Regl. 9049, art. 107-3111
SOLAR ENERGY SYSTEMS
Length: 3,511 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-3111
3111.3 Photovoltaic solar energy systems. Photovoltaic solar energy systems shall be designed
and installed in accordance with this section, the Puerto Rico Fire Code, NFPA 70, the Puerto
Rico Electric Power Authority's Reglamento Complementario al Código Eléctrico Nacional
(Complementary Code), either the Reglamento para Interconectar Generadores con el Sistema de
Distribución Eléctrica de la Autoridad de Energía Eléctrica y Participar en los Programas de
Medición Neta (Regulation 8915) or the Reglamento para Interconectar Generadores con el
Sistema de Transmisión Eléctrica de la Autoridad de Energía Eléctrica y Participar en los
Programas de Medición Neta (Regulation 8916), as applicable, and the manufacturer's installation
instructions.
3111.3.1 Equipment. Photovoltaic panels and modules shall be listed and labeled in
accordance with UL 1703. Inverters shall comply with IEEE 1547 and be listed and labeled in
accordance with UL 1741. Systems connected to the utility grid shall use inverters listed for
utility interaction. Photovoltaic panels, modules and inverters shall be approved and certified
by the Authority having Jurisdiction.
CHAPTER 32 - ENCROACHMENTS INTO THE PUBLIC
RIGHT-OF-WAY
No amendments.
CHAPTER 33 - SAFEGUARDS DURING CONSTRUCTION
No amendments.
CHAPTER 34 - RESERVED
CHAPTER 35 - REFERENCED STANDARDS
PRASA
Puerto Rico Aqueduct and Sewer Authority
PO BOX 7066
SAN JUAN, PR 00916 7066
3149-1984: Reglamento de Normas de Diseño (Complementary Code)
PREPA
Puerto Rico Power Authority
PO Box 364267
San Juan, PR 00936-4267
5676-1997: Reglamento Complementario al Código Eléctrico Nacional (Complementary Code)
[A]108.3, 406.2.9, 2701.1, 3111.3
149
8915-2017: Reglamento para Interconectar Generadores con el Sistema de Distribución Eléctrica
de la Autoridad de Energia Eléctrica y Participar en los Programas de Medición Neta
3111.3
8916-2017: Reglamento para Interconectar Generadores con el Sistema de Transmisión Eléctrica
de la Autoridad de Energía Eléctrica y Participar en los Programas de Medición Neta
3111.3
JCA
Puerto Rico Environmental Quality Board
Apartado 11488
Santurce, PR 00910
8786-2016: Reglamento para el Control y la Prevención de la Contaminación Lumínica
[E]1302.1
APPENDIX A - EMPLOYEE QUALIFICATIONS
No amendments.
APPENDIX B - BOARD OF APPEALS
No amendments.
APPENDIX C - GROUP U - AGRICULTURAL BUILDINGS
No amendments.
APPENDIX D - FIRE DISTRICTS
No amendments.
APPENDIX E - SUPPLEMENTARY ACCESSIBILITY
REQUIREMENTS
No amendments.
APPENDIX F - RODENTPROOFING
No amendments.
APPENDIX G - FLOOD-RESISTANT CONSTRUCTION
SECTION G105 - VARIANCES
G105.3 Historic structures. A variance is authorized to be issued for the repair or rehabilitation
of a historic structure upon a determination that the proposed repair or rehabilitation will not
150
preclude the structure's continued designation as a historic structure, and the variance is the
minimum necessary to preserve the historic character and design of the structure.
Exception: Within flood hazard areas, historic structures or properties that do not meet one
or more of the following designations:
1. Listed or preliminarily determined to be eligible for listing in the National Register of
Historic Places.
2. Determined by the Secretary of the U.S. Department of Interior, Puerto Rico Planning
Board in the Register of Historic Places and Zones, Board of Directors of the Institute
of Puerto Rican Culture, and the Puerto Rico Legislative Assembly, as contributing to
the historical significance of a registered historic district or zone or a district
preliminarily determined to qualify as an historic district or zone.
3. Designated as historic or having historic significance under applicable state or law,
ordinance or resolution.
