250-RICR-150-10-6
250-RICR-150-10-6. Rules Establishing Minimum Standards Relating to Location, Design, Construction and Maintenance of Onsite Wastewater Treatment Systems (version Amendment, 11/25/2018 to 11/25/2018)
To view the official Final Regulation for accessibility and readability, click Download Regulation:
Download Regulation
6.1 Purpose
The purpose of these rules is
to protect public health and the environment by establishing minimum
standards for the proper location, design, construction and
maintenance of onsite wastewater treatment systems (OWTSs) used for
the treatment and dispersal of wastewater.
6.2 Authority
These rules are promulgated
pursuant to R.I. Gen. Laws Chapter 42-17.1 Environmental Management;
Chapter 5-56 Installers of Individual Sewage Disposal Systems;
Chapter 5-56.1 Designers of Individual Sewage Disposal Systems;
Chapter 23-19.5 Percolation Tests and Water Table Elevations; Chapter
23-24.3 Substances or Compounds Used as Sewerage System Cleaners;
Chapter 46-13.2 Drilling of Drinking Water Wells, and Chapter
23-19.15 Rhode Island Cesspool Act of 2007; in accordance with
Chapter 42-35 Administrative Procedures.
6.3 Liberal Application
The terms and provisions of
these rules shall be liberally construed to allow the Department to
effectuate the purposes of state laws, goals, and policies.
6.4 Severability
If any provision of these
rules, or application thereof to any person or circumstances, is held
invalid by a court of competent jurisdiction, the validity of the
remainder of the rules shall not be affected thereby.
6.5 Applicability
A. These rules apply to the
discharge of wastewater to an OWTS. Other wastewater that does not
meet the definition in § 6.8 of this Part discharged to the
subsurface must be done in accordance with Subchapter
05 Part 4 of this Chapter . Where an OWTS is approved for
discharge of wastewater from commercial or industrial uses, the
Director may require the applicant to obtain an approval from the
Groundwater Discharge Program if, in the opinion of the Director,
there is a reasonable risk that materials used in commercial or
industrial processing may be discharged to the system.
B. These rules provide minimum
requirements for the design of an OWTS and its components. In
addition, the rules provide for the approval of alternative or
experimental technologies (§ 6.41 of this Part) that may be used in
conjunction with, or as an alternative to, the OWTSs and components
specified herein.
C. No provision of these rules
nor permit granted hereunder shall be construed to prevent
enforcement of any other state, federal or local laws and regulations
duly adopted for the purpose of protecting the public health or
environmental quality.
D. Nothing in these rules
shall affect the Director’s power and duty to issue an immediate
compliance order or take any other action pursuant to the R.I. Gen.
Laws.
E. These rules shall apply to
all applications submitted to the Department after the effective date
of these rules. Applications submitted to the Department prior to the
effective date of these rules shall be governed by the rules in
effect at that time.
6.6 Administrative Findings
A. OWTSs are an integral part
of our total wastewater infrastructure representing the decentralized
systems on the Rhode Island landscape. The people of the State should
be assured that adequate OWTSs have been and are being provided and
maintained for all dwellings and buildings not served by public
wastewater systems.
B. OWTSs must be viewed as
wastewater treatment and dispersal systems, not merely as disposal
systems. OWTSs must be located, designed, constructed, operated, and
maintained in a manner to produce an effluent that, when released
into the environment, will not cause adverse public health or
environmental impacts.
C. The improper location,
design, construction, operation and maintenance of OWTSs may have the
following harmful effects:
1. Public health may be
imperiled by diseases and other health hazards relating to
inadequately treated wastewater;
2. The public health and
interest may be harmed by contamination of groundwater resources that
are now used or which may be used in the future as sources of public
or private drinking water supply;
3. The public health and
interest may be harmed by contamination of public or private drinking
water wells and other water supplies or tributaries thereto;
4. Freshwater and coastal
waters of the State may be imperiled by high nutrient and
bacteriological contamination;
5. The people of the State may
be inconvenienced or harmed by nuisance conditions such as odors and
OWTS overflows; and
6. The public use and
enjoyment of the water resources of the State for recreational
endeavors may be disrupted or imperiled by contamination of those
resources.
D. The science and technology
for onsite wastewater treatment and disposal is rapidly advancing,
necessitating that licensed professionals and the Department continue
to evaluate and share information and knowledge in order to more
effectively protect the public health and the environment.
E. Properly functioning OWTS,
other than those employing nitrogen reducing technologies, remove
only a small percent of nitrogen in the wastewater. Excess nitrogen
is a contaminant in drinking water. Excess nitrogen in estuarine
environments causes eutrophication, which results in depleted
dissolved oxygen conditions and habitat loss.
F. Phosphorus in OWTS
wastewater is a contaminant that can cause eutrophication in fresh
water environments, which results in habitat loss.
G. Cesspools are not an
approved method of wastewater disposal under these rules, and all
existing cesspools are considered to be substandard.
1. There exists a need to
abate pollution and threats to public health caused by cesspools;
2. Cesspools contribute
directly to groundwater and surface water contamination and
environmental impacts will be exacerbated by increased precipitation,
storm frequency, and sea level rise;
3. Wastewater disposed from
cesspools can pose significant health threats to people who come into
contact with, or consume, contaminated surface waters or
groundwaters;
4. Appropriate treatment of
wastewater disposed into the ground is essential to the protection of
public health and the environment, particularly in relation to
Narragansett Bay and the rest of the State's coastal region, and
public drinking water resources;
5. Replacement of cesspools
with modern OWTS technology reduces risks to public health and the
environment;
6. In areas served by public
wastewater systems, connection to said system offers a readily
available, low-cost means of mitigating problems and threats caused
by cesspools; and
7. A fund exists to assist
homeowners with the costs of removing cesspools and inadequate septic
systems and replacing them with an approved OWTS if the community in
which the homeowner resides has created a wastewater management
district in accordance with R.I. Gen. Laws Chapter 24.5 of Title 45.
H. OWTSs must be properly
maintained to prevent their malfunction or failure in order to help
avoid both contamination of State waters and the associated risks to
the public health and to help preserve natural ecosystems.
I. Prior to January 1, 2008,
the Department used the term “Individual Sewage Disposal Systems,”
or ISDS, in these rules when referring to onsite wastewater treatment
systems. The term “Onsite Wastewater Treatment Systems,” or OWTS,
has been used since January 1, 2008, and is synonymous with ISDS.
6.7 Incorporated Materials
A. These regulations hereby
adopt and incorporate the ASTM International “Standard
Specification for Precast Concrete Septic Tanks C-1227-10a” (2010)
by reference, not including any further editions or amendments
thereof and only to the extent that the provisions therein are not
inconsistent with these regulations.
B. These regulations hereby
adopt and incorporate the International Association of Plumbing and
Mechanical Officials “American National Standard for Prefabricated
Septic Tanks IAPMO/ANSI Z1000-2007” (2007) by reference, not
including any further editions or amendments thereof and only to the
extent that the provisions therein are not inconsistent with these
regulations.
C. These regulations hereby
adopt and incorporate the NSF International/American National
Standards Institute Standard 41 "Non-liquid Saturated Treatment
Systems" (2005) by reference, not including any further editions
or amendments thereof and only to the extent that the provisions
therein are not inconsistent with these regulations.
D. These regulations hereby
adopt and incorporate the NSF International/American National
Standards Institute Standard 245 "Nitrogen Reduction Wastewater
Treatment Systems" (2010) by reference, not including any
further editions or amendments thereof and only to the extent that
the provisions therein are not inconsistent with these regulations.
E. These regulations hereby
adopt and incorporate 40 C.F.R. §§ 9, 144, 145, and 146 (1999) by
reference, not including any further editions or amendments thereof
and only to the extent that the provisions therein are not
inconsistent with these regulations.
F. These regulations hereby
adopt and incorporate the National Electrical Manufacturers
Association Standard 250-2014 "Enclosures for Electrical
Equipment (1000 Volts Maximum)" (2014) by reference, not
including any further editions or amendments thereof and only to the
extent that the provisions therein are not inconsistent with these
regulations.
G. These regulations hereby
adopt and incorporate the ASTM International “Standard
Specification for Concrete Aggregates C33/C33M-16e1)” (2016) by
reference, not including any further editions or amendments thereof
and only to the extent that the provisions therein are not
inconsistent with these regulations.
6.8 Definitions
A. As used in these rules, the
following terms shall, where the context permits, be construed as
follows:
1. "Advanced treatment
unit" means an alternative and experimental treatment system
that has been approved to reduce the BOD5 and TSS to 30/30 mg/L or
less.
2. “Alternative OWTS
component” means any part of an OWTS that does not meet the design
or construction requirements as provided by these rules, but has been
demonstrated through field testing, calculations and other
engineering evaluations to be equal to, or provide the equivalent
performance of any part of an OWTS within these rules or to enhance
or facilitate treatment, maintenance, longevity or efficiency of an
OWTS, and for which a certification from DEM has been issued.
3. “Alternative technology”
means any OWTS technology for which design parameters are not
specified in these rules, but has been demonstrated through field
testing, calculations and other engineering evaluations to comply
with performance standards consistent with these rules, and for which
a certification from DEM has been issued.
4. "APD" means
advanced pressure drainfield.
5. “Applicant” means the
owner or owners of the property or easement that is the subject of
the application, or it must be the person who holds a valid purchase
and sales agreement for said property.
6. “Area subject to storm
flowage” means drainage swales and channels which lead into, out
of, pass through, or connect other watercourses, and which carry
flows resulting from storm events but may remain relatively dry at
other times.
7. "ASTM" means ASTM
International, formerly known as the American Society for Testing and
Materials.
8. "Basal area"
means the horizontal surface in an APD or LPP designed to receive
effluent.
9. “Bedrock” means rock,
commonly called ledge, that forms the earth’s crust. Bedrock
includes rotten rock.
10. “Bedroom” means any
room in a residential structure which is greater than seventy (70)
square feet in area, which is susceptible to present or future use as
a private sleeping area and which satisfies all of the following
requirements:
a. Has at least one (1) window
that meets the four point four (4.4) square foot minimum size and all
other requirements of the “Rhode Island State Building Code SBC-1
or SBC-2”;
b. Has at least one (1)
interior method of entry and egress, excluding closets and bathrooms,
allowing the room to be closed off from the remainder of the
residence for privacy; and
c. Is a heated living space
that is unrestricted for year-round use. Rooms located below grade
that are not recognized as bedrooms by the “Rhode Island State
Building Code SBC-1 or SBC-2” are not recognized as bedrooms under
these rules.
11. “Blackwater” means
liquid and solid human body waste and the carriage waters generated
through toilet usage.
12. "BOD5" means
biochemical oxygen demand - five day. BOD5 is determined by a five
day laboratory test which determines the amount of dissolved oxygen
used by microorganisms in the biochemical oxidation (breakdown) of
organic matter. BOD5 concentrations are used as a measure of the
strength of a wastewater.
13. "BSF" means
bottomless sand filter. A BSF is a timed-dosed sand filter used
specifically as a dispersal / drainfield option for pretreated
effluent which at least meets the BOD5 and TSS requirements of thirty
(30) mg/l, and FOG of five (5) mg/l. The filter is intermittently
pressure dosed with the effluent followed by periods of drying and
oxygenation of the filter bed. Wastewater applied to the surface of a
bottomless sand filter flows through that filter media once before
infiltrating to the underlying native soils.
14. “Building sewer” means
the pipe that begins outside the building foundation wall and extends
to the septic tank, the pipe that begins outside the building
foundation wall and extends to the grease tank, the pipe from a
grease tank to a septic tank, or the pipe carrying laundry wastes
directly to a leachfield.
15. “Cesspool” means any
buried chamber, including, but not limited to, any perforated metal
tank, perforated concrete vault or covered hollow or excavation,
which receives discharges of wastewater from a building sewer for the
purpose of collecting solids and discharging liquids to the
surrounding soil.
16. “Change of use” means
any change in use or occupancy of any structure or part thereof which
would violate any provision of the Rhode Island State Building Code,
R.I. Gen. Laws Chapter 23-27.3, or any regulation promulgated thereto
without first obtaining a certificate of occupancy indicating that
the structure complies with the provisions of the State building code
for the proposed new use. Change of use shall also be held to mean a
conversion of a seasonally used structure to a structure for
year-round use.
17. “Coastal shoreline
feature” means a part of the shore as categorized by the State of
Rhode Island Coastal Resources Management Program using the following
categories: coastal beaches; barrier islands and spits; coastal
wetlands; coastal headlands, bluffs and cliffs; rocky shores; manmade
shorelines; and dunes.
18. “Compost toilet” means
any self‑contained toilet from which no liquid or solid waste
materials are regularly discharged and from which a humus-like end
product is produced.
19. “Department” or “DEM”
means the Rhode Island Department of Environmental Management.
20. “Director” means the
Director of the Rhode Island Department of Environmental Management
or any subordinate(s) to whom the Director has delegated the powers
and duties vested in him/her pursuant to R.I. Gen. Laws Chapters
46-12 and 42-17.1, or any other duly authorized Agent.
21. “Dispersal trench”
means a shallow ditch with vertical sides, filled with stone, in
which a single perforated distribution line or other suitable
distribution device is laid and over which a cover of earth is
placed.
22. “Distribution box”
means a watertight compartment that receives effluent and distributes
it in approximately equal portions to two (2) or more distribution
lines leading to some type of leachfield.
23. "Distribution
laterals" (pressure dosed) means usually small diameter PVC pipe
with orifices evenly spaced, used to uniformly distribute wastewater
over a treatment zone in an enclosed component or drainfield.
24. “Distribution line”
means the imperforated and perforated pipe or other suitable
distribution device used to disperse effluent that extends from the
distribution box.
25. “Dosing” means the
pumped or regulated flow of wastewater.
26. "Dosing tank"
means a tank that collects wastewater and from which wastewater is
discharged it into another treatment or dispersal step; equivalent to
a dosing chamber.
27. "Drainfield"
means a soil treatment area.
28. "Effluent" means
liquid that is discharged from a septic tank, filter, or other onsite
wastewater system component.
29. “Experimental
technology” means any OWTS technology that does not meet the
location, design or construction requirements as provided by these
rules, but has been demonstrated in theory to meet the requirements
of these rules and may not be in use in Rhode Island or elsewhere as
an approved technology for wastewater treatment.
30. “Failed OWTS” means
any OWTS that does not adequately treat and disperse wastewater so as
to create a public or private nuisance or threat to public health or
environmental quality, as evidenced by, but not limited to, one or
more of the following conditions:
a. Failure to accept
wastewater into the building sewer;
b. Discharge of wastewater to
a basement; subsurface drain; stormwater collection, conveyance, or
treatment device; or watercourse unless expressly permitted by the
Department;
c. Wastewater rising to the
surface of the ground over or near any part of OWTS or seeping from
the absorption area at any change in grade, bank or road cut;
d. The top of the inlet or the
top of the outlet for a septic tank, distribution box, or pump tank
is submerged;
e. The liquid depth in a
cesspool is less than six (6) inches from the inlet pipe invert;
f. Pumping of the cesspool or
septic tank is required more than two (2) times per year;
g. OWTS is shown to have
contaminated a drinking water well or watercourse;
h. If a septic tank, pump
tank, distribution box, or cesspool is pumped and groundwater seeps
into it;
i. Any deterioration, damage,
or malfunction relating to any OWTS that would preclude adequate
treatment and dispersal of wastewater; or
j. Excessive solids are
evident in the distribution box or distribution lines.
31. "Filter" means a
device or structure for removing suspended solid, colloidal material,
or BOD5 from wastewater.
32. "Filter fabric"
means any man-made permeable textile material used with foundations,
soil, rock, or earth.
33. "Filter media"
means the material through which wastewater is passed for the purpose
of treatment.
34. “Financial surety”
means a general obligation bond, revenue bond, performance bond, or
any other type of financial guaranty, in fully marketable form, as
evidence to the commitment of the construction of a public wastewater
project.
35. “Floodplain” means
that land area adjacent to a river or stream or other body of flowing
water which is, on the average, likely to be covered with flood
waters resulting from a one hundred (100) year frequency storm. A one
hundred (100) year frequency storm is one that is to be expected to
be equaled or exceeded once in one hundred (100) years; or may be
said to have a one percent (1%) probability of being equaled or
exceeded in any given year. Rainfall intensity data for a one hundred
(100) year frequency storm are those established for New England
locations by the National Weather Service.
36. "FOG" means
fats, oils, and grease contained in wastewater.
37. “Foundation drain”
means any mechanical or gravity drainage system, including all porous
media installed to facilitate drainage, that lowers the groundwater
elevation beneath a building foundation and which has an outlet for
the collected groundwater.
38. “Freshwater wetland”
is defined as set forth in R.I. Gen. Laws § 2-1-20(8), and as
further defined by the Department's "Rules and Regulations
Governing the Administration and Enforcement of the Fresh Water
Wetlands Act." The term shall further be held to include those
wetland types defined by the remainder of R.I. Gen. Laws § 2-1-20
and the wetland regulations, including, but not limited to: marshes,
swamps, bogs, ponds, rivers, river and stream floodplains and banks,
areas subject to flooding or stream water, including rivers and
streams, and that area of land within fifty (50) feet of the edge of
any bog, marsh, swamp or pond or that area within one hundred (100)
feet of a flowing body of water less than ten (10) feet wide or that
area within two hundred (200) feet of a flowing body of water greater
than ten (10) feet in width.
39. “Graywater” means
wastewater drained from sinks, tubs, showers, dishwashers, clothes
washers, and other non-toilet sources.
40. “Groundwater table”
means the upper surface of the zone of saturation in an unconfined
aquifer; includes a perched groundwater table.
41. “Holding tank” means a
closed watertight structure used to contain wastewater prior to being
removed from the premises. A holding tank does not discharge
wastewater to the surface of the ground or to the subsurface.
42. “Human transported
material” means any materials, other than those emplaced pursuant
to these rules, including but not limited to artifacts, organic
materials, soil, rock, or sediment moved horizontally by directed
human activity.
43. "Influent" means
wastewater being applied to a treatment unit or to a drainfield.
44. “Invert” means the
lowest portion of the interior of a pipe or fitting.
45. “Large onsite wastewater
treatment system” means an OWTS that meets any of the following:
a. Any single OWTS designed to
treat five thousand (5,000) gallons or more per day;
b. Multiple OWTSs for any
project on one or more parcels of land, excluding residential
subdivisions, where the total design flow for the project is five
thousand (5,000) gallons or more per day;
c. All OWTSs serving more than
one (1) unit in a residential subdivision, provided that the total
design flow of these OWTSs, each serving more than one unit, is five
thousand (5,000) gallons or more per day; or
d. Proposed OWTSs and existing
OWTSs on the parcel that will result in a total design flow for the
parcel exceeding five thousand (5,000) gallons per day.
46. “Large capacity
cesspool” means a cesspool that serves any non-residential facility
that has the capacity to serve more than twenty (20) people per day
or serves any multi-family residence or apartment building.
47. “Leachfield” means a
group of one (1) or more dispersal chambers or trenches designed for
the final treatment and dispersal of wastewater into the underlying
soil. The leachfield shall be held to mean the horizontal and
vertical lines circumscribing the outermost edges including the area
between the chambers or trenches and the depth to the bottom of
stone.
48. “Linear loading rate”
means the loading rate per linear foot of leachfield (gallons per day
per linear foot) along the land’s contour.
49. "LPP" means low
pressure pipe:
a. Application of effluent
over an infiltrative surface via pressurized orifices and associated
devices and parts (including pump, filters, controls, and piping).
b. Distribution via a network
of small diameter laterals with small orifices installed in a soil
treatment area; also called low- pressure-pipe (LPP) distribution.
50. “Maintenance” means
the regular cleaning of any concrete chamber, cesspool, septic tank,
building sewer, distribution lines or any other component of an OWTS
for the purpose of removing accumulated liquid, scum or sludge. The
term, "maintenance," shall also be held to include
regularly required servicing or replacement of any related
mechanical, electrical, or other component equipment.
51. “Nitrogen reducing
technology” means a wastewater treatment technology that is
accepted by the Department as capable of reducing the total nitrogen
concentrations by at least fifty percent (50%) and meeting an
effluent concentration of less than or equal to nineteen (19) mg/l.
52. "O&M service
provider" means a professional who performs operation and
maintenance on a wastewater treatment system.
53. “Onsite wastewater
treatment system" or "OWTS” means any system of piping,
tanks, dispersal areas, alternative toilets or other facilities
designed to function as a unit to convey, store, treat or disperse
wastewater by means other than discharge into a public wastewater
system.
54. “Original ground”
means those soils that have been deposited or developed by natural
processes, excluding storm deposited sand in the backdune
environment.
55. “Owner” means any
person who holds legal title to any real property; or has possession
or control of any real property through any agent, executor,
executrix, administrator, administratrix, trustee or guardian of the
estate of a holder of a legal title. Each such person is bound to
comply with the provisions of these rules.
56. "Particle size"
means the diameter (in millimeters) of a soil or sand particle,
usually measured by sedimentation or sieving methods.
57. “Person” means any
individual, group of individuals, firm, corporation, association,
partnership or any federal, state or municipal governmental entity.
58. “Private drinking water
well” means any manmade opening into the ground developed for the
purpose of meeting a person's current potable drinking water needs
provided said well does not supply a public water system. This
definition shall include proposed private drinking water wells on an
applicant’s property and on other properties with an approved OWTS
permit. Wells serving non-potable or non-drinking water needs are not
considered private drinking water wells under these rules. A well on
a property that is connected to a public water system is not
considered a private drinking water well under these rules.
59. “Probe” means any
exploratory test employing a driving rod, tool or other device to
establish the depth of bedrock.
60. "PSND" means
pressurized shallow narrow drainfield.
61. “Public drinking water
supply well” or “public well” means any manmade opening into
the ground developed for the purpose of meeting all or part of a
public water system needs.
62. “Public water system”
means any water system that provides piped water to the public for
human consumption, provided that such system has at least fifteen
(15) service connections or serves an average of twenty-five (25)
individuals daily at least sixty (60) days out of the year. A public
water system shall include all sources and facilities involved in
collecting, treating, storing and distributing the water.
63. “Pump tank” means a
watertight structure equipped with one (1) or more pumps designed to
discharge wastewater intermittently into a leachfield.
64. “Residence” means any
structure used for housing purposes, including, but not limited to,
single or multiple family dwellings, duplexes, tenements, apartment
buildings, residential condominiums, mobile homes, recreational
vehicles or trailers.
65. “Restrictive layer”
means a soil horizon that is assigned to a soil category 10 as
defined in § 6.16(L) of this Part.
66. “Rotten rock” means
any decomposed but still coherent rock. Rotten rock is greater than
fifty percent (50%) coherent rock and lies above equal or more
coherent rock.
67. “Seasonal high
groundwater table” means the elevation of the groundwater table
during that time of the year at which it is highest as determined in
accordance with § 6.16(M) of this Part.
68. “Septage” means any
solid, liquid or semi-solid removed from septic tanks, cesspools,
privies, wastewater holding tanks or other similar onsite wastewater
treatment systems.
69. “Septic tank” means a
watertight receptacle which receives the discharge of wastewater from
a building sewer, and is designed and constructed to permit the
deposition of settled solids, the digestion of the matter deposited,
and the discharge of the liquid portion into the next treatment
component or distribution box.
70. “Septic tank effluent
pipe” means the pipe that begins at the outlet of the septic tank
or other treatment tank and extends to the next treatment component
or distribution box.
71. “Single-service
articles” means tableware, carry-out utensils, and other items such
as bags, containers, placemats, stirrers, straws, toothpicks, and
wrappers that are designed and constructed for use one time by one
individual.
72. "Soil texture"
means the relative proportions of soil separates (sand, silt, and
clay particles) in a particular soil. (USDA soil texture
abbreviations illustrated in § 6.37(B)(4) of this Part are defined
as: cos= coarse sand; fs = fine sand; lfs = loamy fine sand; ls =
loamy sand; fsl = fine sandy loam; sl = sandy loam; l= loam; vfs =
very fine sand; lvfs = loamy very fine sand; vfsl = very fine sandy
loam; sil = silt loam; vfsl = very fine sandy loam; si = silt; sicl =
silty clay loam.)
73. “Storm drain” means
any pipe or structure designed to collect, carry and divert surface
water runoff.
74. “Structure” means any
residence (as defined herein), building, garage, shack, trailer or
other permanent or semi-permanent facility, whether commercial or
non-commercial in use, which is proposed to be placed or has been
built or otherwise placed on a parcel of real property.
75. “Subdivision” means
the division or re-division of a lot, tract, or parcel of land into
two (2) or more lots, tracts, or parcels. For the purpose of these
rules, subdivisions will also include two (2) or more contiguous lots
of record under common ownership when located on a public right of
way or roadway, including paper streets, or where property line
changes are proposed.
76. “Subdivision layout”
means any proposed design or arrangement of lots, roads, structures,
easements, utilities or other features to be incorporated into a
subdivision.
77. “Substantial
improvement” means any construction, renovation, or improvements
made within any twelve (12) month period and costing in excess of
fifty percent (50%) of the physical value of the building prior to
the start of construction.
78. “Subsurface drains”
means any system of below surface piping or highly permeable material
intended to lower the groundwater table of an area, and which has an
outlet to the surface for the collected groundwater.
79. “System inspector”
means a person on a DEM-approved list (can be found at the following
address:
http://www.dem.ri.gov/programs/benviron/water/licenses/isds/pdfs/deslist.pdf)
with the minimum qualifications of holding a Class I, II, or III
Designers License or being a Registered System Inspector with the New
England Onsite Wastewater Training Center.
80. “Test hole” means any
excavation in the area of the proposed leachfield to collect
information on the soil profile, depth to a restrictive layer or
bedrock, depth to seasonal high groundwater table or any other
applicable field information.
81. “Transfer” means a
transfer of real property except between the following relationships:
a. Between current spouses;
b. Between parents and their
children;
c. Between full siblings; or
d. Where the grantor transfers
the real property to be held in a revocable or irrevocable trust,
where at least one of the designated beneficiaries is of the first
degree of relationship to the grantor.
82. “Tributary” means any
flowing body of water or watercourse that provides intermittent or
perennial flow to down-gradient watercourses that eventually
discharge to the waters of concern (e.g., reservoir impoundment or
salt pond).
83. “Tributary wetland”
means freshwater wetlands within a watershed that are connected via a
watercourse to the waters of concern (e.g., drinking water supply
impoundment or coastal wetland or tidal waters).
84. "TSS" means
total suspended solids. The measure of solids that either float on
the surface of, or are in suspension in, water or wastewater. A
measure of wastewater strength, often used in conjunction with BOD5.
85. "U.C." means
uniformity coefficient, a numeric quantity which is calculated by
dividing the size of a sieve opening which will pass 60% by weight of
a sand media sample by the size of the sieve opening which will pass
10% by weight of the same sand media sample. Note that 50% of the
sample is retained between the two. The uniformity coefficient is a
measure of the degree of size uniformity of the sand particles in a
sand media sample. As the U.C. value approaches one (1), the more
uniform in particle size the sand media is. The larger the U.C., the
less uniform the particle size.
86. “Vendor” means the
person seeking an alternative or experimental technology approval.
87. “Wastewater” means
human or animal excremental liquid or substance, putrescible animal
or vegetable matter or garbage and filth, including, but not limited
to, water discharged from toilets, bath tubs, showers, laundry tubs,
washing machines, sinks, and dishwashers. Both blackwater and
graywater are considered wastewater under these rules.
88. “Watercourse” means
any river, stream, brook, pond, lake, swamp, marsh, bog, fen, wet
meadow, area subject to storm flowage, or any other standing or
flowing body of water, including such watercourses that may be
affected by the tides.
89. “Wellhead protection
area” means the area as designated by the Director in the DEM
“Groundwater Quality Rules” surrounding a public well or
wellfield through which water will move toward and reach such well or
wellfield.
6.9 Prohibitions
A. No individual shall prepare
plans, applications, certifications or specifications for the design
of an OWTS that is to be submitted to the Department pursuant to
these rules, unless such individual has a valid license in accordance
with the provisions of these rules to conduct such activity.
B. No individual shall
install, construct, alter, or repair an OWTS pursuant to these rules
unless such individual has a valid license in accordance with the
provisions of these rules to conduct such activity. This prohibition
does not apply to a property owner installing, constructing,
altering, or repairing an OWTS to serve a building the owner occupies
or will occupy as the owner’s intended permanent domicile, provided
that the owner has obtained written permission for that work and has
obtained the Director’s approval of the plans and specifications
for that work prior to the start of any construction.
C. No person shall install,
construct, alter or repair or cause to be installed, constructed,
altered or repaired any OWTS without first obtaining the Director’s
written approval of the plans and specifications for such work and
without adhering to each and every term of the approval. OWTS repairs
in accordance with § 6.18(G)(4) of this Part are exempt from this
prohibition.
D. No person shall utilize an
OWTS permitted under these rules:
1. In a manner that causes
wastewater flow to exceed the OWTS’s design capacity;
2. For other wastewater that
doesn’t meet the definition in § 6.8 of this Part; or
3. In a manner that does not
conform with the terms of the Department issued permit.
E. Use of a failed OWTS is
prohibited except in accordance with the requirements of an
enforcement notice or order issued by the Director.
F. No person shall install an
OWTS leachfield in an area designated as a freshwater wetland unless
approved by the DEM Freshwater Wetlands Program or specifically
exempted by regulation or are otherwise allowed by rule.
G. No person shall discharge
or allow the entrance of wastewater, treated or untreated, into any
watercourse, nor shall they discharge or permit the entrance of such
wastewater into any open or covered drain tributary to such
watercourse, without the approval of the Director.
H. No person shall discharge
any treated or untreated wastewater to the surface of the ground
without the approval of the Director. However, this shall not
interfere with the spreading of animal manure or compost containing
wastewater biosolids originating from a DEM-approved municipal
composting facility on the surface of the ground in accordance with
normal agricultural practices.
I. The use of acid and organic
chemical solvents in any OWTS is hereby prohibited. The Department
does not recognize any additive product as being beneficial to the
operation of an OWTS.
J. No person shall engage in
the business of pumping, cleaning or transporting septage unless such
person has obtained a Hazardous Waste Transporter Permit from the
Director in accordance with the Rhode Island Rules and Regulations
for Hazardous Waste Management.
K. Commercial laundromat(s)
shall not be permitted to discharge to an OWTS. Self-service laundry
facilities operating in compliance with R.I. Gen. Laws § 46-29-3,
“Phosphate Reduction,” are exempt from this prohibition.
L. Deep concrete chambers
(galleys) as described in § 6.35 of this Part are prohibited for
OWTS Applications for New Building Construction and OWTS Applications
for Alterations to a Structure (§ 6.18 of this Part).
M. Roof drains, surface
drains, and subsurface drains shall not be permitted to discharge to
an OWTS.
N. Floor drains that receive
wastewater that does not meet the definition in § 6.8 of this Part
shall not be permitted to discharge to an OWTS. The Department may
prohibit any floor drain from discharging to an OWTS where there is a
reasonable likelihood that such wastewater may enter such floor
drain.
O. Holding tanks for
wastewater are prohibited for Applications for New Building
Construction and Applications for Alteration to a Structure.
P. Siphons are prohibited for
OWTS with a design flow less than five thousand (5,000) gallons per
day unless used as part of an approved Alternative or Experimental
Technology approved pursuant to § 6.41 of this Part.
Q. The use of large capacity
cesspools is prohibited in accordance with U.S. Environmental
Protection Agency “Revisions to the Underground Injection Control
Regulations for Class V Injection Wells”, December 7, 1999, 40
C.F.R. §§ 9, 144, 145 and 146 (1999), incorporated above at §
6.7(E) of this Part. Any such large capacity cesspool shall cease to
be used and shall be properly removed or abandoned in accordance with
§ 6.56 of this Part.
R. Marine pumpout facilities
are prohibited from discharging wastewater to an OWTS other than a
holding tank installed pursuant to § 6.29 of this Part.
6.10 Class I, II, III, and IV
Licenses
A. Class I Designer's License
- A Class I License authorizes the design of a repair to an OWTS, or
any component thereof, provided that the repaired OWTS meets one of
the criteria below:
1. OWTS, other than
alternative or experimental systems, permitted under these rules for
residential use with a design flow of less than or equal to nine
hundred (900) gallons per day; or
2. Alternative or experimental
OWTS for residential use designated by the Director as suitable for a
Class I Licensed Designer with a design flow of less than or equal to
nine hundred (900) gallons per day.
B. Class II Designer's License
- A Class II License authorizes the design of the following:
1. The design of an OWTS
repair or OWTS for an alteration to a structure as defined in § 6.18
of this Part, provided that the OWTS meets one of the criteria below:
a. OWTS, other than
alternative or experimental systems, permitted under these rules for
residential use with a design flow of less than or equal to two
thousand (2,000) gallons per day;
b. Alternative or experimental
OWTS for residential use designated by the Director as suitable for a
Class II Licensed Designer with a design flow of less than or equal
to two thousand (2,000) gallons per day;
c. OWTS, other than
alternative or experimental systems, permitted under these rules for
commercial use with a design flow of less than or equal to nine
hundred (900) gallons per day; or
d. Alternative or experimental
OWTS for commercial use designated by the Director as suitable for a
Class II Licensed Designer with a design flow of less than or equal
to nine hundred (900) gallons per day.
2. The design of an OWTS for
new building construction as defined in § 6.18 of this Part,
provided that the OWTS meets one of the criteria in § 6.10(B)(1)(a)
through (d) of this Part and the OWTS is on a lot that does not
require a variance from any of the following provisions of the rules:
a. § 6.33 of this Part in
regards to OWTS installation in areas where there is a shallow depth
to the seasonal high groundwater table or to a restrictive layer or
bedrock from the original ground surface;
b. Setbacks in §§ 6.23(C)
and (E) of this Part for drinking water supplies; or
c. Setbacks in § 6.23(D) of
this Part for the Salt Pond and Narrow River Critical Resource Areas.
C. Class III Designer's
License - A Class III license authorizes the design of any OWTS
provided for under these rules.
D. Class IV Soil Evaluator's
License - A Class IV license authorizes the performance of soil
evaluations described in § 6.16 of this Part. Individuals holding a
Class IV license will be referred to herein as soil evaluators.
E. Class I, II, III, and IV
licenses shall be in effect for a period not to exceed three (3)
years following the date of issuance.
6.11 Obtaining a Class I, II, III
or IV License
A. Examination - Any
individual seeking a license under these rules will be required to
pass the appropriate examination administered or sanctioned by the
Department. An examination shall be given for each class at least
once per year. Each applicant for an examination shall submit a
completed application to the Director, which shall include the
non-refundable examination and new license application fee. In the
event that an individual fails an examination given pursuant to these
rules, the individual shall pay the examination and new license fee
for each subsequent time an examination is taken.
