space used for assembly purposes
that is associated with a Group E occupancy is not considered a separate occupancy.
[BG] Accessory with places of religious worship. Accessory religious educational rooms
and religious auditoriums with occupant loads of less than 100 per room or space are not
considered separate occupancies
[BG] Assembly Group A-1. Group A occupancy includes assembly uses, usually with fixed
seating, intended for the production and viewing of performing arts or motion pictures
including, but not limited to:
Motion picture theaters
Symphony and concert hall
Television and radio studios admitting an audience
Theaters
693
[BG] Assembly Group A-2. Group A-2 occupancy includes assembly uses intended for food
and/or drink consumption including, but not limited to:
Banquet halls
Casinos (gaming areas)
Night clubs
Restaurants, cafeterias and similar dining facilities (including associated commercial
kitchens)
Taverns and bars
[BG] Assembly Group A-3. Group A-3 occupancy includes assembly uses intended for
worship, recreation or amusement and other assembly uses not classified elsewhere in Group
A, including, but not limited to:
Amusement arcades Art galleries Bowling alleys Community halls Courtrooms
Dance halls (not including food or drink consumption)
Exhibition halls
Funeral parlors
Greenhouses with public access for the conservation and exhibition of plants
Gymnasiums (without spectator seating)
Indoor swimming pools (without spectator seating) Indoor tennis courts (without
spectator seating)
Lecture halls
Libraries
Museums
Places of religious worship
Pool and billiard parlors
Waiting areas in transportation terminals
[BG] Assembly Group A-4. Group A-4 occupancy includes assembly uses intended for
viewing of indoor sporting events and activities with spectator seating including, but not
limited to:
Arenas
Skating rinks
Swimming pools
Tennis courts
[BG] Assembly Group A-5. Group A-5 occupancy includes assembly uses intended for
participation in or viewing outdoor activities including, but not limited to:
Amusement park structures
Bleachers
Grandstands
Stadiums
694
[BG] Business Group B. Business Group B occupancy includes, among others, the use of
a building or structure, or a portion thereof, for office, professional or service-type transactions,
including storage of records and accounts. Business occupancies shall include, but not be
limited to, the following:
Airport traffic control towers
Ambulatory care facilities
Animal hospitals, kennels and pounds
Banks
Barber and beauty shops
Car wash
Civic administration
Clinic-outpatient
Dry cleaning and laundries: pick-up and delivery stations and self-service
Educational occupancies for students above the 12th grade
Electronic data processing
Food processing establishments and commercial kitchens not associated with
restaurants, cafeterias and similar dining facilities not more than 2,500 square feet (232
m²) in area.
Laboratories: testing and research
Motor vehicle showrooms
Post offices
Print shops
Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
Radio and television stations
Telephone exchanges
Training and skill development not in a school or academic program (This shall
include, but not be limited to, tutoring centers, martial arts studios, gymnastics and
similar uses regardless of the ages served, and where not classified as a Group A
occupancy).
[BG] Educational Group E. Educational Group E occupancy includes, among others, the
use of a building or structure, or a portion thereof, by six or more persons at any one time for
educational purposes through the 12th grade.
[BG] Accessory to places of religious worship. Religious educational rooms and religious
auditoriums, which are accessory to places of religious worship in accordance with Section
303.1.4 of the Puerto Rico Building Code and have occupant loads of less than 100 per
room or space shall be classified as Group A-3 occupancies.
[BG] Group E, day care facilities. This group includes buildings and structures or portions
thereof occupied by more than five children older than 2¹/2 years of age who receive
educational, supervision or personal care services for less than 24 hours per day.
[BG] Within places of worship. Rooms and spaces within places of worship providing such
care during religious functions shall be classified as part of the primary occupancy.
695
[BG] Five or fewer children. A facility having five or fewer children receiving such care shall
be classified as part of the primary occupancy.
[BG] Five or fewer children in a dwelling unit. A facility such as the above within a dwelling
unit and having five or fewer children receiving such care shall be classified as a Group R-3
occupancy or shall comply with the Puerto Rico Residential Code.
[BG] Factory Industrial Group F. Factory Industrial Group F occupancy includes, among
others, the use of a building or structure, or a portion thereof, for assembling, disassembling,
fabricating, finishing, manufacturing, packaging, repair or processing operations that are not
classified as a Group H high-hazard or Group S storage occupancy.
[BG] Factory Industrial F-1 Moderate-hazard occupancy. Factory industrial uses that are
not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate
Hazard and shall include, but not be limited to, the following:
Aircraft (manufacturing, not to include repair) Appliances
Athletic equipment
Automobiles and other motor vehicles
Bakeries
Beverages; over 16-percent alcohol content
Bicycles
Boats
Brooms or brushes
Business machines
Cameras and photo equipment
Canvas or similar fabric
Carpets and rugs (includes cleaning)
Clothing
Construction and agricultural machinery
Disinfectants
Dry cleaning and dyeing
Electric generation plants
Electronics
Engines (including rebuilding)
Food processing and commercial kitchens not associated with restaurants, cafeterias
and similar dining facilities more than 2,500 square feet (232 m²) in area.
Furniture
Hemp products
Jute products
Laundries
Leather products
Machinery
Metals
Millwork (sash and door)
696
Motion pictures and television filming (without spectators)
Musical instruments
Optical goods
Paper mills or products
Photographic film
Plastic products Printing or publishing Refuse incineration Shoes
Soaps and detergents
Textiles
Tobacco
Trailers
Upholstering
Wood; distillation
Woodworking (cabinet)
[BG] Factory Industrial F-2 Low-hazard Occupancy. Factory industrial uses involving
the fabrication or manufacturing of noncombustible materials that, during finishing,
packaging or processing do not involve a significant fire hazard, shall be classified as Group
F-2 occupancies and shall include, but not be limited to, the following:
Beverages; up to and including 16-percent alcohol content
Brick and masonry
Ceramic products
Foundries
Glass products
Gypsum
Ice
Metal products (fabrication and assembly)
High-hazard Group H. High-hazard Group H occupancy includes, among others, the use of
a building or structure, or a portion thereof, that involves the manufacturing, processing,
generation or storage of materials that constitute a physical or health hazard in quantities in
excess of those allowed in control areas complying with Section 5003.8.3, based on the
maximum allowable quantity limits for control areas set forth in Tables 5003.1.1(1)
and5003.1.1(2).
Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in
accordance with this code and the requirements of Section 415 of the Puerto Rico Building
Code. Hazardous materials stored or used on top of roofs or canopies shall be classified as
outdoor storage or use and shall comply with this code.
Uses other than Group H. The storage, use or handling of hazardous materials as described
in one or more of the following items shall not cause the occupancy to be classified as Group
H, but it shall be classified as the occupancy that it most nearly resembles:
1. Buildings and structures occupied for the application of flammable finishes, provided
that such buildings or areas conform to the requirements of Chapter 24 of this code
697
and Section 416 of the Puerto Rico Building Code.
2. Wholesale and retail sales and storage of flammable and combustible liquids in
mercantile occupancies conforming to Chapter 57.
3. Closed piping system containing flammable or combustible liquids or gases utilized
for the operation of machinery or equipment.
4. Cleaning establishments that utilize combustible liquid solvents having a flash point
of 140°F (60°C) or higher in closed systems employing equipment listed by an
approved testing agency, provided that this occupancy is separated from all other areas
of the building by 1-hour fire barriers in accordance with Section 707 of the Puerto
Rico Building Code or 1-hour horizontal assemblies in accordance with Section 711
of the Puerto Rico Building Code, or both.
5. Cleaning establishments that utilize a liquid solvent having a flash point at or above
200°F (93°C).
6. Liquor stores and distributors without bulk storage.
7. Refrigeration systems.
8. The storage or utilization of materials for agricultural purposes on the premises.
9. Stationary storage battery systems installed in accordance with Section 1206.2.
10. Corrosive personal or household products in their original packaging used in retail
display.
11. Commonly used corrosive building materials.
12. Buildings and structures occupied for aerosol product storage shall be classified as
Group S-1, provided that such buildings conform to the requirements of Chapter 51.