APPENDIX H - SIGNS
No amendments.
APPENDIX I - PATIO COVERS
No amendments.
APPENDIX J - GRADING
No amendments.
APPENDIX K - ADMINISTRATIVE PROVISIONS
No amendments.
APPENDIX L - EARTHQUAKE RECORDING
INSTRUMENTATION
No amendments.
APPENDIX M - TSUNAMI-GENERATED FLOOD HAZARD
No amendments.
APPENDIX N - REPLICABLE BUILDINGS
SECTION N103 - REPLICABLE DESIGN REQUIREMENTS
N103.1 Prototypical construction documents. A replicable design shall establish prototypical
construction documents for application at multiple locations. The construction documents shall
include details appropriate to each wind region, seismic design category, Special Flood Hazard
Area (SFHA), and climate zone for locations in which the replicable design is intended for
151
application. Application of replicable design shall not vary with regard to the following, except for
allowable variations in accordance with Section N106.
1. Use and occupancy classification.
2. Building heights and area limitations.
3. Type of construction classification.
4. Fire-resistance ratings.
5. Interior finishes.
6. Fire protection system.
7. Means of egress.
8. Accessibility.
9. Structural design criteria.
10. Energy efficiency.
11. Type of mechanical and electrical systems.
12. Type of plumbing system and number of fixtures.
13. Special Flood Hazard Area (SFHA).
N104.1.2 Structural plans, specifications and engineering details. Where approval of the
structural requirements of the replicable design is sought, the submittal documents shall include
details for each wind region, seismic design category, Special Flood Hazard Area (SFHA), and
climate zone for which approval is sought; and shall include the following:
1. Signed and sealed structural design calculations that support the member sizes on the
drawings.
2. Design load criteria, including: frost depth, live loads, snow loads, flood loads, wind
loads, earthquake design date, and other special loads.
3. Details of foundations and superstructure.
4. Provisions for special inspections.
APPENDIX O - ALTERNATE STRUCTURAL PROVISIONS FOR
ONE AND TWO STORY BUILDINGS ONE AND TWO STORIES
BUILDING CONSTRUCTION
SECTION O101 - APPLICABILITY AND SCOPE
0101.1 General. The structural design and construction of new qualified one and two story
reinforced concrete buildings can be performed in accordance with these alternate provisions, as
an alternate to those included in the 2018 Puerto Rico Building Code (IBC 2018) and the Puerto
Rico Residential Code 2018. For additions or modifications of existing structures, follow the
Puerto Rico Existing Building Code 2018. A qualified building shall meet the requirements set
forth in this section as follows:
152
1. The building consists of a reinforced concrete structure with or without concrete block infill
walls. The floor area of each story shall not exceed five thousand (5,000) square feet and
any story level shall not exceed 12 feet in height.
2. The building shall have a nearly symmetrical plan configuration in both principal directions.
The distance between the center of mass and the center of rigidity of the building shall not
exceed five (5) percent of the plan dimension measured normal to the direction of the load.
3. All reinforced concrete structural elements supporting vertical and lateral loads shall be castin-place.
4. A lateral force resisting system (LFRS), consisting of moment frames or shear walls or a
combination of both, shall be provided in both principal directions of the building. The outof-plane stiffness of the walls shall not be considered as part of the LFRS.
5. All vertical structural elements shall be continuous down to the foundation, with no
horizontal offset and no reduction in sectional area. Rigid structural systems on the second
level, like reinforced concrete or concrete block shear walls that are supported by frame
systems on the first level, shall be identified as a soft story at the first level and shall not
be allowed.
6. The maximum difference in base elevation between adjacent footings shall not exceed
twelve (12) inches. Additionally, the final grading elevation around the building shall not
exceed three (3) feet above the ground slab elevation.
7. The second-floor slab area shall not exceed that of the ground floor, except that for balconies
or overhangs the second-floor slabs are permitted up to six (6) feet from the faces of the
four façades of the building, but not larger than 1/3 of the adjacent interior span.
8. The resulting design seismic base shear, calculated as per these alternate provisions, shall
not be reduced due to ductility considerations.