B. Minimum Qualifications - In
order to qualify for an examination, the applicant must demonstrate
to the Department with appropriate documentation that the minimum
qualifications below are met for the respective examination:
1. Class I - A valid
Installer’s License authorizing the installation of OWTSs pursuant
to § 6.14 of this Part, or registration as a Professional Land
Surveyor with the Rhode Island State Board of Registration for
Professional Land Surveyors, or Registration as a Professional
Engineer with the Rhode Island State Board of Registration for
Professional Engineers. Professional Engineers registered in Rhode
Island after December 31, 1994 must be registered as a Civil Engineer
or Environmental Engineer.
2. Class II - Registration as
a Professional Land Surveyor with the Rhode Island State Board of
Registration for Professional Land Surveyors or Registration as a
Professional Engineer with the Rhode Island State Board of
Registration for Professional Engineers. Professional Engineers
registered in Rhode Island after December 31, 1994 must be registered
as a Civil Engineer or Environmental Engineer.
3. Class III - Registration as
a Professional Engineer with the Rhode Island State Board of
Registration for Professional Engineers. Professional Engineers
registered in Rhode Island after December 31, 1994 must be registered
as a Civil Engineer or Environmental Engineer.
4. Class IV
a. The minimum qualifications
for the Class IV exam shall be satisfied by meeting any one of the
following:
(1) Registration as a
professional soil scientist by the Society of Soil Scientists of
Southern New England or the American Registry of Certified
Professionals in Agronomy, Crops and Soils;
(2) Four (4) years
professional experience in soil studies for OWTS design in Rhode
Island or in soil classification, mapping, interpretation or a
combination thereof; and successful completion of nine (9) semester
hours in soil science from an accredited college or university; or
(3) Two (2) years professional
experience in soil studies for OWTS design in Rhode Island or in soil
classification, mapping, interpretation or a combination thereof; and
a bachelor's degree or graduate degree from an accredited college or
university in soil science, geology, engineering or similar
discipline with successful completion of nine (9) semester hours in
soil science.
b. The Director reserves the
right to determine which courses are acceptable in meeting the
requirement for nine (9) semester hours in soil science in §§
6.11(B)(4)(a)((2)) and ((3)) of this Part above. The Director may
determine that certain courses or training other than those from an
accredited college or university are an equivalent and acceptable
alternative to all or part of the requirement in §§
6.11(B)(4)(a)((2)) and ((3)) of this Part above for nine (9) semester
hours in soil science.
C. Examination Descriptions
1. The examination for a Class
I Designer's License shall be a written examination that, at minimum,
addresses the following:
a. Principles of onsite
wastewater treatment and dispersal;
b. Understanding of the
applicable state rules;
c. Analysis of OWTS failures;
and
d. Design and construction of
OWTS repairs, with consideration given to soil types and related
constraints.
2. The examination for a Class
II Designer's License shall, at minimum, address the following:
a. Principles of onsite
wastewater treatment and dispersal;
b. Analysis of OWTS failures;
c. Design and construction of
OWTS repairs, with consideration given to soil types and related
constraints;
d. Advanced principles of
onsite wastewater treatment and dispersal;
e. Understanding of the
applicable state rules; and
f. Design and construction of
new OWTSs, including constraints to design imposed by soils.
3. The examination for a Class
III Designer's License shall be a two (2) part written examination,
each of which will be graded separately. The first part shall consist
of the test given for the Class II License. Passage of the first part
makes the applicant eligible for the Class II Designer’s License.
Active Class II Licensed Designers in good standing need only take
the Class III portion of the exam. The two parts of the Class III
examination do not have to be passed concurrently. However, if more
than three (3) years elapse after the applicant passes one of the
components of the examination, the applicant must retake that portion
of the examination originally passed more than three (3) years
earlier, unless a Class II License has been issued and is in good
standing. In addition to including the Class II examination, the
Class III examination shall address the following:
a. Understanding of additional
applicable state rules;
b. Groundwater hydrology;
c. Commercial wastewater
treatment;
d. Advanced wastewater
treatment technologies; and
e. Operation of electrical and
mechanical components of OWTSs.
4. The examination for a Class
IV License shall have a written and field component, each of which
shall be graded separately. The written and field examinations for
Class IV do not have to be passed concurrently. However, if more than
three (3) years elapse after the applicant passes one of the
components of the examination, the applicant must retake that portion
of the examination originally passed more than three (3) years
earlier. The Class IV License examination shall at minimum address
the following:
a. Principles of onsite
wastewater treatment and dispersal;
b. Understanding of the
applicable state rules;
c. Geology and soils of Rhode
Island;
d. Soil textural analysis and
profile descriptions;
e. Estimating mean seasonal
high groundwater elevations using soil morphology; and
f. Soil moisture and drainage
characteristics of soils.
D. Examination Application
Submission - Completed applications for examinations, fees and
evidence that the applicant meets the minimum qualifications
specified in § 6.11(B) of this Part shall be received by the DEM at
least forty-five (45) days prior to the date of the applicable
examination. Within thirty (30) days of receipt of an application for
an examination, the applicant shall be notified as to whether the
minimum qualifications in § 6.11(B) of this Part have been met, if
more information is needed, or if the applicant is eligible for the
examination. If the applicant is determined ineligible, the
Department shall provide the applicant with reasons for the
determination. The applicant may appeal the Director's decision of
ineligibility with the Administrative Adjudication Division.
E. Examination Results - The
Department shall notify the applicant of examination results no later
than sixty (60) days after the examination date. Minimum passing
score for an examination shall be a seventy percent (70%) correct
response for all questions comprising the examination. For those
applicants that pass the examination, the notification will include a
license application form.
F. The license shall be issued
to natural persons only and is not transferable or assignable.
6.12 Expiration and Renewal of a
Class I, II, III or IV License
A. Expiration - Once a license
issued pursuant to this rule has expired, the individual that held
such license is prohibited to practice as a Licensed Designer or Soil
Evaluator.
B. Renewal Prior to Expiration
- A license issued pursuant to this rule may be renewed provided
that:
1. The applicant pays the
renewal fee;
2. The applicant certifies
that the professional license(s) required as a minimum qualification
for the respective exam is valid;
3. The applicant demonstrates
satisfactory completion of a minimum of four (4) continuing education
units of appropriate professional development per year since the
applicant's license was issued or renewed. Events eligible for this
continuing education shall be rated by the Director with
consideration of their value and applicability to the relevant design
class. Eligible events will be assigned “continuing education
units.” The Director shall maintain a list of approved continuing
education events and the units assigned to each; and
4. The applicant demonstrates
satisfactory compliance with any unresolved OWTS regulatory
requirements, including submission of properly completed Certificates
of Construction and, where necessary, as-built plans.
C. Renewal After Expiration -
If the license has expired, the license may be renewed provided the
request is made within three years of the license expiration, the
applicant pays a late fee, and the applicant demonstrates compliance
with § 6.12(B) of this Part. The licensing exam may not be taken in
lieu of satisfying the renewal provisions herein. If the license is
not renewed within the three (3) year period after expiration, the
applicant must retake and pass the appropriate examination, then
reapply for the license.
6.13 Disciplinary Action for Class
I, II, III and IV Licensees
A. Where the Director has
identified negligence, incompetence or misconduct on the part of a
licensee in fulfilling the requirements of these rules, the Director
may issue a notification letter to the licensee documenting the
transgression. A copy of the notification shall be placed in the
licensee's file, and a copy shall be provided to the review panel
established pursuant to § 6.13(E) of this Part.
B. Denial, Suspension, or
Revocation of License - The Director may deny, suspend or revoke a
license if the individual has failed to comply with the requirements
in these rules or where the individual:
1. Provided incorrect,
incomplete or misleading information in obtaining the license;
2. Demonstrated gross or
repeated negligence, incompetence or misconduct in representation of
site conditions; design of an OWTS; preparation of any plans,
certifications or applications submitted to the Department; in the
inspection of an installation of an OWTS; in the supervision of
subordinates performing work covered under these rules; or by lack of
responsiveness to inquiry by the Department pursuant to a complaint
being investigated by the Department;
3. Committed a felony
involving moral turpitude; or
4. Has a professional license
that is a minimum qualification to obtain the designer's license in §
6.11(B) of this Part which has expired, is suspended or is revoked.
C. Penalties - The Director
may assess penalties in association with any suspension or revocation
of a license or where a licensee has failed to comply with the
requirements in these rules. Penalties shall be assessed in
accordance with the Department’s “Rules and Regulations for the
Assessment of Administrative Penalties”, Part
130-00-1 of this Title .
D. Denial of License Renewal -
The Director may deny the renewal of a license if the individual has
failed to comply with the requirements in these rules or where the
individual:
1. Provided incorrect,
incomplete or misleading information in obtaining the license;
2. Demonstrated gross or
repeated negligence, incompetence or misconduct in representation of
site conditions; design of an OWTS; preparation of any plans,
certifications or applications submitted to the Department; in the
inspection of an installation of an OWTS; or in the supervision of
subordinates performing work covered under these rules;
3. Committed a felony
involving moral turpitude;
4. Failed or neglected to
comply with the professional development continuing education
requirements;
5. Failed to comply with a
quality control plan submission or requirements as required by the
Department to address deficiencies in application submittals; or
6. Has a professional license
that is a minimum qualification to obtain the designer's license in §
6.11(B) of this Part which has expired, is suspended or is revoked.
E. Review Panel - The Director
shall appoint a Review Panel which shall consist of five (5) members,
at least three (3) of whom shall be licensed under this rule and not
be employed by the Director. Members of the Review Panel shall be
appointed for a two (2) to five (5) year term. The Director may
appoint new members to serve out the remaining time of those members
who leave the Review Panel before the end of their term. The Director
may also limit the number of terms an individual can serve. The
Review Panel shall conduct regular meetings as needed, but shall meet
not less than once every six (6) months. The Review Panel shall have
the authority to:
1. Review complaints against
Licensed Designers and Soil Evaluators, including requesting
information to aid such review;
2. Review the performance
related deficiencies identified pursuant to § 6.13(A) of this Part;
and
3. Recommend to the Director
to suspend or revoke a license, including the time period for the
suspension or revocation, and other remedial action that may be
appropriate, which would depend on the characterization of the
severity of the violations involved.
F. The Director shall be
responsible for all final decisions regarding denial, suspension and
revocation of licenses issued pursuant to these rules as well as any
other disciplinary actions to be brought against a licensee. Nothing
herein shall prevent or restrict the Director from initiating any
disciplinary action regarding denial, suspension or revocation of a
license without the recommendation of the Review Panel.
G. Complaint Review - The
procedure for Departmental review of complaints regarding Licensed
Designers or Soil Evaluators is described below. At any time during
the review of the complaint, the Director may request an informal
meeting with the licensee to discuss the complaint.
1. Upon receipt of a written
complaint regarding a Licensed Designer or Soil Evaluator, the
Director shall contact the licensee and all relevant parties to the
complaint as part of the Director's preliminary review.
2. If as a result of the
preliminary review, the Director concludes that the complaint lacks
merit or is not within the Department's jurisdiction under these
rules, the Director shall dismiss the complaint and no record of the
complaint shall be placed in the licensee's file.
3. If as a result of the
preliminary review, the Director concludes that the complaint may
have merit, the Director shall forward the complaint and a report of
any findings to the Review Panel.
4. The Review Panel shall
review the complaint and make recommendations appropriate to its
authority to the Director.
H. Notice of Intent - In
accordance with R.I. Gen. Laws § 42-35-14, before the Director
denies renewal of, suspends or revokes a license, the Director will
issue a Notice of Intent by certified mail or hand delivery to the
licensee notifying the licensee of the Director's intention to deny
renewal of, revoke or suspend the license and the reasons why the
Director intends to take such action. The licensee receiving the
Notice of Intent may request a preliminary hearing before the
Director or his or her designee to show cause why the Director should
not deny, revoke or suspend the license. Such hearing shall be held
within thirty (30) days of the Director’s receipt of a written
request by the licensee or an attorney representing the licensee for
such preliminary hearing. If the licensee fails to request a
preliminary hearing within twenty (20) days of receipt of the Notice
of Intent, fails to make himself or herself reasonably available to
attend a preliminary hearing, or fails to show cause to the Director
or his or her designee why the Director should not deny renewal,
revoke or suspend the license, the Director may deny renewal, revoke
or suspend the license in accordance with these rules and other
applicable statutes or regulations. If the Director finds that public
health, safety, or welfare imperatively requires emergency action,
and incorporates a finding to that effect in its order, summary
suspension may be ordered pending proceedings for revocation or other
action.
I. Request for Hearing -
Requests for a hearing on the denial of examination eligibility,
denial of renewal, suspension, or revocation of a license must be
filed with the clerk of the Department of Environmental Management,
Administrative Adjudication Division within thirty (30) days of the
date of the licensee’s receipt of such notice by certified mail or
hand delivery.
J. Censure - The Director may
publicly censure any Licensed Designer or Soil Evaluator whose
license has been subject to an official enforcement action.
K. Suspension - Any individual
with a suspended license is prohibited from practicing any work
allowed under the license, renewing the license, or applying for a
new license for the period of the suspension.
L. Revocation - Any individual
who has a license revoked pursuant to this Rule shall not petition
the Director for reinstatement for a period of time to be determined
by the Director.
6.14 Installer's License
A. Installer’s License - An
Installer’s License authorizes an individual to install, construct,
alter or repair an OWTS. A Licensed Installer shall install an OWTS
in accordance with § 6.47 of this Part.
B. Obtaining an Installer’s
License
1. Each applicant for an
Installer’s License shall submit a completed application to the
Director along with a non-refundable application fee.
2. Applicants for an
Installer’s License will be required to demonstrate possession of
and ability to properly use a level or transit and to obtain a
passing grade on a written examination given by the Director. The
examination shall be intended to demonstrate an applicant’s
understanding of the rules and the ability to read and interpret
approved plans and specifications for OWTSs.
3. Installer’s Licenses are
not transferable or assignable and shall automatically become invalid
upon suspension or revocation.
4. Installer’s Licenses
shall be in effect for a period not to exceed three (3) years
following the date of issuance.
C. Expiration, Renewal, and
Reinstatement of Installer’s Licenses
1. Once an Installer’s
License issued pursuant to this rule has expired, the individual that
held such license is prohibited to practice as a Licensed Installer.
2. An Installer’s License
shall be renewed upon payment of a renewal fee and the submittal of
proof of completion of any professional development continuing
education required by the Director.
3. If an installer’s license
has expired for less than one (1) year, the license may be reinstated
in accordance with § 6.14(C)(2) of this Part. If the license has
expired for greater than one (1) year, the license may be reinstated
provided the request is made within three (3) years of the license
expiration; the applicant pays a reinstatement fee; and the applicant
demonstrates completion of any professional development continuing
education as required by the Director. If the license is not
reinstated within the three (3) year period after expiration, the
applicant must reapply for the license and take the installer’s
examination.
D. Denial, Suspension and
Revocation of Installer’s Licenses
1. The Director may deny,
suspend or revoke an Installer’s License if the individual has
failed to comply with the requirements in these rules or where the
individual:
a. Provided incorrect,
incomplete or misleading information in obtaining the license; or
b. Demonstrated gross or
repeated negligence, incompetence or misconduct in installing OWTSs.
2. In accordance with R.I.
Gen. Laws § 42-35-14, before the Director suspends or revokes a
license, the Director will issue a Notice of Intent to Revoke/Suspend
a license by certified mail or hand delivery to the licensee
notifying the licensee of the Director's intention to revoke or
suspend the license and the reasons why the Director intends to take
such action. The licensee receiving the Notice of Intent to
Revoke/Suspend may request a preliminary hearing before the Director
or his or her designee to show cause why the Director should not
revoke or suspend the license. Such hearing shall be held within
thirty (30) days of the Director’s receipt of a written request by
the licensee or an attorney representing the licensee for such
preliminary hearing. If the licensee fails to request a preliminary
hearing within twenty (20) days of receipt of the Notice of Intent to
Revoke/Suspend, fails to make himself or herself reasonably available
to attend a preliminary hearing, or fails to show cause to the
Director or his or her designee why the Director should not revoke or
suspend the license, the Director may revoke or suspend the license
in accordance with these rules. If the Director finds that public
health, safety, or welfare imperatively requires emergency action,
and incorporates a finding to that effect in its order, summary
suspension may be ordered pending proceedings for revocation or other
action.
3. The licensee may request a
hearing on the denial, suspension, or revocation of a license with
the Department of Environmental Management, Administrative
Adjudication Division within thirty (30) days of the date of receipt
of such notice.
4. The Director may publicly
censure any Licensed Installer whose license has been suspended or
revoked.
5. Any individual with a
suspended Installer’s License is prohibited from practicing any
work allowed under the license, renewing the license, or applying for
a new license for the period of the suspension.
6. Any individual who has an
Installer’s License revoked pursuant to this rule shall not
petition the Director for reinstatement for a period of time to be
determined by the Director.
6.15 Onsite Wastewater Treatment
Systems - General
A. Any dwelling or other
building having plumbing fixtures from which wastewater is produced,
in a location where no public wastewater system is available or
accessible, shall be provided with an OWTS of type and design
approved by the Director.
B. All of the components of an
OWTS shall be located within the boundary of the property upon which
the building or dwelling served by the OWTS is located. Exemption to
this requirement may be granted for OWTSs serving more than one (1)
unit in a proposed subdivision or for any OWTS repair.
C. Household Laundry Systems -
For an OWTS designed to receive household laundry waste only, a
leachfield sized to accept twenty percent (20%) of the design flow
may be used without the installation of a septic tank.
D. Issuance of Building
Permits For Activities Requiring Approval Under These Rules ‑ A
municipality shall not issue a building permit pursuant to R.I. Gen.
Laws Chapter 23‑27.3, unless all written approvals by the
Director required by these rules have been presented to the
municipality and said approvals are valid at the time of the issuance
of the building permit.
E. Connection to a Public
Wastewater System - An OWTS application shall not be approved if such
OWTS is proposed to serve a premises for which a public wastewater
system is reasonably accessible as determined by the Director, and
for which permission to enter the public wastewater system can be
obtained from the authority having jurisdiction. The Director shall
require the owner or occupant to connect the structure to a public
wastewater system within a specified period of time if the following
occur:
1. The OWTS is failing;
2. Public wastewater system is
reasonably accessible as determined by the Director; and
3. Permission to connect to
the public wastewater system can be obtained from the authority
having jurisdiction over it.
F. Component Substitution -
For an OWTS approved, but not yet installed, with a septic tank,
grease tank, pump tank, or distribution box that does not meet the
updated construction standards in these rules, a substitution of
components complying with these rules may be made provided as-built
plans are submitted to the Department upon completion of
construction. No substitution of leachfields or leachfield components
may be made under this § 6.15(F) of this Part.
G. Data Quality - Effluent
samples and water quality samples shall be collected, stored,
transported, and analyzed in accordance with the United States
Environmental Protection Agency approved procedures.
6.16 Soil Evaluation
A. Soil Evaluation Required -
A soil evaluation shall be required for an OWTS Application for New
Building Construction, for an OWTS Application for Alteration of a
Structure, and for an OWTS Application for Repair for non-residential
uses in accordance with § 6.18 of this Part.
B. Validity of Field Data -
Field data shall be considered valid for a period of five (5) years
from the time of initial certification by the Department or five (5)
years from the date of initial approval of any OWTS application,
design, or subdivision suitability where the data were used,
whichever occurred most recently. Field data older than five (5)
years may be used provided that §§ 6.16(B)(1) through (3) of this
Part are met. Field data cannot be renewed independent of an OWTS
application or subdivision site suitability certification
application.
1. The field conditions are
essentially unchanged;
2. The field data was
initially compiled and certified after July 20, 1987 for subdivisions
or after December 31, 1992 for individual lots; and
3. Its continuing validity is
properly certified on the OWTS application or Application for
Subdivision Site Suitability Certification.
C. Soil Evaluation
Requirements - The soil evaluation shall be prepared on forms
approved by the Director. The soil evaluation shall contain a site
sketch and the information in §§ 6.16(C)(1) through (6) of this
Part. The information in §§ 6.16(C)(1) and (2) of this Part shall
be completed by a Soil Evaluator, and may be required to be witnessed
by the Director in accordance with § 6.16(E) of this Part. The
information in items §§ 6.16(C)(3) through (6) of this Part shall
be determined by a Class II or III Licensed Designer or a Soil
Evaluator. The test holes excavated for the soil evaluation shall be
within the area of the proposed leachfield as described in § 6.16(I)
of this Part.
1. Comprehensive soil profile
description and textural analysis identifying the characteristics of
the soil and using the terminology in the DEM Soil Evaluation
Guidance Document (this document can be found at:
http://www.dem.ri.gov/programs/benviron/water/permits/isds/pdfs/seg0108.pdf);
2. Identification of the
seasonal high groundwater table in accordance with § 6.16(M) of this
Part;
3. General description of
slope;
4. Presence of any
watercourse, wetlands, or surface water bodies within two hundred
(200) feet of the proposed leachfield;
5. Presence of any drains that
may influence the seasonal high groundwater table; and
6. Approximate location of
property lines.
D. Soil Evaluation Application
- An application form shall be submitted to the Director by the Soil
Evaluator prior to conducting the soil evaluation field work on the
site. Such application will be on forms approved by the Director and
will require at minimum a locus map and photocopy of the relevant
page or section thereof from the U.S. Department of Agriculture Soil
Survey with the site location marked. The Director shall determine if
the soil evaluation must be witnessed by the Department. The Director
shall notify the applicant within ten (10) business days of receipt
of the application as to whether or not the soil evaluation must be
witnessed by the Department.
E. Soil Evaluation Witnessed
by the Department
1. At the time of the
notification in § 6.16(D) of this Part, an appointment will be
scheduled for the Department to witness the soil evaluation. This
appointment shall be within fifteen (15) business days of the
Director's notification in § 6.16(D) of this Part.
2. Requests for cancellation
of the soil evaluation appointment will be accepted by the Director a
minimum of twenty-four (24) hours in advance of the scheduled
appointment, and if requested, will be rescheduled for the next
available date. All other cancellations, including instances where
the Director is onsite and the Licensed Designer or Soil Evaluator is
not present, will require reapplication to the Director. If the
Director is not onsite for the scheduled appointment, the completed
soil evaluation shall be submitted to the Director prior to the
submission of the application for an OWTS permit.
3. The Soil Evaluator shall
complete the soil evaluation form prior to the arrival of the
Director onsite for the scheduled appointment with the Department.
While in the field, the Director shall determine which of the
following apply:
a. The Director concurs with
the determination of the soil evaluation. The soil evaluation form
shall be submitted to the Department within ninety (90) days of the
scheduled appointment and may be submitted concurrently with the OWTS
Application;
b. The Director and the Soil
Evaluator concur that results of the seasonal high groundwater table
determination are inconclusive, and a determination will have to be
made during the wet season in accordance with § 6.16(M)(4) of this
Part; or
c. The Director does not
concur with the soil evaluation. If soil conditions are in dispute,
the Department, upon request of the Soil Evaluator, shall provide an
additional field review in an effort to resolve the dispute.
(1) If the determination of
the seasonal high groundwater table remains in dispute after the
additional field review and all other elements of the soil evaluation
are agreed upon, the Soil Evaluator has the option to conduct a wet
season determination of the seasonal high groundwater table in
accordance with § 6.16(M)(4) of this Part.
(2) If elements of the soil
evaluation other than the seasonal high groundwater table remain in
dispute after the additional field review, the Department shall
disclaim the determinations of the soil evaluation and provide an
explanation for not accepting it.
F. Soil Evaluation Not
Witnessed by the Department - If the Director determines that the
Department need not witness the soil evaluation, the Licensed
Designer or Soil Evaluator shall notify the Department during normal
business hours by telephone of the date and time of the soil
evaluation at least twenty-four (24) hours prior to conducting the
soil evaluation. The Department, at its discretion, may make
unannounced inspections of any soil evaluation. The soil evaluation
form shall be submitted to the Director prior to the submission of
the application for an OWTS permit and within ninety (90) days of the
day the soil evaluation was conducted.
1. If bedrock is encountered
within a test hole during a soil evaluation not witnessed by the
Department, the Licensed Designer shall apply to the Department for
bedrock testing.
2. After review of the soil
evaluation, the Director shall either:
a. Accept the determination of
the soil evaluation;
b. Determine that the soil
evaluation is not in compliance with these rules or that more
information must be collected, in which case a revised soil
evaluation must be submitted to the Director; or
c. Disclaim the determinations
of the soil evaluation, and provide an explanation for not accepting
it.
G. Soil Evaluation
Certification - Individuals conducting a soil evaluation shall
certify that the soil evaluation was conducted in a manner consistent
with these rules and that it is an accurate portrayal of site
conditions on the day and time it was conducted. If more than one
individual licensed under these rules participated in the development
of the soil evaluation it must be specified who prepared which part
and include a certification from each licensee.
H. Department Acceptance -
Acceptance of a soil evaluation indicates only that the Department
accepts the data for design of an OWTS, however, the Department
reserves the right to question the data. This acceptance is not an
indication of the correctness or quality of the soil evaluation.
I. Test Hole Requirements
1. A minimum of two (2) test
holes within twenty-five (25) feet of the proposed leachfield, shall
be excavated at least twenty-five (25) feet apart with one pit on the
up-gradient side and one on the down-gradient side of the proposed
leachfield. The Director may waive the requirement for a second test
hole where the conditions indicate that such test hole is not
necessary.
2. The test holes shall be
excavated to a depth of five (5) feet, unless site conditions prevent
doing so (e.g., a flooded pit due to a high water table) in order to
allow detailed examination by the Soil Evaluator. The Soil Evaluator
shall complete the soil evaluation form provided by the Director
using the terminology in the DEM Soil Evaluation Guidance Document
(this document can be found at:
http://www.dem.ri.gov/programs/benviron/water/permits/isds/pdfs/seg0108.pdf).
3. From the depth excavated
for § 6.16(I)(2) of this Part to a minimum of ten (10) feet, to the
extent possible, the Soil Evaluator shall provide the information
requested on the soil evaluation form from material removed from the
test hole without entering the test hole. This information shall
include at minimum the soil texture, structure and consistence for
each soil horizon observed. This can be done in an additional test
hole, or in the test hole used to complete work for § 6.16(I)(2) of
this Part after such work has been witnessed by the Department, if
required.
4. If a restrictive layer or
bedrock is encountered or the test hole becomes unstable due to lack
of soil cohesion or the presence of groundwater, the test hole may be
terminated at a depth of less than ten (10) feet. Sites with test
holes which have been terminated at less than ten (10) feet may
require additional testing as determined by the Director.
5. It is recommended that
individuals performing the soil evaluation not enter into portions of
a test hole that have been excavated to depths greater than five (5)
feet below the surrounding ground surface. It is the responsibility
of individuals performing or witnessing the soil evaluation to comply
with all applicable federal, state and local laws and regulations
governing occupational safety.
J. Soil Class - The
information collected from the test hole shall be used to assign the
soil to one of the soil classes below, except for Class G soils in
which case the soil class for the substratum shall also be indicated.
1. Class A - Glacial
Lodgement Till: Silt loam to loamy sand texture. Lower profiles tend
to have a platy structure and are dense to very dense. Excavation is
difficult. High probability of hydraulically restrictive lower
layers. Angular rock fragments and occasional cobbles and stones.
2. Class B - Glacial
Ablation Till: Silt loam to loamy sand throughout the profile. Lower
horizons tend to be more sandy. These soils tend to be looser than
lodgement tills and typically do not have hydraulically restrictive
layers. Lower horizons may be firm. Angular rock fragments and
occasional cobbles and stones.
3. Class C - Proglacial
Outwash: Also referred to as stratified drift, soil textures range
from silt loam to loamy sand (in the upper horizons) to a
sandy/gravely substratum. Stratified layers of water sorted materials
may be present. Entire profile tends to be loose and easy to dig
except saturated horizons may be firm or cemented or both. Horizons
of rounded rock fragments are common.
4. Class D - Glacial Ice
Contact Deposit: Outwash deposits of well to poorly sorted sands and
gravel. Texture can be highly variable over short distances and may
include pockets or lenses of silt or silt loam. Stratification may be
irregular or absent. Sub-rounded to rounded stones and cobbles are
possible.
5. Class E - Coastal Dune:
Fine to coarse sands, well sorted, often finely stratified. Little or
no silt and clay. Typically no sediment larger than coarse sand.
Deposited by wind action or storm overwash.
6. Class F - Alluvial
Deposits: Material transported and deposited by streams and rivers.
Typically well sorted, stratified, fine textured sediment that may
have dark layers in the substratum which were at one time surface
layers. Subject to seasonal flooding.
7. Class G - Eolian
Deposits: Wind blown silts deposited after the retreat of the
Wisconsin glaciation ranging in thickness of several inches to
several feet. Underlain by outwash, ablation till, or lodgement till.
K. Soil Category - Each
observed soil horizon shall be assigned to one of the soil categories
from § 6.16(L) of this Part below. Soil category will be used to
determine the minimum leaching area by the Class II or III Licensed
Designer in accordance with § 6.33 of this Part.
L. Soil Category
Soil
Category
Loading
Rate (gals/sq ft/day)
Pursuant
to § 6.33(B) of this Part
Starred
items (*) are for soils with coarse fragment modifiers
Soil
Texture
Soil
Structure
Soil
Consistence
Typical
Soil Class
Consistence
In-Hand Using Soil Clods
Excavation
Difficulty
1
.70
cos,
s, lcos, ls, cosl, fs
structureless-
single grain
subangular
blocky
loose
friable
N/A
Outwash
(Class C), ice contact (Class D) and coarse ablation till (Class
B) deposits
.61*
2
.61
vfs,
lvfs
structureless-
single grain
loose
N/A
Outwash
(Class C) and ice contact (Class D) deposits
3
.70
ls,
sl, l
granular,
subangular blocky
very
friable to friable
low
Lodgement
Till (Class A), Ablation Till (Class B), Outwash (Class C), or
Ice Contact (Class D)
4
.61
lfs,
lvfs, fsl, vfs
granular,
subangular blocky
very
friable to friable
low
Lodgement
Till (Class A), Ablation Till (Class B), Outwash (Class C), or
Ice Contact (Class D)
.70*
5
.52
sil,
si, vfsl
subangular
blocky
very
friable to friable
low
Typically
Eolian deposits (Class G)
6
.61
lcos,
cosl, lfs, ls, sl, l,
structureless
massive
very
friable to friable
low
Ablation
till (Class B)
.70*
7
.52
fsl,
vfsl, sil, si, vfs
structureless-
massive
very
friable to friable
low
to moderate
Ablation
till (Class B)
.61*
8
.46
all
textures
structureless-massive
firm
to very firm
moderate
Lodgement
till (Class A)
.48*
9
.40
all
textures
platy,
structureless- massive
firm
to very firm
high
Lodgement
till (Class A)
.43*
10
Not
Allowed (Impervious)
all
textures
platy,
structureless- massive
extremely
firm
very
high to extremely high
Lodgement
till (Class A)
M. Determination of Seasonal
High Groundwater Table
1. The Soil Evaluator shall
use the depth to, type, location and abundance of hydromorphic
features and other characteristics to determine the depth to the
seasonal high groundwater table. The depth to the seasonal high
groundwater table shall be measured from the original ground surface.
The criteria to use in evaluating hydromorphic features include, but
are not limited to the following:
a. Redox depletions and redox
concentrations occupy two percent (2%) or more of the exposed horizon
surface;
b. Soil matrix and redox
concentrations or depletions vary two (2) or more units in chroma; or
c. Presence of a depleted
horizon, which is a soil layer that has a chroma of two (2) or less
and a value of four (4) or more that develops or maintains gleyed
colors because of substantial saturation.
2. In cases where the soil is
class C or D as determined in § 6.16(J) of this Part and there are
no observable hydromorphic features to use to make a determination in
accordance with § 6.16(M)(1) of this Part, an adjustment factor may
be applied to the observed groundwater table in order to correct to
the seasonal high groundwater table. This adjustment factor shall be
determined by the Director. When groundwater is not encountered in a
test hole at least ten (10) feet deep, the adjustment factor may be
applied as measured from the bottom of the test hole.
3. A perforated pipe at least
four (4) inches in diameter shall be installed to the full depth of
the excavation in each test hole at the conclusion of the soil
evaluation, unless such requirement is waived by the Director. The
pipe shall be wrapped in filter fabric that meets the requirements of
§ 6.33(L) of this Part, capped at the top and mounded to prevent the
accumulation of surface water.
4. Wet Season Determinations -
Determination of the seasonal high groundwater table during the wet
season shall be made by a Class II or III Licensed Designer, or a
Soil Evaluator January 1 through April 1.
a. The groundwater table
observations shall be made using the pipe placed in the test holes in
accordance with § 6.16(M)(3) of this Part or using a pipe that meets
these requirements placed in a minimum of two (2) excavations to a
depth of ten (10) feet within the area in § 6.16(I)(1) of this Part.
Such pipe should remain in place until a permit has been issued by
the Director.
b. Groundwater table
observations shall be made no sooner than forty-eight (48) hours
after excavation and shall be verified by the Director unless
otherwise waived. At least three (3) groundwater table observations
shall be made and the observations shall be a minimum of five (5)
days apart. The groundwater table observations shall be submitted for
review by April 1 on forms approved by the Director.
c. Wet season determinations
are intended to measure the groundwater table at its annual highest
level. Yearly fluctuations in the groundwater table may necessitate
that the Department add adjustment factors to compensate for periods
of low groundwater recharge that results in the seasonal high
groundwater table to be lower than normal.
5. The soil evaluation that is
submitted to the Director by the Soil Evaluator shall include wet
season data, if applicable, along with the final determination of the
seasonal high groundwater table.
6.17 Additional Site Testing
A. Determination of depth to
bedrock and the presence of storm deposited sand in the backdune
environment or human transported material, as required in §§
6.17(B) and (C) of this Part, shall be made by a Class II or III
Licensed Designer or a Soil Evaluator on forms approved by the
Director.
B. Determination of Depth to
Bedrock
1. Bedrock test holes,
conducted in accordance with § 6.17(B)(2) of this Part, shall be
required when any of the following occur:
a. Bedrock is encountered
within eight (8) feet of original ground surface in the excavation of
any of the test holes for the soil evaluation;
b. Bedrock outcrops are
visible in the surrounding area; or
c. Landscape conditions
warrant bedrock test holes.
