AUTOMATIC SPRINKLER SYSTEMS
Length: 149 wordsOfficial source
Cite as Reglamento Núm. 9049, Art. 107-903 dup2
903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3
shall be provided throughout all buildings with a Group R fire area.
Exceptions:
1. Residential occupancy Group R-2, construction type I, when the floor level having
an occupant load of 30 or less that is located 45 feet (16.76 m) or less above the
lowest level of fire department vehicle access.
2. Residential occupancy Group R-3.
903.2.8.1 Group R-3. An automatic sprinkler system installed in accordance with Section
903.3.1.3 shall be permitted in Group R-3 occupancies.
903.2.8.2 Group R-4, Condition 1. An automatic sprinkler system installed in accordance
with Section 903.3.1.3 shall be permitted in Group R-4, Condition 1 occupancies.
903.2.8.3 Group R-4, Condition 2. An automatic sprinkler system installed in accordance
with Section 903.3.1.2 shall be permitted in Group R-4, Condition 2 occupancies.
727
903.2.8.4 Care facilities. An automatic sprinkler system installed in accordance with