9. These provisions shall apply only to buildings with Occupancy Category I and II as defined
in Table O102.2 or Table 1604.5 (IBC 2018) (Minimum Design Loads for Buildings and
Other Structures). The qualified buildings shall not have an Importance Factor greater than
1.0.
SECTION O102 - DESIGN LOADS
O102.1. Permanent Loads. Dead, fixed and permanent loads used for the design shall be as per
the IBC 2018 provisions.
O102.2. Live Loads: Design live loads shall be as per the IBC 2018 provisions or PRBC-2018
amendments.
O102.3. Lateral Forces. The general provisions for the calculation of the design lateral loads shall
be as per this section.
0102.3.1. Hurricane Wind Loads:
0102.3.1.1. General. All buildings and their components, and accessories and their
attachments subject to wind loads, shall be designed to withstand the pressures and meet
the requirements of this section. Building components, such as windows, panels, doors,
153
roof equipment, antennas and the architectural features exposed to the wind shall be
designed for the wind loads specified. The wind shall be assumed as approaching the
structure from any horizontal direction. Reductions on the design wind pressures shall not
be permitted. Reductions in load associated with protection or shielding provided by
adjacent structures shall not be permitted. However, the calculated capacity of the
components may be increased by a factor of 1.3 to account for the short duration of the
wind loads.
0102.3.1.2. Basic wind speed. Wind pressures listed in this section are based on a wind
speed of three (3) seconds gust criteria, as defined by the ASCE 7 design standard. Design
wind pressures as per this section are unfactored service loads.
0102.3.1.3. Design wind pressure. The net wind pressure, at strength load condition,
acting on the main wind force resisting system shall not be less than 54 psf, acting normal
to both the windward (positive pressure) and leeward (negative pressure) façades of the
building, concurrently with a roof vertical pressure of 54 psf acting on the roof upward or
42 psf acting on the roof downward. The two load cases specified above shall be considered
separately and the structural element shall be designed for the larger load combination. The
total shear force induced by wind shall be calculated based on these criteria.
O102.3.1.4. Components and Cladding - The wind pressures acting on any structural or
non-structural component or cladding element shall not be less than those listed on Table
I. Designer shall refer to ASCE 7 standard, to obtain the design wind pressures for those
components not listed in this section. Wall edge zones shall be defined as the portion of
the wall located within a distance of ten (10) feet measured horizontally from the corners
of the building.
154
Table O102.1: Design Wind Pressures for Components and Cladding
DESIGN pressure NORMAL to surface
TYPE OF Component and Cladding
(IN psf)
Wall components and their connections to
90 (inward or outward) at edge zone and
LFRS, including, but not limited to,
65 (inward or outward) elsewhere
structural members, concrete block walls,
exterior wall panels, doors, windows,
permanent terrace covers and nonretractable shade curtains and all exterior
architectural components, All Roof
structure components.
All equipment and components supported
90 (acting in any direction)
by the roof including, but not limited to,
54 (acting upward and downward)
solar water heaters, solar panels, water
cisterns, A/C units, equipment, and
associated conduit and ductwork and all
attachments. Also, skylights, ventilation
and extraction fans and all their
attachments.
All parapets or extension of wall elements
90 (acting inward, outward or upward
above roof elevation.
Roof membranes installed for
90 (acting inward or outward)
impermeabilization and climate control
110 (acting upward) at edge zones and
purposes.
flashings and 65 (acting upward) elsewhere
O102.3.2 Earthquake Loads:
0102.3.2.1 General. All qualified buildings and all their components shall be designed to
meet the seismic requirements of this section.
0102.3.2.2 Seismic loads. The design horizontal seismic force shall be applied at the level
of each story and located at a distance of plus or minus five (5) percent of the maximum
plan dimension normal to the direction of the load from the center of rigidity of each story.
This distance shall be considered the accidental eccentricity. The seismic load need not be
applied concurrently along both principal directions of the building. For all non-structural
components, the design seismic force shall be applied at their center of mass. The seismic
forces calculated as per these alternate provisions are factored loads based on the elastic
structural behavior and shall not be reduced to account for any ductility considerations.