2. Bedrock test holes
a. Bedrock test holes shall be
excavated to a depth of ten (10) feet in the center and four corners
of the proposed leachfield. Additional test holes or probe tests
shall be required within twenty-five (25) feet of the proposed
leachfield, the number and location depending on the site. Bedrock
depth shall be determined on all sides of the proposed leachfield. In
order for DEM approval, testing must demonstrate that:
(1) Bedrock is at least five
(5) feet below the bottom elevation of the stone in the leachfield in
the area of the proposed leachfield and within twenty-five (25) feet
of the proposed leachfield. The five (5) foot vertical separation
requirement may be waived on the up-gradient side as long as bedrock
is no higher than the bottom of the stone in the leachfield within
twenty-five (25) feet of the proposed leachfield (§ 6.59 of this
Part, Figure 1); and
(2) Depth to Bedrock from
original ground surface must be a minimum of four (4) feet within
twenty-five (25) feet on all sides of the leachfield, including the
upgradient side.
b. A bedrock test hole shall
be witnessed by the Director unless the Director waives this
requirement.
c. If during the bedrock
exploration work the Director determines that additional bedrock test
holes or probe tests are not warranted, then the Director may waive
such additional testing.
C. Human Transported Material
and Storm Deposited Sand - If human transported material or storm
deposited sand in the backdune environment is encountered in the
excavation of any test hole or is evident within twenty-five (25)
feet of any test hole, an adequate number of additional test holes
shall be excavated to a sufficient depth to determine the lateral and
vertical extent of this material within twenty-five (25) feet of the
leachfield. Limitations for OWTS design regarding depth to
groundwater and depth to bedrock shall be determined from original
ground surface. The Director may require that this material existing
in the area of the proposed leachfield be removed. Test holes in
human transported material or storm deposited sand in the backdune
environment shall be witnessed by the Director unless the Director
waives this requirement.
6.18 OWTS Applications
A. Applicant’s
Responsibilities - The applicant shall be responsible for providing
all information required by these rules in a complete, accurate,
clear and legible manner. The applicant for an OWTS must be the owner
or owners of the property or easement that is the subject of the
application, or it must be the person who holds a valid purchase and
sales agreement for said property.
B. Designer’s Responsibility
- Class I, II and III Licensed Designers shall design an OWTS for a
site that is in compliance with these rules. The design shall be
based on the information provided in the soil evaluation report. This
design shall be submitted to the Director in accordance with §§
6.18 and 6.19 of this Part.
C. Local Ordinances - It is
the applicant’s responsibility to ensure that the OWTS application
to the Department is in compliance with local ordinances regarding
the location, design, construction and maintenance of an OWTS prior
to submission to the Department. City or Town Councils may petition
the Department to require municipal review for compliance with local
ordinances prior to DEM initiating its review. The petition must
state the local standard(s), as embodied in local ordinance, that is
more stringent than the standard(s) in these rules and the municipal
official responsible for local review. In municipalities where the
petition has been approved, applicants must submit documentation to
DEM on forms approved by DEM that the municipality has certified that
the application is in compliance with all local ordinances.
D. OWTS Suitability
Determination - An OWTS Suitability Determination is a determination
as to whether or not an existing OWTS is suitable for a proposed
building construction, renovation or change of use so as to protect
public health and the environment. For OWTS with no available
records, a Class II or Class III Licensed Designer may prepare an
engineering analysis that must show the OWTS complies with current
rules. An OWTS Suitability Determination Application may be submitted
to the Department in order to determine the applicability of this
rule. OWTS suitability is determined by the following:
1. Excluding holding tanks,
for OWTSs where all components have been installed with State
approval on or after April 9, 1968:
a. The OWTS is suitable and no
application to the Department is necessary for any building
construction, renovation or change in use, that, for residential
uses, does not result in an increase in the number of bedrooms in a
residential structure beyond the number in the original State
approval; or, for all other uses, an increase in the wastewater flow
greater than the OWTS approved design flow for any OWTS. However, the
OWTS is unsuitable and an OWTS Application for New Building
Construction or an OWTS Application for Alteration to a Structure,
whichever is applicable, must be submitted when any of the following
in §§ 6.18(D)(1)(a)((1)) through ((3)) of this Part apply, even if
there is no increase in number of bedrooms or increase in flow:
(1) Whenever the proposed
construction or renovation changes the structure’s footprint such
that the OWTS is not in compliance with these rules;
(2) If the proposed change of
use is from a facility that does not prepare food to a restaurant or
other facility that prepares food; or
(3) For a change in use, if
the OWTS for the new use meets the definition of a large OWTS
pursuant to § 6.39(A) of this Part.
b. The OWTS is unsuitable if
the OWTS is located within the Salt Pond or Narrow River Critical
Resource Areas, includes any existing components permitted and
installed prior to February 6, 2002, and does not utilize nitrogen
reducing technology in accordance with § 6.43(B) of this Part at the
time of application and the applicant proposes building construction
or renovation meeting any of the conditions listed below in §§
6.18(D)(1)(b)((1)) and ((2)) of this Part. In-kind (i.e. same number
of bedrooms) replacement of mobile homes in a licensed mobile and
manufactured home park is exempt from this provision § 6.18(D)(1)(b)
of this Part.
(1) Increasing the total
enclosed area of the structure by more than six hundred (600) square
feet. All construction on each floor shall be counted towards the six
hundred (600) square foot total for the structure. Any change to the
building footprint shall not encroach on the setback distances
established in § 6.23 of this Part so as to require physical
modification of the OWTS. Garages are exempt from this provision §
6.18(D)(1)(b)((1)) of this Part provided they do not encroach on the
setback distances established in § 6.23 of this Part; or
(2) Involves demolition or
replastering or replacement of interior wallboard, interior walls,
ceilings, flooring, windows, plumbing fixtures, electrical wiring or
kitchen cabinetry, which in total affects over fifty percent (50%) or
more of the living area of the existing structure.
c. The OWTS is unsuitable for
any building construction, renovation, or change of use, that results
in an increase in the number of bedrooms in a residential structure
beyond the number in the original State approval; or an increase in
the wastewater flow greater than the OWTS approved design flow for
any OWTS. An OWTS Application for New Building Construction or an
OWTS Application for Alteration to a Structure shall be required in
accordance with §§ 6.18(E) or (F) of this Part, respectively,
whichever is applicable, before the proposed building construction,
renovation or change of use may be allowed.
2. For OWTSs where any
existing components have been installed without State approval,
holding tanks, cesspools, and OWTSs installed prior to April 9, 1968:
Whenever a person proposes any building construction, renovation, or
change of use (as defined in § 6.8 of this Part) of a structure
served by such an OWTS, the OWTS is unsuitable and shall be upgraded
to the standards herein. An OWTS Application for New Building
Construction or an OWTS Application for Alteration to a Structure
shall be required in accordance with §§ 6.18(E) or (F) of this
Part, respectively, whichever is applicable. For the purposes of this
rule, the terms "building construction” and “building
renovation" shall be defined as any addition, replacement,
demolition and reconstruction, or modification of a structure on the
subject property which:
a. Results in any increase in
wastewater flow into the OWTS, which for residential structures is
equivalent to the addition of one (1) or more bedrooms;
b. Involves demolition or
replastering or replacement of interior wallboard, interior walls,
ceilings, flooring, windows, plumbing fixtures, electrical wiring or
kitchen cabinetry, which in total affects over fifty percent (50%) or
more of the living area of the existing structure. In-kind (i.e. same
number of bedrooms) replacement of mobile homes in a licensed mobile
and manufactured home park is exempt from this provision §
6.18(D)(2)(b) of this Part;
c. Involves adding an
additional floor level or portion of floor level to the structure; or
d. Increases the footprint of
enclosed space of the structure. Garages are exempt from this
provision § 6.18(D)(2)(d) of this Part provided they do not encroach
on the setback distances established in § 6.23 of this Part. In-kind
(i.e. same number of bedrooms) replacement of mobile homes in a
licensed mobile and manufactured home park is exempt from this
provision § 6.18(D)(2)(d) of this Part.
3. Imminent Sewer Exemption -
An owner subject to the requirements of §§ 6.18(D)(1)(a)(1) through
(3), § 6.18(D)(1)(b), § 6.18(D)(1)(c), or § 6.18(D)(2) of this
Part whose property is proposed to be served by a public wastewater
system in the future shall be exempt from those requirements,
provided an OWTS Suitability Determination Form is submitted to the
local building official demonstrating that all of the conditions in
§§ 6.18(D)(3)(a) and (b) of this Part are met. A copy of the
completed form shall be provided to the Department. In order to claim
exemption, the owner must:
a. Provide a letter
demonstrating that the municipality holds a form of financial surety
for expansion of a public wastewater system to the area of the
structure served by the OWTS within five (5) years of the date of the
submission of the OWTS Suitability Determination Form; and
b. Certify that:
(1) The OWTS is not failed;
(2) For a residential
structure, any increase in wastewater flow to the OWTS is limited to
that equivalent to one bedroom. For all other uses, no increase in
wastewater flow to the OWTS is allowed; and
(3) The structure will be
connected within sixty (60) days of the public wastewater system
becoming available.
E. OWTS Application for New
Building Construction - All OWTS Applications for New Building
Construction shall be made in conformance with all requirements under
these rules. Applications not in conformance with these rules may be
approved only through the variance procedures set forth in § 6.51 of
this Part.
1. An OWTS Application for New
Building Construction shall be made whenever an applicant proposes
to:
a. Construct a new structure
from which wastewater will be disposed of by means of an OWTS;
b. Modify a structure, not
previously permitted to dispose of wastewater, to require the
disposal of wastewater to an OWTS;
c. Increase wastewater flow to
an OWTS by an amount greater than twenty‑five percent (25%) of
the original design flow with all flows adjusted using the design
flows in § 6.22 of this Part, provided that using the design flows
and loading rates in these rules would result in a leachfield larger
than that previously approved by the Department; or
d. Add more than one bedroom.
2. All plans and
specifications for an OWTS Application for New Building Construction
shall be prepared by a Class II or Class III Licensed Designer in
accordance with §§ 6.10 and 6.11 of this Part.
3. No person shall submit
applications, plans and specifications to the Director for an OWTS
for New Building Construction without first obtaining the Director's
acceptance of a soil evaluation or field concurrence with the soil
evaluation in accordance with § 6.16 of this Part. If the Director
concurs with the determination of the soil evaluation in accordance
with § 6.16(E)(3)(a) of this Part and the soil conditions meet the
minimum requirements of these rules, the soil evaluation may be
submitted with the application for an OWTS permit.
F. OWTS Application for
Alteration to a Structure
1. An OWTS Application for
Alteration to a Structure shall be made whenever an applicant
proposes any physical alteration to a structure that meets any of the
following:
a. In the case of a residence,
the addition of not more than one bedroom;
b. In all other cases, an
increased flow of wastewater in an amount less than or equal to
twenty‑five percent (25%) of the original design flow adjusted
using the design flows in § 6.22 of this Part provided that using
the design flows and loading rates in these rules would result in a
leachfield larger than that previously approved by the Department; or
c. If the OWTS is determined
to be unsuitable pursuant to § 6.18(D) of this Part with no increase
in flow.
2. All plans and
specifications for an OWTS Application for Alteration to a Structure
shall be prepared by a Class II or Class III Licensed Designer in
accordance with §§ 6.10 and 6.11 of this Part. The Director
reserves the right to require that the plans and specifications for
an OWTS Application for Alteration to a Structure be prepared by a
Class III Licensed Designer.
3. No person shall submit
applications, plans and specifications to the Director for an OWTS
for an Alteration to a Structure without first obtaining the
Director's acceptance of a soil evaluation or field concurrence with
the soil evaluation in accordance with § 6.16 of this Part. If the
Director concurs with the determination of the soil evaluation in
accordance with § 6.16(E)(3)(a) of this Part and the soil conditions
meet the minimum requirements of these rules, the soil evaluation may
be submitted with the application for an OWTS permit.
4. Applicants shall meet the
requirements of these rules to the greatest extent possible. The
applicant shall identify which rules, if any, the proposed OWTS fails
to meet. If necessary, certain requirements under these rules may be
relaxed at the discretion of the Director, provided that the
applicant considers the Department approved alternative or
experimental technology in accordance with § 6.41 of this Part that
may allow the applicant to meet most of the requirements of these
rules. The protection of the public health and the environment shall
be given priority over all other considerations. Nothing herein shall
prevent the Director from requesting additional information or
imposing any requirement under these rules. Variance application
procedures will only apply to OWTS Applications for Alteration to a
Structure that propose an increase in wastewater flow. OWTS
Applications for Alteration to a Structure that include a request for
a variance from the provisions of these rules are exempt from the
notification requirements in § 6.51(F)(1) of this Part.
G. OWTS Application for Repair
‑ An application for a repair of any OWTS, or any component
thereof, shall be made when an OWTS or component has failed, as
defined by § 6.8 of this Part. An application for repair shall not
propose any change of use, building renovation pursuant to §§
6.18(D)(2)(a) through (d) of this Part or any increased flow to the
OWTS. The Department may allow an OWTS Application for Repair to be
submitted when, after the effective date of these rules, a fire or
other catastrophic occurrence necessitates that a structure served by
an OWTS be replaced. The applicant may also submit an OWTS
Application for Repair when the property owner desires to upgrade or
modernize the OWTS (e.g., replacement of cesspool).
1. All plans and
specifications for an OWTS application for Repair shall be prepared
by a Class I, II or III Licensed Designer in accordance with §§
6.10 and 6.11 of this Part. The applicant is not required to have a
soil evaluation pursuant to § 6.16 of this Part prepared unless the
Department specifies otherwise. The Director reserves the right to
require that the plans and specifications for a repair be prepared by
a Class II or Class III Licensed Designer.
2. Applicants shall meet the
requirements of these rules to the greatest extent possible. If
necessary, certain requirements under these rules may be relaxed at
the discretion of the Director, provided that such modification is
consistent with the protection of the public health and the
environment. In reviewing any request for relaxation of these rules,
the protection of the public health and the environment shall be
given priority over all other considerations.
3. Deep concrete chambers will
not be permitted for OWTS Applications for Repair where another type
of leachfield designed in accordance with §§ 6.33, 6.34, and 6.35
of this Part can be sited and is deemed acceptable by the Department.
The Licensed Designer must demonstrate that the repair alternatives
to a deep concrete chamber, other than a bottomless sand filter or
pressurized shallow narrow drainfield, are not feasible.
4. Exemptions for OWTS
Application for Repair - Under the limited circumstances in §§
6.18(G)(4)(a) through (e) of this Part, an OWTS Application for
Repair will not be necessary prior to repairing the OWTS. Any repair
or installation work done in accordance with §§ 6.18(G)(4)(a)
through (e) of this Part that is found not to be in compliance with
these rules, will have to be corrected and will be considered a
violation of these rules.
a. Septic Tank Replacement -
When a crushed tank or other failure necessitates replacement to
maintain wastewater handling capacity at a facility and averting a
public health threat, the installer must receive verbal authorization
from the Department prior to septic tank installation and the owner
must submit a proper and complete repair application by the end of
the next business day.
b. Building Sewer - Replacing
a crushed or otherwise repairing a faulty building sewer between the
building and the septic tank does not require prior authorization of
the Department or notification to the Department once the work is
completed.
c. Access Openings - The
following work on access openings does not require prior
authorization of the Department or notification to the Department
once the work is completed:
(1) Installation of access
openings to finished grade; and
(2) Compliance with the
requirements to upgrade the cover of existing tanks that have access
openings to finished grade in accordance with §§ 6.26(L), 6.27(O),
6.29(G), 6.30(H), and 6.35(H)(2)(d) of this Part.
d. Retrofitting for a septic
tank effluent screen - Such work does not require prior authorization
of the Department or notification to the Department once the work is
completed.
e. In-kind emergency
replacement of a failed mechanical or electrical device does not
require prior authorization of the Department or notification to the
Department once the work is completed.
H. Unacceptable Application -
When the Department determines that an application is unacceptable
for any reason, the applicant has one (1) year from the date of the
unacceptable notice to correct all deficiencies identified by the
Department. However, if any of the deficiencies are related to an
application to the DEM Freshwater Wetlands Program or a Rhode Island
Department of Health Public Drinking Water New Source Approval
Application, the applicant has two (2) years from the date of the
unacceptable notice to correct all deficiencies identified by the
Department. If all of the deficiencies are not corrected in the time
specified above, the applicant must submit a new application and
application fee.
I. Suspension of Application
Process - The Department may, at its discretion, suspend the
processing of an application if the property that is the subject of
the OWTS Application is the subject of any unresolved violation of
these rules, or which is the subject of any non-compliance with a
Department, administrative, or judicial consent agreement, order, or
judgment. The Department shall notify the applicant in writing of the
suspension.
J. Public Records - All
applications received by the Department of Environmental Management
are subject to the Public Records Act, R.I. Gen. Laws Chapter 38‑2,
and are available in accordance with the Act for public inspection
and copying at the OWTS Program of DEM between the hours of 8:30 AM
and 4:00 PM; a prior appointment may be required. A fee for such
copying shall be charged in accordance with R.I. Gen. Laws § 38‑2‑4.
6.19 Required Content of OWTS
Submissions
A. Application - All
applications for the approval of plans and specifications for OWTS
permits shall be made on forms approved by the Director. Nothing in
these rules shall prevent the Director from requiring any additional
information deemed necessary to carry out obligations in enforcing
these rules.
B. Plan - All applications for
New Building Construction, Alterations to a Structure, or redesigns
of previously approved applications for New Building Construction or
Alterations to a Structure, except those submitted under §
6.20(A)(1)(c) of this Part, shall be accompanied by four (4) sets of
plans that include a plan view of the entire property drawn to scale,
a plan view of the pertinent portion of the property at a minimum
scale of one (1) inch equals forty (40) feet, a profile of the system
from the building foundation to the limits of the leachfield with
invert elevations shown, and a cross-section of the leachfield. The
plans shall include the items below. The Director reserves the right
to require any additional information that is deemed necessary. For
applications submitted under § 6.20(A)(1)(c) of this Part, six (6)
sets of plans must be included.
1. Location map;
2. Rhode Island Coastal
Resources Management Council jurisdictional line, if applicable;
3. The size and location of
the OWTS;
4. A fixed benchmark within
one hundred fifty (150) feet of the OWTS that will not be disturbed
during construction;
5. The location of all test
holes;
6. The existing and proposed
finished grades in the vicinity of the OWTS;
7. The size and location of
all existing and proposed buildings and the number of bedrooms and
other building features used to determine the maximum daily flow
contained therein;
8. The location of any public
wastewater system line within two hundred (200) feet of the property
lines;
9. The location of any
drinking water line within fifty (50) feet of the proposed OWTS;
10. Wells:
a. The location of existing
and proposed private drinking water wells within the setback distance
from the leachfield specified in § 6.23(E) of this Part plus one
hundred (100) feet;
b. The location of all
existing and proposed wells serving non-potable uses within one
hundred (100) feet of the leachfield;
c. The location of existing
and proposed public drinking water supply wells within five hundred
(500) feet of the proposed OWTS and a determination as to whether the
public well is a bedrock well or a gravel packed, gravel developed or
driven well; and
d. The location of any
existing or proposed drinking water well, public or private, serving
the structure that the proposed OWTS will serve;
11. The location of all
watercourses, wetlands, and drains within two hundred (200) feet of
the proposed OWTS;
12. The location of all
stormwater management structures and subsurface drains within two
hundred (200) feet of the proposed OWTS and a determination and
whether said drain discharges, directly or indirectly, into a
critical resource area as identified in § 6.42 of this Part;
13. Plans must indicate if the
proposed OWTS is within a Critical Resource Area as identified in §
6.42 of this Part and must specify the distance to the nearest
critical resource of concern. If the Critical Resource Area boundary
crosses the parcel that is the subject of the application, the
boundary line shall be shown.
14. The location and design
flow of all existing OWTSs within two hundred (200) feet of any
private well and four hundred (400) feet of any public well shown in
accordance with § 6.19(B)(10) of this Part on the subject property.
Plans must also show the location and design flow of any existing
OWTS with a design flow of greater than one thousand (1,000) gallons
per day within four hundred (400) feet of any well to be installed on
the subject property. Records and data on file with the Department
may be used to obtain information on proposed OWTSs and wells;
15. Areas on the subject
property where soil has been excavated and where storm deposited sand
in the backdune environment or human transported material has been
deposited;
16. Details of all system
components;
17. Erosion controls;
18. Plat and lot boundaries
and numbers;
19. Title block, legend and
north arrow;
20. Signature and stamp where
applicable of the Licensed Designer;
21. The location of driveway
access from the roadway to the proposed dwelling; and
22. The location of all
structures, existing OWTSs, and water supplies within one hundred
(100) feet of all adjacent property lines.
C. Additional Information -
Other information to be provided by the applicant shall include, but
not be limited to, the items listed below:
1. Soil evaluation for OWTS
Applications for New Building Construction and for OWTS Applications
for an Alteration to a Structure and those that were required by the
Director for OWTS Applications for Repair;
2. Results of seasonal high
groundwater table determinations and percolation tests for lots not
required to conduct a soil evaluation;
3. Determination of the
potential for flooding on the subject property; and
4. Copy of the municipal
property tax card for all OWTS Applications for Alterations to a
Structure and OWTS Applications for Repair.
D. Applications for Repair -
Applications for repair shall at a minimum include information
specified on the Department’s “OWTS Repair Submission
Requirements” document (this document can be found at:
http://www.dem.ri.gov/programs/benviron/water/permits/isds/pdfs/rprcklst.pdf).
E. Application for Transfer -
Applications for transfer of an approved OWTS application shall
include the items listed below.
1. New OWTS application form
signed by the new owner;
2. Copy of the current valid
approval; and
3. Proof of ownership of the
property served by the proposed OWTS.
6.20 Applications Involving the
DEM Freshwater Wetlands Program and the Coastal Resources Management
Council
A. Applications Involving the
DEM Freshwater Wetlands Program
1. All applications pursuant
to these rules associated with a construction project which may
affect a freshwater wetlands regulated by the Department shall be
submitted in accordance with §§ 6.20(A)(1)(a), (b), or (c) of this
Part:
a. The OWTS application may be
accompanied by the appropriate determination or permit required by
the DEM Freshwater Wetlands Program. Accordingly, where an applicant
proposes to construct OWTS, the applicant must apply for and receive
the appropriate determination or permit from the Freshwater Wetlands
Program prior to submission to the OWTS Program;
b. The applicant may submit
applications to the Freshwater Wetlands Program and the OWTS Program
at the same time. No OWTS Application for a construction project
which may affect a freshwater wetlands will be approved without the
appropriate determination or permit from the Freshwater Wetlands
Program; or
c. For Applications for New
Building Construction or Applications for Alteration to a Structure
on a single family house lot in proximity to DEM’s Freshwater
wetlands permitting jurisdiction, the applicant may submit a joint
OWTS/Freshwater Wetlands application on a form approved by the
Director for this purpose. Approval of a joint OWTS/Freshwater
Wetlands application will be held to satisfy both sets of regulations
and include conditions as may be needed. Permits issued under this
process may not be renewed.
2. If the Department
determines that there is a reasonable doubt as to the location of a
freshwater wetlands boundary or applicability of the DEM Rules and
Regulations Governing the Administration and Enforcement of the
Freshwater Wetlands Act to a proposed new construction or new
installation of an OWTS, the Department may require that the
applicant obtain a separate determination or permit from the
Department pursuant to said Wetlands regulations.
3. Erosion and sedimentation
controls shall be designed, shown on plans, installed, operated and
maintained to protect any wetland or watercourse from potential
adverse effects of the construction project associated with an
approved OWTS application.
B. Applications Involving the
Rhode Island Coastal Resources Management Council
1. The Rhode Island Coastal
Resources Management Council has authority over construction proposed
in certain coastal regions of the State. The coastal region includes:
All coastal features and all land within two hundred (200) feet of
tidal waters, salt water ponds, salt water marshes, salt water
wetlands or other land subject to Coastal Resources Management
Council jurisdiction. Review of impacts to “freshwater wetlands in
the vicinity of the coast” is under the sole jurisdiction of the
Coastal Resources Management Council in accordance with the “Rules
and Regulations Governing the Protection and Management of Freshwater
Wetlands in the Vicinity of the Coast.”
2. The Director reserves the
right to request the applicant to obtain a Preliminary Determination
from the Rhode Island Coastal Resources Management Council. The
applicant is required to obtain a Preliminary Determination from the
Coastal Resources Management Council prior to submitting any OWTS
Application that includes a variance request pursuant to § 6.51 of
this Part for OWTS located within two hundred (200) feet of the
inland edge of the coastal shoreline feature bordering a tidal water
area (corresponding to the jurisdiction of the Rhode Island Coastal
Resources Management Council). For OWTS Applications for New Building
Construction and OWTS Applications for Alteration to a Structure
proposing an OWTS that has a design flow greater than two thousand
(2,000) gallons per day for any single system or design flow greater
than two thousand (2,000) gallons per day for any combination of
systems owned or controlled by a common owner, applicants must
receive a Preliminary Determination from the Coastal Resources
Management Council before submitting an application for an OWTS to
the DEM unless the OWTS Application provides sufficient information
to determine the location of the coastal shoreline feature. After
receiving a permit for an OWTS from the Director, the applicant
should consult with the Coastal Resources Management Council before
undertaking any construction on the property. It is the applicant’s
responsibility to obtain a Coastal Resources Management Council
permit if necessary.
6.21 Subdivisions
A. Administrative
1. No person shall begin
construction in any subdivision requiring a Subdivision Site
Suitability Certification in accordance with this rule until the
Director has approved such certification.
2. Any subdivision of five (5)
lots or less that does not have frontage on an existing road and all
subdivisions of six (6) lots or more shall apply for a Subdivision
Site Suitability Certification in accordance with § 6.21(B) of this
Part.
3. Subdivisions of five (5)
lots or less that have frontage on an existing road have the option
to apply for a Subdivision Site Suitability Certification pursuant to
§ 6.21(B) of this Part or submit OWTS applications for individual
lots in accordance with § 6.18 of this Part. If applications for
individual lots are submitted, the submittal shall be in accordance
with the following:
a. The applications must be
submitted together;
b. Each application shall
clearly state that the lot is part of a subdivision of five (5) lots
or less with existing road frontage; and
c. Each lot must meet all
requirements of these rules in order for an OWTS permit to be issued
by the Department for any of the lots.
4. Subdivision Soil Evaluation
- A soil evaluation shall be conducted for each lot in accordance
with § 6.16 of this Part. Soil evaluations for subdivisions are
exempt from the requirement in § 6.16(I)(1) of this Part that the
test holes be within twenty-five (25) feet of the proposed
leachfield, unless the Director determines that soil conditions
justify that the test holes must be placed within twenty-five (25)
feet of the proposed leachfield. Soil evaluations must be accepted by
the Director prior to submission of an application for Subdivision
Site Suitability Certification.
5. An approved Subdivision
Site Suitability Certification shall not operate as an approval for
the construction of any OWTS as required by § 6.18 of this Part.
6. Land within the original
property boundaries that is designated for future development will
not be part of the review for Subdivision Site Suitability
Certification. However, it must be shown that one (1) unit can be
built on the land designated for future development.
7. OWTSs installed without
State approval, OWTSs installed prior to April 9, 1968 and cesspools
on existing lots in a proposed subdivision shall be upgraded to the
current standards, to the extent possible, in accordance with these
rules as part of a Subdivision Site Suitability Certification within
one (1) year of the recording of the subdivision.
8. The applicant for a
Subdivision Site Suitability Certification must demonstrate that the
OWTS for the proposed use on each proposed lot in a subdivision meets
all the requirements of these rules in order for a Subdivision Site
Suitability Certification to be issued by the Department.
9. Nothing in this § 6.21 of
this Part shall prevent the Director from requesting any or all of
the procedures established in these rules for a single lot if the
Director determines it is necessary for the protection of the public
health and environment.
10. Easement Filing - Where
subdivision lots will require filling beyond lot lines, an easement
for that human transported material must be submitted with the
application for the individual lots.
B. Subdivision Site
Suitability Certification - Application for Subdivision Site
Suitability Certification shall be prepared by a Class II or Class
III Licensed Designer, as appropriate, on forms approved by the
Director and shall include the information in §§ 6.21(B)(1) through
(5) of this Part and any other information the Director may require.
The application for Subdivision Site Suitability Certification will
be reviewed for all information necessary to determine the
suitability of a parcel of land to be divided as shown on the
application.
1. Location Map - A location
map or sketch showing existing highways, streets and/or other
identifiable landmarks or distances thereto, shall be furnished to
facilitate an inspection of the site. This may be incorporated on the
topographic map.
2. Soil Survey - A copy of the
page or pages of the latest Soil Survey published by the Natural
Resource Conservation Service of the U.S. Department of Agriculture
illustrating the location of the subdivision.
3. Topographic Map
a. The topographic map shall
show ground elevations on the tract as follows:
(1) For land that slopes less
than approximately two (2) percent, show spot elevations at all
breaks in grade, along all drainage channels or swales, and at
selected points not more than one hundred (100) feet apart in all
directions; and
(2) For land that slopes more
than approximately two (2) percent show broken line contours with an
interval of not more than two (2) feet.
b. The datum on which the
elevations or contours are based shall be reported including a
permanent reference benchmark. Where cut or fill of more than one (1)
foot can be anticipated and estimated, it should be indicated by
solid line contours showing approximate finished grade. Plan and
profile showing existing and proposed finished grades of proposed
roads must be provided.
c. The topographic map shall
show the following for the entire area of the subdivision:
(1) Proposed house locations;
(2) Existing structures,
public and private water supplies and OWTSs;
(3) Rights of way or
easements;
(4) Watercourses,
drainageways, and drainage basins;
(5) Rock outcrops and wooded
areas;
(6) Stone walls;
(7) Location of proposed water
supplies and OWTSs on lots within the subdivision conforming with
requirements of § 6.23 of this Part;
(8) Location of test holes
used for the soil evaluation; and
(9) Location of any critical
resource area as defined in § 6.42 of this Part within the property.
4. For lands immediately
adjacent to the subdivision, the items below shall be shown,
designated or reported. Distances below shall be determined from the
subdivision property boundary.
a. Watercourses within two
hundred (200) feet;
b. Private drinking water
wells (existing and those proposed on an approved OWTS permit) within
two hundred (200) feet;
c. Public wells (existing and
proposed) approved by the Rhode Island Department of Health within
five hundred (500) feet; and
d. Location of any existing
OWTS or drain within one hundred (100) feet of the property.
5. Water Quality Assessment -
Where in the opinion of the Director, a substantial question exists
regarding the cumulative impact of the operation of OWTSs within the
subdivision on surface water or groundwater quality, the Director may
require an assessment of such potential cumulative impacts, including
appropriate studies, to be submitted by the applicant. This
assessment may include, but not be limited to, a determination of
whether the operation of the OWTSs will result in a loss of a use or
violation of a surface water or groundwater quality standard assigned
to that body of groundwater or surface water in question as
designated by the Department.
6. Certification - The
Subdivision Site Suitability Certification shall be accompanied by a
certification, on a form approved by the Director, that the work was
conducted in a manner consistent with these rules and that it is an
accurate portrayal of site conditions. If more than one individual
licensed under these rules participated in the development of the
subdivision site suitability report, the report must specify who
prepared which part and include a certification from each licensee.
C. Expiration of Subdivision
Site Suitability Certification-
1. Except for permits eligible
for tolling pursuant to R.I. Gen. Laws § 42-17.1-2.5 as provided in
§ 6.21(C)(2) of this Part, a Subdivision Site Suitability
Certification shall expire five (5) years from the date of issuance
unless the subdivision has been platted or recorded as evidenced by
the submission of a copy of the recorded subdivision plat map. After
expiration, certification may be obtained only by reapplying under
the rules in effect at the time of re-application. Once a subdivision
has been platted or recorded, no further certification shall be
required and all lots may proceed with the application process for
their OWTS in accordance with these rules.
a. In the event that there is
any change in the configuration of any lot or road depicted in an
approved Subdivision Site Suitability Certification, the applicant
shall submit revised subdivision layout plans to the Department for
its review. If the changes to the subdivision are found to be
substantial, the Director may order the applicant to apply for a new
Subdivision Site Suitability Certification based on the new plans.
b. Whenever the configuration
of any lot or road in a subdivision depicted in an approved
Subdivision Site Suitability Certification is altered so as to affect
twenty-five percent (25%) or more of the original lots, a new
Application for Subdivision Site Suitability Certification shall be
submitted.
2. Subdivision Site
Suitability Certifications that were valid on, or issued after
November 9, 2009 that are subject to tolling pursuant to R.I. Gen.
Laws § 42-17.1-2.5 shall be tolled for the period provided by R.I.
Gen. Laws § 42-17.1-2.5 and expire on the date five (5) years after
approval plus the tolling period in accordance with said statute,
unless the subdivision has been platted or recorded as evidenced by
the submission of a copy of the recorded subdivision plat map.
6.22 Wastewater Flow
A. Determination of Wastewater
Flow
1. An OWTS must be designed to
dispose of the estimated maximum daily flow from the building(s) it
serves. The maximum daily flow is estimated by multiplying flow per
unit from § 6.22(B) of this Part by the maximum design capacity of
the building. For facilities with more than one use listed in §
6.22(B) of this Part (e.g., a retail store with a restaurant), the
maximum daily flow for the facility shall be the total of the flows
from the separate uses using § 6.22(B) of this Part. The employee
contribution to the design flow shall be included for non-residential
uses other than restaurants by estimating the maximum number of
employees who may be present during a single day of operation
multiplied by a design flow of 15 gallons per person per day.
2. For establishments not
listed in § 6.22(B) of this Part, the maximum daily flow shall be
determined by either of the following:
a. Two (2) times the average
daily meter reading taken from a minimum of two (2) comparable
establishments for one (1) month during the period of the year that
represents the greatest water use for the establishment; or
b. If six (6) months of daily
meter readings are available for a minimum of two (2) comparable
establishments that includes the period of the year that represents
the greatest water use for the establishment, the OWTS shall be
designed using the highest daily flow without the use of a peaking
factor.
B. Wastewater Design Flows
TYPE
OF USE
UNIT
GALLONS
PER DAY
RESIDENTIAL
[Minimum
design flow for residential use shall be three hundred forty-five
(345) gallons per day (three (3) bedrooms), unless otherwise
permitted in accordance with § 6.22(D) of this Part.]