13. Display and storage of nonflammable solid and nonflammable or noncombustible
liquid hazardous materials in quantities not exceeding the maximum allowable
quantity per control area in Group M or S occupancies complying with Section
5003.8.3.5.1.
14. The storage of black powder, smokeless propellant and small arms primers in
Groups M and R-3 and special industrial explosive devices in Groups B, F, M and
S, provided such storage conforms to the quantity limits and requirements of this code.
15. Stationary fuel cell power systems installed in accordance with this code.
16. Capacitor energy storage systems in accordance with this code.
17. Group B higher education laboratory occupancies complying with Section 428 of
the Puerto Rico Building Code and Chapter 38 of this code.
High-hazard Group H-1. Buildings and structures containing materials that pose a
detonation hazard shall be classified as Group H-1. Such materials shall include, but not be
limited to, the following:
Detonable pyrophoric materials
Explosives: Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6
Organic peroxides, unclassified detonable
698
Oxidizers, Class 4
Unstable (reactive) materials, Class 3 detonable, and
Class
4
Occupancies containing explosives not classified as H-1.
The following occupancies containing explosive materials shall be classified as follows:
1. Division 1.3 explosive materials that are used and maintained in a form where
either confinement or configuration will not elevate the hazard from a mass fire
hazard to mass explosion hazard shall be allowed in Group H-2 occupancies.
2. Articles, including articles packaged for shipment, that are not regulated as a
Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives
regulations, or unpackaged articles used in process operations that do not propagate a
detonation or deflagration between articles shall be allowed in H-3 occupancies.
High-hazard Group H-2. Buildings and structures containing materials that pose a
deflagration hazard or a hazard from accelerated burning shall be classified as Group
H-2. Such materials shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids that are used or stored in
normally open containers or systems, or in closed containers or systems pressurized
at more than 15 pounds per square inch gauge (103.4 kPa)
Combustible dusts where manufactured, generated or used in such a manner that the
concentration and conditions create a fire or explosion hazard based on information
prepared in accordance with Section 414.1.3 of the Puerto Rico Building Code
Cryogenic fluids, flammable
Flammable gases
Organic peroxides, Class I
Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed
containers or systems pressurized at more than 15 pounds per square inch gauge (103.4 kPa)
Pyrophoric liquids, solids and gases, nondetonable Unstable (reactive) materials, Class 3,
nondetonable Water-reactive materials, Class 3
High-hazard Group H-3. Buildings and structures containing materials that readily support
combustion or that pose a physical hazard shall be classified as Group H-3. Such materials
shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids that are used or stored in
normally closed containers or systems pressurized at 15 pounds per square inch gauge
(103.4 kPa) or less.
Combustible fibers, other than densely packed baled cotton, where manufactured,
699
generated or used in such a manner that the concentration and conditions create a fire
or explosion hazard based on information prepared in accordance with Section 414.1.3
of the Puerto Rico Building Code Consumer fireworks, 1.4G (Class C, Common)
Cryogenic fluids, oxidizing
Flammable solids
Organic peroxides, Class II and III Oxidizers, Class 2
Oxidizers, Class 3, that are used or stored in normally closed containers or systems pressurized
at 15 pounds per square inch gauge (103 kPa) or less
Oxidizing gases
Unstable (reactive) materials, Class 2
Water-reactive materials, Class 2
High-hazard Group H-4. Buildings and structures containing materials that are health
hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the
following:
Corrosives
Highly toxic materials
Toxic materials
High-hazard Group H-5. Semiconductor fabrication facilities and comparable research and
development areas in which hazardous production materials (HPM) are used and the
aggregate quantity of materials is in excess of those listed in Tables 5003.1.1(1) and
5003.1.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and
constructed in accordance with Section 415.11 of the Puerto Rico Building Code.
[BG] Institutional Group I. Institutional Group I occupancy includes, among others, the
use of a building or structure, or a portion thereof, in which care or supervision is provided to
persons who are or are not capable of selfpreservation without physical assistance or in which
persons are detained for penal or correctional purposes or in which the liberty of the
occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-
4.
[BG] Institutional Group I-1. Institutional Group I-1 occupancy shall include buildings,
structures or portions thereof for more than 16 persons, excluding staff, who reside on a 24-
hour basis in a supervised environment and receive custodial care. Buildings of Group I-1
shall be classified as one of the occupancy conditions indicated below. This group shall
include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities
Congregate care facilities
Group homes
Halfway houses
Residential board and care facilities
Residential board and custodial care facilities
700
Social rehabilitation facilities
[BG] Condition 1. This occupancy condition shall include buildings in which all persons
receiving custodial care who, without any assistance, are capable of responding to an
emergency situation to complete building evacuation.
[BG] Condition 2. This occupancy condition shall include buildings in which there are any
persons receiving custodial care who require limited verbal or physical assistance while
responding to an emergency situation to complete building evacuation.
[BG] Six to 16 persons receiving custodial care. A facility housing not fewer than six and not
more than 16 persons receiving custodial care shall be classified as Group R-4.
[BG] Five or fewer persons receiving custodial care. A facility with five or fewer persons
receiving custodial care shall be classified as Group R-3 or shall comply with the Puerto Rico
Residential Code provided an automatic sprinkler system is installed in accordance with
Section 903.3.1.3 or with Section P2904 of the Puerto Rico Residential Code.
[BG] Institutional Group I-2. Institutional Group I-2 occupancy shall include buildings and
structures used for medical care on a 24-hour basis for more than five persons who are not
capable of self-preservation. This group shall include, but not be limited to, the following:
Foster care facilities
Detoxification facilities
Hospitals
Nursing homes
Psychiatric hospitals
[BG] Occupancy Conditions. Buildings of Group I-2 shall be classified as one of
the following occupancy conditions:
[BG] Condition 1. This occupancy condition shall include facilities that provide
nursing and medical care but do not provide emergency care, surgery, obstetrics, or
in-patient stabilization units for psychiatric or detoxification, including, but not limited
to, nursing homes and foster care facilities.
[BG] Condition 2. This occupancy condition shall include facilities that provide
nursing and medical care and could provide emergency care, surgery, obstetrics, or
inpatient stabilization units for psychiatric or detoxification, including, but not limited
to, hospitals.
[BG] Five or fewer persons receiving medical care. A facility with five or fewer
persons receiving medical care shall be classified as Group R-3 or shall comply
with the Puerto Rico Residential Code provided an automatic sprinkler system is
installed in accordance with Section 903.3.1.3 or with Section P2904 of the Puerto
Rico Residential Code.
701
[BG] Institutional Group I-3. Institutional Group I-3 occupancy shall include
buildings and structures which are due to security measures not under the occupants'
control. This group shall include, but not be limited to, the following:
Correctional centers
Detention centers Jails
Prerelease centers
Prisons
Reformatories
Buildings of Group I-3 shall be classified as one of the following occupancy conditions:
[BG] Condition 1. This occupancy condition shall include buildings in which free movement
is allowed from sleeping areas and other spaces where access or occupancy is permitted to
the exterior via means of egress without restraint. A Condition 1 facility is permitted to be
constructed as Group R.
[BG] Condition 2. This occupancy condition shall include buildings in which free movement
is allowed from sleeping areas and any other occupied smoke compartment to one or more
other smoke compartments. Egress to the exterior is impeded by locked exits.
[BG] Condition 3. This occupancy condition shall include buildings in which free movement
is allowed within individual smoke compartments, such as within a residential unit comprised
of individual sleeping units and group activity spaces, where egress is impeded by remotecontrolled release of means of egress from such smoke compartment to another smoke
compartment.
[BG] Condition 4. This occupancy condition shall include buildings in which free movement
is restricted from an occupied space. Remote-controlled release is provided to permit
movement from sleeping units, activity spaces and other occupied areas within the smoke
compartment to other smoke compartments.
[BG] Condition 5. This occupancy condition shall include buildings in which free movement
is restricted from an occupied space. Staff-controlled manual release is provided to permit
movement from sleeping units, activity spaces and other occupied areas within the smoke
compartment to other smoke compartments.