155
0102.3.2.3 Minimum design seismic force. The design seismic load shall not be less than
that calculated by the following formula:
Vᵤ = 0.50W
where;
W = Total weight of the structure including all structural and non-structural components,
equipment and any other permanent attachment to the structure that modifies the inertial
properties of the structure.
Vᵤ = Total horizontal base shear force at factored level.
For one story structures, the total base shear, Vu, shall be applied to the roof level. For two
story structures, Vu shall be applied in equal proportions to the first and roof levels.
0102.3.2.4 Horizontal Distribution of Seismic Force. The total shear force applied at each
level shall be distributed among all components of the LFRS in proportion to their relative
stiffness. The floor and roof slabs shall be used as horizontal rigid diaphragms. Slabs
thickness shall not be less than four (4) inches and shall be cast-in-place without horizontal
construction joints.
O102.3.2.5 Minimum horizontal design seismic forces on nonstructural components: All
non-structural components and their attachments to the principal structure shall be designed
to withstand as a minimum, the lateral loads calculated in accordance with the following
formula:
Fₚ = 0.60Wₚ
where,
Wₚ = Total weight of the non-structural components or equipment.
Fₚ = Total design horizontal seismic force at factored level.
O102.4. Load Combinations: The required strength of the structure and all its components shall
be determined from the Load and Resistance Factor Design load combinations and load factors
provided in Section 1605 of the IBC 2018.
SECTION O103 - FOUNDATIONS
0103.1 General. The foundation design of qualified buildings shall meet the requirements of this
section. Structures designed as per these alternate provisions may be supported by isolated or
combined footings or by a mat foundation. Minimum concrete compressive strength is 3,000 psi
at 28 days and 60,000 ksi for steel reinforcement conforming to ASTM A615-09. Welding of
reinforcement bars shall not be permitted.
156
0103.2 Minimum foundation thickness. The foundation thickness shall not be less than the
following:
1. For spread footings under load bearing walls twelve (12) inches.
2. For spread footings under columns twelve (12) inches.
3. For mat foundations, twelve (12) inches under concrete walls, twelve (12) inches under
columns and six (6) inches elsewhere. Changes in thickness shall be done gradually in a 1:1
slope down towards the thickened portion.
0103.3 Minimum foundation width. The foundation width shall not be less than the following:
1. For combined footings and mat foundations under interior load bearing walls, twelve (12)
inches measured from each face of the wall. For the case of combined footings and mat
foundations under exterior load bearing walls, fifteen (15) inches measured from each face
of the wall.
2. For spread footings and combined footings under interior and exterior columns, eighteen
(18) inches measured from each face of the column. For the case of mat foundations under
interior columns, eighteen (18) inches measured from each face of the column. For the
case of mat foundations under exterior columns, fifteen (15) inches measured from each
face of the column.
0103.4 Minimum steel reinforcement - Foundation reinforcement shall not be less than 0.002
of the gross sectional area.
0103.5 Minimum concrete cover. The concrete clear cover of steel reinforcement cast against
earth or permanently exposed to earth, shall not be less than three (3) inches or two (2) inches if
the complete foundation is cast against an unperforated bituminous or plastic vapor barrier
membrane conforming to ASTM E-1993 and ASTM 1745 of at least six thousandths of an inch (6
mils) thick. Membrane installation shall be as per ASTM 1643.
0103.6 Type L Footings. Type "L" footings shall not be used except at those instances required
to avoid conflicts with property lines. In such cases, their design shall consider soil bearing
pressure variations caused by the eccentricity of the applied load. The full footprint of the
foundation shall remain in bearing contact with the soil when subjected to service level loads
combinations as per IBC 2018.
SECTION O104 REINFORCED CONCRETE FRAMES
0104.1 General. The design of reinforced concrete frames designated to be part of the LFRS shall
meet the provisions of this section.
O104.2 Materials. The specified materials shall satisfy or exceed the following minimum
requirements:
157
1. Concrete. The specified 28 days concrete compressive strength for all components of the
frame components shall not be less than three thousand pounds per square inches (3,000
psi).