Single
family residence
per
bedroom (2 persons per bedroom)
115
Multiple
family residence
per
bedroom (2 persons per bedroom)
115
INSTITUTIONAL
Assisted
living facility
per
bedroom (2 persons per bedroom)
115
Church
per
seat
1
Church
hall (fellowship hall)
per
seat
5
Hospital
per
bed
150
Library
per
visitor
5
Nursing
home/rest home
per
bed
125
Group
home
per
bed
200
Correctional,
rehabilitation facility
per
bed
100
Gymnasium
per
seat
3
Gymnasium
per
participant
15
Highway
rest stop
per
person
5
Public
park with toilets
per
person
5
add
for showers
per
person
10
CAMPS
AND CAMPGROUNDS
Day
camp
per
person
15
add
for mess hall
per
person/meal
3
Camp
- overnight
per
person
25
add
for mess hall
per
person/meal
3
Campground
with washroom and toilets
per
site
50
Recreational
vehicle park with water service
per
site
100
Add
for central dining facilities
per
seat
35
Recreational
vehicle park without water service
per
site
50
Add
for central dining facilities
per
seat
35
Add
for central washroom and toilet facilities
per
site
50
SCHOOLS
School
per
person
10
add
for cafeteria
per
person
5
add
for gymnasium and showers
per
person
10
Boarding
school, college
per
person
50
Day
care center
per
person
10
RESTAURANTS
[Minimum
design flow for restaurants shall be 500 gallons per day.]
Restaurant
per
seat
40
Restaurant
- with single-service articles
with
public restrooms
per
seat
25
without
public restrooms
per
seat
20
add
for drive-up window
500
Lounge,
bar (no food service at that seat)
per
seat
10
Banquet
hall
per
seat
5
Ice
cream parlor, take out service only
per
store
500
COMMERCIAL
[Minimum
design flow for commercial use shall be 100 gallons per day]
Auto
service station
per
pump
25
per
repair bay
100
Barber
shop/Beauty salon
per
chair
50
add
for sink
per
hair care sink
200
Bed
& Breakfast
per
bedroom
110
Bowling
alley
per
alley
100
Catering
kitchen, no food service on-site
per
meal prepared
3
Country
club
dining
room
per
seat
40
snack
bar/lounge
per
seat
20
lockers
and showers
per
locker
20
Doctors
/Chiropractor/ Therapist office
per
doctor/chiropractor/therapist
250
Dog/Pet
grooming
per
station
500
Dentist
office
per
chair
200
Drive-in
theater
per
vehicle stall
5
Factory/Industrial
plant
per
person
15
add
for cafeteria
per
person
5
Food
store < 5,000 square feet (See Note 1)
per
store
350
add
for deli flow
per
store
100
add
for bakery flow
per
store
100
add
for meat dept. flow
per
store
150
add
for fish market flow
per
store
150
add
for public restrooms
per
store
200
Food
store > 5,000 square feet (See Note 1)
per
store
700
add
per
square foot>5,000 sq ft
0.05
add
for deli flow
per
store
200
add
for bakery flow
per
store
200
add
for meat dept. flow
per
store
300
add
for fish market flow
per
store
300
add
for public restrooms
per
store
400
Funeral
home
per
parlor
500
Hotel,
motel
per
unit
100
With
efficiency units
per
unit
150
Health
club
per
participant
15
Kennel
per
kennel
10
Marina
(shore-side facilities)
per
slip
10
add
for showers
per
slip
10
Mobile
home park/Manufactured home park
per
site
230
Office
building
per
employee
15
Retail
store
per
employee
15
Rooming
house/Boarding house
per
bedroom
80
Self-Service
Laundry (See Note 2)
per
machine
500
Shopping
center/Strip mall/Multi-use retail
Calculate
on the largest of either:
a)
the total flow for the uses within as determined from this
table, or
b)
per square foot
per
square foot
0.1
Skating
rink
per
seat
3
Swimming
pool
per
person
15
Tennis
court - outdoor
per
court
100
Tennis
court - indoor
per
court
400
Theater,
auditorium
per
seat
3
Veterinary
office
per
veterinarian
200
Notes:
(1)The
design flow for a stand alone deli, bakery, meat store or fish
market will be three hundred fifty (350) gallons per day if the
facility is less than five thousand (5,000) square feet or seven
hundred (700) gallons per day if the facility is five thousand
(5,000) square feet or more.
(2)Self-Service
laundry OWTS designs must include pretreatment to remove lint from
the wastewater.
C. Determining the Number of
Bedrooms in a Single Family Residential Dwelling - For purposes of
aiding the planning, designing, building, renovation, remodeling or
expansion of residential dwellings, the following guidelines shall be
used in determining the number of bedrooms. These guidelines are
presented in acknowledgement that, in many cases, houses contain
rooms meeting the strict definition of bedroom as defined in these
rules, but which are not intended to be nor will be used as bedrooms.
1. No residence served by an
OWTS shall be allowed to have more bedrooms than is permitted under
the Department issued permit for the OWTS serving the dwelling. A
dwelling exceeding the number of bedrooms provided for in the permit
shall be in violation of these rules.
2. In determining the number
of bedrooms contained in any residence, it shall be presumed that all
residences contain a living room, a kitchen, a bathroom and at least
one (1) bedroom.
3. For OWTSs installed without
State approval, OWTSs installed prior to April 9, 1968 and cesspools,
the determination on number of bedrooms shall be based on the
consideration of municipal records, floor plans and the guidelines
herein. In the case of a one (1) bedroom residence, the determination
shall be based on municipal records.
4. When a determination of the
number of bedrooms shall be based on total number of rooms, §
6.22(D) of this Part shall be used. Foyers, closets, bathrooms and
rooms without windows are not counted as rooms in § 6.22(D) of this
Part. Functionally combined kitchens/dining rooms and living/dining
rooms greater than three hundred (300) square feet shall be counted
as two (2) rooms. § 6.22(D) of this Part may be used by applicants
for any OWTS application to the Department.
D. Determination of Number of
Bedrooms
Total
Number of Rooms
Assumed
Number of Bedrooms
5
or less
2
6-7
3
8-10
4
11-12
5
13
or more
6
1. The Director may permit the
filing of a deed restriction by which an applicant may self-restrict
the use of a residence to one less bedroom than may be determined in
accordance with § 6.22(D) of this Part. In no case shall the deed
restriction be for less than two bedrooms. The Director may consider
the gross square footage of a residence as a factor against granting
a bedroom restriction by deed.
E. Separate OWTSs- Where
residential uses need to install separate OWTSs, the following
proportions of the total flow shall be used unless there is definite
data available as to the exact distribution of flow: blackwater forty
percent (40%) and graywater sixty percent (60%). If a separate system
is used for laundry wastes, it shall be designed on twenty percent
(20%) of the total flow.
F. Misrepresented Applications
- An OWTS Application that has been approved but later shown to
contain faulty or misrepresented information shall not, in and of
itself, be used to determine the number of bedrooms in a residential
dwelling or the design flow for a non-residential structure.
6.23 Minimum Setback Distances
A. The horizontal distances
between the parts of an OWTS and the items listed in §§ 6.23(B)
through (E) of this Part shall not be less than those shown. Where a
proposed OWTS cannot meet the horizontal distances in §§ 6.23(B)
through (E) of this Part a variance request shall be required
pursuant to § 6.51 of this Part unless the setback reduction is
specifically allowed in Notes accompanying each Table.
B. Minimum Setback Distances -
General
Building
Sewer, Grease Tank, Distribution Box, Pump Tank, Septic Tank,
Septic Tank Effluent Pipe (ft) (Note 12)
Leachfield
(ft)
(Note 12)
Well
Serving Non-potable Uses (Note 13)
25
50
Water
Supply Line
10
(Note
1)
25
Property
Line
10
(Note
2)
Design
Flow (gpd)
(ft)
0-2000
10
>2000-5000
Note (3)
50
>
5000
Note
(4)
min.
50 (Note 5)
Foundation
5
(Not
applicable to building sewer)
25
(Note
6)
Subsurface
drains, foundation drains, or storm drains (see also §§ 6.23(C)
and (D) of this Part):
--
Upgradient and side gradient of the OWTS:
--
Downgradient of the OWTS:
15
(Note
7)
25
(Note
7)
25
(Note
8)
50
(Note
9)
Edge
of any land at a level lower than the invert of the distribution
line
10
10
Stormwater
Infiltration System
25
(Note 10)
25
(Note 10)
Swimming
Pools:
In-ground:
Above
ground:
10
10
25
10
Design
Flow <5000 gpd
Design
Flow ?5000 gpd (Note 4)
Design
Flow <5000 gpd
Design
Flow ?5000 gpd (Note 4)
Coastal
Shoreline Feature (Note 11) not in a Critical Resource Area,
Flowing Water (Rivers and Streams), Open Bodies of Water (Lakes
and Ponds), Other Watercourses Not Mentioned Above, and Any
Stormwater Management Structure That Potentially Intercepts
Groundwater
25
50
50
100
Notes:
The reductions in setback distances allowed below in Notes (1)
through (13) will not be granted if the setback distances in §
6.23(B) of this Part can be met. A variance request pursuant to §
6.51 of this Part shall not be required for the reductions
indicated below.
(1)
The distance between the building sewer or septic tank effluent
pipe and a water supply line may be reduced and the lines may
cross provided that either the building sewer or septic tank
effluent pipe or water supply line is sleeved whenever the lines
are within ten (10) feet of each other. The sleeve shall be
seamless or schedule 40 PVC or equivalent with watertight joints
and it shall have a watertight seal that is fastened to the pipes
with a stainless steel retractable clamp. Whenever possible, the
building sewer and septic tank effluent pipe should be laid below
water supply lines at crossings.
(2)
Pressurized building sewers or pressurized septic tank effluent
pipes shall be laid below water supply lines at crossings. If the
setbacks to a water supply line for a public water system cannot
be met, the applicant must obtain, and submit to the Department,
written permission from the water supplier.
(3)
Any single leachfield designed to treat more than two thousand
(2,000) but less than five thousand (5,000) gallons per day.
(4)
As defined in § 6.39(A)(1) of this Part.
(5)
Distance shown is the minimum for upgradient and side gradient
directions. Downgradient separation distance will be based on
nitrate modeling undertaken pursuant to § 6.39 of this Part and
shall be a minimum of fifty (50) feet.
(6)
Distance may be reduced to fifteen (15) feet with no foundation
drain. Full foundation details must be shown on the plan. Distance
may be reduced to eight (8) feet where a foundation slab
elevation, pile foundation, or the basement floor elevation is
higher than the invert of the distribution lines in the
leachfield.
(7)
The distance between the building sewer or septic tank effluent
pipe and a drain may be reduced and the building sewer or effluent
pipe may cross the drain provided that the building sewer or
septic tank effluent pipe is sleeved whenever they are within
twenty-five (25) feet of the drain. The sleeve shall be seamless
or schedule 40 PVC or equivalent with watertight joints, and it
shall have a watertight seal that is fastened to the pipes with a
stainless steel retractable clamp.
(8)
If the slope of the original land surface over the area of the
leachfield and fifty (50) feet in all directions from the edge of
the leachfield is less than three (3) percent, the minimum setback
distance between the leachfield and the drain must be fifty (50)
feet in all directions. If the applicant conducts a groundwater
flow study that conclusively demonstrates the drain is upgradient
of the leachfield, the Director may allow a twenty-five (25) foot
separation distance on the upgradient and side gradient side.
(9)
If a drain is watertight and bedded in sand or bank run gravel, or
laid at an elevation above the seasonal high groundwater table,
this setback distance may be reduced to twenty-five (25) feet.
Applications shall include a detail drawing of the drain pipe
joints and bedding material.
(10)
On a residential property with both an OWTS and a stormwater
infiltration system, the distance between any OWTS component and
the stormwater infiltration system may be reduced to fifteen (15)
feet if the stormwater infiltration system has been designed in
accordance with the Rhode Island Stormwater Design and
Installation Standards Manual.
(11)
The minimum setback distance from the inland edge of the coastal
shoreline feature of the ocean or Narragansett Bay is either fifty
(50) feet or twenty-five (25) feet plus the CRMC calculated
shoreline change setback pursuant to 650-RICR-20-00-1.1.9,
whichever is greater. Shoreline change rates and maps are
available on CRMC’s web site. This setback distance is doubled
for OWTSs with design flow greater than five thousand (5,000)
gallons per day.
(12)
The distance between the septic tank and the edge of the
leachfield shall be a minimum of ten (10) feet.
(13)
The minimum setback from a geothermal well and its associated
piping shall be twenty-five (25) feet.
C. Minimum Setback Distances
from Drinking Water Supply Watershed Critical Resource Area Features
(distances in feet from all OWTS components). See also § 6.60 of
this Part, Figure 2. If it is shown to the Department’s
satisfaction by clear and convincing evidence that the feature of
concern in this table is upgradient (for both groundwater and surface
water flow) of the OWTS, the minimum setback distance will be
determined from § 6.23(B) of this Part. Subsurface drains to lower
the seasonal high groundwater table are not permitted in accordance
with § 6.44(B) of this Part.
Feature
OWTS
Design Flow
<
5000 gpd
OWTS
Design Flow ? 5000 gpd
(Note
1)
Impoundment
with Intake for Drinking Water Supply and Adjacent Wetlands (Note
2)
200
400
Subsurface
Drains and Foundation Drains that Discharge Directly to the
Impoundment
200
400
Subsurface
Drains and Foundation Drains that Discharge to a Drainage Swale
that Subsequently Discharges to the Impoundment:
Paved
Swale
Unpaved
Swale <200 feet long
Unpaved
Swale ?200 feet long
200
200
100
400
400
200
Tributaries,
Tributary Wetlands, Swales, and Storm Drains that Discharge
Directly to the Impoundment
100
(Note
3)
200
(Note
3)
Subsurface
Drains, Foundation Drains, and Storm Drains that Discharge to
Tributaries and Tributary Wetlands
100
(Note
3)
200
(Note
3)
Any
other Watercourse in the Drinking Water Supply Watershed (Not
Connected to the Impoundment) or
Areas
Subject to Storm Flowage
50
100
Notes:
The reductions in setback distances allowed below in Note (3)
will not be granted if the setback distances in § 6.23(C) of
this Part can be met. A variance request pursuant to § 6.51 of
this Part shall not be required for the reductions indicated
below.
(1)
As defined in § 6.39(A)(1) of this Part.
(2)
Distances measured from the yearly high water mark.
(3)
The distance between the building sewer or septic tank effluent
pipe and a drain may be reduced and the building sewer or
effluent pipe may cross the drain provided that the building
sewer or septic tank effluent pipe is sleeved whenever they are
within twenty-five (25) feet of the drain. The sleeve shall be
seamless or schedule 40 PVC or equivalent with watertight joints,
and it shall have a watertight seal that is fastened to the pipes
with a stainless steel retractable clamp.
D. Minimum Setback Distances
from Features in the Salt Pond and Narrow River Critical Resource
Area (distances in feet from all OWTS components). See also § 6.61
of this Part, Figure 3. If it is shown to the Department’s
satisfaction by clear and convincing evidence that the feature of
concern in this table is upgradient (for both groundwater and surface
water flow) of the OWTS, the minimum setback distance will be
determined from § 6.23(B) of this Part. Applications for an OWTS
permit that are approved by DEM are subject to the requirements of
CRMC.
Feature
OWTS
Design Flow
<
5000 gpd
OWTS
Design Flow ? 5000 gpd
(Note
1)
Salt
Pond/Narrow River Coastal Shoreline Features, excluding the ocean
200
400
Subsurface
Drains and Foundation Drains that Discharge Directly to the Salt
Pond/Narrow River
200
400
Subsurface
Drains and Foundation Drains that Discharge to an open Drainage
Swale that Subsequently Discharges to the Salt Pond/Narrow River:
Paved
Swale
Unpaved
Swale <200 feet long
Unpaved
Swale ?200 feet long
200
200
150
400
400
300
Tributaries,
Tributary Wetlands, Swales, and Storm Drains that Discharge
Directly to the Salt Pond/Narrow River
150
(Note
2)
300
(Note
2)
Subsurface
Drains, Foundation Drains, and Storm Drains that Discharge to
Tributaries and Tributary Wetlands
150
300
Any
Other Watercourse in Salt Pond/Narrow River Critical Resource
Area (Not Connected to Salt Pond/Narrow River),
Areas
Subject to Storm Flowage, or the inland edge of the coastal
shoreline feature of the ocean. (Note 3)
50
100
Notes:
The reductions in setback distances allowed below in Note (2)
will not be granted if the setback distances in § 6.23(D) of
this Part can be met. A variance request pursuant to § 6.51 of
this Part shall not be required for the reductions indicated
below.
(1)
As defined in § 6.39(A)(1) of this Part.
(2)
The distance between the building sewer or septic tank effluent
pipe and a drain may be reduced and the building sewer or
effluent pipe may cross the drain provided that the building
sewer or septic tank effluent pipe is sleeved whenever they are
within twenty-five (25) feet of the drain. The sleeve shall be
seamless or schedule 40 PVC or equivalent with watertight joints,
and it shall have a watertight seal that is fastened to the pipes
with a stainless steel retractable clamp.
(3)
The minimum setback distance from the inland edge of the coastal
shoreline feature of the ocean is either fifty (50) feet or
twenty-five (25) feet plus the CRMC calculated shoreline change
setback pursuant to 650-RICR-20-00-1.1.9 ,
whichever is greater. Shoreline change rates and maps are
available on CRMC’s web site. This minimum setback distance is
doubled for OWTSs with design flow greater than five thousand
(5,000) gallons per day.
E. Minimum Setback Distances
from Drinking Water Wells
OWTS
Design Flow
(gpd)
Distance
in Feet from Leachfield/Septic Tank Effluent Pipe, Tanks/Building
Sewer(Notes 1,5)
Distance
in Feet From All OWTS Components
(Notes
1,5)
Private
Drinking Water Well
(Note
2)
Public
Well - Drilled (rock), Driven, or Dug
Public
Well- Gravel Packed, Gravel Developed
<1000
100/75/50
(Note 3,4)
200
400
1000-<2000
150/75/50
200
400
2000
- <5000
200/75/50
200
400
5000-
<10000
300/75/50
300
400
? 10000
400/75/50
400
400
Notes:
The reductions in setback distances allowed below in Notes (2) and
(3) will not be granted if the setback distances in § 6.23(E) of
this Part can be met. A variance request pursuant to § 6.51 of
this Part shall not be required for the reductions indicated
below.
(1)
Large Systems - These distances are minimum distances for large
systems as defined in § 6.39(A)(1) of this Part. Greater
distances may be required based on the Impact Analysis in §
6.39(C) of this Part.
(2)
Distance from the building sewer may be reduced when the building
sewer is constructed of Schedule 40 PVC or equivalent.
(3)
The minimum setback distances to wells on the subject property may
be reduced to 80/60/40 (leachfield/tank/building sewer) feet for
residential OWTSs on lots ten-thousand (10,000) square feet and
larger under the following conditions:
(A)
The design flow is less than five hundred (500) gallons per day;
(B)
The OWTS utilizes a Department-approved nitrogen reducing
technology;
(C)
The OWTS discharges to a pressurized shallow narrow drainfield
designed in accordance with § 6.37(D) of this Part ; and
(D)
The OWTS separation distance between the infiltration surface and
groundwater is three (3) feet or greater.
(4)
The minimum setback distances shall be increased to 150/75/50
(leachfield/tank/building sewer) for OWTSs with a design flow of
less than one thousand (1,000) gallons per day if the OWTS is
designed for Category 1 soils per § 6.33 of this Part. For such
OWTSs utilizing a Department approved nitrogen reducing technology
discharging to a bottomless sand filter or pressurized shallow
narrow drainfield constructed in accordance with § 6.37(D) of
this Part , the minimum setback distances may be 100/75/50
(leachfield/tank/building sewer).
(5)
In addition to the required setbacks between wells and the
proposed OWTS, well setbacks shall also apply between any existing
well serving the building for which the OWTS is proposed and any
other existing OWTS. Such existing OWTS may require upgrade to
meet these rules.
6.24 Subsurface Drains
A. Prior to seeking a permit
for an OWTS that includes a subsurface drain, the applicant shall
have all other relevant state or local approvals or permits for
construction of the subdrain and discharge of the drainage effluent.
Such approvals may include, but are not limited to, DEM Wetlands
Program, the Rhode Island Coastal Resources Management Council
Preliminary Determination, the municipality or the Rhode Island
Department of Transportation.
B. Construction - A subsurface
drain constructed to lower the groundwater table shall consist of not
less than six (6) inches of washed stone three-quarter (¾) inch to
two (2) inches in diameter, over which is laid a perforated pipe at
least four (4) inches in diameter. The stone shall extend above the
pipe to within two (2) feet of the ground surface. A layer of filter
fabric meeting the requirements of § 6.33(L) of this Part shall be
placed above, below and along the sides of the stone for the entire
length of the drain. Changes in direction shall not exceed ninety
(90) degrees. Where a change in direction is greater than forty-five
(45) degrees, a manhole is required, unless the change in direction
is achieved through the use of a thirty-six (36) inch radius sweep.
C. Monitoring - The
effectiveness of subsurface drains used to lower the groundwater
table must be demonstrated through one complete wet season, January 1
through April 15, before consideration can be given to an application
for an OWTS permit. The Department may allow lesser periods of
monitoring if site conditions and wet season conditions warrant.
1. Groundwater table test
holes shall be located within the area of the proposed leachfield
with one (1) on the upgradient side and one (1) on the downgradient
side. The test holes shall not be located within twenty-five (25)
feet of the upgradient subsurface drain or within fifty (50) feet of
the downgradient subsurface drain.
2. Groundwater table initial
readings shall be submitted on forms approved by the Director by
January 30 in order to effectively allow the Department and the
Licensed Designer to monitor the effects of the subsurface drain
through the wet season.
D. Hydraulic Gradient - If the
subsurface drain causes the natural hydraulic gradient to be
reversed, such drain shall be treated as a downgradient drain for the
purpose of establishing appropriate minimum setbacks in accordance
with § 6.23 of this Part. Where only an upgradient drain is
installed, the applicant must demonstrate that the hydraulic gradient
will not be reversed or treat the upgradient drain as a downgradient
drain for the purpose of establishing appropriate minimum setbacks in
accordance with § 6.23 of this Part.
6.25 Building Sewers
A. Size - The building sewer
shall be designed with a capacity, when running full, of not less
than twice the peak rate of flow of the connected fixtures. In no
case shall the building sewer be less than three (3) inches in
diameter.
B. Material - The building
sewer shall be constructed of PVC pipe SDR 35 minimum or equivalent.
When any portion of the building sewer will be subject to vehicular
traffic, it shall be constructed of Schedule 40 PVC or equivalent.
C. Joints - All pipe joints
for the building sewer shall be made watertight and be firmly
connected.
D. Base - The building sewer
shall be laid on a compacted, firm base.
E. Horizontal Alignment
1. The building sewer should
be laid in a straight line wherever possible. Changes in direction
shall not exceed ninety (90) degrees.
2. Where a change in direction
is greater than forty-five (45) degrees, a manhole is required,
unless the change in direction is achieved through the use of a
thirty-six (36) inch radius sweep.
F. Vertical Alignment
1. The slope of the building
sewer from the dwelling to the septic tank shall be not less than one
percent (1%) and not greater than five percent (5%).
2. A manhole is required at
changes of grade requiring a drop box in order to maintain the
maximum five percent (5%) slope.
G. Manholes and Cleanouts - A
manhole with a removable cover of concrete, cast iron, or other
durable material shall be provided at the junction of two (2) or more
building sewer lines and at all sharp changes in direction greater
than forty-five (45) degrees, unless the alignment complies with §
6.25(F) of this Part. A cleanout shall be provided at intervals not
greater than seventy-five (75) feet.
H. Ventilation - The building
sewer shall be vented through the stack or main vent of the building
it serves. No trap shall be installed in the building sewer.
6.26 Grease Tanks
A. See § 6.62 of this Part,
Figure 4.
B. Required Use - Grease tanks
shall be installed in accordance with the following:
1. OWTS Applications for New
Building Construction for restaurants and other facilities that
prepare food shall have kitchen wastes separately plumbed to an
external grease tank;
2. OWTS Applications for
Alterations to a Structure and OWTS Applications for Repair for
restaurants and other facilities that prepare food with a total
design flow equal to or exceeding two thousand (2,000) gallons per
day shall have kitchen wastes separately plumbed to an external
grease tank; and
3. OWTS Applications for
Alterations to a Structure and OWTS Applications for Repair for
restaurants and other facilities that prepare food with a total
design flow less than two thousand (2,000) gallons per day shall have
kitchen wastes separately plumbed to an external grease tank or have
an internal grease removal unit installed.
C. Capacity - Grease tanks
shall have a minimum capacity of one thousand (1,000) gallons, and
shall have sufficient capacity to provide at least a twenty-four (24)
hour detention period for fifty percent (50%) of the design flow for
the OWTS.
D. Construction - Grease tanks
shall be watertight, meet the construction and material standards
required for septic tanks in § 6.27(C) of this Part, and be shaped
as required for septic tanks in § 6.27(D) of this Part.
E. Inlet and Outlet - The
inlet and outlet shall be as required for septic tanks in § 6.27(F)
of this Part. Grease tanks shall be provided with inlet tees and
outlet tees. Baffles may be provided as necessary in conjunction with
tees to maximize the separation of grease from the wastewater.
1. Tees shall be minimum SDR
35 PVC solvent welded and properly supported by a hanger, strap or
other device.
2. The inlet tee shall extend
to the mid-depth of the tank. The outlet tee shall extend to twelve
(12) inches from the bottom of the tank.
3. The tops of the tees shall
extend a minimum of six (6) inches above the flow line, and shall be
left open to provide ventilation. There shall be an air space of at
least three (3) inches between the tops of the tees and the top
interior of the grease tank.
F. Access Openings - Grease
tank access openings shall be as required for septic tanks in §
6.27(H) of this Part. In addition, the lid shall specify that it is
for a grease tank.
G. Location - Grease tanks
shall be installed on a separate building sewer serving that part of
the plumbing system into which the grease shall be discharged. The
discharge from the grease tank shall flow to a properly designed
septic tank.
H. Installation - Grease tank
installation shall be as required for septic tank installation in §
6.27(J) of this Part.
I. Grease Tanks in Series -
Grease tanks may be placed in series provided that the combined
volume meets the requirements of § 6.26(C) of this Part and that
each grease tank meets all other requirements of § 6.26 of this
Part. In no case shall more than two (2) grease tanks be placed in
series.
J. Performance Testing -
Grease tanks shall be certified watertight in accordance with §
6.27(L) of this Part.
K. Maintenance - Grease tanks
shall be cleaned by a licensed permitted septage hauler when
twenty-five percent (25%) of the liquid volume is filled with grease.
L. Existing Grease Tanks -
Grease tanks in place as of January 1, 2008 that have access openings
to finished grade shall be in compliance with § 6.27(H)(2) of this
Part no later than January 1, 2013.
6.27 Septic Tanks
A. See § 6.63 of this Part,
Figure 5.
B. Septic Tank Capacity
1. Residential Dwellings - The
required minimum liquid capacity of a septic tank, below the flow
line, shall be based on the number of bedrooms in the dwelling. For
three (3) bedrooms or less the minimum capacity shall be one thousand
(1,000) gallons. For each additional bedroom, add two hundred fifty
(250) gallons. A garbage grinder or a one hundred (100) gallon or
greater tub will each require the septic tank capacity be increased
by two hundred fifty (250) gallons.
2. Non-Residential Buildings -
The required minimum liquid capacity of the septic tank shall be one
thousand (1,000) gallons or two (2) times the design flow as
determined from § 6.22(B) of this Part, whichever is greater.
C. Construction and Materials
- Septic tanks shall be watertight. They shall be constructed of
sound and durable materials not subject to excessive corrosion, decay
or frost damage or to cracking or buckling due to settlement or soil
pressures. Septic tanks shall be constructed of precast reinforced
concrete, fiberglass, polyethylene or other material approved by the
Director. In addition to the construction and material standards in
§§ 6.27(C)(1) through (3) of this Part, all septic tanks shall meet
the physical design standards in the remainder of § 6.27 of this
Part.
1. Precast reinforced concrete
septic tanks shall conform to the American Society for Testing and
Materials “Standard Specification for Precast Concrete Septic Tanks
C-1227-10a” and any updates thereto, incorporated above at §
6.7(A) of this Part. Any weep holes in the precast reinforced
concrete septic tank shall be placed on the side of the tank bottom
to allow for safe inspection and assurance that the weep hole has
been plugged.
2. Fiberglass septic tanks and
polyethylene septic tanks shall conform to the International
Association of Plumbing and Mechanical Officials “American National
Standard for Prefabricated Septic Tanks IAPMO/ANSI Z1000-2007” and
any updates thereto, incorporated above at § 6.7(B) of this Part.
3. Each septic tank shall be
clearly and permanently marked at the inlet end of the tank with:
a. Date of manufacture;
b. Name or trademark of the
manufacturer;
c. Septic tank capacity; and
d. Indication of external
loads for which the septic tank is designed to resist.
D. Shape - There shall be no
less than twenty-five (25) square feet of surface liquid area. The
distance between the inlet wall of the tank and the outlet wall shall
be no less than six (6) feet. The depth of the tank below the flow
line shall be not less than thirty-nine (39) inches or more than
eight (8) feet. There shall be at least nine (9) inches of air space
between the surface of the liquid and the interior roof of the septic
tank.
E. Compartments - All septic
tanks shall have two (2) compartments with adequate connection at
mid-depth, and all tanks shall meet the following requirements:
1. The first compartment shall
have a liquid volume of approximately two-thirds (?) of the
required liquid volume for the entire tank.
2. The interior compartment
wall shall not extend to the interior roof without providing for
venting equivalent to the cross sectional area of at least a four (4)
inch diameter pipe.
F. Inlet and Outlet
1. One (1) inlet and one (1)
outlet shall be provided through the appropriate end or side wall of
each tank. Where more than one (1) inlet is required for multiple
building sewers, the tank shall be manufactured with the appropriate
number of inlets.
2. Inlet and Outlet Elevations
- The invert elevation of the outlet shall be at least three (3)
inches below the invert elevation of the inlet, and above the
seasonal high groundwater table, unless special construction approved
by the Director is provided.
3. The inlet and outlet pipes
shall be connected to the tank with a watertight sealed flexible
joint. The pipe gasket shall be an integral part of all tanks and the
pipe gasket shall be fastened to the pipe with a stainless steel
retractable clamp.
G. Inlet and Outlet Tees -
Septic tanks shall be provided with an inlet sanitary tee and outlet
tees or other non-corroding equivalent device approved by the
Director. The inlet and outlet tees shall be minimum SDR 35 PVC
solvent welded. The tops of the tees shall extend a minimum of six
(6) inches above the flow line, and shall be left open to provide
ventilation. There shall be an air space of at least three (3) inches
between the tops of the tees and the top interior of the tank.
1. The inlet sanitary tee
shall extend downward at least one (1) foot below the flow line.
2. The outlet tee shall extend
downward one-third (?) of the depth below the flow line. All outlet
tees or other approved outlet devices shall be equipped with an
effluent screen approved by the Department pursuant to § 6.41 of
this Part.
3. Specifications for inlet
tees and outlet tees are for normal, low-flow conditions. High-flow
conditions, created when liquid is pumped from another tank, may
require other dimensions and considerations.
H. Access Openings - A minimum
twenty (20) inch inside diameter access opening shall be located over
both the inlet tee and outlet tee. All septic tank openings shall
meet the following requirements:
1. The access opening over the
outlet tee shall be brought to finished grade. Other access openings
shall either be brought to finished grade or within twelve (12)
inches of the finished grade. Where a riser is required, it shall be
watertight;
2. Lids on the top of the
septic tank (§ 6.64 of this Part, Figure 6) should remain in place
where practical. Lids for the openings at finished grade shall
prevent unauthorized entry by meeting either of the following:
a. Lid shall weigh a minimum
of fifty-nine (59) pounds and fit tightly onto the riser as shown in
§ 6.64 of this Part, Figure 6; or
b. Lid shall be tamper
resistant and mechanically fastened;
3. The septic tank
manufacturers shall provide and the Licensed OWTS Installers shall
attach a label of noncorrosive material in a prominent location at
each access opening to warn that “Entrance Into the Tank Could Be
Fatal”; and
4. Surface water shall be
diverted away from the septic tank openings.
I. Accessibility - Septic
tanks shall be so located on the lot as to be accessible for
servicing and cleaning.
J. Installation - All septic
tanks shall be installed in accordance with the manufacturer’s
minimum requirements. In addition, all septic tanks must meet the
installation requirements specified in the remainder of these rules.
1. Foundation - The septic
tank shall be installed on a level, stable base that will not settle.
2. Backfill - Backfill shall
be placed around the septic tank in such a manner as to avoid damage
to it. All backfill placed around the septic tank shall be free of
large stones, stumps, waste, construction material and rubbish.
3. Floatation - Where any
portion of a septic tank is installed below the seasonal high
groundwater table, the tank’s susceptibility to floatation shall be
determined, and provisions shall be made to prevent floatation where
necessary as determined by the floatation calculations.
4. Septic Tanks in Coastal
Velocity Zones - All fiberglass and polyethylene septic tanks larger
than one thousand (1,000) gallons installed in a Federal Emergency
Management Agency designated V-Zone shall be anchored to prevent
floatation.
K. Septic Tanks in Series -
Septic tanks placed in series are allowed provided they meet the
following requirements:
1. Each tank shall be of
single compartment design and the volume of the first tank shall be
at least two-thirds (?) the required tank size;
2. The outlet tee on the first
tank shall extend down to the mid-depth of the liquid volume; and
3. An effluent screen that
meets the requirements of § 6.27(G)(2) of this Part shall be
provided on the outlet tee of the second tank.
L. Performance Testing - All
septic tanks and their risers must be certified watertight by the
manufacturer or by onsite testing. Onsite testing for septic tank
leakage shall be conducted for tanks assembled at the installation
site. The Director may require onsite testing on a case-by-case
basis. The testing shall be conducted using either:
1. Vacuum Test - Seal the
empty tank and risers and apply a vacuum to two (2) inches (50 mm) of
mercury. The tank is approved if ninety percent (90%) of the vacuum
is held for two (2) minutes; or
2. Water-Pressure Test - Seal
the tank and risers, fill with water to the top of the risers, and
let stand for twenty-four (24) hours. Refill the tank. The tank is
approved if the water level is held for one (1) hour.
M. Pumping to Septic Tanks -
Whenever more than twenty-five percent (25%) of the daily design flow
is pumped into a septic tank, the tank capacity shall be increased by
fifty percent (50%) beyond the minimum capacities specified in §
6.27(B) of this Part.
N. Depth of Cover - The
minimum cover over the invert of the outlet shall be one and one-half
(1½) feet. If the depth of cover exceeds three and one-half (3½)
feet, the OWTS application shall include documentation of the tank’s
ability to structurally withstand the loading, and the tank’s
design shall allow for proper maintenance and access.
O. Existing Septic Tanks -
Septic tanks in place as of January 1, 2008 shall be in compliance
with the provisions of § 6.27(H)(2) of this Part no later than
January 1, 2013.
6.28 Septic Tank Effluent Pipe
A. Size - In no case shall the
septic tank effluent pipe be less than four (4) inches in diameter.