[BG] Institutional Group I-4, day care facilities. Institutional Group I-4 shall include
buildings and structures occupied by more than five persons of any age who receive custodial
care for less than 24 hours by persons other than parents or guardians, relatives by blood,
marriage, or adoption, and in a place other than the home of the person cared for. This group
shall include, but not be limited to, the following:
Adult day care
Child day care
702
[BG] Classification as Group E. A child day care facility that provides care for more than
five but not inhabited by more than five persons who are under more than 100 children 2¹/2
years or less of age, where restraint or security. A Group I-3 facility is occupied by persons
who are generally incapable of self-preservation the rooms in which the children are cared
for are located on a level of exit discharge serving such rooms and each of these child care
rooms has an exit door directly to the exterior, shall be classified as Group E.
[BG] Within a place of religious worship. Rooms and spaces within places of religious
worship providing such care during religious functions shall be classified as part of the primary
occupancy.
[BG] Five or fewer occupants receiving care. A facility having five or fewer persons
receiving custodial care shall be classified as part of the primary occupancy.
[BG] Five or fewer occupants receiving care in a dwelling unit.
A facility such as the above within a dwelling unit and having five or fewer persons receiving
custodial care shall be classified as a Group R-3 occupancy or shall comply with the Puerto
Rico Residential Code.
[BG] Mercantile Group M. Mercantile Group M occupancy includes, among others, the use
of a building or structure or a portion thereof, for the display and sale of merchandise, and
involves stocks of goods, wares or merchandise incidental to such purposes and accessible to
the public. Mercantile occupancies shall include, but not be limited to, the following:
Department stores
Drug stores
Greenhouses with public access that maintain plants for display and sale
Markets
Motor fuel-dispensing facilities
Retail or wholesale stores
Sales rooms
[BG] Residential Group R. Residential Group R includes, among others, the use of a building
or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional
Group I or when not regulated by the Puerto Rico Residential Code in accordance with Section
101.2 of the Puerto Rico Building Code.
[BG] Residential Group R-1. Residential Group R-1 occupancies containing sleeping units
where the occupants are primarily transient in nature, including:
Boarding houses (transient) with more than 10 occupants
Congregate living facilities (transient) with more than 10 occupants
Hotels (transient)
Motels (transient)
703
[BG] Residential Group R-2. Residential Group R-2 occupancies containing sleeping units
or more than two dwelling units where the occupants are primarily permanent in nature,
including:
Apartment houses
Congregate living facilities (nontransient) with more than 16 occupants
Boarding houses (nontransient) Convents
Dormitories
Fraternities and sororities
Monasteries
Hotels (nontransient)
Live/work units
Motels (nontransient)
Vacation timeshare properties
[BG] Residential Group R-3. Residential Group R-3 occupancies where the occupants are
primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, including:
Buildings that do not contain more than two dwelling units
Care facilities that provide accommodations for five or fewer persons receiving care
Congregate living facilities (nontransient) with 16 or fewer occupants
Boarding houses (nontransient) Convents
Dormitories
Fraternities and sororities
Monasteries
Congregate living facilities (transient) with 10 or fewer occupants
Boarding houses (transient)
Lodging houses (transient) with five or fewer guestrooms and 10 or fewer occupants
[BG] Care facilities within a dwelling. Care facilities for five or fewer persons receiving
care that are within a single-family dwelling are permitted to comply with the Puerto Rico
Residential Code provided an automatic sprinkler system is installed in accordance with
Section 903.3.1.3 or Section P2904 of the Puerto Rico Residential Code.
[BG] Lodging houses. Owner-occupied lodging houses with five or fewer guestrooms and
10 or fewer total occupants shall be permitted to be constructed in accordance with the Puerto
Rico Residential Code.
[BG] Residential Group R-4. Residential Group R-4 shall include buildings, structures or
portions thereof for more than five but not more than 16 persons, excluding staff, who reside
on a 24-hour basis in a supervised residential environment and receive custodial care.
Buildings of Group R-4 shall be classified as one of the occupancy conditions indicated below.
This group shall include, but not be limited to, the following:
Alcohol and drug centers Assisted living facilities
Congregate care facilities
704
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-
3, except as otherwise provided for in the Puerto Rico Building Code.
[BG] Condition 1. This occupancy condition shall include buildings in which all persons
receiving custodial care, without any assistance, are capable of responding to an emergency
situation to complete building evacuation.
[BG] Condition 2. This occupancy condition shall include buildings in which there are any
persons receiving custodial care who require limited verbal or physical assistance while
responding to an emergency situation to complete building evacuation.
[BG] Storage Group S. Storage Group S occupancy includes, among others, the use of a
building or structure, or a portion thereof, for storage that is not classified as a hazardous
occupancy.
[BG] Accessory storage spaces. A room or space used for storage purposes that is less than
100 square feet (9.3 m²) in area and accessory to another occupancy shall be classified as part
of that occupancy. The aggregate area of such rooms or spaces shall not exceed the allowable
area limits of Section 508.2 of the Puerto Rico Building Code.
[BG] Moderate-hazard storage, Group S-1. Storage Group S-1 occupancies are buildings
occupied for storage uses that are not classified as Group S-2, including, but not limited to,
storage of the following:
Aerosols, Levels 2 and 3
Aircraft hangar (storage and repair)
Bags: cloth, burlap and paper
Bamboos and rattan
Baskets
Belting: canvas and leather
Books and paper in rolls or packs
Boots and shoes
Buttons, including cloth covered, pearl or bone
Cardboard and cardboard boxes
Clothing, woolen wearing apparel
Cordage
Dry boat storage (indoor) Furniture
Furs
Glues, mucilage, pastes and size
Grains
705
Horns and combs, other than celluloid
Leather
Linoleum
Lumber
Motor vehicle repair garages complying with the maximum allowable quantities of hazardous
materials listed in Table 5003.1.1(1) (see Section 406.8 of the Puerto Rico Building Code)
Photo engravings
Resilient flooring
Self-service storage facility (mini-storage)
Silks
Soaps
Sugar
Tires, bulk storage of
Tobacco, cigars, cigarettes and snuff
Upholstery and mattresses
Wax candles
[BG] Low-hazard storage, Group S-2. Storage Group S-2 occupancies include, among
others, buildings used for the storage of noncombustible materials such as products on wood
pallets or in paper cartons with or without single thickness divisions; or in paper wrappings.
Such products are permitted to have a negligible amount of plastic trim, such as knobs,
handles or film wrapping. Storage uses shall include, but not be limited to, storage of the
following:
Asbestos
Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
Cement in bags
Chalk and crayons
Dairy products in nonwaxed coated paper containers
Dry cell batteries
Electrical coils
Electrical motors
Empty cans
Food products
Foods in noncombustible containers
Fresh fruits and vegetables in nonplastic trays or containers
Frozen foods
Glass
Glass bottles, empty or filled with noncombustible liquids
Gypsum board
Inert pigments
Ivory
Meats
Metal cabinets
Metal desks with plastic tops and trim
Metal parts
706
Metals
Mirrors
Oil-filled and other types of distribution transformers
Parking garages, open or enclosed
Porcelain and pottery
Stoves
Talc and soapstones
Washers and dryers
[BG] Miscellaneous Group U. Buildings and structures of an accessory character and
miscellaneous structures not classified in any specific occupancy shall be constructed,
equipped and maintained to conform to the requirements of this code commensurate with the
fire and life hazard incidental to their occupancy. Group U shall include, but not be limited
to, the following:
Agricultural buildings
Aircraft hangar, accessory to a one- or two-family residence (see Section 412.4 of the
Puerto Rico Building Code)
Barns
Carports
Communication equipment structures with a gross floor area of less than 1,500 square
feet (139 m³)
Fences more than 6 feet (1829 mm) high
Grain silos, accessory to a residential occupancy
Livestock shelters
Private garages
Retaining walls
Sheds
Stables
Tanks
Towers
[BG] OCCUPANT LOAD. The number of persons for which the means of egress of a building
or portion thereof is designed.
OPEN BURNING. The burning of materials wherein products of combustion are emitted directly
into the ambient air without passing through a stack or chimney from an enclosed chamber. Open
burning does not include road flares, smudgepots and similar devices associated with safety or
occupational uses typically considered open flames, recreational fires or use of portable outdoor
fireplaces. For the purpose of this definition, a chamber shall be regarded as enclosed when, during
the time combustion occurs, only apertures, ducts, stacks, flues or chimneys necessary to provide
combustion air and permit the escape of exhaust gas are open.
