Regl. 9049, art. 107-202(IFGC)
GENERAL DEFINITIONS
Length: 6,523 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-202(IFGC)
[M]ACCESS (TO). That which enables a device, appliance or equipment to be reached by ready
access or by a means that first requires the removal or movement of a panel, door or similar
obstruction (see also "Ready access").
AIR CONDITIONER, GAS-FIRED. A gas-burning, automatically operated appliance for
supplying cooled air, dehumidified air, or both, or chilled liquid.
[M]AIR CONDITIONING. The treatment of air so as to control simultaneously the temperature,
humidity, cleanness and distribution of the air to meet the requirements of a conditioned space.
[M]AIR, EXHAUST. Air being removed from any space or piece of equipment or appliance and
conveyed directly to the atmosphere by means of openings or ducts.
[M]AIR-HANDLING UNIT. A blower or fan used for the purpose of distributing supply air to a
room, space or area.
[M]AIR, MAKEUP. Any combination of outdoor and transfer air intended to replace exhaust air
and exfiltration.
[AJALTERATION. A change in a system that involves an extension, addition or change to the
arrangement, type or purpose of the original installation.
ANODELESS RISER. A transition assembly in which plastic piping is installed and terminated
above ground outside of a building.
743
[M]APPLIANCE. Any apparatus or device that utilizes a fuel or a raw material as a fuel to
produce light, heat, power, refrigeration or air conditioning. Also, an apparatus that compresses
fuel gases.
APPLIANCE, AUTOMATICALLY CONTROLLED. Appliances equipped with an automatic
burner ignition and safety shutoff device and other automatic devices that accomplish complete
turn-on and shutoff of the gas to the main burner or burners, and graduate the gas supply to the
burner or burners, but do not affect complete shutoff of the gas.
APPLIANCE, FAN-ASSISTED COMBUSTION. An appliance equipped with an integral
mechanical means to either draw or force products of combustion through the combustion chamber
or heat exchanger.
APPLIANCE TYPE.
Low-heat appliance (residential appliance). Any appliance in which the products of
combustion at the point of entrance to the flue under normal operating conditions have a
temperature of 1,000°F (538°C) or less.
Medium-heat appliance. Any appliance in which the products of combustion at the point
of entrance to the flue under normal operating conditions have a temperature of more than
1,000°F (538°C), but not greater than 2,000°F (1093°C).
APPLIANCE, UNVENTED. An appliance designed or installed in such a manner that the
products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere.
[M]APPLIANCE, VENTED. An appliance designed and installed in such a manner that all of
the products of combustion are conveyed directly from the appliance to the outdoor atmosphere
through an approved chimney or vent system.
[AJAPPROVED. Acceptable to the code official.
[A]APPROVED AGENCY. An established and recognized agency that is regularly engaged in
conducting tests, furnishing inspection services or furnishing certification, where such agency has
been approved by the code official.
ATMOSPHERIC PRESSURE. The pressure of the weight of air and water vapor on the surface
of the earth, approximately 14.7 pounds per square inch (psi) (101 kPa absolute) at sea level.
AUTOMATIC IGNITION. Ignition of gas at the burner(s) when the gas controlling device is
turned on, including reignition if the flames on the burner(s) have been extinguished by means
other than by the closing of the gas controlling device.
BAFFLE. An object placed in an appliance to change the direction of or retard the flow of air,
air-gas mixtures or flue gases.
744
BAROMETRIC DRAFT REGULATOR. A balanced damper device attached to a chimney, vent
connector, breeching or flue gas manifold to protect combustion appliances by controlling chimney
draft. A double-acting barometric draft regulator is one whose balancing damper is free to move
in either direction to protect combustion appliances from both excessive draft and backdraft.
BOILER, LOW-PRESSURE. A self-contained appliance for supplying steam or hot water.
Hot water heating boiler. A boiler in which no steam is generated, from which hot water is
circulated for heating purposes and then returned to the boiler, and that operates at water pressures
not exceeding 160 pounds per square inch gauge (psig) (1100 kPa gauge) and at water
temperatures not exceeding 250°F (121°C) at or near the boiler outlet.
Hot water supply boiler. A boiler, completely filled with water, which furnishes hot water to be
used externally to itself, and that operates at water pressures not exceeding 160 psig (1100 kPa
gauge) and at water temperatures not exceeding 250°F (121°C) at or near the boiler outlet.
Steam heating boiler. A boiler in which steam is generated and that operates at a steam pressure
not exceeding 15 psig (100 kPa gauge).
BONDING JUMPER. A conductor installed to electrically connect metallic gas piping to the
grounding electrode system.