2. Steel. All steel reinforcement shall consist of deformed bars with a minimum yield stress,
Fy, of sixty thousand pounds per square inches (60,000 psi) conforming to ASTM A615-
09. Welding of steel reinforcement bars shall not be permitted.
0104.3 Minimum element dimensions. The depth of frame elements in the plane of the lateral
load under consideration, shall not be less than twelve (12) inches in columns and eighteen (18)
inches in beams, including the slab thickness when cast monolithically. In no case any frame
element shall have a dimension of less than eight (8) inches. In addition, the minimum column
cross sectional area shall not be less than one hundred forty-four (144) square inches.
0104.4 Minimum reinforcement. The beams of the frame shall be provided with at least two (2)
#5 longitudinal reinforcing bars at bottom and top. In no case shall the minimum reinforcement
provided in beams be less than the provisions of Section 10.5 of ACI 318-14. Transverse
reinforcement shall consist of at least #3 closed stirrups spaced no farther apart than six (6) inches
on center. The center of the splice for the positive (bottom) reinforcement shall be located at a
distance of one-fourth (1/4) the clear span from the face of the support and shall have a splice
length of thirty-six (36) times the bar diameter or eighteen (18) inches, whichever is greater. The
negative (top) reinforcement shall be continuous throughout the supports, and the center of the
splice shall be located at mid-span with an overlapping length of thirty (30) times the bar diameter
or twelve (12) inches, whichever is greater. The longitudinal top and bottom reinforcement of
beams shall terminate on exterior columns anchored with 90 degree standard hooks. The
longitudinal reinforcement in columns shall not be less than eight (8) #5 bars. The longitudinal
reinforcement of columns shall terminate anchored with 90 degree standard hooks. The footing
dowels shall be spliced with the column longitudinal reinforcement at column mid-height with an
overlapping of thirty-six (36) times the diameter of the longitudinal bars. Column transverse
reinforcement shall consist of at least #3 closed ties spaced no farther than six (6) inches on center.
Beam stirrups and column ties shall consist of closed hoops in accordance with ACI standards. In
all columns, ties shall be extended through the column-beam joints.
0104.5 Minimum Area of Concrete Columns. The sum of the gross area of all concrete columns,
in square inches and on the base floor must be at least 0.00325 times the total horizontal base shear
Vu, in pounds.
0104.6 Required analysis of moment frames. The structural analysis of moment frames shall be
performed by means of a rational analytical method accepted by the engineering community. The
stiffness contribution and effects of moment frames with Concrete Masonry Units (CMU) infill
shall be considered as per these provisions.
SECTION O105 - REINFORCED CONCRETE WALLS
0105.1 General - The design of reinforced concrete walls designated to be part of the LFRS shall
meet the provisions of this section.
158
0105.2 Materials. The specified materials shall satisfy or exceed the following minimum
requirements:
1. Concrete - The specified 28 days concrete compressive strength for all walls shall not be
less than three thousand pounds per square inches (3,000 psi).
2. Steel - All steel reinforcement shall consist of deformed bars with a minimum yield stress,
Fy, of sixty thousand pounds per square inches (60,000 psi) conforming to ASTM A615-
09. Welding of steel reinforcement bars shall not be permitted.
0105.3 Minimum element dimensions. The length of the wall in the direction of the lateral load
under consideration, shall not be less than forty-eight (48) inches. The perpendicular dimension
of the wall shall not be less than eight (8) inches.
0105.4 Minimum reinforcement. The walls shall be provided with at least two (2) #5
longitudinal reinforcing bars at each end of the wall cross section, confined with #3 ties or hairpins
spaced at six (6) inches along the wall height. In no case shall the minimum horizontal and vertical
reinforcement provided in walls be less than 0.0025 times the gross area of the wall. The vertical
and horizontal reinforcements shall not be spaced further apart than eighteen (18) inches. The
longitudinal reinforcement of walls shall be anchored with 90 degree standard hooks. The footing
dowels shall be spliced with the wall longitudinal reinforcement with an overlapping length of
thirty-six
(36)
times
the
diameter
of
the
longitudinal
bars.
0105.5Minimum Area of Concrete Walls. The sum of the gross area of all concrete walls at the
base floor must be at least 0.005 times the total gross area of the ground level.