OPEN MALL. See "Covered mall building."
707
OPEN MALL BUILDING. See "Covered mall building."
[BG] OPEN PARKING GARAGE. A structure or portion of a structure with the openings as
described in Section 406.5.2 of the Puerto Rico Building Code on two or more sides that is used
for the parking or storage of private motor vehicles as described in Section 406.5 of the Puerto
Rico Building Code.
OPEN SYSTEM. The use of a solid or liquid hazardous material involving a vessel or system
that is continuously open to the atmosphere during normal operations and where vapors are
liberated, or the product is exposed to the atmosphere during normal operations. Examples of
open systems for solids and liquids include dispensing from or into open beakers or containers,
dip tank and plating tank operations.
OPEN-AIR ASSEMBLY SEATING. Seating served by means of egress that is not subject to
smoke accumulation within or under a structure and is open to the atmosphere.
[BE] OPEN-ENDED CORRIDOR. An interior corridor that is open on each end and connects
to an exterior stairway or ramp at each end with no intervening doors or separation from the
corridor.
[BF] OPENING PROTECTIVE. A fire door assembly, fire shutter assembly, fire window
assembly or glass-block assembly in a fire-resistance-rated wall or partition.
OPERATING BUILDING. A building occupied in conjunction with the manufacture,
transportation or use of explosive materials. Operating buildings are separated from one another
with the use of intraplant or intraline distances.
OPERATING LINE. A group of buildings, facilities or workstations so arranged as to permit
performance of the steps in the manufacture of an explosive or in the loading, assembly,
modification and maintenance of ammunition or devices containing explosive materials.
OPERATING PRESSURE. The pressure at which a system operates.
ORGANIC COATING. A liquid mixture of binders such as alkyd, nitrocellulose, acrylic or oil,
and flammable and combustible solvents such as hydrocarbon, ester, ketone or alcohol, which,
when spread in a thin film, convert to a durable protective and decorative finish.
ORGANIC PEROXIDE. An organic compound that contains the bivalent -O-Ostructure and
which may be considered to be a structural derivative of hydrogen peroxide where one or both of
the hydrogen atoms have been replaced by an organic radical. Organic peroxides can present an
explosion hazard (detonation or deflagration) or they can be shock sensitive. They can also
decompose into various unstable compounds over an extended period of time.
Class I. Describes those formulations that are capable of deflagration but not detonation.
Class II. Describes those formulations that burn very rapidly and that pose a moderate
708
reactivity hazard.
Class III. Describes those formulations that burn rapidly and that pose a moderate
reactivity hazard.
Class IV. Describes those formulations that burn in the same manner as ordinary
combustibles and that pose a minimal reactivity hazard.
Class V. Describes those formulations that burn with less intensity than ordinary
combustibles or do not sustain combustion and that pose no reactivity hazard.
Unclassified detonable. Organic peroxides that are capable of detonation. These
peroxides pose an extremely high-explosion hazard through rapid explosive
decomposition.
OUTDOOR ASSEMBLY EVENT. An outdoor gathering of persons for any purpose.
OUTDOOR CONTROL AREA. An outdoor area that contains hazardous materials in amounts
not exceeding the maximum allowable quantities of Table 5003.1.1(3) or Table 5003.1.1(4).
OUTPATIENT CLINIC. See "Clinic, outpatient."
OVERCROWDING. A condition that exists when either there are more people in a building,
structure or portion thereof than have been authorized or posted by the fire code official, or when
the fire code official determines that a threat exists to the safety of the occupants due to persons
sitting and/or standing in locations that may obstruct or impede the use of aisles, passages,
corridors, stairways, exits or other components of the means of egress.
[A] OWNER. Any person, agent, operator, entity, firm or corporation having any legal or
equitable interest in the property; or recorded in the official records of the state, county or
municipality as holding an interest or title to the property; or otherwise having possession or
control of the property, including the guardian of the estate of any such person, and the executor
or administrator of the estate of such person if ordered to take possession of real property by a
court.
OXIDIZER. A material that readily yields oxygen or other oxidizing gas, or that readily reacts
to promote or initiate combustion of combustible materials and, if heated or contaminated, can
result in vigorous self-sustained decomposition.
Class 4. An oxidizer that can undergo an explosive reaction due to contamination or exposure
to thermal or physical shock and that causes a severe increase in the burning rate of
combustible materials with which it comes into contact. Additionally, the oxidizer causes a
severe increase in the burning rate and can cause spontaneous ignition of combustibles.
Class 3. An oxidizer that causes a severe increase in the burning rate of combustible materials
with which it comes in contact.
709
Class 2. An oxidizer that will cause a moderate increase in the burning rate of combustible
materials with which it comes in contact.
Class 1. An oxidizer that does not moderately increase the burning rate of combustible
materials.
OXIDIZING CRYOGENIC FLUID. An oxidizing gas in the cryogenic state.
OXIDIZING GAS. A gas that can support and accelerate combustion of other materials
more than air does.
OZONE-GAS GENERATOR. Equipment which causes the production of ozone.
[BE] PANIC HARDWARE. A door-latching assembly incorporating a device that releases
the latch upon the application of a force in the direction of egress travel. See also "Fire exit
hardware.'
PASS-THROUGH. An enclosure installed in a wall with a door on each side that allows
chemicals, HPM, equipment, and parts to be transferred from one side of the wall to the other.
[BG] PENTHOUSE. An enclosed, unoccupied rooftop structure used for sheltering
mechanical and electrical equipment, tanks, elevators and related machinery, and vertical shaft
openings.
PERMISSIBLE EXPOSURE LIMIT (PEL). The maximum permitted 8-hour timeweighted-average concentration of an airborne contaminant. The exposure limits to be utilized
are those published in DOL 29 CFR Part 1910.1000. The Recommended Exposure Limit
(REL) concentrations published by the U.S. National Institute for Occupational Safety and
Health (NIOSH), Threshold Limit Value-Time Weighted Average (TLV-TWA) concentrations
published by the American Conference of Governmental Industrial Hygienists (ACGIH),
Workplace Environmental Exposure Level (WEEL) Guides published by the American
Industrial Hygiene Association (AIHA), and other approved, consistent measures are allowed
as surrogates for hazardous substances not listed in DOL 29 CFR Part 1910.1000.
[A] PERMIT. An official document or certificate issued by the fire code official that
authorizes performance of a specified activity.
[A] PERSON. An individual, heirs, executors, administrators or assigns, and also includes a
firm, partnership or corporation, its or their successors or assigns, or the agent of any of the
aforesaid.
[BG] PERSONAL CARE SERVICE. The care of persons who do not require medical care.
Personal care involves responsibility for the safety of the persons while inside the building.
PESTICIDE. A substance or mixture of substances, including fungicides, intended for
710
preventing, destroying, repelling or mitigating pests and substances or a mixture of substances
intended for use as a plant regulator, defoliant or desiccant. Products defined as drugs in the
Federal Food, Drug and Cosmetic Act are not pesticides.
[BE] PHOTOLUMINESCENT. Having the property of emitting light that continues for a
length of time after excitation by visible or invisible light has been removed.
PHYSICAL HAZARD. A chemical for which there is evidence that it is a combustible liquid,
cryogenic fluid, explosive, flammable (solid, liquid or gas), organic peroxide (solid or liquid),
oxidizer (solid or liquid), oxidizing gas, pyrophoric (solid, liquid or gas), unstable (reactive)
material (solid, liquid or gas) or water-reactive material (solid or liquid).
PHYSIOLOGICAL WARNING THRESHOLD. A concentration of airborne
contaminants, normally expressed in parts per million (ppm) or milligrams per cubic meter
(mg/ m³), that represents the concentration at which persons can sense the presence of the
contaminant due to odor, irritation or other quick-acting physiological responses. When used
in conjunction with the permissible exposure limit (PEL), the physiological warning
threshold levels are those consistent with the classification system used to establish the PEL.
See the definition of "Permissible exposure limit (PEL)."
PIER. A structure built over the water, supported by pillars or piles, and used as a landing
place, pleasure pavilion or similar purpose.