[M]BRAZING. A metal-joining process wherein coalescence is produced by the use of a
nonferrous filler metal having a melting point above 1,000°F (538°C), but lower than that of the
base metal being joined. The filler material is distributed between the closely fitted surfaces of the
joint by capillary action.
BROILER. A general term including salamanders, barbecues and other appliances cooking
primarily by radiated heat, excepting toasters.
BTU. Abbreviation for British thermal unit, which is the quantity of heat required to raise the
temperature of 1 pound (454 g) of water 1°F (0.56°C) (1 Btu = 1055 J).
BURNER. A device for the final conveyance of the gas, or a mixture of gas and air, to the
combustion zone.
Induced-draft. A burner that depends on draft induced by a fan that is an integral part of the
appliance and is located downstream from the burner.
Power. A burner in which gas, air or both are supplied at pressures exceeding, for gas, the line
pressure, and for air, atmospheric pressure, with this added pressure being applied at the burner.
[A]BUILDING OFFICIAL. The Auxiliary Secretary of the Permits Management Office of the
Department of Economic Development and Commerce (OGPe-DDEC), or a duly authorized
representative.
745
[M]CHIMNEY. A primarily vertical structure containing one or more flues, for the purpose of
carrying gaseous products of combustion and air from an appliance to the outside atmosphere.
Factory-built chimney. A listed and labeled chimney composed of factory-made components,
assembled in the field in accordance with manufacturer's instructions and the conditions of the
listing.
Masonry chimney. A field-constructed chimney composed of solid masonry units, bricks, stones
or concrete.
Metal chimney. A field-constructed chimney of metal.
[M]CLEARANCE. The minimum distance through air measured between the heat-producing
surface of the mechanical appliance, device or equipment and the surface of the combustible
material or assembly.
CLOTHES DRYER. An appliance used to dry wet laundry by means of heated air. Dryer
classifications are as follows:
Type 1. Factory-built package, multiple production. Primarily used in family living environment.
Usually the smallest unit physically and in function output.
Type 2. Factory-built package, multiple production. Used in business with direct intercourse of
the function with the public. Not designed for use in individual family living environment.
[A]CODE. These regulations, subsequent amendments thereto or any emergency rule or
regulation that the administrative authority having jurisdiction has lawfully adopted.
CODE OFFICIAL. The officer or other designated authority of the government agency having
jurisdiction responsible for the enforcement of the pertaining code, or a duly authorized
representative.
[MJCOMBUSTIBLE ASSEMBLY. Wall, floor, ceiling or other assembly constructed of one or
more component materials that are not defined as noncombustible.
[M]COMBUSTIBLE MATERIAL. Any material not defined as noncombustible.
[M]COMBUSTION. In the context of this code, refers to the rapid oxidation of fuel accompanied
by the production of heat or heat and light.
[M]COMBUSTION AIR. Air necessary for complete combustion of a fuel, including theoretical
air and excess air.
[M]COMBUSTION CHAMBER. The portion of an appliance within which combustion occurs.
746
[M]COMBUSTION PRODUCTS. Constituents resulting from the combustion of a fuel with the
oxygen of the air, including inert gases, but excluding excess air.
[M]CONCEALED LOCATION. A location that cannot be accessed without damaging
permanent parts of the building structure or finish surface. Spaces above, below or behind readily
removable panels or doors shall not be considered as concealed.
CONCEALED PIPING. Piping that is located in a concealed location (see "Concealed
location").
CONDENSATE. The liquid that condenses from a gas (including flue gas) caused by a reduction
in temperature or increase in pressure.
CONNECTOR, APPLIANCE (Fuel). Rigid metallic pipe and fittings, semirigid metallic tubing
and fittings or a listed and labeled device that connects an appliance to the gas piping system.
CONNECTOR, CHIMNEY OR VENT. The pipe that connects an appliance to a chimney or
vent.
[AJCONSTRUCTION DOCUMENTS. All of the written, graphic and pictorial documents
prepared or assembled for describing the design, location and physical characteristics of the
elements of the project necessary for obtaining a mechanical permit.
[M]CONTROL. A manual or automatic device designed to regulate the gas, air, water or electrical
supply to, or operation of, a mechanical system.
CONVERSION BURNER. A unit consisting of a burner and its controls for installation in an
appliance originally utilizing another fuel.
COUNTER APPLIANCES. Appliances such as coffee brewers and coffee urns and any
appurtenant water-heating appliance, food and dish warmers, hot plates, griddles, waffle bakers
and other appliances designed for installation on or in a counter.
CUBIC FOOT. The amount of gas that occupies 1 cubic foot (0.02832 m³) when at a temperature
of 60°F (16°C), saturated with water vapor and under a pressure equivalent to that of 30 inches of
mercury (101 kPa).
[M]DAMPER. A manually or automatically controlled device to regulate draft or the rate of flow
of air or combustion gases.