B. Material - The septic tank
effluent pipe shall be constructed of PVC pipe SDR 35 minimum or
equivalent. When any portion of the septic tank effluent pipe will be
subject to vehicular traffic, it shall be constructed of Schedule 40
PVC or equivalent.
C. Joints - All pipe joints
for the septic tank effluent pipe shall be made watertight and be
firmly connected.
D. Slope or Grade - The septic
tank effluent pipe shall have a minimum slope of one percent (1%).
E. Base - The septic tank
effluent pipe shall be laid on a compacted, firm base.
F. Alignment - The septic tank
effluent pipe should be laid in a straight line wherever possible.
Changes in direction shall not exceed ninety (90) degrees. Where a
change in direction is greater than forty-five (45) degrees, a
manhole is required, unless the change in direction is achieved
through the use of a thirty-six (36) inch radius sweep.
G. Manholes and Cleanouts - A
manhole with a removable cover of concrete, cast iron, or other
durable material shall be provided at the junction of two (2) or more
septic tank effluent pipes and at all sharp changes in direction
greater than forty-five (45) degrees, unless the alignment complies
with § 6.28(F) of this Part. A cleanout shall be provided at
intervals not greater than seventy-five (75) feet.
H. Pressurized Septic Tank
Effluent Pipe - The Licensed Designer shall specify pressurized
septic tank effluent pipe sizing and provide backup calculations to
support specification. The pressurized septic tank effluent pipe
shall be PVC Class 200 minimum.
6.29 Holding Tanks
A. Use
1. Holding tanks for
wastewater are prohibited for Applications for New Building
Construction and Applications for Alteration to a Structure.
2. A holding tank may be
allowed only to repair or replace a failed OWTS at the Director’s
discretion.
3. Holding tanks will not be
allowed if a public wastewater system is available for connection.
When a public wastewater system becomes available, any person owning
a holding tank shall connect to said system within thirty (30) days
and the holding tank shall be abandoned in accordance with § 6.56 of
this Part.
4. Holding tanks are allowed
at marine pumpout facilities provided that direct connection to an
existing public wastewater system is not possible and such tanks are
constructed, installed and operated in accordance with appropriate
Department Guidelines and Regulations.
B. Construction - Each holding
tank shall:
1. Have a minimum capacity of
five hundred percent (500%) of the daily design flow or portion
thereof that the holding tank will serve, or two thousand (2,000)
gallons, whichever is larger;
2. Be watertight and meet the
construction and material standards required for septic tanks in §
6.27(C) of this Part;
3. Be equipped with an
audio-visual alarm set to activate when the tank reaches sixty
percent (60%) of its capacity;
4. Have a minimum twenty (20)
inch inside diameter opening that meets the requirements for septic
tank access openings in §§ 6.27(H)(1), 6.27(H)(2)(b), 6.27(H)(3)
and 6.27(H)(4) of this Part; and
5. Be vented such that the
vent is at an elevation higher than the elevation of the highest
fixture served.
C. Installation - Holding tank
installation shall be as required for septic tanks in § 6.27(J) of
this Part.
D. Depth of Cover - The
minimum cover over the invert of the inlet shall be one and one-half
(1½) feet.
E. Pumping - Prior to approval
of the installation of a holding tank the applicant shall provide to
the Department a copy of a contract with a licensed permitted septage
transporter to regularly pump the tank.
F. Performance Testing - All
holding tanks shall be tested on site for leakage in the manner
specified for septic tanks in § 6.27(L)(1) or (2) of this Part.
G. Existing Holding Tanks -
Holding tanks in place as of January 1, 2008 that have access
openings to finished grade shall be in compliance with §
6.27(H)(2)(b) of this Part no later than January 1, 2013.
6.30 Pump Tanks
A. An OWTS that requires a
pump shall have a separate pump tank to house the pump, unless the
pump is placed in the second compartment of the septic tank within a
screened vault approved by the Director. Pump tanks shall be located
following a septic tank unless otherwise approved by the Director.
B. Capacity - Pump tanks shall
have an emergency storage capacity above the working level equal to
the daily design flow of the system. Emergency capacity is not
required if there is less than two (2) inches difference in elevation
between the invert of the outlet of the septic tank and the invert of
the inlet of the pump tank. All pump tanks shall be equipped with
sensors and alarms to protect against high water due to failure of
the pump or pump controls. The volume below the working level shall
include an allowance for the volume of all drainage which may flow
back to the tank when pumping has ceased. The volume of the pump tank
between operating levels shall be adequate to assure the entire
leachfield is dosed each cycle in accordance with the required number
of cycles per day.
C. Construction - Each pump
tank shall:
1. Be watertight and meet the
construction and material standards for septic tanks in § 6.27(C) of
this Part; and
2. Each pump tank or
compartment thereof shall be provided with a minimum twenty (20) inch
inside diameter access opening located so as to facilitate repair or
adjustment of the pump. The access opening shall meet the
requirements for septic tank access openings in §§ 6.27(H)(1)
through (4) of this Part.
D. Inlet and Outlet - The
invert elevation of the inlet and the outlet pipe to the pump tank
shall be located above the maximum water elevation in the pump tank,
and above the seasonal high groundwater table, unless special
construction, approved by the Director is provided.
E. Ventilation - Pump tanks
shall be constructed in a manner that will permit venting through the
building sewer or other suitable outlet.
F. Installation - Pump tank
installation shall be as required for septic tanks in § 6.27(J) of
this Part.
G. Performance Testing - Pump
tanks shall be certified watertight in accordance with § 6.27(L) of
this Part.
H. Existing Pump Tanks - Pump
tanks in place as of January 1, 2008 that have access openings to
finished grade shall be in compliance with § 6.27(H)(2) of this Part
no later than January 1, 2013.
6.31 Pumps
A. Required Use - Pumps are
required for OWTSs that meet any of the following conditions:
1. The OWTS is designed for
intermittent discharge;
2. The OWTS is designed for
pressure dosing;
3. Pump is required for an
approved Alternative or Experimental Technology;
4. The maximum length of a
dispersal trench in the leachfield is between seventy-six (76) feet
and one hundred (100) feet; or
5. The total length of the
distribution lines in the leachfield exceeds five hundred (500) feet.
B. Dual Alternating Pumps
1. When a pump is required,
dual alternating pumps are required for the following (otherwise a
single pump is sufficient):
a. The total length of the
distribution lines in the system exceeds one thousand (1,000) feet;
b. The OWTS serves a use other
than single family residential, the design flow is less than two
thousand (2,000) gallons per day, and there is no storage capacity
for one day’s design flow; and
c. The OWTS serves a use other
than single family residential and the design flow is greater than
two thousand (2,000) gallons per day.
2. Dual alternating pumps
shall operate in the following sequence: pumps off; primary (lead)
pump on; backup (lag) pump on and alarm on; pumps must alternate.
3. When dual alternating pumps
are discharging to separate leachfields, the pump discharge lines
shall be inter-connected and provisions made to permit dosage of both
leachfields with one pump when the other is being serviced.
C. Size - The pump must be
sized to accommodate the proposed use. All system head curves and
associated calculations shall be submitted with the design.
Centrifugal pumps must be capable of passing three-quarter (¾) inch
diameter solids.
D. Piping - The Licensed
Designer shall specify pump discharge pipe sizing and provide backup
calculations to support specification. The pump discharge pipe shall
be PVC Class 200 minimum.
E. Controls and Power Supply -
Pump controls shall be moisture proof if located above the liquid
level. Watertight controls shall be used when the contents are
submerged. All controls and junction boxes on the power supply shall
meet appropriate electrical codes. Standby power shall be provided at
all uses other than single family residential, unless otherwise
approved by the Director.
F. Alarms - All pumps shall be
equipped with a high water level, visible and audible alarm powered
by a circuit separate from the pump power.
G. Installation - Pumps shall
be installed in strict conformance with the manufacturer's
specifications. Provisions should be made to easily remove the pumps
for servicing.
6.32 Distribution Boxes
A. A distribution box shall be
installed immediately preceding the leachfield unless otherwise
approved by the Director.
B. Construction - The
distribution box shall be constructed of concrete or other durable
material. It shall have a top load carrying capacity of three hundred
(300) pounds per square foot and minimal sidewall deflection. Minimum
bottom area shall be three (3) square feet.
C. Inlet - The distribution
box shall be provided with an inlet tee or a suitable baffle. The
invert elevation of the inlet pipe shall be not less than two (2)
inches above the invert elevation of the outlet pipe.
D. Outlets
1. Outlet Elevations - The
invert elevation of all the outlet pipes shall be a minimum of four
(4) inches above the floor of the distribution box. All outlet
inverts shall be at the same elevation.
2. Number of Outlets - There
shall be a separate outlet for each distribution line. In all cases
following a pump tank, the outlets shall be of sufficient size to
accept the wastewater flow at the rate wastewater is delivered to the
distribution box.
E. Distribution Pipes Into the
Distribution Box
1. The distribution pipes
shall extend into the distribution box one (1) inch.
2. Jointing of the
distribution piping with a distribution box shall be made with
non-shrinking gasket materials which shall maintain a watertight
seal.
3. All inverts shall be set
level after the leachfield is installed. Leveling devices may be
installed on the distribution pipes.
F. Cover - The distribution
box shall be provided with a readily removable, fitted cover of
durable material. Distribution boxes are not required to have access
openings at finished grade except as follows. When a tipping
distribution box is used, the distribution boxes shall have a minimum
ten (10) inch diameter access opening brought to finished grade.
OWTSs with a design flow over two thousand (2,000) gallons per day
shall have a minimum eighteen (18) inch manhole over each
distribution box with extra heavy duty metal frames and covers to
finished grade. When manholes to grade are not provided, it is
recommended that a marker over the cover be provided at grade.
G. Foundation - The
distribution box shall be installed on a level stable base that will
not settle.
6.33 Leachfields
A. Applicability - This rule
applies to leachfields with dispersal trenches (§ 6.34 of this
Part), leachfields with concrete chambers in a trench configuration
(§ 6.35 of this Part), and to Alternative or Experimental leachfield
systems approved pursuant to § 6.41 of this Part except for
specifically approved design elements that are not consistent with
this § 6.33 of this Part.
B. Minimum Leaching Area - The
minimum leachfield area necessary for dispersal trench and concrete
chamber leachfields shall be determined by dividing the maximum daily
wastewater flow (design flow) for the facility, as determined from §
6.22 of this Part, by the loading rate established in § 6.33(C) of
this Part. Use the lowest loading rate obtained in the manner
described below:
1. If the bottom of the stone
is above the original grade, use the soil horizon with the lowest
loading rate within five (5) feet of the original ground surface,
excluding any A horizons;
2. If the bottom of the stone
is below the original grade, use the soil horizon with the lowest
loading rate within five (5) feet below the elevation of the
distribution pipe invert, including the soil horizons receiving side
wall effluent;
3. If no natural soil exists
within the five (5) feet referenced in §§ 6.33(B)(1) and (2) of
this Part above because of gravel fill, use the loading rate of the
first naturally occurring soil horizon below that depth.
C. Loading Rates Determined by
Soil Category
Soil
Category
Loading
Rate (gals/sq ft/day)
1
(Note 1)
.70
1m
(Note 2)
.61
2
.61
3
.70
4
.61
4m
.70
5
.52
6
.61
6m
.70
7
.52
7m
.61
8
.46
8m
.48
9
.40
9m
.43
10
Not
Allowed (Impervious)
Notes:
(1)For
OWTS Applications for Repair, a loading rate of .93 may be used
for Soil Category 1.
(2)“m”
Means soil has gravelly or channery coarse fragment modifiers.
D. Effective Leaching Area -
The effective leaching area of OWTSs shall be determined in
accordance with § 6.34 of this Part for dispersal trench OWTSs and §
6.35 of this Part for concrete chamber OWTSs.
E. Depth to Groundwater from
Original Ground Surface - Using the test holes required in § 6.16(I)
of this Part, the seasonal high groundwater table determination that
is closest to the original ground surface shall be used for OWTS
design. The leachfield shall be located in an area where the seasonal
high groundwater table is a minimum of two (2) feet below the
original ground surface. All test holes within twenty-five (25) feet
of the leachfield shall meet the minimum depth to groundwater from
original ground surface. Where the seasonal high groundwater table is
less than four (4) feet below the original ground surface, the
Department shall require additional soil testing to ensure the
minimum depth to groundwater meets the minimum standards within
twenty-five (25) feet of the leachfield. On lots twenty thousand
(20,000) square feet or larger that are not located in the Salt Pond
or Narrow River Critical Resource Areas as defined in § 6.42 of this
Part, the leachfield may be located in an area where the seasonal
high groundwater table is less than twenty-four (24) inches but
greater than or equal to eighteen (18) inches from the original
ground surface if the OWTS utilizes a bottomless sand filter in
accordance § 6.37 of this Part, the applicant has no variance
requests pursuant to § 6.51 of this Part, and the design flow is
less than or equal to six hundred ninety (690) gallons per day of
residential strength wastewater.
F. Depth to Restrictive Layer
or Bedrock from Original Ground Surface - The leachfield shall be
located in an area where a restrictive layer or bedrock is a minimum
of four (4) feet below the original ground surface. The minimum depth
to a restrictive layer or bedrock shall be met within twenty-five
(25) feet of all sides of the leachfield.
G. Leachfield Design Point -
Where the seasonal high groundwater table is greater than or equal to
four (4) feet below the original ground surface, the leachfield shall
be designed using the original ground surface elevation at the center
of the leachfield. Where the seasonal high groundwater table is less
than four (4) feet below the original ground surface, the leachfield
shall be designed using the highest original ground surface elevation
within the leachfield.
H. OWTS Separation Distance to
Groundwater - The bottom of the stone underlying the leachfield (or
surface upon which the biomat develops) shall be at least three (3)
feet above the seasonal high groundwater table.
I. OWTS Separation Distance to
a Restrictive Layer or Bedrock - The bottom of the stone underlying
the leachfield (or surface upon which the biomat develops) shall be
at least five (5) feet above a restrictive layer or bedrock. This
five (5) foot vertical separation shall be maintained to a distance
of twenty-five (25) feet from the side wall of the leachfield. In the
upgradient direction, the five (5) foot vertical separation
requirement may be waived as long as a restrictive layer or bedrock
is no higher than the bottom of the stone within twenty-five (25)
feet of the leachfield (§ 6.59 of this Part, Figure 1). Excavating
into a restrictive layer or bedrock is not permitted unless otherwise
approved by the Director.
J. Excavation - All trees,
brush and stumps within the area of the leachfield and within ten
(10) feet of the leachfield shall be removed. Care must be taken to
assure that the soil at the bottom and sides of the excavation for
the leachfield is not compacted or smeared. The bottom of the
excavation shall be level and the bottom and sides of the excavation
shall be scarified. In no case shall exposed boulders in the walls or
bottom of the excavation be left in place. Voids created by the
removal of boulders shall be filled with gravel meeting the
requirements in § 6.33(M) of this Part. Exposed roots within the
excavation shall be cut back to the walls of the excavation. No part
of the excavation for the leachfield shall be into groundwater. All
storm deposited sand in the backdune environment and human
transported material existing in the proposed leachfield and five (5)
feet around and below shall be removed prior to OWTS installation
unless the material is deemed to be acceptable to the Director.
K. Stone - The stone used in
the leachfield shall consist of clean, washed stone ranging from
three quarter (¾) inch to not more than two (2) inches in size and
free of fines, soils, stone dust or debris. The stone shall be
covered with a layer of synthetic filter fabric that meets the
requirements of § 6.33(L) of this Part.
L. Filter Fabric - A layer of
non-woven synthetic filter fabric shall be placed over all stone used
in the OWTS construction before backfilling. The filter fabric shall
have adequate tensile strength to prevent ripping during installation
and backfilling, adequate air permeability to allow free passage of
gases, and adequate particle retention to prevent downward migration
of soil particles.
M. Gravel
1. The gravel base material
and, where applicable, the gravel between the trenches shall consist
of clean sand and gravel free of organic matter and foreign
substances. The gravel shall not contain any material larger than
three (3) inches and up to ten percent (10%) may be sized between
three-quarters (¾) and three (3) inches. Gravel shall meet the
following criteria:
Sieve
Size
Percent
Passing
3/4”
90%
- 100%
#4
55%
- 100%
#10
40%
- 100%
#40
10%
- 50%
#100
0%
- 20%
#200
0%
- 5%
2. The gravel shall be placed
in shallow lifts and properly compacted. The surface of the gravel
upon which the stone will be laid shall be level and scarified.
N. Depth of Cover - The
minimum cover over the invert of the distribution lines shall be one
and one-half (1½) feet and the maximum cover shall be two and
one-half (2½) feet. Minimum cover elevations shall be maintained
over the full area of the leachfield, including area excavated
pursuant to § 6.34(F)(1) of this Part.
O. Backfill - All backfill
shall be free of boulders and stones greater than six (6) inches in
diameter, frozen clumps of earth, rubbish, masonry, stumps or waste
construction materials. Backfill shall be placed carefully to avoid
displacement and damage to piping and chambers. Heavy machinery shall
not be permitted to pass over the leachfield.
P. Fill Easements - Where
human transported material (“fill”) is required and where it is
necessary to fill beyond the boundary of the subject property to meet
the requirements of these rules, no approval will be granted unless
the adjoining property owner(s) has given a permanent legal release
(easement, etc.) filed in the land evidence records of the
municipality granting such right to the owner of the applicant
property. A copy of such right of access and use shall be attached to
the application.
Q. Adjacent Side Slope - A
minimum ten (10) foot horizontal separation distance shall be
provided between the outer edge of the stone in the outer dispersal
trench and any ground surface elevation less than the elevation of
the invert of the distribution line. The adjacent side slope shall
not be steeper than 3:1 (horizontal: vertical) for a twenty-five (25)
foot minimum distance from the edge of the stone in the dispersal
trench or until the toe of the slope returns to the elevation of the
original grade. The toe of the 3:1 slope shall be a minimum of five
(5) feet from any property line.
R. Structural Retaining Walls
- A minimum of twenty-five (25) feet shall be maintained from the
outer edge of the stone in the outer dispersal trench to any
structural retaining wall. If the structural retaining wall is above
the seasonal high groundwater table a lesser setback distance may be
allowed. A greater setback distance may be required for OWTSs with a
design flow of one thousand (1,000) gallons per day or more. The
Department may require additional information, including but not
limited to an analysis of the hydrogeological conditions of the site.
Structural retaining walls shall be a minimum of two (2) feet from
the property line unless the adjacent property owner grants the
applicant written permission or a construction easement to provide
access to install the wall. The wall design shall ensure adequate
control of surface water runoff. The Director may require that the
structural retaining wall be designed by a Professional Engineer
registered in Rhode Island.
S. Surface Water Drainage -
OWTSs shall be designed to prevent the flow of surface water from the
surrounding area onto the leachfield. The OWTS design shall provide
for diversion of surface water runoff so as not to cause or increase
the severity of drainage problems to adjacent properties.
T. Leachfield Protection
1. Curbing - OWTSs serving
other than individual dwellings shall be adequately curbed or fenced
so as to exclude vehicular traffic, unless the OWTS is a concrete
chamber OWTS constructed in accordance with § 6.35(L) of this Part.
Parking areas adjacent to a leachfield shall be graded or curbed to
divert runoff from the leaching area.
2. The boundary of the
leachfield shall be staked and flagged to protect the leachfield from
vehicle traffic and excessive weight loads before and during
construction of the OWTS and the structure. Flagging shall remain in
place until all construction activities at the site are complete.
U. Finish Grade Stabilization
- Immediately after completion of final grading, the area of
disturbance due to installation of the OWTS shall be stabilized by
mulching and seeding, or sodding, to establish a permanent vegetative
cover to prevent erosion.
6.34 Dispersal Trenches
A. Effective Leaching Area -
The effective leaching area shall be determined by the depth of stone
meeting the requirements of § 6.33(K) of this Part that is placed
below the distribution line in the trench and the width of the
trench. The effective leaching area of dispersal trenches containing
one-half (½) feet of stone below the pipe invert shall be the total
bottom area. Credit will be allowed for added sidewall absorption
area gained by increasing the depth of stone in the trenches. Such
credit shall be determined in accordance with § 6.34(B) of this Part
which gives the square footage allowed per lineal foot of trench as
the depth of stone increases. The maximum depth of stone allowed is
one and one-half (1½) feet. The bottom of the dispersal trench shall
have a maximum width of three (3) feet. The maximum depth of stone
below the pipe invert shall be one-half (½) feet when either of the
following occur:
1. The seasonal high
groundwater table is within two (2) to four (4) feet of the original
ground surface; or
2. A restrictive layer is
within four (4) to six (6) feet of original ground surface.
B. Effective Leaching Area
Depth
of Stone Below Invert (Feet)
Area
Allowed per Linear Foot of Trench (Sq. ft/ft)
24”
Wide Trench
30”
Wide Trench
36”
Wide Trench
0.5
2.0
2.5
3.0
1.0
2.7
3.2
3.7
1.5
3.2
3.7
4.2
C. Distribution Lines
1. That portion of the
distribution line from the distribution box to the beginning of the
dispersal trench shall be a minimum of two (2) feet in length, four
(4) inch diameter SDR 35 PVC, imperforated and laid with firmly
connected watertight joints.
2. The invert of the
distribution lines in the trench shall be two (2) inches lower than
the invert of the outlet of the distribution box. The distribution
lines in the trench shall be level. The first foot of the
distribution line in the trench shall be imperforated SDR 35 PVC.
Beyond the first foot, the distribution lines in the trench must
consist of SDR 35 perforated PVC pipe with a minimum diameter of four
(4) inches, or an equivalent pipe approved by the Director. The
perforations shall be evenly spaced in two (2) rows, one on each side
of center, located at thirty (30) degrees off vertical center in the
lower half of the pipe. The perforations shall be no smaller than
three-eighths (?) inch and no larger than five-eighths (?) inch
in diameter. Pipe joints shall be firmly connected. The ends of all
distribution lines shall be inter-connected.
3. The maximum length of a
dispersal trench shall be as follows:
a. Without dosing - fifty
(50) feet;
b. With a tipping distribution
box - seventy-five (75) feet; or
c. With a pump - one hundred
(100) feet.
D. Stone - The stone
surrounding the distribution lines shall meet the requirements of §
6.33(K) of this Part. The stone shall cover the full width of the
trench, extend to the proper design depth, and extend two (2) inches
above the top of the distribution lines. The stone shall be covered
with a layer of synthetic filter fabric that meets the requirements
of § 6.33(L) of this Part.
E. Leachfield Construction
Where the Invert of the Distribution Lines is Below Original Grade.
(See § 6.65 of this Part, Figure 7)
1. The soil between the
dispersal trenches shall remain undisturbed.
2. The Director may approve
designs where the soil within the entire area of the leachfield is
removed if the applicant shows that trench excavation is impractical,
for example due to the presence of excessive boulders or stumps. If
any B horizon soil remains, only tracked vehicles shall be allowed
within this area to avoid compacting the soil. If the soil within the
entire area of the leachfield is removed, the soil shall be replaced
with properly compacted gravel meeting the requirements of § 6.33(M)
of this Part to an elevation that will be two (2) inches above the
top of the distribution lines. The trenches shall be excavated out of
the compacted gravel.
3. A six (6) inch layer of
gravel meeting the requirements of § 6.33(M) of this Part shall be
placed below the stone in the dispersal trench. Where the bottom of
the stone lies on or within a soil horizon that meets the description
of Soil Category 1 from § 6.16(K) of this Part and such horizon is
at least six (6) inches thick below the stone, the six (6) inch
gravel layer is not necessary. However, if this Soil Category 1
horizon is described as extremely cobbly, the six (6) inch gravel
layer shall be required.
4. The minimum distance
between walls of adjacent dispersal trenches shall be five (5) feet,
however, greater distances are recommended.
F. Leachfield Construction
Where the Invert of the Distribution Lines is Above Original Grade.
(See § 6.66 of this Part, Figure 8)
1. The leachfield and five (5)
feet beyond the leachfield shall be stripped of all topsoil (A
horizons). In order to avoid compaction of the B soil horizon, only
tracked vehicles shall be allowed within this area.
2. Properly compacted gravel
that meets the requirements of § 6.33(M) of this Part shall be
placed throughout the excavation to an elevation that will be two (2)
inches above the top of the distribution lines. Dispersal trenches
shall be excavated out of the compacted gravel. There shall be a
minimum six (6) inch gravel base layer meeting the requirements of §
6.33(M) of this Part below the stone.
3. The maximum depth of stone
below the distribution line invert shall be one-half (½) feet; and
4. The minimum distance
between walls of adjacent dispersal trenches shall be ten (10) feet.
G. Leachfield Construction on
Sloping Sites - Where the dispersal trenches are to be constructed
such that the invert of the distribution lines in the trenches will
not all be at the same elevation, the invert of the distribution
lines shall be below the original grade, the distribution lines in
the trenches shall be laid level, and the leachfield shall be
constructed in accordance with the following (See § 6.67 of this
Part, Figure 9):
1. The distribution box shall
provide equal dosing to each dispersal trench;
2. A tipping distribution box
or pump shall be used;
3. Leachfield trenches shall
be parallel to the contours of the existing grade where possible;
4. The ends of the
distribution lines shall be connected by a relief line that is
imperforated, SDR 35 PVC laid with watertight joints that is of the
same diameter as the perforated pipe that it connects;
5. The minimum distance
between walls of adjacent dispersal trenches shall be ten (10) feet;
6. Gravel shall be placed
below the stone in accordance with § 6.34(E)(3) of this Part;
7. Each dispersal trench must
meet the adjacent side slope requirements of § 6.33(Q) of this Part;
8. The soil between the
dispersal trenches shall remain undisturbed. If the presence of
boulders or other obstacles make trench excavation impractical, the
OWTS shall be constructed in accordance with § 6.34(E) or (F) of
this Part; and
9. The Director may require
that OWTSs with a design flow exceeding six hundred ninety (690)
gallons per day submit additional information regarding wastewater
loading and groundwater flow to ensure OWTS effectiveness on sloping
sites.
H. Location Under Traffic
Areas - The leachfield for a dispersal trench system shall not be
paved or subject to vehicular traffic, including parking.
I. Summary of Dispersal Trench
Construction Details:
Maximum
length per line without dosing
50
feet
Maximum
length per line with tipping distribution box
75
feet
Maximum
length per line with pump
100
feet
Minimum
diameter of distribution lines
4
inches
Maximum
width of dispersal trench bottom
3
feet
Minimum
distance between walls of adjacent trenches
5
feet/10 feet(Note 1)
Minimum
cover over invert of distribution lines
1.5
feet
Maximum
cover over invert of distribution lines
2.5
feet
Note
1: 10 feet for those OWTSs on sloping sites and for those OWTSs
where the invert of the distribution lines is above original
grade.
6.35 Concrete Chambers
A. See § 6.68 of this Part,
Figure 10.
B. An OWTS using precast
concrete chambers may be constructed in lieu of a dispersal trench
OWTS. Concrete chambers must be preceded by a septic tank and must be
installed in a trench configuration. Deep concrete chambers meeting
the requirements of § 6.35(F) of this Part will not be permitted
except for OWTS Applications for Repair when no other type of
leachfield can be utilized.
C. Shallow Concrete Chambers
1. Dimensions - Shallow
concrete chambers are four (4) feet by eight (8) feet by eighteen
(18) inches deep with an open bottom and perforated side walls.
2. Site limitations - Shallow
concrete chambers shall not be permitted where any of the following
occur:
a. The chamber invert would be
more than one (1) foot above the original grade;
b. The chamber inverts would
be set at different elevations; or
c. The seasonal high
groundwater table is less than four (4) feet from the original ground
surface.
D. Shallow Concrete Chamber
Effective Leaching Area - Effective leaching area for shallow
concrete chambers shall be calculated based on § 6.35(E) of this
Part. Required minimum leaching area shall be calculated in
accordance with § 6.33(B) of this Part.
E. Shallow Concrete Chamber
Effective Leaching Area
Shallow
Concrete Chambers
12”
stone below
24”
stone below (Note 1)
Each
end unit (sq. ft.)
78
102
Each
Interior Unit (sq. ft.)
64
80
Note
1: Shallow concrete chambers installed with twenty-four (24)
inches of stone below the chamber may be used for OWTS
Applications for Repair only.
F. Deep Concrete Chambers
1. Dimensions - Deep concrete
chambers are approximately equal in width and depth with an open
bottom and perforated side walls.
2. Limitations - Deep concrete
chambers are prohibited for OWTS Applications for New Building
Construction and OWTS Applications for Alterations to a Structure.
Deep concrete chambers will not be permitted for OWTS Applications
for Repair where another type of leachfield designed in accordance
with §§ 6.33, 6.34, and 6.35 of this Part can be sited and is
deemed acceptable by the Department. The Licensed Designer must
demonstrate that the repair alternatives to a deep concrete chamber,
other than a bottomless sand filter or pressurized shallow narrow
drainfield, are not feasible.
G. Deep Concrete Chamber
Effective Leaching Area - Effective leaching area for deep concrete
chambers shall be calculated based on § 6.35(H) of this Part.
Required minimum leaching area shall be calculated in accordance with
§ 6.33(B) of this Part.
H. Deep Concrete Chamber
Effective Leaching Area
Deep
Concrete Chambers
12”
stone on sides, 12” stone below
Each
end unit (sq. ft.)
98
Each
Interior Unit (sq. ft.)
58
I. Concrete Chamber
Construction
1. Concrete chambers shall be
constructed of precast concrete. The bottom of the chambers shall be
open and the sides and end (end units) shall be perforated.
2. Access - The top of the
chamber trench shall have an access opening into a chamber at
intervals not greater than fifty (50) feet that consists of a
removable cover of concrete, iron or other durable material. For
OWTSs designed to dispose of up to two thousand (2,000) gallons per
day and OWTSs that are not located under a paved area, the top of the
access opening shall accommodate a riser and shall be brought to
within one (1) foot of the finished grade and properly marked. For
OWTSs designed to dispose of greater than two thousand (2,000)
gallons per day, commercial OWTSs, and all OWTSs located under paved
areas, the access openings shall meet the following requirements:
a. Access openings shall have
a riser and shall be brought to finished grade;
b. Lids on the top of the
concrete chambers should remain in place where practical. Lids for
the openings at finished grade shall prevent unauthorized entry by
meeting either of the following:
(1) Lids shall weigh a minimum
of fifty-nine (59) pounds and fit tightly into the riser as shown in
§ 6.64 of this Part, Figure 6; or
(2) Lids shall be tamper
resistant and mechanically fastened.
c. Surface water shall be
diverted away from the access openings; and
d. Concrete chambers in place
as of January 1, 2008 that have access openings to finished grade
shall be in compliance with the provisions of § 6.35(H)(2)(b) of
this Part no later than January 1, 2013.
J. Excavation and Construction
of a Concrete Chamber Leachfield
1. The overall width of the
trench must not exceed six (6) feet.
2. Spacing - The minimum
distance between walls of adjacent trenches in a concrete chamber
leachfield shall be at least six (6) feet.
3. The soil between the
dispersal trenches shall remain undisturbed. The Director may approve
designs where the soil within the entire area of the leachfield is
removed if the applicant shows that trench excavation is impractical,
for example due to the presence of excessive boulders or stumps. When
the soil within the entire area of the leachfield is removed, the
soil shall be replaced with properly compacted gravel meeting the
requirements of § 6.33(M) of this Part to a depth that will be to
the top of the chamber. The trench shall be excavated out of the
compacted gravel.
4. A six (6) inch layer of
gravel meeting the requirements of § 6.33(M) of this Part shall be
placed below the stone in the trench. Where the bottom of the stone
lies on or within a soil horizon that meets the description of Soil
Category 1 from § 6.16(L) of this Part and such horizon is at least
six (6) inches thick below the stone, the six (6) inch gravel base
layer is not necessary. However, if this Soil Category 1 horizon is
described as extremely cobbly, the six (6) inch gravel base layer
shall be required.
5. Stone - Stone meeting the
requirements of § 6.33(K) of this Part shall be placed beneath the
chamber in accordance with §§ 6.35(E) or (H) of this Part. The
space between the excavation and the chamber wall shall be twelve
(12) inches and shall be backfilled with stone to the top of the
chamber. The stone and the top of the chambers shall be covered with
filter fabric that meets the requirements of § 6.33(K) of this Part.
K. Effluent Distribution
1. The invert of the inlet of
the chamber shall be two (2) inches lower than the invert of the
outlet of the distribution box.
2. The maximum length of a
chamber trench shall be as follows:
a. Without dosing - fifty
(50) feet;
b. With a tipping distribution
box - seventy-five (75) feet; or
c. With a pump - one hundred
(100) feet.
3. Effluent shall be applied
to the chamber trenches at least every twenty-five (25) feet.
4. For multiple trench
concrete chamber leachfields, the ends of the chamber trenches shall
be interconnected with imperforated SDR 35 PVC pipe laid with
watertight joints. If the pipe will be subject to vehicular traffic,
it shall be Schedule 40 PVC.
L. Location Under Traffic
Areas - The area subject to vehicular traffic, including parking
areas, shall be limited to twenty-five percent (25%) of the
leachfield area. Where any portion of the leachfield is installed
under an area subject to vehicular traffic, the structure must be
capable of withstanding HS-20 wheel loads. All access manholes in
areas subject to vehicular traffic shall be brought to grade with
covers and frames capable of withstanding HS-20 wheel loads and
meeting the requirements of §§ 6.35(I)(2)(a) through (d) of this
Part. Such OWTSs must be vented with screened vents located in a
protected area.
6.36 Pressurized Drainfields
A. General design parameters
for all pressurized drainfields
1. All pressurized drainfields
shall include timed-dosing, with the use of a control panel
containing elapsed time meters and cycle counters for the pump(s) and
alarm(s).
2. Setback to foundation and
tanks: The minimum setback distance from the pressurized drainfield
to any foundation shall be eight (8) feet, provided that the
elevation of the basement slab in the dwelling is above the design
seasonal high groundwater table (SHWT) depth and that there are no
drains associated with the foundation. The minimum setback distance
from the pressurized drainfield to any tank equal or larger than one
thousand (1000) gallon capacity shall be four (4) feet.
3. Setback to structures
impeding groundwater flow: The interior face of any structural or
landscape retaining wall that may interfere with ground water flow,
down-gradient from the pressurized drainfield, must be located at
least twenty five (25) feet from the pressurized drainfield.
4. All setbacks and all other
regulatory requirements contained in the Department Rules, that are
not mentioned in §§ 6.36, 6.37, and 6.38 of this Part, shall be
met.
