Regl. 9049, art. 107-903.3.1.3
shall be permitted in Group R-3 occupancies.
Length: 62 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-903.3.1.3
[F] 903.2.8.2 Group R-4, Condition 1. An automatic sprinkler system installed in
accordance with Section 903.3.1.3 shall be permitted in Group R-4, Condition 1
occupancies.
[F] 903.2.8.3 Group R-4, Condition 2. An automatic sprinkler system installed in
accordance with Section 903.3.1.2 shall be permitted in Group R-4, Condition 2
occupancies.
[F] 903.2.8.4 Care facilities. An automatic sprinkler system installed in accordance with