PLACE OF RELIGIOUS WORSHIP. See "Religious worship, place of.
[M] PLENUM. An enclosed portion of the building structure, other than an occupiable space
being conditioned, that is designed to allow air movement and thereby serve as part of an air
distribution system.
PLOSOPHORIC MATERIAL. Two or more unmixed, commercially manufactured,
prepackaged chemical substances including oxidizers, flammable liquids or solids, or similar
substances that are not independently classified as explosives but which, when mixed or
combined, form an explosive that is intended for blasting.
PLYWOOD AND VENEER MILLS. Facilities where raw wood products are processed into
finished wood products, including waferboard, oriented strandboard, fiberboard, composite
wood panels and plywood.
PORTABLE OUTDOOR FIREPLACE. A portable, outdoor, solid-fuel-burning fireplace
that may be constructed of steel, concrete, clay or other noncombustible material. A portable
outdoor fireplace may be open in design, or may be equipped with a small hearth opening
and a short chimney or chimney opening in the top.
[BE] POWER-ASSISTED DOOR. Swinging door that opens by reduced pushing or pulling
force on the door-operating hardware. The door closes automatically after the pushing or
pulling force is released, and functions with decreased forces. See also "Low energy power-
711
operated door" and "Power-operated door."
POWERED INDUSTRIAL TRUCK. A forklift, tractor, platform lift truck or motorized
hand truck powered by an electrical motor or internal combustion engine. Powered industrial
trucks do not include farm vehicles or automotive vehicles for highway use.
[BE] POWER-OPERATED DOOR. Swinging, sliding, or folding door that opens
automatically when approached by a pedestrian or opens automatically upon an action by a
pedestrian. The door closes automatically and includes provisions such as presence sensors
to prevent entrapment. See also "Low energy power-operated door" and "Power-assisted
door."
PRESSURE VESSEL. A closed vessel designed to operate at pressures above 15 psig (103
kPa).
PRIMARY CONTAINMENT. The first level of containment, consisting of the inside
portion of that container which comes into immediate contact on its inner surface with the
material being contained.
[BG] PRIVATE GARAGE. A building or portion of a building in which motor vehicles used
by the owner or tenants of the building or buildings on the premises are stored or kept, without
provisions for repairing or servicing such vehicles for profit.
PROCESS TRANSFER. The transfer of flammable or combustible liquids between tank
vehicles or tank cars and process operations. Process operations may include containers, tanks,
piping and equipment.
PROPELLANT. The liquefied or compressed gas in an aerosol container that expels the
contents from an aerosol container when the valve is actuated. A propellant is considered
flammable if it forms a flammable mixture with air, or if a flame is self-propagating in a mixture
with air.
PROXIMATE AUDIENCE. An audience closer to pyrotechnic devices than allowed by
NFPA 1123.
[B] PSYCHIATRIC HOSPITALS. See "Hospitals."
PUBLIC TRAFFIC ROUTE (PTR). Any public street, road, highway, navigable stream or
passenger railroad that is used for through traffic by the general public.
[A] PUBLIC WAY. A street, alley or other parcel of land open to the outside air leading to a
street, that has been deeded, dedicated or otherwise permanently appropriated to the public for
public use and which has a clear width and height of not less than 10 feet (3048 mm).
[BE] PUBLIC-USE AREAS. Interior or exterior rooms or spaces that are made available to
the general public.
712
PYROPHORIC. A chemical with an autoignition temperature in air, at or below a
temperature of 130°F (54°C).
PYROTECHNIC ARTICLE. A pyrotechnic device for use in the entertainment industry,
which is not classified as fireworks.
PYROTECHNIC COMPOSITION. A chemical mixture that produces visible light displays
or sounds through a selfpropagating, heat-releasing chemical reaction which is initiated by
ignition.
PYROTECHNIC SPECIAL EFFECT. A visible or audible effect for entertainment created
through the use of pyrotechnic materials and devices.
PYROTECHNIC SPECIAL-EFFECT MATERIAL. A chemical mixture used in the
entertainment industry to produce visible or audible effects by combustion, deflagration or
detonation. Such a chemical mixture predominantly consists of solids capable of producing
a controlled, self-sustaining and self-contained exothermic chemical reaction that results in
heat, gas sound, light or a combination of these effects. The chemical reaction functions without
external oxygen.
PYROTECHNICS. Controlled exothermic chemical reactions timed to create the effects of
heat, hot gas, sound, dispersion of aerosols, emission of visible light or a combination of such
effects to achieve the maximum effect from the least volume of pyrotechnic composition.
QUANTITY-DISTANCE (Q-D). The quantity of explosive material and separation distance
relationships providing protection. These relationships are based on levels of risk considered
acceptable for the stipulated exposures and are tabulated in the appropriate Q-D tables. The
separation distances specified afford less than absolute safety:
Inhabited building distance (IBD). The minimum separation distance between an
operating building or magazine containing explosive materials and an inhabited building
or site boundary.
Intermagazine distance (IMD). The minimum separation distance between magazines.
Intraline distance (ILD) or Intraplant distance (IPD). The distance to be maintained
between any two operating buildings on an explosives manufacturing site when at least
one contains or is designed to contain explosives, or the distance between a magazine and
an operating building.
RAILWAY. A steam, electric or other railroad or railway that carriers passengers for hire.
[BE] RAMP. A walking surface that has a running slope steeper than one unit vertical in 20 units
horizontal (5-percent slope).
RAMP, EXIT ACCESS. See "Exit access ramp."
713
RAMP, EXTERIOR EXIT. See "Exterior exit ramp."
RAMP, INTERIOR EXIT. See "Interior exit ramp."
RAW PRODUCT. A mixture of natural materials such as tree, brush trimmings, or waste logs
and stumps.
[M] READY ACCESS (TO). That which enables a device, appliance or equipment to be directly
reached, without requiring the removal or movement of any panel, door or similar obstruction
[see "Access (to)"].
READY BOX. A weather-resistant container with a selfclosing or automatic-closing cover that
protects fireworks shells from burning debris. Tarpaulins shall not be considered as ready boxes.
[A] RECORD DRAWINGS. Drawings ("as builts") that document the location of all devices,
appliances, wiring, sequences, wiring methods and connections of the components of a fire alarm
system as installed.
RECREATIONAL FIRE. An outdoor fire burning materials other than rubbish where the fuel
being burned is not contained in an incinerator, outdoor fireplace, portable outdoor fireplace,
barbeque grill or barbeque pit and has a total fuel area of 3 feet (914 mm) or less in diameter and
2 feet (610 mm) or less in height for pleasure, religious, ceremonial, cooking, warmth or similar
purposes.
REDUCED FLOW VALVE. A valve equipped with a restricted flow orifice and inserted into a
compressed gas cylinder, portable tank or stationary tank that is designed to reduce the maximum
flow from the valve under full-flow conditions. The maximum flow rate from the valve is
determined with the valve allowed to flow to atmosphere with no other piping or fittings attached.
REFINERY. A plant in which flammable or combustible liquids are produced on a commercial
scale from crude petroleum, natural gasoline or other hydrocarbon sources.
REFRIGERANT. The fluid used for heat transfer in a refrigeration system; the refrigerant absorbs
heat and transfers it at a higher temperature and a higher pressure, usually with a change of
state.
[M] REFRIGERATING (REFRIGERATION) SYSTEM. A combination of interconnected
refrigerant-containing parts constituting one closed refrigerant circuit in which a refrigerant is
circulated for the purpose of extracting heat.
[A] REGISTERED DESIGN PROFESSIONAL. An architect or engineer, registered or
licensed to practice professional architecture or engineering, as defined by the statutory
requirements of the professional registration laws of the state in which the project is to be
constructed.
714
[BG] RELIGIOUS WORSHIP, PLACE OF. A building or portion thereof intended for the
performance of religious services.
REMOTE EMERGENCY SHUTOFF DEVICE. The combination of an operator-carried
signaling device and a mechanism on the tank vehicle. Activation of the remote emergency shutoff
device sends a signal to the tankermounted mechanism and causes fuel flow to cease.