DECORATIVE APPLIANCE, VENTED. A vented appliance wherein the primary function lies
in the aesthetic effect of the flames.
DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES. A
vented appliance designed for installation within the fire chamber of a vented fireplace, wherein
the primary function lies in the aesthetic effect of the flames.
747
DEMAND. The maximum amount of gas input required per unit of time, usually expressed in
cubic feet per hour, or Btu/h (1 Btu/h = 0.2931 W).
[BS]DESIGN FLOOD ELEVATION. The elevation of the "design flood," including wave
height, relative to the datum specified on the community's legally designated flood hazard map.
In areas designated as Zone AO, the design flood elevation shall be the elevation of the highest
existing grade of the building's perimeter plus the depth number (in feet) specified on the flood
hazard map. In areas designated as Zone AO where a depth number is not specified on the map,
the depth number shall be taken as being equal to 2 feet (610 mm).
DILUTION AIR. Air that is introduced into a draft hood and is mixed with the flue gases.
DIRECT-VENT APPLIANCES. Appliances that are constructed and installed so that all air for
combustion is derived directly from the outdoor atmosphere and all flue gases are discharged
directly to the outdoor atmosphere.
[M]DRAFT. The pressure difference existing between the appliance or any component part and
the atmosphere, that causes a continuous flow of air and products of combustion through the gas
passages of the appliance to the atmosphere.
Mechanical or induced draft. The pressure difference created by the action of a fan,
blower or ejector that is located between the appliance and the chimney or vent
termination.
Natural draft. The pressure difference created by a vent or chimney because of its height, and
the temperature difference between the flue gases and the atmosphere.
DRAFT HOOD. A nonadjustable device built into an appliance, or made as part of the vent
connector from an appliance, that is designed to: provide for ready escape of the flue gases from
the appliance in the event of no draft, backdraft or stoppage beyond the draft hood; prevent a
backdraft from entering the appliance; and neutralize the effect of stack action of the chimney or
gas vent upon operation of the appliance.
DRAFT REGULATOR. A device that functions to maintain a desired draft in the appliance by
automatically reducing the draft to the desired value.
[M]DRIP. The container placed at a low point in a system of piping to collect condensate and
from which the condensate is removable.
DRY GAS. A gas having a moisture and hydrocarbon dew point below any normal temperature
to which the gas piping is exposed.
DUCT FURNACE. A warm-air furnace normally installed in an air distribution duct to supply
warm air for heating. This definition shall apply only to a warm-air heating appliance that depends
for air circulation on a blower not furnished as part of the furnace.
748
[M]DUCT SYSTEM. A continuous passageway for the transmission of air that, in addition to
ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment.
[A]DWELLING UNIT. A single unit providing complete, independent living facilities for one
or more persons, including permanent provisions for living, sleeping, eating, cooking and
sanitation.
EQUIPMENT. Apparatus and devices other than appliances.
EXCESS FLOW VALVE (EFV). A valve designed to activate when the fuel gas passing through
it exceeds a prescribed flow rate.
EXTERIOR MASONRY CHIMNEYS. Masonry chimneys exposed to the outdoors on one or
more sides below the roof line.
[M]FIREPLACE. A fire chamber and hearth constructed of noncombustible material for use
with solid fuels and provided with a chimney.
Factory-built fireplace. A fireplace composed of listed factory-built components
assembled in accordance with the terms of listing to form the completed fireplace.
Masonry fireplace. A hearth and fire chamber of solid masonry units such as bricks, stones, listed
masonry units or reinforced concrete, provided with a suitable chimney.
FIRING VALVE. A valve of the plug and barrel type designed for use with gas, and equipped
with a lever handle for manual operation and a dial to indicate the percentage of opening.
FLAME SAFEGUARD. A device that will automatically shut off the fuel supply to a main
burner or group of burners when the means of ignition of such burners becomes inoperative, and
when flame failure occurs on the burner or group of burners.
FLASHBACK ARRESTOR CHECK VALVE. A device that will prevent the backflow of one
gas into the supply system of another gas and prevent the passage of flame into the gas supply
system.
[BS]FLOOD HAZARD AREA. The greater of the following two areas:
1. The area within a floodplain subject to a 1 percent or greater chance of flooding in any
given year.
2. This area designated as a flood hazard area on a community's flood hazard map, or
otherwise legally designated.
FLOOR FURNACE. A completely self-contained furnace suspended from the floor of the space
being heated, taking air for combustion from outside such space and with means for observing
flames and lighting the appliance from such space.
749
Fan type. A floor furnace equipped with a fan that provides the primary means for circulating air.
Gravity type. A floor furnace depending primarily on circulation of air by gravity. This
classification shall also include floor furnaces equipped with booster-type fans that do not
materially restrict free circulation of air by gravity flow when such fans are not in operation.