5. Designs greater than nine
hundred (900) gallons per day: Where design flows exceed nine hundred
(900) gallons per day, the Department may require additional
technical studies to ensure that the soil will accept and transmit
effluent at the proposed loading rate without excessive mounding of
ground water; seepage outbreak, such as at nearby cut slopes, toe
slopes or property boundaries; adverse effects on the operation of
the pressurized drainfield; or adverse effects on nearby ground water
and surface water resources. The Department shall reserve the right
to require additional supporting engineering calculations for the use
of pressurized drainfields on design flows greater than two thousand
(2000) gallons per day. The Department may require increased setbacks
depending on the site specific conditions. In addition, commercial
systems with high strength waste shall incorporate added treatment
components to ensure treatment limits herein for BOD5, TSS and FOG
are achieved prior to using a pressurized drainfield.
6. Pressurized drainfields
must be designed by a Class II or III Licensed OWTS Designer unless
the Department determines otherwise. No designer or installer shall
undertake the design or installation of a pressurized drainfield
pursuant to regulations unless he/she has received appropriate
training by a vendor, professional organization, or institution
recognized by the Department for this purpose. Any licensed designer
or installer must document to the Department that applicable training
has been completed. Class 1 designers can submit designs to the
Department for low pressure pipe (LPP) that follow septic tank
effluent only. Class 1 designers must document to the Department
completion of training regarding pressurized dosing (selecting a pump
for pressurized systems) that has been conducted by a professional
organization, or institution recognized by the Department for this
purpose.
7. Residual head: Designs
should account for a minimum of two (2) feet of head (pressure) at
the distal end of each distribution lateral.
8. Design maintenance notes:
Designers should provide adequate notes on their plans to facilitate
proper maintenance of all system components.
9. Drainfields at different
elevations and zoned drainfields: Site conditions may not facilitate
installing drainfield trenches or zones at the same elevation. In
these situations, gate valves can be used to provide uniform
wastewater distribution. Alternately, orifice plates may be used to
help equalize flow to trenches that are not at the same elevation.
Ball valves shall not be considered a suitable means for flow
control. Access ports must be installed at the locations of all
valves, lateral ends and orifice plates. Careful attention should be
given to drainback when placing trenches or zones at different
elevations since uneven drainback may overload zones or trenches.
Types of drainfields that can be placed at different elevations shall
conform with the Rules.
10. Sequencing valves: Access
ports or manholes shall be required for sequencing valves and shall
be sufficiently sized to facilitate maintenance.
B. Common components for all
pressurized drainfields
1. General
a. All pressurized drainfields
submitted under §§ 6.36, 6.37, and 6.38 of this Part shall use
programmable timers.
b. All advanced treatment
units to precede pressurized drainfields designed in accordance with
§§ 6.36, 6.37, and 6.38 of this Part must fall within one of the
following categories:
(1) Category 1 technologies:
Advanced treatment units that are timed-dosed and have been
classified by the Department as meeting effluent standards less than
or equal to twenty (20) mg/L for both BOD5 and TSS; and FOG of less
than or equal to five (5) mg/L (see § 6.69 of this Part, Figure 11).
(2) Category 2 technologies:
Advanced treatment units that are not timed-dosed and have been
classified by the Department to at least meet effluent standards of
thirty (30) mg/L for both BOD5 and TSS; and FOG of less than or equal
to five (5) mg/L (see § 6.70 of this Part, Figure 12).
2. Dosing Tank Specifications
a. A dosing tank must be
provided following the advanced treatment step to provide wastewater
storage and to house the pump discharge assembly. All dosing tanks
used in a pressurized drainfield system must be watertight. All inlet
and outlet pipes to concrete dosing tanks shall have flexible rubber
seals secured by stainless steel bands. Watertight rubber grommets
must be used at inlet and outlet pipes to plastic or fiberglass
dosing tanks as well as on plastic manhole risers attached to
concrete tanks.
b. Category 1 technology
dosing tanks shall provide storage volume at least equal to the
design volume dosed onto the pressurized drainfield during one pump
run time. See §§ 6.71 and 6.72 of this Part, Figures 3 and 4.
c. A storage capacity must be
provided in pressurized drainfield dosing tanks that follow Category
2 technologies or for septic tank effluent. The surge storage
capacity shall be positioned between the elevation of the timer
operating control switch and the high water alarm/peak enable control
switch. The high water alarm shall be placed a minimum of two (2)
inches below the invert of the inlet to the tank.
d. Dosing tanks following
treatment units that are not timed-dosed shall be a minimum of four
hundred fifty (450) gallons. For single family residential designs
the required surge storage shall be seventy five (75) gallons per
bedroom; for other designs the surge storage shall be calculated, at
minimum, 50% of the daily design flow. See §§ 6.73, 6.74, and 6.75
of this Part, Figures 15, 16, and 17.
e. The pump servicing the
pressurized drainfield shall be submerged completely at all times.
f. All manhole risers in the
tanks/chambers serving the pressurized drainfield shall be
watertight, and installed to finish grade with secure lids, in
accordance with § 6.27(H)(2) of this Part.
3. Pump, Discharge Assembly
and Transport Line Specifications
a. Pressure requirements:
Pumps shall be sized to provide a minimum of two (2) feet and a
maximum of seven (7) feet of head (i.e. pressure) at the distal end
of each distribution lateral in the pressurized drainfield.
b. Wiring requirements: Pumps
dosing pressurized drainfields following a non timed-dosed system
shall be wired on the same electrical circuit as the advanced
treatment unit.
c. Discharge assembly: The
discharge assembly in the dosing tank shall be provided with a check
valve; a mechanical disconnect from the pump to the discharge
assembly, reachable within twelve (12) inches of the finish grade;
and a valve to hydraulically separate the chamber from the
pressurized drainfield. If the transport pipe needs to be drained
after each pump event, a weep hole (3/16”) shall be placed in a
location within the discharge assembly that allows for drainback.
Spray from the weep hole shall be directed away from sensors and
controls (floats, transducers, etc.).
d. Anti-siphon devices and
check valves: If the transport pipe slopes towards a pressurized
drainfield having distribution piping at a lower elevation than the
maximum water level in the dosing tank, an anti-siphon device shall
be used on the pump discharge assembly, or at the highest point in
the piping system from the tank to the distribution piping.
e. Shallow transport lines
(above frost depth) shall drain after each dose or be insulated. If
site conditions do not allow a transport line to drain, then a two
(2)-foot minimum burial is required and a two inch (2”) minimum
thick by twenty four inch (24”) wide expanded rigid polystyrene
plastic insulation must be placed above the pipe.
f. Pump screen: All pumps
following Category 2 technologies must have either a screened
vault/basket or an in-line effluent filter. All pumps following a
septic tank shall have an effluent screen. See §§ 6.73, 6.74, and
6.75 of this Part, Figures 15, 16, and 17.
g. Piping and fittings: All
piping from the pump flange to the distal end of the drainfield
lateral shall be pressure rated schedule (SCH) 40 polyvinyl chloride
(PVC) or equivalent.
h. Excavation: Sagging in the
transport line shall be prevented by either:
(1) Placing the transport line
in an undisturbed trench bottom excavated to the specified grade; or
(2) Placing a layer of one
inch (1”) minus gravel, or three quarter inch (3/4”) crushed
stone, on the undisturbed trench bottom to bring it to specified
grade.
i. Velocities within pipes:
Liquids shall flow at a minimum velocity of two (2) feet per second
and a maximum of eight (8) feet per second. These apply for discharge
assemblies, transport pipes, manifolds and laterals.
4. Programmable Timer,
Controls and Control Panels
a. Timer settings: The timer
shall be programmed to provide several small doses of wastewater to
the pressurized drainfield throughout a twenty four (24) hour clock
time period.
(1) The system design shall be
based on a minimum of one (1) dose per hour and, for typical single
residential use, up to two (2) doses per hour.
(2) The designer or the
authorized O&M service provider shall insure that the timer is
field-set at the time of system start up.
(3) Two (2) to four (4) weeks
after sufficient use of the system, the service provider shall ensure
that the timer is reset, as needed, based upon actual flow through
the system.
(4) Timer settings shall be
checked at every established maintenance and inspection visit and
when home occupancy changes and adjusted as needed.
b. Controls:
(1) Controls shall be in the
form of signal rated floats, pressure transducers or other methods
approved by the Department. A high water alarm and pump controls
shall be included. A peak enable control shall be included either as
part of the timed-dosed pretreatment system (Category 1 technology)
or as part of the dosing tank for the pressurized drainfield served
by a non timed-dosed pretreatment system or septic tank.
(2) The peak enable control
shall engage the programmable timer into the peak enable mode in the
event of timer malfunctions or temporary excessive water use. The
peak enable mode in dosing tanks for the pressurized drainfield
served by a non timed-dosed pretreatment system shall cut the “off”
time of the pump to half its original setting to catch-up with
excessive temporary flow. The pump “on” time shall stay the same
during the peak enable mode to minimize saturated conditions in the
drainfield.
(3) A low water/redundant off
control is required for pump tank using timed dosed effluent to a
pressurized drainfield (following Category 2 technologies or LPP
receiving septic tank effluent).
c. Control panel:
(1) The control panel box must
be placed outside on a suitable pedestal near the structure that it
serves or be mounted on an outside wall of the structure. The panel
box must be within view of the system location. The control panel
shall be placed at a comfortable height for access.
(2) The control panel and
junction boxes must, at minimum, meet the requirements for the NEMA
4X specifications in the National Electrical Manufacturers
Association Standard 250-2014 "Enclosures for Electrical
Equipment (1000 Volts Maximum)" incorporated above at § 6.7 (F)
of this Part. The electrical conduit to and from the control panel
must have NEMA approved expansion fittings and must also have
appropriate seals to prevent gases and moisture from reaching the
control panel or junction boxes.
(3) The control panel shall
include a pump elapsed time meter ((ETM) to record total pump run
time) and cycle event counters ((CC) recording events for each pump,
peak enable counter, and alarm event). The ETM and CC shall be
non-resettable.
C. Common Final Installation
Steps for all Pressurized Drainfields
1. Head requirements:
Immediately after any pressurized drainfield has been installed, the
head or “squirt height” of the distribution laterals shall be
determined, recorded in the maintenance record and left on site. When
measuring the distal head, the measurement shall begin at the invert
of the lateral.
2. Trees and shrubs: Trees and
woody shrubs shall be kept a minimum distance of ten (10) feet from
the pressurized drainfield.
D. Operation and Maintenance
Requirements for all Pressurized Drainfields
1. General: An O&M
agreement is required to be in place for the life of the system. The
first O&M agreement of the system shall be recorded in the Land
Evidence records of the pertinent City/Town.
2. Site Visits: At each of the
operational and maintenance visits, readings from elapsed time
meters, event counters, and water meters shall be recorded on the
data cards.
3. Routine Periodic
Maintenance
a. Laterals: An eight (8) foot
long clear graduated PVC pipe shall be temporarily attached at the
end of a lateral to measure residual head and compare with the
pressurized drainfield start-up measurement. Increased residual head
(distal head or squirt height) will signal orifice clogging and
lateral cleaning must be performed. Decreased residual head might
indicate pump wear, clogging or other problems in pipe(s) or screens
needing service/cleaning.
b. All pressurized drainfields
shall require lateral flushing / bottle brush treatment at least once
a year.
c. Setback to brush/trees: Any
brush or trees growing within ten (10) feet of the pressurized
drainfield shall be removed.
d. All splice boxes shall be
checked for moisture. If moisture is encountered in any splice box,
the source shall be identified, corrections made (if needed), and
splice box dried and secured before leaving the site.
e. To prevent contamination of
the local water supply, the service provider must use his/her own
hose with a backflow preventer.
f. Sequencing valves:
Sequencing valves shall be tested for proper sequencing through all
the outlets (turn pump on/off through all zones).
6.37 Advanced Pressure Drainfields
(APDs)
A. General
1. An advanced pressure
drainfield must not be used without an advanced treatment unit(s)
that has been approved by the Department to meet either Category 1 or
Category 2 technology designations. An APD shall not be used with
septic tank effluent. APDs include bottomless sand filters (BSFs) and
pressurized shallow narrow drainfields (PSNDs).
2. Protecting the APD from
Damage: The landscape over and immediately adjacent to any APD system
shall be protected in accordance with § 6.33(T)(2) of this Part.
B. APD Common Design
Parameters
1. APD hydraulic loading
rates: Sizing of the APD is based on soil texture, structure and
consistence of the most restrictive horizon within three (3) feet
below the proposed base of the APD (see § 6.37(E)(4) of this part).
A soil evaluation by a Class IV Soil Evaluator is required.
2. Flow Differential Between
the First and Last Orifice in APD Laterals: The maximum head
differential between the first and last orifice on each APD lateral
shall be no greater than ten percent (10%).
3. Maximum Volume per Orifice
per Dose: All APDs covered by this document shall be dosed up to a
maximum of zero point two five (0.25) gallons per orifice per dose.
4. Hydraulic loading rates for
Advanced Pressure Drainfields.
Soil
Category
Soil
Texture
Soil
Structure
Soil
Consistence In-Hand Using Soil Clods
Excavation
Difficulty
Category
1 Technologies Loading Rate (gal/ft2/day)
Category
2 Technologies Loading Rate (gal/ft2/day)
1
cos,
s, lcos, ls, cosl, fs
structureless-
single grain or subangular blocky
loose
friable
none
2.3
1.5
2
vfs,
lvfs
structureless-
single grain
loose
none
2.7
1.9
3
ls,
sl, l
granular,
subangular blocky
very
friable to friable
low
3.5
2.3
4
lfs,
lvfs, fsl, vfs
granular,
subangular blocky
very
friable to friable
low
3.1
2.0
5
sil,
si, vfsl
subangular
blocky
very
friable to friable
low
2.7
1.9
6
lcos,
cosl, lfs, ls, sl, l,
structureless
massive
very
friable to friable
low
2.3
1.5
7
fsl,
vfsl, sil, si, vfs
structureless-
massive
very
friable to friable
low
to moderate
2.1
1.5
8
all
textures
structureless-
massive
firm
to very firm
moderate
1.9
1.3
9
all
textures
platy
or structureless- massive
firm
to very firm
high
1.5
1.0
10
all
textures
platy
or structureless- massive
extremely
firm
very
high to extremely high
Not
Allowed
Not
Allowed
Notes:
(1)
Loading rates shall be based on 115 gallons/bedroom and upon
texture, structure, and consistence of the most restrictive
horizon within 3 feet below the proposed base of the APD. Please
see §§ 6.76, 6.77, 6.79, 6.82, and 6.83 of this Part, Figures
18, 19, 21, 24, and 25.
(2)
Pressurized shallow narrow drainfields placed in cos, vcos,
gravelly or very gravelly soils shall be installed over a
leveled-off 6-inch layer of sand meeting ASTM C-33 incorporated
above at § 6.7(G) of this Part.
C. Bottomless Sand Filters
(BSFs)
1. BSF design guidelines: All
BSFs shall conform to § 6.36(A) of this part “General design
parameters for all pressurized drainfields”.
a. Vertical separation
distances: All vertical separation distances defined in this Part
must be met when using a BSF. The vertical separation distance shall
be measured from the cover stone-sand interface below the PVC
distribution manifold, to the seasonable high water table (SHWT) or
to the impervious layer as defined by the Department. (See §§ 6.76
and 6.77 of this Part, Figures 18 and 19). The required separation
distance to the SHWT shall be measured from twenty-four inches (24”)
above the base of the BSF (the minimum depth of sand media).
b. Hydraulic loading rates:
Hydraulic loading rates for BSFs will be based on the native
receiving soil characteristics and the quality of wastewater being
discharged by the preceding secondary treatment unit. These rates are
provided in the table in § 6.37(B)(4) of this Part.
c. Finished grade: Finished
grade around any BSF shall be a minimum of six inches (6”) and a
maximum of twenty four inches (24”) below the top of the enclosure
to prevent surface water from flowing onto the filter. One (1) layer
of secured pressure treated timbers with minimum nominal dimensions
of six inches by six inches (6" x 6"), (or other suitable
structural support) shall be placed around the top perimeter (See §§
6.76 and 6.77 of this Part, Figures 18 and 19).
d. Fill perimeter: The land
surface elevation two (2) feet below the cover stone-sand media
interface shall be maintained for a distance of at least five (5)
feet from the edge of the BSF. Land surface re-grading adjoining this
five foot (5') perimeter must maintain a minimum of 3:1 (run:rise)
slope down gradient (See § 6.76 of this Part, Figure 18).
e. BSF protection: The
proposed BSF location shall be staked out and protected in accordance
with § 6.33(T)(2) of this Part prior to any site preparation
activities.
f. Setbacks to trees and
shrubs: A minimum buffer of ten (10) feet shall be maintained between
BSFs and neighboring trees and shrubs. Where the 10- foot (10')
buffer cannot be maintained, a root barrier fabric shall be placed
between the trees and shrubs and the filter.
g. No structures, permanent
features, or large, heavy or numerous decorations shall be placed on
top of the BSF that would obstruct, prevent or hinder operation and
maintenance or access to the BSF.
2. Additional components of
the BSF: Bottomless sand filters shall also conform to the components
in § 6.36(B) of this Part: “Common components for all pressurized
drainfields”.
a. BSF Enclosures (See §
6.79, Figure 21)
(1) The walls of BSFs must be
lined with a thirty (30) mil flexible PVC liner with all boots,
patches, repairs, and seams having the same physical properties as
the liner material.
(2) Any penetration through
the PVC liner wall shall be done with a PVC boot attachment glued to
the liner with the appropriate resilient sealer.
(3) Support walls are needed
to prevent caving of the filter walls during construction. These
walls shall be rigid and made of sacrificial plywood or particle
board (or equivalent; plywood is intended to decompose over time) and
supported by at least one row of six inch by six inch (6" x 6")
nominal dimension pressure treated timbers (or equivalent) above the
finish grade.
(4) A permanent top frame
structure (such as pressure treated six inch by six inch (6" x
6") nominal dimension timbers, or other suitable structural
support) must be provided on any portion of a BSF that is installed
above grade. The top frame structure shall be a minimum of six inches
(6”) but no higher than twenty four inches (24”) above grade. The
design shall include cross-bracing to maintain structural integrity
of the frame. Below grade use of timbers is prohibited.
b. Bottomless Sand Filter
Media Specifications: All media within the enclosure and below the
cover stone shall have an effective size (D10) of 0.33 mm (+/-) and
uniformity coefficient (D60/D10) of 2.0 to 4.0. The maximum allowable
percentage of fines passing through a Number 200 sieve shall be one
percent (1%). Other than the gradation and fine content specified
above, the sand media shall meet the other ASTM C- 33 sand
specifications.
c. BSF distribution laterals
(1) General: Influent applied
to a BSF shall be distributed over the sand surface using small
diameter, pressure rated SCH 40 PVC pipe.
(2) Orifices: A series of
clean, uniform, one-eighth (1/8") inch diameter holes (orifices)
shall be drilled in the distribution laterals and spaced no less than
fourteen (14") inches and no more than twenty four (24")
inches apart. Two (2) orifices in each lateral shall be drilled
pointing up (12 o'clock position) and be located approximately one
third (1/3) and two thirds (2/3), respectively, along the length of
each lateral. All other orifices shall be drilled pointing down (6
o'clock position). Orifice shields shall be placed over each orifice
(above or below the lateral, as required). Orifice shields placed
below any orifice shall contain slots or holes to provide free
draining (usually referred to as cold weather orifice shields, see §
6.80 of this Part, Figure 22).
(3) Laterals: Laterals shall
be spaced between fourteen (14) inches and twenty four (24) inches on
center and shall be no longer than fifty (50) feet.
(4) Lateral ends: The distal
end of each BSF lateral shall be fitted with a forty five (45) degree
elbow and closed off with either a ball valve or a threaded end and
cap (see § 6.81 of this Part, Figure 23).
(5) Orifice square grid and
space to liner: Lateral spacing and orifice spacing shall be as close
to square as practicable. The space from the ends of the laterals to
the liner shall be close to half the orifice spacing and be able to
accommodate the fittings (i.e.: 45 degree elbow, threaded end adapter
and cap) and have sufficient space for maintenance activities. See §
6.78 of this Part, Figure 20.
d. BSF inspection well: One
(1) inspection well shall be installed in the approximate center of
the filter and extend down to the sand and native soil interface (See
§§ 6.76, 6.77, and 6.78 of this Part, Figures 18, 19 and 20).
Larger zoned BSFs shall have at least one (1) inspection well per
zone.
e. BSF cover stone: A three
eighths to one half (3/8 - 1/2") inch round or sub-rounded,
screened or crushed, uniform in size so that no more than five
percent (5%) of the sample is greater than one half inch (1/2”) and
no more than five percent (5%) shall pass a three eighths inch (3/8”)
sieve, non-shale or other soft stone, double washed, containing
little or no fines shall be used for cover stone on the BSF. Total
depth of the stone shall be eight to nine (8-9) inches, depending on
the size of the lateral (see § 6.79 of this Part, Figure 21 and
installation procedures).
3. BSF Installation
Specifications
a. The proposed BSF location
shall be staked out and protected prior to any site preparation
activities.
b. Installation of BSF media
(1) BSF base: Sod, vegetation,
or dead or decaying organic litter or any organic soil horizon shall
be removed from the area planned for the BSF installation. Once the
proper design elevation for the BSF base has been reached and the
enclosure is in place, three (3) inches of the native soil material
shall be scarified and thoroughly mixed with 3 inches of the sand
media (see § 6.79 of this Part, Figure 21). Perimeter stripping is
prohibited. Excavation of soil beneath the established native soil
and filter sand interface is prohibited unless a boulder, stone,
fill, or other unexpected condition is encountered. Only approved
gravel (§ 6.33(M) of this Part) or BSF sand media shall be placed
for backfilling the base of the BSF before placement of the required
sand media.
(2) Placing sand media: All
sand media placed within the BSF enclosure and below the cover stone
must meet the requirements of § 6.37(C)(2)(b) of this Part and must
be a minimum of twenty-four (24) inches deep. The excavator or
backhoe bucket used to place media in the filter shall be washed
thoroughly to remove any mud or fines before the loading process
begins. The sand media shall be placed in level eight (8) inch lifts
in the filter. Each lift of sand media shall be lightly compacted.
(3) Placing stone cover: After
the required amount of filter sand has been added to the filter,
place three (3) inches of three-eighths inch (3/8") double
washed stone over the filter sand. After the distribution laterals
and orifice shields have been assembled atop the cover stone, six (6)
more inches of cover stone shall be added. The total depth of cover
stone over the sand media will be eight (8) to nine (9) inches,
depending on the size of lateral pipe employed (see § 6.79 of this
Part, Figure 21).
(4) Burial precautions: BSFs
shall not be buried or covered by topsoil or any other material which
will limit the gas or oxygen movement into and out of the filter.
Designer shall also note on their plans that the area of the BSF
shall be treated as a wastewater utility as tampering with a BSF may
present a public health risk. The BSF shall be accessed and serviced
by trained professionals only.
D. Pressurized Shallow Narrow
Drainfield
1. PSND Design Guidelines:
PSNDs shall also conform to § 6.36(A) of this part, “Common design
parameters for all pressurized drainfields”.
a. Vertical separation
distances: All vertical separation distances defined in §§ 6.33(H),
6.33(I), 6.43(E), and 6.44(C) of this Part must be met when using a
PSND. The vertical separation distance shall be measured from the
base of the PSND (the natural receiving soil surface), to the SHWT or
to impervious layer. The bottom of each lateral must be kept level.
The required separation distance to the SHWT shall be twenty four
inches (24”) statewide; the required separation distance to any
impervious material shall be forty eight inches (48”) statewide
unless otherwise specified by permit.
b. Trench spacing: The minimum
trench spacing shall be two and one-half (2.5) feet on-center (one
and one-half (1.5) feet edge-to-edge).
c. Shape and geometry: PSND
laterals shall be placed lengthwise along the existing site contours.
Laterals can be broken into zones of different shapes, so long as the
total basal area of each shape (zone) is the same as the other zones.
d. Finished grade: Finished
grade shall prevent surface water ponding and prevent surface runoff
over the PSND area.
e. Fill perimeter: The land
surface elevation of the infiltrative surface of each trench shall be
maintained for a distance of five (5) feet from the edge of the PSND.
Land surface re-grading adjoining this five foot (5') perimeter must
maintain a minimum of 3:1 (run:rise) slope down gradient for at least
twenty five (25) feet before meeting existing grade.
f. Soil between trenches:
Preservation of the native soil between trenches and minimizing its
disruption and compaction during construction is essential to
maintaining soil structure and therefore water and gas movement in
the soil around the trenches. For this reason construction is to be
trench-by-trench (relief from this requirement may be granted by the
Department on a case-by-case basis when informed of unanticipated
site conditions encountered during construction, see § 6.82 of this
Part, Figure 24). Excavation equipment with minimal pressure impact
(i.e.: mini excavators) shall be used when constructing PSNDs.
2. Additional Components of
the PSND: PSNDs shall also conform to the components in § 6.36(B) of
this Part, “Common components for all pressurized drainfields”.
a. Orifices: A series of
clean, uniform, one-eighth (1/8) inch diameter holes (orifices) shall
be made in the top of the distribution laterals (12 o’clock
position) and spaced according to the dosing requirements of the
system. Every fifth orifice along the lateral shall be drilled from
the bottom of the pipe (6 o’clock positions and eliminating the
up-facing orifice in that location) to allow drainage after a dose
and to prevent lateral freezing in cold weather.
b. Lateral clean outs: SCH 40
PVC or equivalent sweep elbows shall be attached to the distal end of
each PSND lateral to facilitate maintenance and inspection (§ 6.83
of this Part, Figure 25). A standard ninety (90) degree elbow shall
not be used here because it will interfere with maintenance
activities.
c. Lateral access ports: The
ends of the sweep elbows shall be readily accessible by means of a
six (6) to eight (8) inch diameter access box or port brought to
finish grade (see §§ 6.82 and 6.83 of this Part, Figures 24 and
25). Access ports shall be placed every twenty (20) feet maximum
along each lateral but no more than two (2) access ports are required
for each lateral (one at the midpoint of the lateral and one at the
clean out).
d. Drainfield Cover: The
dome-like covering over the PSND should be made of twelve (12) inch
diameter PVC plastic or an approved equivalent (see §§ 6.82 and
6.83 of this Part, Figures 24 and 25). Support bars (see §
6.37(D)(3)(c) of this Part, "PSND Installation Specifications")
shall be used along the trench to provide a larger bearing surface
that keeps the thin edge of the dome (PIP pipe only) from digging
deep into the infiltrative soil surface.
e. Trench Maximum Length:
Maximum trench length shall not exceed fifty (50) feet.
3. PSND Installation
Specifications
a. The proposed PSND location
shall be staked out and protected prior to any site preparation
activities.
b. Trenches: Each trench base
must be level. Do not over-dig the width or depth of the individual
trenches; minimal backfilling on bottom and sides provides a more
stable enclosure. Scarify each trench bottom before installing
components. PSNDs placed in cos, vcos, gravelly or very gravelly
soils shall have a leveled-off six (6) inch ASTM C-33 sand layer. Do
not remove the soil between the trenches. If the presence of
boulders, heavy roots, or other obstacles make trench construction
impractical, the basal area may be excavated as necessary, backfilled
with a maximum of ten (10) inches of ASTM C-33 sand (concrete sand)
to the design elevation of the bottom bed, the PSND constructed and
backfilled with native soil material (see § 6.82 of this Part,
Figure 24). Prior approval by the Department and notification of the
designer of record is required in order to remove material between or
under trenches.
c. Support bars: One (1) inch
diameter by fourteen (14) inch long Schedule 40 PVC support pipes
shall be used to support the dome (and pressure pipe), to act as a
spreader device and to provide a greater bearing surface for the
dome. These support/spreader pipes shall be spaced approximately four
(4) feet apart or whenever a drainfield cover joint occurs. Notches
shall be cut one (1) inch from either end of the support pipes for
the cover to fit into.
d. Laterals: Laterals shall be
as specified in § 6.37(D)(2) of this Part and shall be installed
over the support bars.
e. Drainfield cover: The
dome-like cover should snap over the spreader bars and into the
notches. A minimum of three (3) inches overlap shall exist between
drainfield cover joints. Filter fabric shall cover the overlap joint.
f. Inspection/access ports and
ends of trenches shall be as specified in § 6.37(D)(2) of this Part
and installed in access holes in the drainfield cover.
g. Grass cover: PSNDs shall
be kept free of debris and planted to a sod cover or seeded with
grass and protected. A watering program shall be in place until a
healthy and sustainable grass cover is obtained.
6.38 Low Pressure Pipe (LPP)
A. LPP design guidelines: LPPs
shall also conform to § 6.36(A) of this Part: “General design
parameters for all pressurized drainfields”.
1. All LPP systems under this
guidance shall conform to the design sizing parameters contained in
this Part for leachfields. Trench end interconnections are not
required when using LPP. If drainfield reduction size is sought due
to using advanced treatment technology, it shall conform to the
approved letter from the advanced treatment technology immediately
before the LPP.
2. Wastewater quality: When
using LPPs with advanced treated wastewater, the pretreatment must
meet the requirements for either Category 1 or Category 2
technologies. When using LPPs with residential septic tank effluent,
the quality of the effluent shall conform to BOD5 less than or equal
to one hundred seventy (170) mg/L, TSS less than or equal to sixty
(60) mg/L and FOG less than or equal to twenty five (25) mg/L
(residential strength septic tank effluent).
3. Vertical separation
distances: All vertical separation distances defined in §§ 6.33(H),
6.33(I), 6.43(E), and 6.44(C) of this Part must be met when using
LPP. The vertical separation distance shall be measured from the base
of the LPP (the natural receiving soil surface), to the SHWT or to
impervious layer.
4. Cover: The cover from the
top of the LPP to the proposed grade shall be from six inches (6”)
to eighteen inches (18”) (see §§ 6.84 and 6.85 of this Part,
Figures 26 and 27).
5. All LPPs shall be
timed-dosed, either by the timed-dosed technology preceding it (i.e.
Category 1 technology) or by incorporating a timed-dosed component as
specified in § 6.36(B) of this Part.
6. Flow differential between
first and last orifice in the laterals: The maximum head differential
between the first and last orifice on each lateral shall be no
greater than fifteen percent (15%).
7. Pump events per day and
maximum dose per LPP orifice: The number of dose events per day shall
be between twelve (12) and twenty four (24). The maximum dose per LPP
orifice shall be zero point five (0.50) gallons.
B. Components of the LPP: LPPs
shall also conform to other components in § 6.36(B) of this Part:
“Common components for all pressurized drainfields”.
1. Schedule 40 PVC or
equivalent sweep elbows (also called "turnups") shall be
attached to the distal end of each lateral to facilitate maintenance
and inspection. A standard ninety (90) degree elbow shall not be
used.
2. Orifice size and spacing:
For advanced treated effluent one eighth (1/8) inch diameter
(minimum) orifices shall be made in the top of the distribution
laterals (12 o’clock position) and spaced according to the dosing
requirements of the system. Orifice size for use with septic tank
effluent shall be three sixteenths (3/16) inch diameter. Every fifth
orifice along the lateral shall be drilled from the bottom of the
distribution laterals (at the 6 o’clock position, with no upfacing
hole at that location) to allow drainage after a dose and to prevent
lateral freezing in cold weather.
3. Orifice shields or sleeves
for dispersal trenches: Orifice shields shall be used at every
orifice. Cold weather orifice shields are required for the down
facing orifices (6 o’clock position). In lieu of orifice shields,
the pressure lateral may be inserted into a three or four-inch (3”or
4”) diameter high density polyethylene HDPE corrugated slotted or
perforated pipe. The sleeve shall extend to the sweep elbow and into
the inspection port. Pipe slots or perforations shall point in a
downward (6 o’clock) direction (see § 6.84 of this Part, Figure
26). When using plastic chambers, the laterals shall be suspended
from the inside top of the plastic chamber with appropriate ties. The
ties shall be spaced, at minimum, every three (3) feet. When using
concrete chambers, the laterals shall be placed above the crushed
stone under the concrete chambers or inside the precast concrete
channel. When the lateral is installed above the crushed stone, the
knockout at the bottom of each concrete chamber unit shall be open so
not to crush the pressure lateral upon installation (see § 6.85 of
this Part, Figure 27). When the lateral is placed inside the precast
concrete channel inside the concrete chamber, the concrete
observation ports shall be removed, only at the required manhole
riser interval. For either plastic or concrete chambers, orifice
shields shall be placed on the up facing orifices only when the
orifice lies within an observation port or manhole. For concrete
chambers with laterals installed on top of the crushed stone and for
all plastic chambers, orifice shields must be used on all the down
facing orifices. Orifice shields are not needed if an HDPE corrugated
perforated or slotted pipe sleeve is used or if the lateral is
installed inside the precast concrete channel on concrete chambers
(other than the upfacing orifices within the risers extending to
grade).
4. Inspection port: The ends
of the sweep elbows shall be readily accessible by means of a six (6)
to eight (8) inch diameter access box or port brought to the ground
surface.
C. LPP Installation and
maintenance specifications: Other than the components specific to
LPP’s, the trenches shall be installed and maintained in accordance
with the current Department Rules or the Department approved
technology equivalent replacement approval letters.
6.39 Large OWTS Requirements
A. Applicability - Large OWTSs
defined below shall comply with all other applicable provisions of
these rules in addition to the requirements in this § 6.36 of this
Part. A large OWTS shall be any OWTS designed, installed or operated
that meets any of the criteria in §§ 6.39(A)(1) through (4) of this
Part below.
1. Any single OWTS designed to
treat five thousand (5,000) gallons or more per day;
2. Multiple OWTSs for any
project on one or more parcels of land, excluding residential
subdivisions, where the total design flow for the project is five
thousand (5,000) gallons or more per day;
3. Multiple OWTSs serving more
than one (1) unit in a residential subdivision provided that the
total design flow of these OWTSs, each serving more than one (1)
unit, is five thousand (5,000) gallons or more per day; or
4. Proposed OWTSs and existing
OWTSs on the parcel that will result in a total design flow for the
parcel exceeding five thousand (5,000) gallons per day.