REMOTE SOLVENT RESERVOIR. A liquid solvent container enclosed against evaporative
losses to the atmosphere during periods when the container is not being utilized, except for a
solvent return opening not larger than 16 square inches (10 322 mm²). Such return allows pumpcycled used solvent to drain back into the reservoir from a separate solvent sink or work area.
REMOTELY LOCATED, MANUALLY ACTIVATED SHUTDOWN CONTROL. A
control system that is designed to initiate shutdown of the flow of gases or liquids that is manually
activated from a point located some distance from the delivery system.
REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor
vehicles.
RESIN APPLICATION AREA. An area where reinforced plastics are used to manufacture
products by hand lay-up or spray-fabrication methods.
RESPONSIBLE PERSON. A person trained in the safety and fire safety considerations
concerned with hot work. Responsible for reviewing the sites prior to issuing permits as part of
the hot work permit program and following up as the job progresses.
RETAIL DISPLAY AREA. The area of a Group M occupancy open for the purpose of viewing
or purchasing merchandise offered for sale. Individuals in such establishments are free to circulate
among the items offered for sale which are typically displayed on shelves, racks or the floor.
ROLL COATING. The process of coating, spreading and impregnating fabrics, paper or other
materials as they are passed directly through a tank or trough containing flammable or
combustible liquids, or over the surface of a roller revolving partially submerged in a flammable
or combustible liquid.
RUBBISH (TRASH). Combustible and noncombustible waste materials, including residue from
the burning of coal, wood, coke or other combustible material, paper, rags, cartons, tin cans,
metals, mineral matter, glass crockery, dust and discarded refrigerators, and heating, cooking or
incineratortype appliances.
SAFETY CAN. An approved container of not more than 5gallon (19 L) capacity having a springclosing lid and spout cover so designed that it will relieve internal pressure when subjected to fire
exposure.
SAFETY DATA SHEET (SDS). Information concerning a hazardous material which is prepared
in accordance with the provisions of DOL 29 CFR Part 1910.1200 or in accordance with the
715
provisions of a federally approved state OSHA plan. A document titled as a Material Safety Data
Sheet (MSDS) is equivalent to an SDS for the purposes of this code.
[BE] SCISSOR STAIRWAY. Two interlocking stairways providing two separate paths of
egress located within one exit enclosure.
SECONDARY CONTAINMENT. That level of containment that is external to and separate
from primary containment.
SEED COTTON. See "Cotton."
SEGREGATED. Storage in the same room or inside area, but physically separated by distance
from incompatible materials.
[BF] SELF-CLOSING. As applied to a fire door or other opening, means equipped with an
approved device that will ensure closing after having been opened.
[BE] SELF-LUMINOUS. Illuminated by a self-contained power source, other than batteries,
and operated independently of external power sources.
SELF-PRESERVATION, INCAPABLE OF. See "Incapable of self-preservation."
SELF-SERVICE MOTOR FUEL-DISPENSING FACILITY. That portion of motor fueldispensing facility where liquid motor fuels are dispensed from fixed approved dispensing
equipment into the fuel tanks of motor vehicles by persons other than a motor fuel-dispensing
facility attendant.
SEMICONDUCTOR FABRICATION FACILITY. A building or a portion of a building in
which electrical circuits or devices are created on solid crystalline substances having electrical
conductivity greater than insulators but less than conductors. These circuits or devices are
commonly known as semiconductors.
SERVICE CORRIDOR. A fully enclosed passage used for transporting HPM and purposes other
than required means of egress.
SHELF STORAGE. Storage on shelves less than 30 inches (762 mm) deep with the distance
between shelves not exceeding 3 feet (914 mm) vertically. For other shelving arrangements, see
the requirements for rack storage.
SINGLE-STATION SMOKE ALARM. An assembly incorporating the detector, the control
equipment and the alarm-sounding device in one unit, operated from a power supply either in
the unit or obtained at the point of installation.
[BG] SITE. A parcel of land bounded by a lot line or a designated portion of a public right-of-way.
716
[BG] SITE-FABRICATED STRETCH SYSTEM. A system, fabricated on site and intended
for acoustical, tackable or aesthetic purposes, that is composed of three elements:
1. A frame constructed of plastic, wood, metal or other material used to hold fabric in
place.
2. A core material (infill, with the correct properties for the application).
3. An outside layer, comprised of a textile, fabric or vinyl, that is stretched taut and held
in place by tension or mechanical fasteners via the frame.
SKY LANTERN. An unmanned device with a fuel source that incorporates an open flame in
order to make the device airborne.
[BG] SLEEPING UNIT. A single unit providing rooms or spaces for one or more persons that
includes permanent provisions for sleeping and can include provisions for living, eating and either
sanitation or kitchen facilities but not both. Such rooms and spaces that are also part of a dwelling
unit are not sleeping units.
SMALL ARMS AMMUNITION. A shotgun, rifle or pistol cartridge and any cartridge for
propellant-actuated devices. This definition does not include military ammunition containing
bursting charges or incendiary, trace, spotting or pyrotechnic projectiles.
SMALL ARMS PRIMERS. Small percussion-sensitive explosive charges, encased in a cap, used
to ignite propellant powder.
SMOKE ALARM. A singleor multiple-station alarm responsive to smoke. See also "Singlestation smoke alarm" and "Multiple-station smoke alarm."
[BF] SMOKE BARRIER. A continuous membrane, either vertical or horizontal, such as a wall,
floor, or ceiling assembly, that is designed and constructed to restrict the movement of smoke.
[BG] SMOKE COMPARTMENT. A space within a building enclosed by smoke barriers on all
sides, including the top and bottom.
[BF] SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed
to resist the passage of smoke. The device is installed to operate automatically, controlled by a
smoke detection system, and where required, is capable of being positioned from a fire command
center.
SMOKE DETECTOR. A listed device that senses visible or invisible particles of combustion.
SMOKE PARTITION. A wall assembly that extends from the top of the foundation or floor
below to the underside of the floor or roof sheathing, deck or slab above or to the underside of the
ceiling above where the ceiling membrane is constructed to limit the transfer of smoke.
[BG] SMOKE-DEVELOPED INDEX. A comparative measure, expressed as a dimensionless
number, derived from measurements of smoke obscuration versus time for a material tested in
717
accordance with ASTM E84.
SMOKELESS PROPELLANTS. Solid propellants, commonly referred to as smokeless
powders, used in small arms ammunition, cannons, rockets, propellant-actuated devices and
similar articles.
[BF] SMOKEPROOF ENCLOSURE. An interior exit stairway designed and constructed so
that the movement of the products of combustion produced by a fire occurring in any part of the
building into the enclosure is limited.
[BE] SMOKE-PROTECTED ASSEMBLY SEATING. Seating served by means of egress
that is not subject to smoke accumulation within or under a structure for a specified design time
by means of passive design or by mechanical ventilation.
SOLID. A material that has a melting point and decomposes or sublimes at a temperature greater
than 68°F (20°C).
SOLID BIOFUEL. Densified biomass made in the form of cubiform, polyhedral, polyhydric or
cylindrical units, produced by compressing milled biomass.
SOLID BIOMASS FEEDSTOCK. The basic materials of which solid biofuel is composed,
manufactured or made.
SOLID SHELVING. Shelving that is solid, slatted or of other construction located in racks and
which obstructs sprinkler discharge down into the racks.
SOLVENT DISTILLATION UNIT. An appliance that receives contaminated flammable or
combustible liquids and which distills the contents to remove contaminants and recover the
solvents.
SOLVENT OR LIQUID CLASSIFICATIONS. A method for classifying solvents or liquids
according to the following classes:
Class I solvents. Liquids having a flash point below 100°F (38°C).
Class II solvents. Liquids having a flash point at or above 100°F (38°C) and below 140°F
(60°C).
Class IIIA solvents. Liquids having a flash point at or above 140°F (60°C) and below
200°F (93°C).
Class IIIB solvents. Liquids having a flash point at or above 200°F (93°C).
Class IV solvents. Liquids classified as nonflammable.
718
SPECIAL AMUSEMENT BUILDING. A building that is temporary, permanent or mobile that
contains a device or system that conveys passengers or provides a walkway along, around or
over a course in any direction as a form of amusement arranged so that the egress path is not
readily apparent due to visual or audio distractions or an intentionally confounded egress path,
or is not readily available because of the mode of conveyance through the building or structure.