FLUE, APPLIANCE. The passage(s) within an appliance through which combustion products
pass from the combustion chamber of the appliance to the draft hood inlet opening on an appliance
equipped with a draft hood or to the outlet of the appliance on an appliance not equipped with a
draft hood.
FLUE COLLAR. That portion of an appliance designed for the attachment of a draft hood, vent
connector or venting system.
FLUE GASES. Products of combustion plus excess air in
appliance flues or heat exchangers.
[M]FLUE LINER (LINING). A system or material used to form the inside surface of a flue in a
chimney or vent, for the purpose of protecting the surrounding structure from the effects of
combustion products and for conveying combustion products without leakage to the atmosphere.
FUEL GAS. A natural gas, manufactured gas, liquefied petroleum gas or mixtures of these gases.
[M]FURNACE. A completely self-contained heating unit that is designed to supply heated air to
spaces remote from or adjacent to the appliance location.
FURNACE, CENTRAL. A self-contained appliance for heating air by transfer of heat of
combustion through metal to
the air, and designed to supply heated air through ducts to spaces remote from or adjacent to the
appliance location.
FURNACE, ENCLOSED. A specific heating, or heating and ventilating, furnace incorporating
an integral total enclosure and using only outside air for combustion.
FURNACE PLENUM. An air compartment or chamber to which one or more ducts are
connected and that forms part of an air distribution system.
GAS CONVENIENCE OUTLET. A permanently mounted, manually operated device that
provides the means for connecting an appliance to, and disconnecting an appliance from, the
supply piping. The device includes an integral, manually operated valve with a non-displaceable
valve member and is designed so that disconnection of an appliance only occurs when the
manually operated valve is in the closed position.
GAS PIPING. An installation of pipe, valves or fittings installed on a premises or in a building
and utilized to convey fuel gas.
750
[F]GASEOUS HYDROGEN SYSTEM. See Section 702.1.
[M]HAZARDOUS LOCATION. Any location considered to be a fire hazard for flammable
vapors, dust, combustible fibers or other highly combustible substances. The location is not
necessarily categorized in the building code as a high hazard group classification.
HOUSE PIPING. See "Piping system."
[F]HYDROGEN FUEL-GAS ROOM. See Section 702.1.
HYDROGEN-GENERATING APPLIANCE. See Section 702.1.
IGNITION PILOT. A pilot that operates during the lighting cycle and discontinues during main
burner operation.
[M]IGNITION SOURCE. A flame, spark or hot surface capable of igniting flammable vapors
or fumes. Such sources include appliance burners, burner ignitors and electrical switching
devices.
INCINERATOR. An appliance used to reduce combustible refuse material to ashes and that is
manufactured, sold and installed as a complete unit.
INDUSTRIAL AIR HEATERS, DIRECT-FIRED NON-RECIRCULATING. A heater in
which all the products of combustion generated by the burners are released into the air stream
being heated. The purpose of the heater is to offset building heat loss by heating only outdoor air.
INDUSTRIAL AIR HEATERS, DIRECT-FIRED RECIRCULATING. A heater in which all
the products of combustion generated by the burners are released into the air stream being heated.
The purpose of the heater is to offset building heat loss by heating outdoor air, and, if applicable,
indoor air.
INFRARED RADIANT HEATER. A heater that directs a substantial amount of its energy
output in the form of infrared radiant energy into the area to be heated. Such heaters are of either
the vented or unvented type.
[M]JOINT, FLANGED. A joint made by bolting together a pair of flanged ends.
[M]JOINT, FLARED. A metal-to-metal compression joint in which a conical spread is made on
the end of a tube that is compressed by a flare nut against a mating flare.
JOINT, MECHANICAL. A general form of gas-tight joints obtained by the joining of metal parts
through a positive-holding mechanical construction, such as a press joint, flanged joint, threaded
joint, flared joint or compression joint.
751
[M]JOINT, PLASTIC ADHESIVE. A joint made in thermoset plastic piping by the use of an
adhesive substance that forms a continuous bond between the mating surfaces without dissolving
either one of them.
[M]JOINT, PLASTIC HEAT FUSION. A joint made in thermoplastic piping by heating the
parts sufficiently to permit fusion of the materials when the parts are pressed together.
(JOINT REGULATION) JOINT PERMITS REGULATIONS FOR THE EVALUATION
AND ISSUANCE OF PERMITS RELATED TO DEVELOPMENT, LAND USE AND
BUSINESS OPERATION. As defined in the "Reglamento Conjunto de Permisos para Obras de
Construcción y Uso de Terrenos de Puerto Rico, (Reglamento Conjunto)" as established by the
Act No. 161 of December 1, 2009, "Ley para la Reforma del Proceso de Permisos de Puerto Rico,
as amended".
