AUTOMATIC SPRINKLER SYSTEMS

Length: 149 wordsOfficial source

Cite as Reglamento Núm. 9049, Art. 107-903 dup2

903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. Exceptions: 1. Residential occupancy Group R-2, construction type I, when the floor level having an occupant load of 30 or less that is located 45 feet (16.76 m) or less above the lowest level of fire department vehicle access. 2. Residential occupancy Group R-3. 903.2.8.1 Group R-3. An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-3 occupancies. 903.2.8.2 Group R-4, Condition 1. An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-4, Condition 1 occupancies. 903.2.8.3 Group R-4, Condition 2. An automatic sprinkler system installed in accordance with Section 903.3.1.2 shall be permitted in Group R-4, Condition 2 occupancies. 727 903.2.8.4 Care facilities. An automatic sprinkler system installed in accordance with