B. Application Requirements -
All submittals for OWTSs meeting the definitions in § 6.39(A) of
this Part shall include the following:
1. Notice Requirements: Each
application for a large OWTS shall be accompanied by a list
identifying the names and addresses of the local building official,
the water supply agency whose water supply is drawn from the
watershed or wellhead protection area wherein the property is
located, if applicable, all property owners within four hundred (400)
feet of any component of the proposed OWTS, and all abutting property
owners.
a. Upon application, the
applicant shall notify each person identified in § 6.39(B)(1) of
this Part above, of the application by certified mail, return receipt
requested.
b. Each notice shall
substantially conform to a form to be provided by the Director and
shall include the application number and a certificate of service.
c. The applicant shall clearly
mark each return receipt with the application number and the words
“5000 Gallon OWTS.”
d. All persons subject to the
notice shall be permitted twenty (20) days from the date specified in
the certificates of service within which to submit written comments
or information bearing upon the subject application.
e. All timely submitted
comments or information bearing upon the subject application and
relating to the intent and purpose of these rules shall be considered
by the OWTS Program staff as part of their review of the application.
f. When all certified receipts
have been returned to the applicant, copies of each notice,
accompanied by the appropriate certified receipt, shall be filed with
the OWTS Program along with a letter requesting that the application
be reviewed for final determination.
g. If a correctly addressed,
certified notice is returned to the applicant, the applicant may
submit the returned envelope and certified receipt, unopened, along
with the other return receipts as proof of the applicant’s good
faith attempt to serve the notice.
2. Soil evaluation, where
required by § 6.16 of this Part;
3. Description of the OWTS and
the treatment objectives;
4. Characteristics of the
wastewater;
5. Groundwater mounding
calculations for any of the component leachfields that are sized for
a design flow of five thousand (5,000) gallons per day or greater;
6. Impact analysis in
accordance with § 6.39(C) of this Part where the groundwater is
classified GA or GAA in accordance with the DEM “Groundwater
Quality Rules”;
7. Construction materials;
8. Schedule for phased
development if applicable; and
9. Plan for operation and
maintenance of the OWTS including qualifications of those responsible
for maintenance and long-term agreements for maintenance. Such plan
shall specify frequency of monitoring and performance inspections and
shall include routine maintenance logs needed for proper operation of
the OWTS.
C. Impact Analysis -
Applicants shall be required to demonstrate that the proposed
disposal site is capable of accepting, treating and transmitting
effluent at the proposed application rate without adverse impact to
surface water or groundwater. Such analysis shall include, but not
necessarily be limited to:
1. Surface Water: Applicants
shall submit an evaluation of the effect of estimated pollutant
loading to surface waters; and
2. Groundwater: Applicants
shall conduct modeling of nitrate concentrations in groundwater
downgradient of the OWTS at any compliance point defined as the
property boundary, drinking water well, or other sensitive receptor
as determined by the Director. This compliance point may extend
downgradient beyond the applicant’s property line if the adjacent
property is designated as a groundwater discharge zone in accordance
with the DEM “Groundwater Quality Rules.” The nitrate
concentration modeling shall be done in accordance with the
following:
a. For a single OWTS designed
to treat five thousand (5,000) gallons or more per day (§ 6.39(A)(1)
of this Part), the applicant shall conduct a nitrate impact analysis
that models a contaminant plume emanating from the OWTS;
b. For large OWTS defined
pursuant to §§ 6.39(A)(2), (3), or (4) of this Part where one or
more of the OWTSs is designed to treat one thousand (1,000) gallons
or more per day but less than five thousand (5,000) gallons per day,
the nitrate impact analysis may use the entire project site for
nitrate dilution modeling unless the Director requires a nitrate
impact analysis that models a contaminant plume emanating from any of
the OWTSs; or
c. For large OWTS defined
pursuant to §§ 6.39(A)(2), (3), (4) of this Part where all of the
OWTSs are designed to treat less than one thousand (1,000) gallons
per day, the nitrate impact analysis may utilize the entire project
site for nitrate dilution modeling.
D. Groundwater Monitoring -
Groundwater monitoring for nitrate and other possible contaminants,
at a frequency to be determined by the Director, may be a required
condition of the permit approval. Pursuant to the DEM “Groundwater
Quality Rules,” the Department may require that actions be taken by
the applicant when concentrations of nitrate in the groundwater at
the point of compliance exceed the preventive action limit of five
(5) mg/l.
6.40 Alternative Toilets
A. Alternative toilets include
composting toilets that meet or exceed performance standards
equivalent to the requirements of the National Sanitation Foundation
Standard 41, incorporated above at § 6.7(C) of this Part and
incinerator toilets.
1. Alternative toilets shall
be installed, operated and maintained in accordance with the
manufacturer’s specifications; have a positive ventilation system;
and must convert toilet contents to an inert, stable, or otherwise
harmless condition.
2. The owner shall hold a
valid maintenance contract at all times with an entity or individual
that is certified by the alternative toilet vendor to provide
maintenance of the alternative toilet. The minimum maintenance
contract term shall be two (2) years.
3. The owner shall record the
approved OWTS construction permit application form and associated
permit conditions for this alternative toilet and the initially
executed maintenance contract for the system in the municipal land
evidence records and provide DEM a copy of the recorded document
prior to DEM issuing a certificate of conformance.
4. Two (2) years after the
issuance of the certificate of conformance, and every two (2) years
thereafter, the owner shall submit a report prepared by a System
Inspector documenting the condition of all aspects of the OWTS,
including, but not limited to, certification that the OWTS has not
been modified and the design remains as permitted.
5. The Department may impose
additional conditions on the approval of an alternative toilet to
ensure proper operation and protection of public health and the
environment.
B. Separate OWTS - When an
alternative toilet is utilized, a separate OWTS shall be provided for
the treatment of any graywater and designed on sixty percent (60%) of
the normal daily design flow as determined by § 6.22 of this Part.
If wastewater from any conventional toilets is directed to this
leachfield, the leachfield must be designed for one hundred percent
(100%) of the daily design flow.
C. Residuals - Solids produced
by alternative toilets may be buried on site, unless prohibited by §
6.43 of this Part. Residuals shall not be applied to food crops.
Alternative toilets that may generate excess liquids shall either be
designed such that the residual liquids are pumped to the graywater
septic tank or to a separate holding tank. Liquids shall be removed
from this separate holding tank by a DEM permitted septage
transporter. This holding tank shall be designed as follows:
1. Have a capacity of two
hundred fifty (250) gallons or one year’s projected flow as
determined by the manufacturer, whichever is greater;
2. Be watertight and meet the
construction and materials standards for septic tanks in § 6.27(C)
of this Part; and
3. Be equipped with an
audio-visual alarm set to activate when the tank reaches eighty
percent (80%) of its capacity.
D. Removal and Replacement -
The property owner shall submit an OWTS Application for New Building
Construction pursuant to § 6.18(E) of this Part in order to remove
or replace the alternative toilet.
6.41 Alternative or Experimental
Technology Approval
A. No person shall submit an
OWTS design application incorporating an alternative or experimental
component or technology for wastewater treatment unless such
technology has been placed on the Department's approved Alternative
or Experimental Technology List.
B. Administrative - The
Department shall:
1. Maintain a list of all the
approved Alternative or Experimental technologies and all approved
guidance documents;
2. Charge fees to cover the
cost of administering the Alternative or Experimental approval
procedure, and reviewing, monitoring and tracking the performance of
alternative or experimental technologies; and
3. Have the authority to
remove any approved Alternative or Experimental technology from the
Department's approved list whenever the applicant fails to submit
reports or monitoring data; fails to perform required maintenance; or
fails to fulfill any other required tasks stated within these rules,
the approval letter or the approved guidance document.
C. Application Procedure -
Application shall be on forms approved by the Director, and shall
include the proper fee, all required submittals, performance data and
a draft guidance document that details all design, installation,
operation and maintenance, and other requirements.
D. Alternative Technology
Evaluation Criteria - The Director may approve an alternative OWTS or
technology if it meets the following criteria:
1. Class One:
a. The vendor provides at
least four (4) consecutive years of performance data per installation
for no fewer than ten (10) installations with data collected no less
frequently than quarterly that demonstrates that Department standards
are met; and
b. The vendor demonstrates
that the technology has been approved and utilized successfully for
at least four (4) consecutive years in Rhode Island with no fewer
than ten (10) installations or at least four (4) consecutive years in
at least three other jurisdictions with no fewer than ten (10)
installations in each jurisdiction.
2. Class Two: Satisfy either
§§ 6.41(D)(2)(a) or (b) of this Part below:
a. For any technology:
(1) The vendor provides at
least two (2) consecutive years of performance data per installation
for no fewer than ten (10) installations with data collected no less
frequently than quarterly, that documents that Department standards
are met;
(2) The vendor demonstrates a
theory or applied research; and
(3) The vendor demonstrates
that the technology has been approved and utilized successfully for
at least two (2) consecutive years in Rhode Island or at least two
(2) consecutive years in another jurisdiction with no fewer than ten
(10) installations in each jurisdiction.
b. For a nitrogen reducing
technology:
(1) The vendor provides
certification that the technology meets NSF International/American
National Standards Institute “Standard 245- Wastewater Treatment
Systems- Nitrogen Reduction”, incorporated above at § 6.7(D) of
this Part and the testing results show a preponderance of treated
effluent nitrogen concentrations of nineteen (19) mg/l or less; or
(2) The vendor demonstrates
approval for use in another jurisdiction in an area where the
temperature conditions are similar to or colder than those in Rhode
Island and with technology review criteria substantially equivalent
to Class One or Class Two listed above in §§ 6.41(D)(1) or
6.41(D)(2)(a) of this Part. Substantially equivalent review in
another jurisdiction shall be held to mean the other jurisdiction has
a minimum nitrogen reduction standard of fifty percent (50%)
reduction in total nitrogen concentration and a maximum effluent
total nitrogen concentration of nineteen (19) milligrams per liter
and the other jurisdiction has a review process in which the vendor’s
data is evaluated in light of a technology performance claim.
3. Only those alternative
technologies that have been approved and are on the approved
Alternative or Experimental Technology List shall be permitted by the
Director.
E. Alternative OWTS Component
Evaluation Criteria - The Director may approve an Alternative OWTS
Component if it meets the following criteria:
1. Class One:
a. The applicant documents
that applicable manufacturer’s and material standards are met;
b. The applicant provides at
least two (2) consecutive years of performance data for no fewer than
ten (10) installations that demonstrates Department standards are
met, if applicable; and
c. The applicant demonstrates
that the component has been approved and utilized successfully for at
least two (2) consecutive years in Rhode Island or at least two (2)
years in at least three (3) other jurisdictions for no fewer than ten
(10) installations in each jurisdiction.
2. Class Two:
a. The applicant documents
that applicable manufacturer’s and material standards are met;
b. The applicant provides one
(1) year of performance data for no fewer than ten (10) installations
that demonstrates Department standards are met, if applicable;
c. The applicant demonstrates
a theory or applied research; and
d. The applicant demonstrates
that the component has been approved and utilized successfully for a
minimum of one (1) year in Rhode Island or in at least one (1) other
jurisdiction with no fewer than ten (10) installations.
3. Only those Alternative OWTS
components that have been approved and are on the approved
Alternative or Experimental Technology List shall be permitted by the
Director.
F. Experimental Technology
Evaluation Criteria - The intent of an Experimental Technology
Approval is to evaluate, under actual field conditions, alternative
OWTS that appear technically capable of providing levels of
environmental protection at least equivalent to those provided by an
OWTS installed in compliance with these rules. Data gathered under an
Experimental Technology approval may be used to apply for Alternative
Technology Class Two approval.
1. Site Selection -
Experimental Technology vendors shall propose at least three (3)
sites and no more than ten (10) sites where the technology will be
applied. The technology may be approved for additional sites in
future years if the vendor demonstrates the initial installations
meet performance claims. Each location shall provide a suitable area
for the installation of an OWTS permitted under these rules or an
OWTS on the Department's approved Alternative Technology list. The
Director reserves the right to waive this requirement for
multi-family or commercial OWTSs.
2. The Director may approve an
Experimental Technology if the vendor meets the following criteria:
a. Prior to the approval of
any OWTS utilizing the Experimental Technology, the vendor shall
supply data that demonstrates that the Experimental Technology will
work in practice and in theory;
b. The vendor agrees in
writing to retain a third party acceptable to the Department to
conduct sampling on each of the OWTS with data collected no less
frequently than quarterly to document that the Experimental
Technology meets performance claims;
c. Substandard Performance -
The vendor agrees in writing to the following conditions regarding
the performance of the Experimental Technology:
(1) For OWTS Applications for
New Building Construction and OWTS Applications for Alteration to a
Structure where design flow is increased, the vendor must guarantee
the performance of the Experimental Technology and provide for
replacement with an OWTS on the Department’s Alternative Technology
List if the Department determines that the Experimental Technology
fails to meet the performance claim(s) after two (2) years;
(2) For OWTS Applications for
Repair and OWTS Applications for Alteration to a Structure where
there is no increase in flow, the vendor or system owner may, at the
Department’s discretion, be required to repair, replace, or take
any other action as required by the Department if the Department
determines that the Experimental Technology fails to meet the
performance claims after two (2) years or is found to be a failed
OWTS.
d. Financial Responsibility -
The vendor proposing the Experimental Technology, the property owner
and subsequent purchasers shall submit a signed statement to the
Director agreeing to repair, replace, or modify the Experimental
Technology, including to install an OWTS permitted under these rules
or an OWTS listed on the Department’s Approved Alternative
Technology List if the Department determines that the Experimental
Technology fails to perform as designed. The signed statement must
clearly state who is responsible for the cost of repairing,
replacing, or modifying the OWTS, whether through a bond or other
form of financial security posted by the vendor and acceptable to the
Director, or by the written agreement of the system owner to accept
financial responsibility.
G. Review and Approval
1. The Director shall review
the application and respond as follows:
a. Approve or deny the
application as submitted;
b. Recommend resubmission of
the application with modifications as proposed by the Director;
c. Recommend resubmission and
reclassification under §§ 6.41(D) through (F) of this Part; or
d. Recommend both resubmission
of the application with modifications and reclassification.
2. Technical Review - The
Department shall establish an Onsite Wastewater Treatment System
Technical Review Committee (OWTS TRC) consisting of individuals with
technical or scientific knowledge applicable to OWTS whose purpose is
to provide technical advice to the Director. The Department shall
select members for the OWTS Technical Review Committee from one or
more of the following organizations: Department of Environmental
Management; CRMC or other state agencies; University/college academic
communities; OWTS design and installation firms; Environmental
organizations; Public utilities; Builders; Local municipalities; and
other parties. At the request of the Director, the OWTS Technical
Review Committee may review the application and submit
recommendations on the proposed Alternative Technology, Alternative
OWTS Component or Experimental Technology. Recommendations from the
OWTS Technical Review Committee shall be submitted to the Director
within ninety (90) days from the application date.
3. The Director may establish
special conditions as necessary to ensure adequate protection of the
public health and the environment in its approval of alternative or
experimental technologies. Such conditions may include without
limitations: special qualification requirements for designers and
installers; specification of site characteristics; or monitoring,
testing and reporting requirements.
4. If the Alternative or
Experimental Technology is approved by the Director, the applicant
shall submit a finalized guidance document to the Director detailing
all design, installation, operation and maintenance requirements.
Once the guidance document has been approved, the applicant shall
schedule one (1) or more training events for Licensed OWTS Designers
and Licensed OWTS Installers. The Alternative or Experimental
Technology shall be placed on the Department's list after the first
training event has been held. The Department shall maintain the
approved Alternative or Experimental Technology List and maintain all
appropriate guidance documents for the following:
a. Alternative or Experimental
Technologies that are approved by the Director; and
b. Alternative OWTS Components
that are approved by the Director.
H. Approved Alternative or
Experimental Technologies
1. The Director may require
any of the following:
a. Monitoring or sampling of
any OWTS or OWTS component;
b. Submittal of evaluation
reports when an OWTS or OWTS component's performance is evaluated; or
c. An annual report of all
OWTS or component installations, failures and corrective action
taken.
2. Persons desiring to modify
an approved Alternative or Experimental Technology currently on the
approved Alternative or Experimental Technology List shall make the
request in writing and submit the following to the Department:
a. Documentation demonstrating
the applicant's compliance with the terms or conditions of the
original approval of the Alternative or Experimental Technology; and
b. Required fees, in
accordance with § 6.54 of this Part for Alternative or Experimental
Technology.
3. In order to remain on the
Department's approved Alternative or Experimental Technology List,
the applicant shall submit:
a. Application for renewal
ninety (90) days before expiration of the certification;
b. Renewal fee in accordance
with § 6.54 of this Part; and
c. Documentation that the
applicant is in compliance with the requirements of these rules and
in compliance with the expiring certification.
I. OWTS Applications Utilizing
Alternative or Experimental Technology - Once an Alternative or
Experimental Technology application is approved, individual
applications to design, construct, alter, or install a Department
approved Alternative or Experimental Technology may be submitted to
the OWTS section of the Office of Water Resources.
1. All applicants obtaining an
OWTS permit for a Department approved Alternative or Experimental
Technology requiring special operation and maintenance procedures
shall:
a. File a copy of the
initially executed contract for the OWTS’s operation and
maintenance, (including all required maintenance procedures and
monitoring schedules) with the land evidence records of the
municipality in which the OWTS is located; and
b. Submit to the Department a
certified copy of the recorded contract setting forth the date of the
recordation and the book and page where the contract is located in
the records of the municipal land evidence office.
2. The Department shall not
issue a conformance until the documents in §§ 6.41(I)(1) of this
Part are recorded with the municipality and a certified copy of the
recorded contract is submitted to the Department.
6.42 Critical Resource Areas -
General
A. Areas have been identified
as critical resource areas which are deemed to be particularly
sensitive to the detrimental effects of nutrients, pathogenic
organisms, organic chemicals and other substances that may be present
in effluent from OWTSs. These areas are in need of special protection
from such effects due to the unique and irreplaceable value of the
resource as a public water supply, fisheries habitat or public
recreation area.
B. Standards for siting and
design of OWTSs in these §§ 6.42, 6.43, and 6.44 of this Part are
established to enhance the treatment capability of OWTSs and thereby
reduce the potential for adverse effects to critical resources. In
areas designated as critical resources, the standards of §§ 6.42,
6.43, and 6.44 of this Part shall supersede minimum standards
wherever applicable.
C. Designation - Areas
designated as critical resource areas are defined below in §§
6.42(C)(1) through (3) of this Part. If the applicant disputes a
delineation in §§ 6.42(C)(1) through (3) of this Part, the
applicant may submit information on groundwater or surface water flow
to demonstrate to the Director by a preponderance of clear and
scientifically valid evidence that the delineation in question is
incorrect.
1. Salt Pond Critical Resource
Area: The watersheds, or portion thereof, to the salt ponds of
Charlestown, Narragansett, South Kingstown, and Westerly as
determined by the Rhode Island Coastal Resources Management Council’s
Salt Ponds Region Special Area Management Plan (See § 6.86 of this
Part, Figure 28), unless a determination of the groundwater recharge
area to the salt ponds has been adopted by the Department and the
Coastal Resources Management Council. The Salt Pond critical resource
area includes the watersheds, or portion thereof, to the following:
Maschaug Pond, Winnapaug Pond, Quonochontaug Pond, Ninigret Pond,
Green Hill Pond, Trustom Pond, Cards Pond, Potter Pond, and Pt.
Judith Pond.
2. Narrow River Critical
Resource Area: The Narrow River watershed, or portion thereof, as
determined by the Rhode Island Coastal Resources Management Council’s
Narrow River Special Area Management Plan (See § 6.87 of this Part,
Figure 29), unless a determination of the groundwater recharge area
to the Narrow River has been adopted by the Department and the
Coastal Resources Management Council.
3. Drinking Water Supply
Watersheds: Watersheds of public water system drinking water supply
reservoirs, unless a determination of the groundwater recharge area
to the reservoir has been adopted by the Department. The public water
systems include the following and any other public water system with
a drinking water supply reservoir approved by the Rhode Island
Department of Health (See §§ 6.88 through 6.91, Figures 30-33):
Bristol County Water Authority, Cumberland (town of), Eleanor Slater
Hospital/Zambarano Unit, Jamestown (town of), New Shoreham (town of),
Newport (city of), Pawtucket Water Supply Board, Providence Water
Supply Board, Stone Bridge Fire District, Woonsocket (city of), and
Yawgoog Scout Reservation.
D. OWTS Location - The
applicant shall be required to certify the location of a disposal
area with respect to any critical resource area. If the Department
determines that an OWTS may be wholly or partially located within a
critical resource area, the applicant shall be required to provide
evidence of the location with respect to the critical resource.
E. OWTS Applications for
Alteration to a Structure in Critical Resource Areas - An OWTS
Application for Alteration to a Structure which will result in an
increase in the flow or change in the type of wastewater within a
Critical Resource Area may not be approved unless the OWTS meets all
design and siting requirements of the rules in effect at the time of
permit application. The Department may grant an exemption to this
provision through the variance process pursuant to § 6.51 of this
Part if it is demonstrated that the deviation from the standard is
minor.
6.43 Requirements in the Salt Pond
and Narrow River Critical Resource Areas
A. For OWTSs located in the
Salt Pond and Narrow River critical resource areas as defined in §§
6.42(C)(1) and (2) of this Part, respectively, the standards
established in §§ 6.42 and 6.43 of this Part shall supersede
minimum standards established elsewhere in these rules.
B. Nitrogen Reducing
Technology
1. Nitrogen reducing
technology shall be required for all OWTS Applications for New
Building Construction, all OWTS Applications for Alteration to a
Structure, and OWTS Applications for Repair in the Salt Pond and
Narrow River critical resource areas. DEM may waive this requirement
for Applications for Repair involving only the replacement of the
septic tank if the applicant demonstrates that the leachfield is not
failed based on the criteria in § 6.8 of this Part, met the rules in
effect when the leachfield was installed, and is located more than
two hundred (200) feet from a coastal shoreline feature. Applicants
must still meet all CRMC established density and other requirements
where applicable.
2. Use of Composting Toilets -
Composting toilets meeting the criteria of § 6.40 of this Part may
be approved for use as a nitrogen reducing technology provided that:
a. Solid and liquid residuals
produced by the composting toilet are removed from the site and
properly disposed of at an approved facility beyond the boundary of
the Salt Pond and Narrow River Critical Resource Area;
b. All blackwater from the
structure must receive treatment via the composting toilet; and
c. All liquid residuals are
directed to a holding tank consistent with § 6.40(C) of this Part.
3. Exemptions for Applications
for Repair - The provisions of § 6.43(B)(1) of this Part may not
apply to an OWTS Application for Repair if the Municipality where the
OWTS is located:
a. Adopts an ordinance that
the Department determines reduces the long-term nitrogen load to the
Salt Ponds or Narrow River equivalent to or more than the provisions
of § 6.43(B)(1) of this Part; and
b. Enters into a legally
binding agreement with the Department and petitions the Department
for prior review of pertinent applications pursuant to § 6.18(C) of
this Part.
C. Location - The horizontal
distances between the parts of any OWTS and the feature requiring a
setback shall not be less than those shown in §§ 6.23(B) and (D) of
this Part.
D. Site Suitability - OWTS
shall not be located where the seasonal high groundwater table is
within five (5) feet of the original ground surface, or where a
restrictive layer or bedrock is within seven (7) feet of the original
ground surface, except in areas where the seasonal high groundwater
table is within two (2) to five (5) feet of the original ground
surface, or where a restrictive layer or bedrock is within four (4)
to seven (7) feet of the original ground surface and either of the
following in §§ 6.43(D)(1) or (2) of this Part occur. Twenty-five
(25) feet shall be maintained from the leachfield to any area where
the groundwater table is less than two (2) feet to the original
ground surface, or where bedrock is less than four (4) feet to the
original ground surface.
1. Application is for an
Alternative or Experimental OWTS approved pursuant to § 6.41 of this
Part for use under these conditions; or
2. Application is for a
dispersal trench OWTS that meets the following conditions:
a. The maximum depth of stone
below the distribution pipe invert is one-half (0.5) feet; and
b. The minimum distance
between walls of adjacent dispersal trenches is ten (10) feet.
E. OWTS Vertical Separation
Distance to Groundwater - The bottom of the stone underlying the
leachfield (or surface upon which the biomat develops) shall be at
least four (4) feet above the seasonal high groundwater table when
either soil category 1, 2, 3, 4, or 6 are encountered in determining
the maximum leachfield loading rate in accordance with § 6.33(B)(2)
of this Part.
6.44 Requirements in Drinking
Water Supply Watershed Critical Resource Areas
A. For OWTSs located in
drinking water supply watersheds as defined in § 6.42(C)(3) of this
Part, the standards established in §§ 6.42 and 6.44 of this Part
shall supersede minimum standards established elsewhere in these
rules.
B. Subsurface Drains -
Subsurface drains to lower the seasonal high groundwater table are
not permitted.
C. OWTS Separation Distance to
Groundwater - The bottom of the stone underlying the leachfield (or
surface upon which the biomat develops) shall be at least 4 feet
above the seasonal high groundwater table when either soil category
1, 2, 3, 4, or 6 are encountered in determining the maximum
leachfield loading rate in accordance with § 6.33(B)(2) of this
Part.
D. Location - The horizontal
distances between the parts of any OWTS and the feature requiring a
setback shall not be less than those shown in § 6.23(C) of this
Part.
6.45 Nitrogen Loading in Areas of
Onsite Drinking Water Wells
A. Applicability - For all
OWTS applications for New Building Construction and for Alterations
to a Structure, the design flow for an OWTS shall not exceed three
hundred forty-five (345) gallons per day per twenty thousand (20,000)
square feet of applicant’s lot area where the property utilizing
the OWTS or any adjacent lot is served by an onsite drinking water
well (public or private), or if there is a drinking water well within
two hundred (200) feet of the proposed OWTS, except as provided for
below in § 6.45(B) and (C) of this Part. The Director may require
this standard to be met for OWTS Applications for Repair in areas
where the groundwater is shown to exceed the Preventive Action Limit
for nitrate of five (5) mg/l, pursuant to the DEM “Groundwater
Quality Rules.” The three hundred forty-five (345) gallons per day
per twenty thousand (20,000) square feet loading limitation is
equivalent to approximately one-sixth (1/6) acre of applicant’s lot
area per bedroom. This rule applies to all OWTS except those subject
to the requirements of § 6.39 of this Part. Applicants must still
meet all CRMC established density and other requirements where
applicable. Compliance with § 6.45 of this Part does not relieve
applicants of the nitrogen reducing technology requirements in §
6.43 of this Part.
B. Design Flow Calculation -
The three hundred forty-five (345) gallons per day per twenty
thousand (20,000) square feet design limit may be exceeded for OWTSs
utilizing nitrogen reducing technology. The allowed design flow with
a nitrogen reducing technology is derived using the Equation in §
6.45(C) of this Part or read from § 6.45(D) of this Part. For the
purposes of § 6.45 of this Part, there are no limits on the design
flow of OWTSs with nitrogen reducing technologies that are approved
by the Director as meeting the nitrogen standard of ten (10) mg/l.
C. Nitrogen Loading
D. Nitrogen Loading
Nitrogen
Removal (Percentage)
Effluent
Nitrogen Concentration (mg/l)
Maximum
Design Flow per 20,000 sq. ft. (gpd)
50
19
690
66
13
1015
75
10
1380
E. Exceedance of Design Flow
Calculation - The three hundred forty five (345) gallons per day per
twenty thousand (20,000) square feet design limit or other design
limit utilizing nitrogen reducing technologies pursuant to § 6.45(B)
of this Part may be exceeded by the establishment of nitrogen credit
land meeting the requirements of § 6.45(F) of this Part under the
following circumstances:
1. For subdivisions - The
design limit must be met over the entire area of the subdivision.
This can be met by designating portions of the subdivision as
nitrogen credit land.
2. For individual lots - The
design limit can be calculated by establishing adjacent properties as
nitrogen credit land with the consent of the property owner.
F. Nitrogen Credit Land -
Nitrogen credit land cannot be designated on land that is already
being used to meet the nitrogen loading requirements for an OWTS
approved by the Director. Nitrogen credit land must be restricted by
a deed restriction, conservation easement, or other appropriate legal
instrument recorded in the municipal land evidence records such that:
1. Addition of nitrogen from
wastewater discharge, nitrogenous fertilizer (synthetic or natural),
and raising and grazing livestock is prohibited; and
2. Impervious surfaces, which
reduce recharge, including paved streets, paved parking areas, and
structures are prohibited.
6.46 Permit Expiration
A. Expiration of Permits for
OWTS Applications for New Building Construction and OWTS Applications
for Alteration to a Structure
1. Except for permits eligible
for tolling pursuant to R.I. Gen. Laws § 42-17.1-2.5 as provided in
§ 6.46(A)(2) of this Part, all permits for OWTSs for New Building
Construction and OWTSs for Alteration to a Structure approved in
accordance with § 6.17 of this Part shall expire five (5) years from
the date of the issuance of the permit.
2. Pursuant to R.I. Gen. Laws
§ 42-17.1-2.5, and unless otherwise ordered by the Department,
permits for New Building Construction or Alteration to a Structure
relating to the development of property that were valid on, or issued
after, November 9, 2009 that are subject to tolling pursuant to R.I.
Gen. Laws § 42-17.1-2.5 shall be tolled for the period provided by
R.I. Gen. Laws § 42-17.1-2.5 and expire on the date five (5) years
after approval plus the tolling period in accordance with said
statute.
B. Expiration of Permit after
Start of Construction
1. Notwithstanding § 6.46(A)
of this Part, where a permit for an OWTS for New Building
Construction has been issued, and construction of the building
foundation or OWTS has begun, the applicant shall have one (1) year
from the start of construction, within which to complete both the
foundation and OWTS. If the building foundation and OWTS are not
completed within one (1) year of the commencement of construction,
the permit, including any variances or decisions issued through the
variance process or by the Director, shall expire. The Director may
waive this expiration requirement for good cause.
2. Where a permit for an OWTS
for New Building Construction has been issued relating to the
development of property and construction of the building foundation
or OWTS was initiated between November 10, 2008 and November 9, 2009
inclusive, the applicant shall have until June 30, 2013 within which
to complete both the foundation and OWTS. If the building foundation
and OWTS are not completed by June 30, 2013, the permit, including
any variances or decisions issued through the variance process or by
the Director, shall expire.
C. Expiration of Permits for
OWTS Repairs - All permits for repairs to OWTSs issued in accordance
with § 6.18(G) of this Part shall expire as follows:
1. Where a permit for OWTS
repair is issued following the property owner’s receipt of a Notice
of Violation issued by the Department, all repair work must be
completed within the time periods set forth in the Notice of
Violation; and
2. In all other cases, permits
for OWTS repair shall expire as specified in the permit itself. In no
case shall any permit for a repair to an OWTS be valid for more than
one (1) year from the date of issuance of the permit.
D. Expiration of Unconformed
Installed Systems - OWTSs that have been installed but are not able
to be conformed, as of the effective date of these rules, because the
building sewer has not been connected through the building foundation
to the interior plumbing or for other reasons shall be reviewed on a
case-by-case basis.
E. Expiration of OWTS
Suitability Determinations - OWTS Suitability Determinations may not
be renewed. All OWTS Suitability Determinations issued in accordance
with § 6.18(D) of this Part shall expire as follows:
1. All OWTS Suitability
Determinations issued prior to the effective date of these rules
shall expire five (5) years from the date of issue, or one (1) year
from the effective date of these rules, whichever is later.
2. All OWTS Suitability
Determinations issued after the effective date of these rules shall
expire five (5) years from the date of determination, or concurrent
with the expiration date of the building permit, whichever is later.
Building permit must be issued within one (1) year of the date of the
OWTS Suitability Determination.
6.47 OWTS Installation
A. License Required -
Installation, construction, alteration, or repair of any OWTS shall
be performed by an installer licensed in accordance with § 6.14 of
this Part, or a master plumber licensed under R.I. Gen. Laws Chapter
5-20. This requirement does not apply to an applicant installing,
constructing, altering, or repairing an OWTS to serve a building the
applicant occupies or will occupy as the applicant’s intended
permanent domicile, provided that the applicant has obtained written
permission for that work and has obtained the Director’s approval
of the plans and specifications for that work prior to the start of
any construction.
B. Responsibilities of a
Licensed Installer - A Licensed Installer shall adhere to the
following:
1. Perform all work in
compliance with approved plans and specifications only;
2. Report to the Licensed
Designer discrepancies on an approved plan which the installer may
note during construction;
3. Utilize only quality grade
construction materials approved by the Director;
4. Utilize only the best
construction techniques to provide for the best possible
installations;
5. Work only under valid plans
approved by the Director, and to commence work only after completely
reviewing the entire approval including the application, the layout
plans, all typical specification sheets, and other attachments;
6. Adhere to each and every
term of approval as stipulated by the Director in his or her approval
of the particular plan; and
7. Stop construction and
notify the Licensed Designer if unanticipated conditions are
encountered that indicate the OWTS cannot be installed in accordance
with the approved application, plan and specifications, or any terms
and conditions contained therein.
C. Responsibilities of a
Licensed Designer - The Licensed Designer shall be responsible for
witnessing and inspecting the installation of the OWTS that the
Licensed Designer has designed. In no case shall the individual
witnessing and inspecting the installation of the OWTS be the
Licensed Installer who installs the OWTS, except for the repair of an
OWTS. Any individual assisting a Licensed Designer in witnessing and
inspecting the installation of an OWTS must be an employee of the
same business entity as the Licensed Designer, and such individual
must work under the Licensed Designer’s direct supervision in
respect to witnessing and inspecting the installation of the OWTS.
The Licensed Designer shall be available to directly witness and
inspect the system installation to resolve any instances of
non-compliance, design conflicts resulting from changed conditions or
other circumstances, or as may be requested by the Department. The
Licensed Designer shall inform the owner, in writing, of any special
conditions, operating requirements, or periodic maintenance needs
associated with the installed OWTS.
D. Areas Served by Private
Drinking Water Wells - Prior to installation of an OWTS in areas
served by private drinking water wells, the Licensed Designer shall
verify that conditions on site and adjacent to the site are the same
as at the time of design approval, or have not changed in a manner
that would affect the original design. If conditions have changed in
a manner that would affect the original design, the Licensed Designer
shall notify the Department prior to installation of the OWTS.
E. Notification to Department
- The Licensed Designer shall notify the Department during normal
business hours at least twenty-four (24) hours prior to the
installation of any OWTS. The Department, at its discretion, may
inspect any aspect of the installation. All Department-required
inspections must be inspected by the Licensed Designer prior to
notification to the Department.
F. Inspection - The Licensed
Designer shall, at minimum, inspect and make measurements, where
appropriate, of the following components and steps in the
installation of the OWTS:
1. The exposed bottom of the
excavation for the leachfield;
2. The size and condition of
all structures such as the septic tank, distribution box, flow
diffusers, etc.;
3. The elevation of all pipe
inverts;
4. All sand media and
aggregate is in accordance with specifications and is placed in
accordance with the design plan;
5. Completed installation
prior to covering;
6. The type of backfill and
that the backfill is properly placed and compacted;
7. Final soil cover; and
8. All horizontal setbacks,
including from the building and any wells on the site or on abutting
lots.