[M]JOINT, WELDED. A gas-tight joint obtained by the joining of metal parts in molten state.
[A]LABELED. Equipment, materials or products to which have been affixed a label, seal, symbol
or other identifying mark of a nationally recognized testing laboratory, approved agency or other
organization concerned with product evaluation that maintains periodic inspection of the
production of the above-labeled items and whose labeling indicates either that the equipment,
material or product meets identified standards or has been tested and found suitable for a specified
purpose.
LEAK CHECK. An operation performed on a gas piping system to verify that the system does
not leak.
LIMIT CONTROL. A device responsive to changes in pressure, temperature or level for turning
on, shutting off or throttling the gas supply to an appliance.
LIQUEFIED PETROLEUM GAS or LPG (LP-GAS). Liquefied petroleum gas composed
predominately of propane, propylene, butanes or butylenes, or mixtures thereof that is gaseous
under normal atmospheric conditions, but is capable of being liquefied under moderate pressure
at normal temperatures.
[A]LISTED. Equipment, materials, products or services included in a list published by an
organization acceptable to the code official and concerned with evaluation of products or services
that maintains periodic inspection of production of listed equipment or materials or periodic
evaluation of services and whose listing states either that the equipment, material, product or
service meets identified standards or has been tested and found suitable for a specified purpose.
[M]LIVING SPACE. Space within a dwelling unit utilized for living, sleeping, eating, cooking,
bathing, washing and sanitation purposes.
LOG LIGHTER. A manually operated solid fuel ignition appliance for installation in a vented
solid fuel-burning fireplace.
752
LUBRICATED PLUG-TYPE VALVE. A valve of theplug and barrel type provided with means
for maintaining a lubricant between the bearing surfaces.
MAIN BURNER. A device or group of devices essentially forming an integral unit for the final
conveyance of gas or a mixture of gas and air to the combustion zone, and on which combustion
takes place to accomplish the function for which the appliance is designed.
METER. The instrument installed to measure the volume of gas delivered through it.
MODULATING. Modulating or throttling is the action of a control from its maximum to
minimum position in either predetermined steps or increments of movement as caused by its
actuating medium.
[M]NONCOMBUSTIBLE MATERIALS. Materials that, where tested in accordance with
ASTM E136, have not fewer than three of four specimens tested meeting all of the following
criteria:
1. The recorded temperature of the surface and interior thermocouples shall not at any
time during the test rise more than 54°F (30°C) above the furnace temperature at the
beginning of the test.
2. There shall not be flaming from the specimen after the first 30 seconds.
3. If the weight loss of the specimen during testing exceeds 50 percent, the recorded
temperature of the surface and interior thermocouples shall not at any time during the
test rise above the furnace air temperature at the beginning of the test, and there shall
not be flaming of the specimen.
[AJOCCUPANCY. The purpose for which a building, or portion thereof, is utilized or occupied.
[M]OFFSET (VENT). A combination of approved bends that makes two changes in direction
bringing one section of the vent out of line but into a line parallel with the other section.
(OGPe-DDEC) Permits Management Office: As defined in the Act 141, of July 10, 2018, "Ley
de Ejecución del Plan de Reorganización del Departamento de Desarrollo Económico y
Comercio".
ORIFICE. The opening in a cap, spud or other device whereby the flow of gas is limited and
through which the gas is discharged to the burner.
OUTLET. The point at which a gas-fired appliance connects to the gas piping system.
OXYGEN DEPLETION SAFETY SHUTOFF SYSTEM(ODS). A system designed to act to
shut off the gas supply to the main and pilot burners if the oxygen in the surrounding atmosphere
is reduced below a predetermined level.
PILOT. A small flame that is utilized to ignite the gas at the main burner or burners.
753
[M]PIPING. Where used in this code, "piping" refers to either pipe or tubing, or both.
Pipe. A rigid conduit of iron, steel, copper, copper-alloy or plastic.
Tubing. Semirigid conduit of copper, copper-alloy aluminum, plastic or steel.
PIPING SYSTEM. The fuel piping, valves and fittings from the outlet of the point of delivery to
the outlets of the appliance shutoff valves.
[M]PLASTIC, THERMOPLASTIC. A plastic that is capable of being repeatedly softened by
increase of temperature and hardened by decrease of temperature.
POINT OF DELIVERY. For natural gas systems, the point of delivery is the outlet of the service
meter assembly or the outlet of the service regulator or service shutoff valve where a meter is not
provided. Where a valve is provided at the outlet of the service meter assembly, such valve shall
be considered to be downstream of the point of delivery. For undiluted liquefied petroleum gas
systems, the point of delivery shall be considered to be the outlet of the service pressure regulator,
exclusive of line gas regulators, in the system.