[A] SPECIAL EXPERT. An individual who has demonstrated qualifications in a specific area,
outside the practice of architecture or engineering, through education, training and experience.
SPECIAL INDUSTRIAL EXPLOSIVE DEVICE. An explosive power pack containing an
explosive charge in the form of a cartridge or construction device. The term includes but is not
limited to explosive rivets, explosive bolts, explosive charges for driving pins or studs, cartridges
for explosive-actuated power tools and charges of explosives used in automotive air bag inflators,
jet tapping of open hearth furnaces and jet perforation of oil well casings.
SPRAY BOOTH. A mechanically ventilated appliance of varying dimensions and construction
provided to enclose or accommodate a spraying operation and to confine and limit the escape of
spray vapor and residue and to exhaust it safely.
SPRAY ROOM. A room designed to accommodate spraying operations, constructed in
accordance with the Puerto Rico Building Code.
SPRAYING SPACE. An area in which dangerous quantities of flammable vapors or combustible
residues, dusts or deposits are present due to the operation of spraying processes. The fire code
official is authorized to define the limits of the spraying space in any specific case.
[BE] STAIR. A change in elevation, consisting of one or more risers.
[BE] STAIRWAY. One or more flights of stairs, either exterior or interior, with the necessary
landings and platforms connecting them, to form a continuous and uninterrupted passage from one
level to another.
STAIRWAY, EXIT ACCESS. See "Exit access stairway."
STAIRWAY, EXTERIOR EXIT. See "Exterior exit stairway."
STAIRWAY, INTERIOR EXIT. See "Interior Exit Stairway."
STAIRWAY, SCISSOR. See "Scissor stairway."
[BE] STAIRWAY, SPIRAL. A stairway having a closed circular form in its plan view with
uniform section-shaped treads attached to and radiating from a minimum-diameter supporting
column.
STANDBY POWER SYSTEM. A source of automatic electric power of a required capacity and
duration to operate required building, hazardous materials or ventilation systems in the event of a
719
failure of the primary power. Standby power systems are required for electrical loads where
interruption of the primary power could create hazards or hamper rescue or fire-fighting
operations.
STANDPIPE, TYPES OF. Standpipe types are as follows:
Automatic dry. A dry standpipe system, normally filled with pressurized air, that is arranged
through the use of a device, such as a dry pipe valve, to admit water into the system piping
automatically upon the opening of a hose valve. The water supply for an automatic dry
standpipe system shall be capable of supplying the system demand.
Automatic wet. A wet standpipe system that has a water supply that is capable of supplying
the system demand automatically.
Manual dry. A dry standpipe system that does not have a permanent water supply attached
to the system. Manual dry standpipe systems require water from a fire department pumper to
be pumped into the system through the fire department connection in order to supply the
system demand.
Manual wet. A wet standpipe system connected to a water supply for the purpose of
maintaining water within the system but which does not have a water supply capable of
delivering the system demand attached to the system. Manual wet standpipe systems require
water from a fire department pumper (or the like) to be pumped into the system in order to
supply the system demand.
Semiautomatic dry. A dry standpipe system that is arranged through the use of a device,
such as a deluge valve, to admit water into the system piping upon activation of a remote
control device located at a hose connection. A remote control activation device shall be
provided at each hose connection. The water supply for a semiautomatic dry standpipe system
shall be capable of supplying the system demand.
STANDPIPE SYSTEM, CLASSES OF. Standpipe system classes are as follows:
Class I system. A system providing 2¹/2 -inch (64 mm) hose connections to supply
water for use by fire departments and those trained in handling heavy fire streams.
Class II system. A system providing 11/2 -inch (38 mm) hose stations to supply water
for use primarily by the building occupants or by the fire department during initial
response.
Class III system. A system providing 11/2 -inch (38 mm) hose stations to supply water
for use by building occupants and 2¹/ -inch (64 mm) hose connections to supply a larger
volume of water for use by fire departments and those trained in handling heavy fire
streams.
720
STATIC PILES. Piles in which processed wood product or solid biomass feedstock is mounded
and is not being turned or moved.
STATIONARY BATTERY ARRAY. An arrangement of individual stationary storage
batteries in close proximity to each other, mounted on storage racks or in modules, battery
cabinets or other enclosures.
STEEL. Hotor cold-rolled as defined by the Puerto Rico Building Code.
STORAGE, HAZARDOUS MATERIALS. The keeping, retention or leaving of hazardous
materials in closed containers, tanks, cylinders, or similar vessels; or vessels supplying operations
through closed connections to the vessel.
[BG] STORY. That portion of a building included between the upper surface of a floor and the
upper surface of the floor or roof next above (see "Basement," "Building height," "Grade plane"
and "Mezzanine"). A story is measured as the vertical distance from top to top of two successive
tiers of beams or finished floor surfaces and, for the topmost story, from the top of the floor finish
to the top of the ceiling joists or, where there is not a ceiling, to the top of the roof rafters.
[BG] STORY ABOVE GRADE PLANE. Any story having its finished floor surface entirely
above grade plane, or in which the finished surface of the floor next above is:
1. More than 6 feet (1829 mm) above grade plane; or
2. More than 12 feet (3658 mm) above the finished ground level at any point.
SUBORDINATE (FIRE PROTECTION AND LIFE SAFETY SYSTEM). A system that is
activated by another fire protection or life safety system. For example, where a fire alarm system
activates a smoke removal or elevator recall system, the smoke removal or elevator recall system
is considered to be "subordinate" to the fire alarm system.
SUPERVISING STATION. A facility that receives signals and at which personnel are in
attendance at all times to respond to these signals.
SUPERVISORY SERVICE. The service required to monitor performance of guard tours and
the operative condition of fixed suppression systems or other systems for the protection of life and
property.
SUPERVISORY SIGNAL. A signal indicating the need of action in connection with the
supervision of guard tours, the fire suppression systems or equipment, or the maintenance features
of related systems.
SUPERVISORY SIGNAL-INITIATING DEVICE. An initiating device such as a valve
supervisory switch, water level indicator, or low-air pressure switch on a dry-pipe sprinkler system
whose change of state signals an off-normal condition and its restoration to normal of a fire
protection or life safety system; or a need for action in connection with guard tours, fire
suppression systems or equipment, or maintenance features of related systems.
721
SYSTEM. An assembly of equipment consisting of a tank, container or containers,
appurtenances, pumps, compressors and connecting piping.
TANK. A vessel containing more than 60 gallons (227 L).
TANK, ATMOSPHERIC. A storage tank designed to operate at pressures from atmospheric
through 1.0 pound per square inch gauge (760 mm Hg through 812 mm Hg) measured at the top
of the tank.
TANK, PORTABLE. A packaging of more than 60-gallon (227 L) capacity and designed
primarily to be loaded into or on or temporarily attached to a transport vehicle or ship and
equipped with skids, mountings or accessories to facilitate handling of the tank by mechanical
means. It does not include any cylinder having less than a 1,000-pound (454 kg) water capacity,
cargo tank, tank car tank or trailers carrying cylinders of more than 1,000-pound (454 kg) water
capacity.
TANK, PRIMARY. A listed atmospheric tank used to store liquid. See "Primary containment."
TANK, PROTECTED ABOVE GROUND. A tank listed in accordance with UL 2085 consisting
of a primary tank provided with protection from physical damage and fire-resistive protection
from a high-intensity liquid pool fire exposure. The tank may provide protection elements as a
unit or may be an assembly of components, or a combination thereof.
TANK, STATIONARY. Packaging designed primarily for stationary installations not intended
for loading, unloading or attachment to a transport vehicle as part of its normal operation in the
process of use. It does not include cylinders having less than a 1,000-pound (454 kg) water
capacity.
TANK VEHICLE. A vehicle other than a railroad tank car or boat, with a cargo tank mounted
thereon or built as an integral part thereof, used for the transportation of flammable or combustible
liquids, LP-gas or hazardous chemicals. Tank vehicles include self-propelled vehicles and full
trailers and semitrailers, with or without motive power, and carrying part or all of the load.