PORTABLE FUEL CELL APPLIANCE. A fuel cell generator of electricity, which is not fixed
in place. A portable fuel cell appliance utilizes a cord and plug connection to a grid-isolated load
and has an integral fuel supply.
PRESSURE DROP. The loss in pressure due to friction or obstruction in pipes, valves, fittings,
regulators and burners.
PRESSURE TEST. An operation performed to verify the gas-tight integrity of gas piping
following its installation or modification.
(PRPB) PUERTO RICO PLANNING BOARD. Government Agency created by ACT No. 75
of June 1975 as amended, hereinafter PRPB. In addition, it is the State Agency Coordinator of
the National Flood Insurance Program.
PURGE. To free a gas conduit of air or gas, or a mixture of gas and air.
QUICK-DISCONNECT DEVICE. A hand-operated device that provides a means for
connecting and disconnecting an appliance or an appliance connector to a gas supply and that is
equipped with an automatic means to shut off the gas supply when the device is disconnected.
[M]READY ACCESS (TO). That which enables a device, appliance or equipment to be directly
reached, without requiring the removal or movement of any panel, door or similar obstruction (see
"Access").
REGISTERED DESIGN PROFESSIONAL. An individual who is licensed to practice the
profession of architect or engineer as defined by the provisions of the Act No. 173 of August 12,
1988, as amended, and according to with the provisions of Act No. 135 of June 15, 1967, as
754
amended, (Certification Law); engaged by the owner to prepare the construction documents,
make application to the building official and obtain the required permit.
REGULATOR. A device for controlling and maintaining a uniform supply pressure, either
pounds-to-inches water column (MP regulator) or inches-to-inches water column (appliance
regulator).
REGULATOR, GAS APPLIANCE. A pressure regulator for controlling pressure to the
manifold of the appliance.
REGULATOR, LINE GAS PRESSURE. A device placed in a gas line between the service
pressure regulator and the appliance for controlling, maintaining or reducing the pressure in that
portion of the piping system downstream of the device.
REGULATOR, MEDIUM-PRESSURE (MP Regulator). A line pressure regulator that reduces
gas pressure from the range of greater than 0.5 psig (3.4 kPa) and less than or equal to 5 psig (34.5
kPa) to a lower pressure.
REGULATOR, MONITORING. A pressure regulator set in series with another pressure
regulator for the purpose of automatically taking control of the pressure downstream of the
monitored regulator when that pressure exceeds a set minimum.
REGULATOR, PRESSURE. A device placed in a gas line for reducing, controlling and
maintaining the pressure in that portion of the piping system downstream of the device.
REGULATOR, SERIES. A pressure regulator in series with one or more other pressure
regulators.
REGULATOR, SERVICE PRESSURE. For natural gas systems, a device installed by the
serving gas supplier to reduce and limit the service line pressure to delivery pressure. For undiluted
liquefied petroleum gas systems, the regulator located upstream from all line gas pressure
regulators, where installed, and downstream from any first stage or a high pressure regulator in
the system.
RELIEF OPENING. The opening provided in a draft hood to permit the ready escape to the
atmosphere of the flue products from the draft hood in the event of no draft, back draft or stoppage
beyond the draft hood, and to permit air into the draft hood in the event of a strong chimney
updraft.
RELIEF VALVE (DEVICE). A safety valve designed to forestall the development of a
dangerous condition by relieving either pressure, temperature or vacuum in the hot water supply
system.
RELIEF VALVE, PRESSURE. An automatic valve that opens and closes a relief vent,
depending on whether the pressure is above or below a predetermined value.
755
RELIEF VALVE, TEMPERATURE.
Manual reset type. A valve that automatically opens a relief vent at a predetermined temperature
and that must be manually returned to the closed position.
Reseating or self-closing type. An automatic valve that opens and closes a relief vent, depending
on whether the temperature is above or below a predetermined value.
RELIEF VALVE, VACUUM. A valve that automatically opens and closes a vent for relieving
a vacuum within the hot water supply system, depending on whether the vacuum is above or below
a predetermined value.
RISER, GAS. A vertical pipe supplying fuel gas.
ROOM HEATER, UNVENTED. See "Unvented room heater."
ROOM HEATER, VENTED. A free-standing heating unit used for direct heating of the space
in and adjacent to that in which the unit is located (see "Vented room heater").
SAFETY SHUTOFF DEVICE. See "Flame safeguard."
[BF]SHAFT. An enclosed space extending through one or more stories of a building, connecting
vertical openings in successive floors, or floors and the roof.
[A]SLEEPING UNIT. A room or space in which people sleep, which can also include permanent
provisions for living, eating and either sanitation or kitchen facilities, but not both. Such rooms
and spaces that are also part of a dwelling unit are not sleeping units.
SPECIFIC GRAVITY. As applied to gas, specific gravity is the ratio of the weight of a given
volume to that of the same volume of air, both measured under the same condition.
STATIONARY FUEL CELL POWER PLANT. A self-contained package or factory-matched
packages that constitute an automatically operated assembly of integrated systems for generating
electrical energy and recoverable thermal energy that is permanently connected and fixed in place.
THERMOSTAT.
Electric switch type. A device that senses changes in temperature and controls electrically,
by means of separate components, the flow of gas to the burner(s) to maintain selected
temperatures.
[P]THIRD-PARTY CERTIFICATION AGENCY. An approved agency operating a product or
material certification system that incorporates initial product testing, assessment and surveillance
of a manufacturer's quality control system.
[PJTHIRD-PARTY CERTIFIED. Certification obtained by the manufacturer indicating that the
function and performance characteristics of a product or material have been determined by testing
756
and ongoing surveillance by an approved third-party certification agency. Assertion of
certification is in the form of identification in accordance with the requirements of the third-party
certification agency.
[PJTHIRD-PARTY TESTED. Procedure by which an approved testing laboratory provides
documentation that a product, material or system conforms to specified requirements.
TOILET, GAS-FIRED. A packaged and completely assembled appliance containing a toilet that
incinerates refuse instead of flushing it away with water.
[MJTRANSITION FITTINGS, PLASTIC TO STEEL. An adapter for joining plastic pipe to
steel pipe. The purpose of this fitting is to provide a permanent, pressure-tight connection between
two materials that cannot be joined directly one to another.
UNIT HEATER. A self-contained, automatically controlled, vented, fuel-gas-burning, spaceheating appliance, intended for installation in the space to be heated without the use of ducts, and
having integral means for circulation of air.
UNLISTED BOILER. A boiler not listed by a nationally recognized testing agency.
UNVENTED ROOM HEATER. An unvented heating appliance designed for stationary
installation and utilized to provide comfort heating. Such appliances provide radiant heat or
convection heat by gravity or fan circulation directly from the heater and do not utilize ducts.
VALVE. A device used in piping to control the gas supply to any section of a system of piping or
to an appliance.
Appliance shutoff. A valve located in the piping system, used to isolate individual appliances for
purposes such as service or replacement.
Automatic. An automatic or semiautomatic device consisting essentially of a valve and operator
that control the gas supply to the burner(s) during operation of an appliance. The operator shall
be actuated by application of gas pressure on a flexible diaphragm, by electrical means, by
mechanical means, or by other approved means.
Automatic gas shutoff. A valve used in conjunction with an automatic gas shutoff device to shut
off the gas supply to a water-heating system. It shall be constructed integrally with the gas shutoff
device or shall be a separate assembly.
Individual main burner. A valve that controls the gas supply to an individual main burner.
Main burner control. A valve that controls the gas supply to the main burner manifold.
Manual main gas-control. A manually operated valve in the gas line for the purpose of
completely turning on or shutting off the gas supply to the appliance, except to pilot or pilots that
are provided with independent shutoff.
757
Manual reset. An automatic shutoff valve installed in the gas supply piping and set to shut off
when unsafe conditions occur. The device remains closed until manually reopened.
Service shutoff. A valve, installed by the serving gas supplier between the service meter or source
of supply and the customer piping system, to shut off the entire piping system.
VENT. A pipe or other conduit composed of factory-made components, containing a passageway
for conveying combustion products and air to the atmosphere, listed and labeled for use with a
specific type or class of appliance.
Special gas vent. A vent listed and labeled for use with listed Category II, III and IV
appliances.
Type B vent. A vent listed and labeled for use with appliances with draft hoods and other
Category I appliances that are listed for use with Type B vents.
Type BW vent. A vent listed and labeled for use with wall furnaces.
Type L vent. A vent listed and labeled for use with appliances that are listed for use with
Type L or Type B vents.
VENT CONNECTOR. See "Connector."
VENT GASES. Products of combustion from appliances plus excess air plus dilution air in the
vent connector, gas vent or chimney above the draft hood or draft regulator.
VENT PIPING.
Breather. Piping run from a pressure-regulating device to the outdoors, designed to
provide a reference to atmospheric pressure. If the device incorporates an integral pressure
relief mechanism, a breather vent can also serve as a relief vent.
Relief. Piping run from a pressure-regulating or pressure-limiting device to the outdoors,
100484719
designed to provide for the safe venting of gas in the event of excessive pressure in the gas
piping system.