TEMPORARY SPECIAL EVENT STRUCTURE. Any temporary ground-supported structure,
platform, stage, stage scaffolding or rigging, canopy, tower supporting audio or visual effects
equipment or similar structures not regulated within the scope of the Puerto Rico Building Code.
TENT. A structure, enclosure, umbrella structure or shelter, with or without sidewalls or drops,
constructed of fabric or pliable material supported in any manner except by air or the contents it
protects (see "Umbrella structure").
THEFT RESISTANT. Construction designed to deter illegal entry into facilities for the storage
of explosive materials.
[BF] THROUGH-PENETRATION FIRESTOP SYSTEM. An assemblage consisting of a
722
fire-resistance-rated floor, floor-ceiling or wall assembly, one or more penetrating items passing
through the breaches in both sides of the assembly and the materials or devices, or both, installed
to resist the spread of fire through the assembly for a prescribed period of time.
TIMBER AND LUMBER PRODUCTION FACILITIES. Facilities where raw wood products
are processed into finished wood products.
TIRES, BULK STORAGE OF. Storage of tires where the area available for storage exceeds
20,000 cubic feet (566
TOOL. A device, storage container, workstation or process machine used in a fabrication area.
TORCH-APPLIED ROOF SYSTEM. Bituminous roofing systems using membranes that are
adhered by heating with a torch and melting asphalt back coating instead of mopping hot asphalt
for adhesion.
[A] TOWNHOUSE. A single-family dwelling unit constructed in a group of three or more
attached units in which each unit extends from the foundation to roof and with open space on not
less than two sides.
TOXIC. A chemical falling within any of the following categories:
1. A chemical that has a median lethal dose (LD50) of more than 50 milligrams per
kilogram, but not more than 500 milligrams per kilogram of body weight when
administered orally to albino rats weighing between 200 and 300 grams each.
2. A chemical that has a median lethal dose (LD50) of more than 200 milligrams per
kilogram but not more than 1,000 milligrams per kilogram of body weight when
administered by continuous contact for 24 hours (or less if death occurs within 24 hours)
with the bare skin of albino rabbits weighing between 2 and 3 kilograms each.
3. A chemical that has a median lethal concentration (LC50) in air of more than 200 parts
per million but not more than 2,000 parts per million by volume of gas or vapor, or more
than 2 milligrams per liter but not more than 20 milligrams per liter of mist, fume or dust,
when administered by continuous inhalation for 1 hour (or less if death occurs within 1
hour) to albino rats weighing between 200 and 300 grams each.
TRAFFIC CALMING DEVICES. Traffic calming devices are design elements of fire apparatus
access roads such as street alignment, installation of barriers, and other physical measures
intended to reduce traffic and cut-through volumes, and slow vehicle speeds.
[BG] TRANSIENT. Occupancy of a dwelling unit or sleeping unit for not more than 30 days.
[BG] TRANSIENT AIRCRAFT. Aircraft based at another location and that is at the transient
location for not more than 90 days.
TRANSVERSE FLUE SPACE. See "Flue space-Transverse."
723
TRASH. See "Rubbish."
TROUBLE SIGNAL. A signal initiated by the fire alarm system or device indicative of a fault in
a monitored circuit or component.
TUBE TRAILER. A semitrailer on which a number of tubular gas cylinders have been mounted.
A manifold is typically provided that connects the cylinder valves enabling gas to be discharged
from one or more tubes or cylinders through a piping and control system.
TWENTY-FOUR HOUR BASIS. See "24-hour basis" before the "A" entries.
UMBRELLA STRUCTURE. A structure, enclosure or shelter with or without sidewalls or
drops, constructed of fabric or pliable material supported by a central pole or poles (see "Tent").
UNAUTHORIZED DISCHARGE. A release or emission of materials in a manner which does
not conform to the provisions of this code or applicable public health and safety regulations.
UNSTABLE (REACTIVE) MATERIAL. A material, other than an explosive, which in the pure
state or as commercially produced, will vigorously polymerize, decompose, condense or become
self-reactive and undergo other violent chemical changes, including explosion, when exposed to
heat, friction or shock, or in the absence of an inhibitor, or in the presence of contaminants, or in
contact with incompatible materials. Unstable (reactive) materials are subdivided as follows:
Class 4. Materials that in themselves are readily capable of detonation or explosive
decomposition or explosive reaction at normal temperatures and pressures. This class
includes materials that are sensitive to mechanical or localized thermal shock at normal
temperatures and pressures.
Class 3. Materials that in themselves are capable of detonation or of explosive
decomposition or explosive reaction but which require a strong initiating source or which
must be heated under confinement before initiation. This class includes materials that are
sensitive to thermal or mechanical shock at elevated temperatures and pressures.
Class 2. Materials that in themselves are normally unstable and readily undergo violent
chemical change but do not detonate. This class includes materials that can undergo
chemical change with rapid release of energy at normal temperatures and pressures, and
that can undergo violent chemical change at elevated temperatures and pressures.
Class 1. Materials that in themselves are normally stable but which can become unstable
at elevated temperatures and pressure.
UNWANTED FIRE. A fire not used for cooking, heating or recreational purposes or one not
incidental to the normal operations of the property.
USE (MATERIAL). Placing a material into action, including solids, liquids and gases.
724
VAPOR PRESSURE. The pressure exerted by a volatile fluid as determined in accordance with
ASTM D323.
[M] VENTILATION. The natural or mechanical process of supplying conditioned or
unconditioned air to, or removing such air from, any space.
VESSEL. A motorized watercraft, other than a seaplane on the water, used or capable of being
used as a means of transportation. Nontransportation vessels, such as houseboats and boathouses,
are included in this definition.
VISIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the
sense of sight.
WATER MIST SYSTEM, AUTOMATIC. See "Automatic water mist system."
WATER-REACTIVE MATERIAL. A material that explodes; violently reacts; produces
flammable, toxic or other hazardous gases; or evolves enough heat to cause autoignition or
ignition of combustibles upon exposure to water or moisture. Water-reactive materials are
subdivided as follows:
Class 3. Materials that react explosively with water without requiring heat or confinement.
Class 2. Materials that react violently with water or have the ability to boil water. Materials
that produce flammable, toxic or other hazardous gases, or evolve enough heat to cause
autoignition or ignition of combustibles upon exposure to water or moisture.
Class 1. Materials that react with water with some release of energy, but not violently.
WET FUELING. See "Mobile fueling."
WET HOSING. See "Mobile fueling."
WET-CHEMICAL EXTINGUISHING AGENT. A solution of water and potassiumcarbonate-based chemical, potassium-acetate-based chemical or a combination thereof, forming
an extinguishing agent.
WHARF. A structure or bulkhead constructed of wood, stone, concrete or similar material built
at the shore of a harbor, lake or river for vessels to lie alongside of, and to anchor piers or floats.
WILDFIRE RISK AREA. Land that is covered with grass, grain, brush or forest, whether
privately or publicly owned, which is so situated or is of such inaccessible location that a fire
originating upon it would present an abnormally difficult job of suppression or would result in
great or unusual damage through fire or such areas designated by the fire code official.
[BE] WINDER. A tread with nonparallel edges.
725
WIRELESS PROTECTION SYSTEM. A system or a part of a system that can transmit and
receive signals without the aid of wire.
WORKSTATION. A defined space or an independent principal piece of equipment using HPM
within a fabrication area where a specific function, laboratory procedure or research activity
occurs. Approved or listed hazardous materials storage cabinets, flammable liquid storage cabinets
or gas cabinets serving a workstation are included as part of the workstation. A workstation is
allowed to contain ventilation equipment, fire protection devices, detection devices, electrical
devices and other processing and scientific equipment.
[BG] YARD. An open space, other than a court, unobstructed from the ground to the sky, except
where specifically provided by the Puerto Rico Building Code, on the lot on which a building is
situated.
ZONE. A defined area within the protected premises. A zone can define an area from which a
signal can be received, an area to which a signal can be sent or an area in which a form of control
can be executed.
ZONE, NOTIFICATION. An area within a building or facility covered by notification
appliances which are activated simultaneously.
CHAPTER 3 - GENERAL REQUIREMENTS