VENTED APPLIANCE CATEGORIES. Appliances that are categorized for the purpose of vent
selection are classified into the following four categories:
Category I. An appliance that operates with a nonpositive vent static pressure and with a vent gas
temperature that avoids excessive condensate production in the vent.
Category II. An appliance that operates with a nonpositive vent static pressure and with a vent
gas temperature that is capable of causing excessive condensate production in the vent.
758
Category III. An appliance that operates with a positive vent static pressure and with a vent gas
temperature that avoids excessive condensate production in the vent.
Category IV. An appliance that operates with a positive vent static pressure and with a vent gas
temperature that is capable of causing excessive condensate production in the vent.
VENTED ROOM HEATER. A vented self-contained, freestanding, non-recessed appliance for
furnishing warm air to the space in which it is installed, directly from the heater without duct
connections.
VENTED WALL FURNACE. A self-contained vented appliance complete with grilles or
equivalent, designed for incorporation in or permanent attachment to the structure of a building,
mobile home or travel trailer, and furnishing heated air circulated by gravity or by a fan directly
into the space to be heated through openings in the casing. This definition shall exclude floor
furnaces, unit heaters and central furnaces as herein defined.
VENTING SYSTEM. A continuous open passageway from the flue collar or draft hood of an
appliance to the outdoor atmosphere for the purpose of removing flue or vent gases. A venting
system is usually composed of a vent or a chimney and vent connector, if used, assembled to form
the open passageway.
Forced-draft venting system. A portion of a venting system using a fan or other mechanical
means to cause the removal of flue or vent gases under positive static vent pressure.
Induced draft venting system. A portion of a venting system using a fan or other mechanical
means to cause the removal of flue or vent gases under nonpositive static vent pressure.
Mechanical draft venting system. A venting system designed to remove flue or vent gases by
mechanical means, that consists of an induced draft portion under nonpositive static pressure or a
forced draft portion under positive static pressure.
Natural draft venting system. A venting system designed to remove flue or vent gases under
nonpositive static vent pressure entirely by natural draft.
WALL HEATER, UNVENTED-TYPE. A room heater of the type designed for insertion in or
attachment to a wall or partition. Such heater does not incorporate concealed venting arrangements
in its construction and discharges all products of combustion through the front into the room being
heated.
[M]WATER HEATER. Any heating appliance or equipment that heats potable water and
supplies such water to the potable hot water distribution system
CHAPTER 3 - GENERAL REGULATIONS
No amendments
759
CHAPTER 4 - GAS PIPING INSTALLATIONS.
No amendments
CHAPTER 5 - CHIMNEYS AND VENTS
No amendments
CHAPTER 6 - SPECIFIC APPLIANCES
No amendments
CHAPTER 7 - GASEOUS HYDROGEN SYSTEMS
No amendments
CHAPTER 8 - REFERENCED STANDARDS
No amendments
APPENDIX A - SIZING AND CAPACITIES OF GAS PIPING
(IFGS)
No amendments
APPENDIX B - SIZING OF VENTING SYSTEMS SERVING
APPLIANCES EQUIPPED WITH DRAFT HOODS, CATEGORY
I APPLIANCES AND APPLIANCES LISTED FOR USE WITH
TYPE B VENTS (IFGS)
No amendments
APPENDIX C - EXIT TERMINALS OF MECHANICAL DRAFT
AND DIRECT-VENT VENTING SYSTEMS (IFGS)
No amendments
APPENDIX D - RECOMMENDED PROCEDURE FOR SAFETY
INSPECTION OF AN EXISTING APPLIANCE INSTALLATION
(IFGS)
No amendments
760
761
PUERTO RICO CODES
PRECC
Puerto Rico Energy Conservation Code
FRENCIA
OEDU
OF
PUERTO RICO ENERGY CONSERVATION CODE 2018
As amended from
INTERNATIONAL ENERGY CONSERVATION CODE 2018
"These AMENDMENTS to the 2018 INTERNATIONAL ENERGY CONSERVATION CODE
contain copyrighted material from the 2018 International Energy Conservation Code, which is a
copyrighted work owned by the International Code Council, Inc. Without advance written
permission from the copyright owner, no part of this book may be reproduced, distributed, or
transmitted in any form or by any means, including, without limitation, electronic, optical or
mechanical means (by way of example and not limitation, photocopying, or recording by or in an
information storage retrieval system). For information on permission to copy material exceeding
fair use, please contact: Publications, 4051 West Flossmoor Road, Country Club Hills, IL 60478-
5771. Phone 1-888-ICC-SAFE (422-7233). Trademarks: "International Code Council," the
"International Code Council" logo and the "International Mechanical Code" are trademarks of the
International Code Council, Inc."
763
764
CHAPTER 1 [CE] - SCOPE AND ADMINISTRATION
PART 1 - SCOPE AND APPLICATION