G. Unforeseen Conditions - If
conditions are encountered during construction which indicate that
the OWTS cannot be installed or is not installed in accordance with
the permit, or any terms and conditions contained therein, the
Licensed Designer shall notify the Director as soon as possible, but
no later than twenty-four (24) hours after discovery. The Department
shall maintain written guidance on specifications for construction
tolerances as well as conditions under which as-built plans and
redesigned plans are required. The Licensed Designer shall stop
construction if conditions are such that a redesign is required.
Notification is not required if all design elements are within the
tolerances established by the Department through written guidance. In
response to the designer's notification, the Director shall either:
1. Authorize the Licensed
Designer to proceed with the work onsite and to provide appropriate
documentation to the Department as may be required by the Director;
2. Require the Licensed
Designer to submit as-built plans within ten (10) business days after
the OWTS is installed to record changes that are in compliance with
the standards in these rules, but which need to be documented; or
3. Require the Licensed
Designer to submit redesigned plans and specifications to the
Director for approval showing changes from the original approved
application, plan and specifications.
H. Installation Verification -
The Licensed Designer shall collect the information in §§
6.47(H)(1) through (4) of this Part that can be used to verify that
the installation of the OWTS was performed as specified. The Licensed
Designer shall keep this information on file for a minimum of ten
(10) years from the date of the Certificate of Construction in §
6.48 of this Part. At the Department's request, the Licensed Designer
shall make this information available for review.
1. Daily inspection report
(weather conditions, individuals onsite, work accomplished, and other
information customarily included in inspection reports);
2. A minimum of two
photographs of the OWTS being installed, which must include the
bottom bed and the completed system prior to covering;
3. List of all materials used,
their source, and the dates delivered to the site; and
4. Product specification
sheets, if different from those specified in the approved design.
I. Replacement Designer - An
applicant may apply to the Director for approval to have a Licensed
Designer, other than the one that designed the OWTS, be responsible
for witnessing and inspecting the installation under the conditions
specified in §§ 6.47(I)(1) and (2) of this Part. The Director may
grant the approval provided the replacement Licensed Designer has a
license issued in accordance with §§ 6.10 and 6.11 of this Part
authorizing the Licensed Designer to design the type of OWTS in
question, and the replacement Licensed Designer signs an affidavit
assuming full responsibility for installation of the OWTS in
accordance with the DEM issued permit.
1. An applicant may apply to
the Director for a replacement Licensed Designer in either of the
following circumstances:
a. The Licensed Designer of
the OWTS is incapable of witnessing and inspecting the OWTS;
b. The Licensed Designer of
the OWTS is unavailable or absent after a period of thirty (30) days
as confirmed by the Department; or
c. The applicant contracted
with a business entity for design services and the Licensed Designer
who prepared the OWTS design is no longer employed by that business
entity.
2. An applicant may choose to
select a replacement Licensed Designer for reasons other than those
in § 6.47(I)(1) of this Part, in which case the applicant must
submit a redesign prepared by the replacement Licensed Designer. Any
variance previously approved by the Department shall remain valid,
provided that the Department agrees that the circumstances and facts
regarding the variance are the same as the facts under which the
original variance was granted or that the variance in the redesign
represents less of a deviation from the rules than the original
variance.
J. Certificate of Construction
- The Licensed Designer that is responsible for the OWTS installation
shall complete a Certificate of Construction in accordance with §
6.48 of this Part. The Certificate of Construction shall not be
construed to release the Licensed Installer from liability.
K. Once the Licensed Designer
has certified that the OWTS has been properly installed and is
operational, the Licensed Designer shall provide information and
recommendations to the applicant in writing on specific OWTS
operation and maintenance practices, including those needed to reduce
the risk of premature failure and avoid pollution of the waters of
the State.
L. The Licensed Designer is
not responsible for any negligent act or omission of a user of an
OWTS, including but not limited to, failure to properly use and
maintain the OWTS, which causes damage to the OWTS.
6.48 Certificate of Construction
A. Certificate of Construction
Required - The Licensed Designer that is responsible for the OWTS
installation in accordance with § 6.47 of this Part shall complete a
Certificate of Construction that certifies that the OWTS was
installed in conformance with the approved application, plans,
specifications, applicable statutes and regulations and that the
License Designer is responsible for having witnessed and inspected
the installation. The Certificate of Construction shall be on forms
approved by the Director. The Certificate of Construction shall
include, but not be limited to, the following:
1. Name and license number of
the Licensed Designer;
2. Name and license number of
the Licensed Installer; and
3. Distances from two building
foundation corners to the septic tank manhole, to the distribution
box, and to the leachfield corners.
B. Submittal to Department -
The Certificate of Construction shall be submitted to the Director
within five (5) business days after the OWTS, building foundation,
drinking water well, and other appurtenances, as may be specified in
written Department guidance, have been constructed in accordance with
the design plan. If an operations and maintenance agreement is
required pursuant to the terms of the permit a copy of the agreement
shall be submitted to the Department with the Certificate of
Construction. The Licensed Designer who performs the witnessing of an
OWTS installation may not withhold issuance of the Certificate of
Construction provided the requirements of this § 6.48 of this Part
are met. The Licensed Designer shall provide a copy of the
Certificate of Construction to the property owner.
6.49 Certificate of Conformance
A. The applicant for an OWTS
permit shall obtain a Certificate of Conformance from the Department
prior to use of any OWTS. The Certificate of Conformance means that
the OWTS that has been installed appears to substantially conform
with the design requirements and other requirements as indicated on
the application and associated plans and specifications.
B. Any applicant who
constructs a new building or building improvement which requires a
new or altered OWTS and a Certificate of Occupancy prior to use shall
obtain a Certificate of Conformance prior to such occupancy.
C. A municipality may only
grant a Certificate of Occupancy pursuant to R.I. Gen. Laws §
23-27.2-13 and Chapter 23-27.3, where the person applying for such
Certificate of Occupancy presents to the municipality the written
Certificate of Conformance of the Director as required in § 6.49(A)
of this Part.
D. The OWTS permit remains
valid once the Certificate of Conformance has been issued.
6.50 Permit Suspensions and
Revocations
A. Applicability - The
Director may suspend or revoke any permit granted under these rules
in the event that subsequent examination reveals that the application
is incomplete, incorrect or not in compliance with these rules, or
any conditions at the site are such that the approved design is no
longer in accordance with these rules.
B. Notice - The applicant
shall be given written notice by certified mail, return receipt
requested, of such action to suspend or revoke a permit by the
Director. Such notice shall be in conformance with the Administrative
Procedures Act, R.I. Gen. Laws §§ 42‑35‑9(b) and
42-35-14.
C. Request for Hearing - An
applicant may request a hearing on the suspension or revocation with
the Department of Environmental Management, Administrative
Adjudication Division. Such request must be in writing and shall be
filed with the Department’s Administrative Adjudication Division
within thirty (30) calendar days of receipt of the notice of permit
suspension or revocation.
D. Cessation of Work - Upon
issuance of a suspension or revocation of any permit from the OWTS
Program, no construction activity may be performed or continue to be
performed on the property until such time as the suspension or
revocation is rescinded or released by the Director. Where the
applicant requests a hearing in accordance with § 6.50(C) of this
Part, the suspension or revocation shall be stayed. However, any and
all work performed on the property shall be at the applicant's own
risk.
E. Investigations - The
Director shall conduct an investigation of any signed, written
complaint received from any person regarding an application for an
OWTS. The complaint shall specify the nature of the problems and
include all appropriate information to allow the Director to evaluate
the complaint.
6.51 Variance Requests
A. Applicability -
Applications for the approval of plans and specifications for an OWTS
may include a request for a variance from the provisions of the Rules
Establishing Minimum Standards Relating to Location, Design,
Construction, and Maintenance of Onsite Wastewater Treatment Systems.
Requests for variance will not be required for OWTS Applications for
Alteration to a Structure where there will be no increase in
wastewater flow or OWTS Applications for Repair.
B. Requests for variances
shall be attested to by a Class II or Class III Licensed Designer.
C. Contents of Variance
Request - Requests for variances shall be on forms approved by the
Director. It is the applicant’s responsibility to demonstrate by a
preponderance of clear and scientifically valid evidence by means of
a comprehensive analysis having a probative value that the requested
variance(s) will not be contrary to the public health, the public
interest or the environment. Applicants must comply with local
ordinances, however, such compliance cannot be used to justify or
support a variance request under these rules.
1. The comprehensive analysis
shall provide adequate scientific and technical evidence on how the
proposed design will mitigate potential adverse impacts on the
following:
a. Public health;
b. Any surface water drinking
water supply or tributary thereto and any public or private drinking
water well and any associated transmission lines that may be
affected, including the cumulative impacts of the system to the
surrounding area;
c. Any body of water
including, but not limited to, impacts on groundwater or surface
water quality and to the ability of the water body to support or
maintain flora and fauna as well as other designated water uses;
d. Public use and enjoyment of
any recreational resource; and
e. Surrounding persons or
property as a potential cause of any public or private nuisance.
2. The comprehensive analysis
shall include, but not be limited to:
a. An analysis of any limiting
conditions of the site;
b. An analysis of the amount
and characteristics of the wastewater discharged; and
c. An analysis of the ability
of the site to accept, transmit and treat wastewater.
3. The variance request(s)
shall be accompanied by a list identifying the names and addresses of
the local building official and all property owners within two
hundred (200) feet of any component of the proposed OWTS for which a
variance(s) has been requested.
4. Nothing herein shall
prevent the Director from requesting additional information deemed
necessary.
5. For OWTS located within two
hundred (200) feet of the inland edge of the coastal shoreline
feature bordering a tidal water area (corresponding to the
jurisdiction of the Rhode Island Coastal Resources Management
Council), the variance request shall be accompanied by a Preliminary
Determination from the Coastal Resources Management Council.
D. Compensatory Mitigation -
Other elements of the applicant’s system design (in which no
variance is requested) may result in greater protection of the public
health and the environment than is required by meeting the minimum
standards of these rules. In such case, the applicant may include how
these elements of the system provide compensatory mitigation for the
variance(s) requested as part of the comprehensive analysis required
in § 6.51(C)(2) of this Part. Compensatory mitigation may be in the
form of, but is not limited to: alternative or experimental
technologies approved pursuant to § 6.41 of this Part provided such
systems are not required by other rules herein, greater setback
distances than required in § 6.23 of this Part, greater separation
distances to groundwater than required in § 6.33(E) of this Part,
reductions in design flow, reductions in pollutant loading on
neighboring properties, decreasing the loading rate per square foot
of leachfield, and decreasing the linear loading rate.
E. Cumulative Impact
Assessment - Any application for an OWTS proposed to be installed on
a lot less than ten thousand (10,000) square feet in area which
requires more than one (1) variance and which will be located within
one hundred (100) feet of any public or private drinking water well
will not be approved unless a Cumulative Impact Assessment of the
variances is conducted by the applicant and submitted to the
Department along with the variance request. The Cumulative Impact
Assessment shall include, but not be limited to: a description of all
abutting properties identifying the location of all OWTSs, surface
waters, wetlands, and private or public drinking water wells; a
concise description of all variances granted in the permitting of
these abutting OWTSs; and any additional information which the
Director may deem appropriate.
F. Notification Requirements
1. Once the applicant's plans
and specifications have been determined to be complete by the
Department, the applicant shall notify the local municipal building
official and all property owners within two hundred (200) feet of any
component of the proposed OWTS of the pending application for an OWTS
with variance(s). If a variance is requested from the minimum setback
requirement to a public water supply well, public water line or a
surface water reservoir including tributaries and tributary wetlands
or subsurface drains directly discharging thereto, then the applicant
shall also notify the applicable public water system entity or
agency.
2. Exemptions from
Notification Requirements
a. OWTS applications for
Alteration to a Structure that include a request for a variance from
the provisions of these rules are exempt from the notification
requirements in § 6.51(F) of this Part.
b. The Director may waive the
notification requirements in § 6.51(F) of this Part if the variance
request is limited to a variance from a provision of these rules
specifying horizontal setbacks from a feature on the applicant’s
property only.
c. The Director may waive the
notification requirements in § 6.51(F) of this Part if, in the
opinion of the Director, the variance request will be denied based on
the information submitted, or lack thereof, or based on the standards
in § 6.52(B)(2) of this Part.
3. Each notice shall include:
a. A copy of the Variance
Request Form(s) submitted to the OWTS Program;
b. A cover letter conforming
to a form to be provided by the Director, which shall include at
least the following information:
(1) The application number;
(2) A statement of the purpose
of the notification;
(3) A certificate of service;
and
(4) A statement advising the
recipient that the recipient may, within twenty (20) days of the date
specified in the certificate of service, provide the Director with
written comments or information bearing upon the subject application;
and
c. Reduced-scale site plans
identical to those submitted to the DEM OWTS Program.
4. All notices shall be
forwarded by certified mail, return receipt requested. The applicant
shall clearly mark each return receipt with the application number
and the words “Variance Request.”
5. When all certified receipts
have been returned to the applicant, copies of each cover letter,
accompanied by the appropriate certified receipt, shall be filed with
the OWTS Program along with a letter requesting that the application
be submitted to the variance review process for final review and
determination.
6. If a correctly addressed,
certified notice is returned to the applicant, the applicant may
submit the returned envelope and certified receipt, unopened, along
with the other return receipts as proof of the applicant’s good
faith attempt to serve the notice.
G. Redesign Applications - For
redesign applications submitted to the Department, any variance
request previously approved by the Department shall remain valid,
provided that the Department determines that either:
1. The circumstances and facts
regarding the variance are the same as the facts under which the
original variance was granted; or
2. The variance in the
redesign represents no greater deviation from the rules than the
original variance.
6.52 Variance Review Process
A. Preliminary Review and
Recommendation - All variance requests shall be reviewed by the
Department for the purpose of determining whether such variance(s)
would be contrary to the public health, the public interest or the
environment. In reviewing the applicant's variance requests, the
Department may consult with other experts, whether employed by the
Department or not. As part of the review of any variance request(s),
the Department shall consider:
1. All evidence submitted by
the applicant, the local municipal building official and the notified
property owners bearing upon the subject application;
2. The number and extent of
the limiting conditions at the site and surrounding area; and
3. Whether the site
characteristics are less than optimum for wastewater treatment and
dispersal.
B. Variance Review Standards
1. Approval - A variance
request from the minimum standards set forth in these rules shall be
approved if it is determined that such a variance(s) will not be
contrary to the public health, the public interest, or environmental
quality.
2. Denial - A variance request
from the minimum standards set forth in these rules shall be denied
when:
a. The applicant has failed to
provide clear, accurate, and substantive information to enable the
Department to determine that the requested variance will not be
contrary to the public health, the public interest, or environmental
quality;
b. The evidence fails to
demonstrate that the same degree of environmental protection provided
under these rules can be achieved without strict application of the
provision for which the variance has been requested;
c. The evidence demonstrates
that the OWTS will not function as proposed in the application;
d. The evidence indicates that
the approval of the OWTS would otherwise be contrary to the public
health, the public interest, or environmental quality; or
e. The variance request is for
one of the following:
(1) The variance request is
for an action that is prohibited in § 6.9 of this Part, excluding
the prohibition regarding holding tanks in § 6.9(O) of this Part;
(2) The variance request is
from the requirements of § 6.15(B) of this Part on a site located in
the Salt Pond or Narrow River Critical Resource Areas unless the
applicant demonstrates that a net reduction in overall, long-term
nitrogen loading to the watershed will result;
(3) The variance request
resulted from the applicant subdividing the property after December
31, 1995 unless the applicant demonstrates that the reason for the
variance requested is not the result of action by the applicant, or
prior owners of the property;
(4) The variance request is
from the requirement that soil and seasonal high groundwater table
data must have been determined within the past five (5) years;
(5) There is a public
wastewater system reasonably accessible to the structure to be served
by the OWTS;
(6) The variance request is
for new lots under ten thousand (10,000) square feet platted or
otherwise created after June 18, 1992 unless the applicant
demonstrates that the reason for the variance requested is not the
result of action by the applicant, or prior owners of the property;
(7) The variance request is
for less than the eighty (80) foot minimum setback distance from a
private drinking water well in § 6.23(E) of this Part, Note 3;
(8) The variance request is
from the two hundred (200) foot public well setback requirement for a
drilled rock, driven, or dug well in § 6.23(E) of this Part or from
the four hundred (400) foot public well setback from a gravel packed
or gravel developed well in § 6.23(E) of this Part. Such a variance
request may be approved if either of the following occurs:
(AA) If the public well is not
on the same property that is subject to the OWTS Application, the
applicant provides documentation that the well owner has an approved
variance from the Rhode Island Department of Health for an inner
protective zone that does not include the location of the proposed
OWTS; or
(BB) If the public well is on
the same property that is subject to the OWTS Application, the
applicant provides documentation that the Rhode Island Department of
Health has approved of the requested activity;
(9) The variance request is
for a depth to groundwater from original ground surface of less than
twelve (12) inches or for a depth to a restrictive layer or bedrock
of less than thirty-six (36) inches;
(10) The variance request is
from the nitrogen reducing technology requirements in the Salt Pond
and Narrow River Critical Resource Areas in § 6.43(B) of this Part;
or
(11) The variance request is
from the requirements in § 6.45 of this Part (Nitrogen Loading in
Areas of Onsite Drinking Water Wells).
3. Terms and Conditions - The
variance decision may contain such terms and conditions as the
Director deems necessary to protect the public interest, the public
health, or the environment.
C. Recommended Determination -
Upon completion of their review, the OWTS Program Staff shall prepare
a written recommendation of approval or denial of the variance
request. The review shall identify the factors considered in the
review process, specify the bases for their recommendation, and
identify any suggested conditions for approval.
D. Final Determination - Upon
review of the recommendation submitted in accordance with § 6.52(C)
of this Part, the Director shall render a final written decision
approving or denying the requested variance(s). In arriving at a
final decision, the Director may:
1. Adopt the recommendation,
with or without additional written comments or conditions;
2. Reject the recommendation;
in which case the Director shall render a written decision specifying
the bases for the rejection; or
3. Remand the matter back to
the OWTS Program Staff for further review and consideration of
certain specified factors.
6.53 Appeals
A. Right to Appeal - Any
person whose permit application is denied may appeal to the Director
for review of the decision on which the denial is based by filing an
appeal with the Administrative Adjudication Division.
B. Filing of Appeal - All
appeals shall be in writing and shall be filed with the Department's
Administrative Adjudication Division within thirty (30) calendar days
of receipt of the denial of the subject application.
C. Contents of Appeal - Every
appeal shall contain:
1. A detailed basis upon which
the appeal is taken;
2. A plat plan of the area of
the subject application;
3. A list of the names and
addresses of:
a. The applicant;
b. The municipality in which
the property is located;
c. The owner of any surface
water supply as identified by § 6.42(C) of this Part, if applicable;
and
d. The owners of record of
real property within two hundred (200) feet of any component of the
applicant's proposed OWTS; and
4. A certified check, bank
draft or money order in the amount of one thousand five hundred
($1,500) dollars in accordance with § 6.54(D) of this Part.
D. Notice of Administrative
Hearing - Upon the filing of an appeal with the Administrative
Adjudication Division, and once the hearing schedule allows, the
Administrative Adjudication Division shall notify the following, by
first class mail, of the date, time and place of the adjudicatory
hearing, in conformance with R.I. Gen. Laws § 42‑35‑9:
the applicant; the municipality in which the property is located; the
owner of any surface water supply as identified by § 6.42(C) of this
Part, if applicable; and the owners of record of real property within
two hundred (200) feet of any component of the applicant's proposed
OWTS.
E. Conduct of Hearing - The
notice and conduct of the hearing by the Department of Environmental
Management, Administrative Adjudication Division, shall comply in all
respects with the provisions of the Administrative Procedures Act,
R.I. Gen. Laws Chapter 42‑35, and the Rules of Practice and
Procedure for the Administrative Adjudication Division for
Environmental Matters, Part
20-00-1 of this Title .
F. Burden of Proof - At the
adjudicatory hearing, the applicant shall have the burden of proof to
demonstrate through clear and convincing evidence that:
1. A literal enforcement of
the rules will result in unnecessary hardship;
2. That the OWTS will function
as proposed in the application; and
3. That the issuance of a
permit will not be contrary to the public interest, public health and
the environment. In order to demonstrate that the proposed OWTS will
not be contrary to the public interest, public health and the
environment, the applicant must introduce clear and convincing
evidence to the satisfaction of the Director that:
a. The waste from the proposed
OWTS will not be a danger to public health;
b. The OWTS to be installed
will be located, operated and maintained so as to prevent the
contamination of any drinking water supply or tributary thereto;
c. The waste from the proposed
OWTS will not pollute any body of water or wetland;
d. The waste from the proposed
OWTS will not interfere with the public use and enjoyment of any
recreational resource; and
e. The waste from the proposed
OWTS will not create a public or private nuisance.
G. The Director may approve a
permit or grant a variance from a provision of these rules, except
for the prohibitions in § 6.9 of this Part, where it is determined
by the Director that:
1. A literal enforcement of
such provisions will result in unnecessary hardship to the applicant;
2. That the OWTS will function
as proposed in the application; and
3. That the permit or variance
sought will not be contrary to the public interest, public health and
the environment.
H. The decision of the
Director may contain such terms and conditions as deemed necessary to
protect the public interest, public health and the environment.
6.54 Fees
A. Administrative
1. All applicants, except for
state and local governmental entities, shall be liable for the
payment of fees to the Department as set forth below.
2. Payment of Fees - All fees
shall be due at the time the initial form or request is submitted to
DEM requesting that it undertake one of the activities specified in §
6.54(B) of this Part below. The Department will not undertake any
such activity until payment has been received.
3. Commercial OWTSs - For the
purpose of assessing fees, all duplex and multi‑family
residential OWTSs shall be considered commercial OWTSs.
4. Field testing pursuant to
§§ 6.16 or 6.17 of this Part must be completed on the scheduled day
of witnessing. Conditions encountered or lack of preparedness by the
Licensed Designer that requires additional witnessing by the
Department will require an additional fee.
B. Fee Schedule
DESCRIPTION
FEE
Soil
Evaluations
$150.00
per OWTS
Wet
Season Determinations
$100.00
per OWTS
Bedrock
Test Holes
$100.00
per OWTS
Test
Holes in Storm Deposited Sand or Human Transported Material
$100.00
per OWTS
Reinspection
$100.00
Application
for OWTS Suitability Determination
$100.00
OWTS
Application for New Building Construction and OWTS Application
for Alteration to a Structure. The fees for applications
utilizing a pretreatment technology, excluding leachfield systems
and components, approved as an Alternative or Experimental
Technology pursuant to § 6.41 of this Part or a technology not
included in these rules specifically engineered for the
application, shall be two (2) times the following fees:
(The
fee for a Joint OWTS/Freshwater Wetlands Application is the sum
of the OWTS fee and the Wetlands Preliminary Determination fee.)
Single
Family Residences:
Single
Family Residence
$150.00
Commercial
OWTSs:
Less
than 2,000 gpd
$200.00
2,000
gpd to 4,999 gpd
$500.00
5,000
gpd to 9,999 gpd
$1,000.00
10,000
gpd or More
$2,000.00
Subdivision
Review
1
to 9 Lots
$100.00
per lot
10
Lots or More
$1,000.00
plus $50.00 per lot for each lot over 10
OWTS
Application for Repair. The fees for applications utilizing a
pretreatment technology, excluding leachfield systems and
components, approved as an Alternative or Experimental Technology
pursuant to § 6.41 of this Part or a technology not included in
these rules specifically engineered for the application, shall be
two (2) times the following fees:
Single
Family Residence
$100.00
Commercial
OWTSs:
Less
than 2,000 gpd
$150.00
2,000
gpd to 4,999 gpd
$300.00
5,000
gpd to 9,999 gpd
$600.00
10,000
gpd or More
$1,000.00
Application
Transfer, including Joint OWTS/Freshwater Wetlands Application
$50.00
Any
Variance Request for OWTSs: Residential and Commercial (Variance
Request Fee is in addition to the application fee)
$300.00
If
the application has been previously reviewed by the Department
and found deficient and the re-submission does not address these
deficiencies, then the Department will assess a fee for the
second re-submission equal to fifty percent (50%) of the original
fee. In no case shall this resubmission fee exceed $300.00.
Alternative
or Experimental Technology:
Alternative
OWTS or Technology:
Class
One
$1,000.00
Upgrade
from Class Two to Class One
$500.00
Class
Two
$1,000.00
Alternative
OWTS Component:
Class
One
$200.00
Class
Two
$300.00
Experimental
OWTS or Technology
$2,000.00
Renewal
of Alternative or Experimental Technology Application:
Alternative
OWTS or Technology Class Two
$500.00
Alternative
OWTS Component Class Two
$150.00
Experimental
OWTS or Technology
$1,000.00
Approval
Modification
$200.00
Installer's
Licenses:
Examination
and New License Application (3 years, the Department may pro-rate
fee if the license is issued for less than 3 years)
$175.00
License
Renewal (3 years, the Department may pro-rate fee if the renewal
is for less than 3 years)
$150.00
Class
I, II, III, and IV Licenses:
Examination
and New License Application (3 years, the Department may pro-rate
fee if the license is issued for less than 3 years)
$200.00
License
Renewal (3 years, the Department may pro-rate fee if the renewal
is for less than 3 years)
$150.00
License
Renewal Late Fees
<1
year expired
$100.00
1-2
years expired
$200.00
2-3
years expired
$300.00
C. Additional Fees - These
additional fees shall be collected prior to the Department's review
of the submission(s) under consideration. No final approval or denial
shall be issued by the Director until such time as these additional
fees have been received.
DESCRIPTION
FEE
Designers
Affidavit Continuing Validity - per lot
$50.00
Designers
Affidavit - Subdivisions
$100.00
Revision
to Subdivision (1 to 9 lots) per lot
$50.00
Revision
to Subdivision (10 or more lots)
$500.00
As
Builts - Requested or Submitted
$50.00
Redesign
- Single Family
$100.00
Redesign
- Commercial - less than 2,000 gpd
$150.00
Redesign
- Commercial - more than 2,000 gpd
$400.00
Redesign
- Joint OWTS/Freshwater Wetlands Application
$150.00
D. Costs of Appeal - Any
person who requests an appeal pursuant to § 6.53 of this Part shall
also be liable for fees to cover costs incurred in the holding of the
hearing. The fee shall be sufficient to defray the costs incurred by
the Administrative Adjudication Division for, but not limited to: all
investigations; the appearance of a stenographer and the original
transcript; renting a room, when necessary; and the costs associated
with the appearance of the hearing officer. The applicant must pay
the Director the sum of one thousand five hundred dollars ($1,500.00)
as a deposit against the actual costs of a hearing before a hearing
will be scheduled.
6.55 Operation and Maintenance
A. Operation - It is the
property owner’s responsibility to ensure that the OWTS achieves
the performance requirements applicable to the approved OWTS. Where
required by an Alternative or Experimental Technology approval or
under the terms of the approved OWTS Application, the property owner
shall maintain a valid operations and maintenance agreement for the
life of the OWTS.
B. Maintenance - All OWTSs
shall be maintained in good repair by the owner. The Director may
order the owner to maintain or repair an OWTS within a reasonable
time if the Director finds them to be in need of the same. In order
to maintain long-term viability of the OWTS, it is the owner's
responsibility to:
1. Ensure that the OWTS is
used only for wastewater in amounts that do not exceed the design
flow;
2. Properly maintain the OWTS,
including but not limited to, inspection of the OWTS or pumping of
the septic tank as needed;
3. Protect the OWTS from
physical disturbance;
4. Ensure that all access
opening covers are secured and maintained; and
5. Ensure that trees and
shrubs are not growing within the area of the leachfield and within
ten (10) feet of the leachfield.
C. The provisions of §§
6.55(A) and (B) of this Part for operation and maintenance apply to
any OWTS that has been issued a Certificate of Conformance pursuant
to § 6.49 of this Part.
D. Future Modifications - Once
a Certificate of Conformance has been issued pursuant to § 6.49 of
this Part, nothing in these rules shall prevent the property owner
from retaining another qualified Licensed Designer, including another
Licensed Designer from the same business entity that originally
designed the OWTS, that the property owner chooses to conduct work on
the OWTS.
6.56 Removal and Abandonment
A. Removal - Any OWTS
components that are excavated and removed off-site must be properly
disposed of at a licensed solid waste landfill.
B. Abandonment On Site -
Septic tanks, grease tanks, pump tanks, holding tanks, concrete
chambers and cesspools that are no longer in use shall be properly
abandoned. The structure shall be emptied of all wastes and then
either removed, filled with clean sand or crushed and the area
backfilled with clean soil.
6.57 Cesspool Phase Out
A. General - Cesspools are not
an approved method of wastewater disposal in Rhode Island, and all
existing cesspools are considered to be substandard in accordance
with § 6.6(G) of this Part. Cesspools in Rhode Island must be
removed and replaced if they meet the failure criteria in § 6.8 of
this Part, meet the definition of a large capacity cesspool in § 6.8
of this Part, local government ordinances require removal and
replacement, or if they are subject to the requirements of § 6.57(C)
of this Part pursuant to R.I. Gen. Laws Chapter 23-19.15.
B. Large Capacity Cesspools -
The use of large capacity cesspools is prohibited statewide in
accordance with U.S. Environmental Protection Agency “Revisions to
the Underground Injection Control Regulations for Class V Injection
Wells”, December 7, 1999, 40 C.F.R. §§ 9, 144, 145 and 146,
incorporated above at § 6.7(E) of this Part. Any such large capacity
cesspool shall cease to be used and shall be properly removed or
abandoned in accordance with § 6.56 of this Part. Any large capacity
cesspool shall be properly removed or abandoned within one (1) year
of discovery unless an immediate public health hazard is identified,
in which case the Director may require a shorter period of time.
C. Cesspool Removal and
Replacement - Cesspools shall cease to be used for wastewater
disposal and shall be properly abandoned in accordance with the
schedule below in §§ 6.57(C)(1) through (3) of this Part. Any
cesspool required to be abandoned pursuant to this Rule shall be
properly abandoned in accordance with § 6.56 of this Part and such
cesspool shall be replaced with an approved OWTS, or the building
served by the cesspool shall be connected to a public wastewater
system, prior to the applicable deadlines contained in this rule.
1. Any cesspool deemed by the
Department or a System Inspector to be failed shall be properly
abandoned within one (1) year of discovery unless an immediate public
health hazard is identified, in which case the Director may require a
shorter period of time.
2. Any cesspool found to be
serving a building or use subject to sale or transfer shall be
removed or abandoned within twelve (12) months of the date of sale or
transfer. Should the manner of wastewater disposal be unknown, an
inspection shall be conducted to determine if a cesspool is present
on the property. This inspection shall be done by a System Inspector
prior to the time of sale or transfer.
3. Any cesspool within two
hundred (200) feet of the inland edge of a coastal shoreline feature
bordering a tidal water area (corresponding to the jurisdiction of
the R.I. Coastal Resources Management Council), or within two hundred
(200) feet of a public drinking water supply well, or within two
hundred (200) feet of a surface drinking water supply impoundment
with an intake for the water supply, shall be removed or abandoned by
January 1, 2014.
D. Temporary Hardship
Extension - The Director may grant an extension for the removal and
replacement requirements in § 6.57(C)(3) of this Part provided the
homeowner demonstrates undue hardship and the cesspool is not a
failed system. Undue hardship is defined as having an annual income
of less than or equal to eighty percent (80%) of the appropriate
household size area median income determined by federal Housing and
Urban Development standards for the community within which the
cesspool is located (Area median income data is available online at
https://www.huduser.gov/portal/datasets/il.html). Requests for a
hardship waiver shall be on forms provided by the Director and
accompanied by all necessary financial information specified on the
form. Said extension letter shall be recorded in the land evidence
records of the municipality where the property is located. No
extension shall extend beyond January 1, 2019. Any extension granted
shall expire upon transfer or sale of the land or easement upon which
the cesspool is located and any such cesspool shall be replaced
within one (1) year of the transfer or sale or by January 1, 2019,
whichever is sooner.
E. Exemptions
1. The provisions of §§
6.57(C)(2) and (3) of this Part shall not apply to any cesspool
located in an area of a community covered by a municipal onsite
wastewater management ordinance that requires the risk-based
phase-out of cesspools prior to January 1, 2014. The Department shall
maintain a list of exempt communities.
2. The provisions of §§
6.57(C)(2)and (3) of this Part shall not apply to any cesspool
located on a property that is properly designated to be served by a
public wastewater system no later than January 1, 2020 provided that:
a. It is not a failed
cesspool;
b. The sewering project is
identified in the city, town or sewer district’s wastewater
facilities plan as approved by the Department prior to January 1,
2013;
c. The municipality, acting
through its city or town council, states in writing to the Director
by January 1, 2013 that the municipality will complete construction
of the sewering project on or before January 1, 2020;
d. The property owner
certifies, in writing, that the dwelling/building will be connected
to the public wastewater system within six (6) months of receipt of
the notification to connect to said system and that no increase in
flow or number of bedrooms in the structure will occur until the
connection is made; and
e. No later than December 31,
2014, the municipality holds bonding authorization or some other
dedicated financial surety for expansion of the public wastewater
system to the area of the building served by the cesspool. If the
municipality fails to demonstrate such surety, exemption under §
6.57(E)(2) of this Part shall terminate and the cesspool shall be
replaced by June 30, 2015.
6.58 Guidance Documents
A. Issuance - The Department
is authorized to issue guidance documents that support the intent and
purpose of these rules. Such guidance documents shall not serve to
alter the intent of the rules herein. The documents may serve as
guidance on interpreting the evolving science and technologies that
are used to support the rules or to explain in further detail the
administrative procedures for complying with these rules.
B. Review - Department
prepared guidance documents shall be subject to review and comment
through either formal public notice, the Technical Review Committee
(§ 6.41(G)(2) of this Part), or through other Department convened
stakeholder groups. Once a guidance document is issued by the
Department, it shall be subject to, at minimum, an annual review, at
which time all comments received within the past year shall be
considered.
6.59 Figure 1: Leachfield Over
Restrictive Layer or Bedrock
6.60 Figure 2: Minimum Setback
Distances in Drinking Water Supply Watershed Critical Resource Areas
6.61 Figure 3: Minimum Setback
Distances in the Salt Pond and Narrow River Critical Resource Areas
Note: The
setback distances in Figure 3 are for OWTS with design flow less
than 5000 gpd. For OWTS with design flow greater than 5000 gpd, the
setback distances are doubled. See Table 22.3.
6.62 Figure 4: Grease Tanks
6.63 Figure 5: Septic Tanks
6.64 Figure 6: Septic Tank Riser
Detail
6.65 Figure 7: Leachfield
Construction, Invert of Distribution Lines Below Original Grade
6.66 Figure 8: Leachfield
Construction, Invert of Distribution Lines Above Original Grade
6.67 Figure 9: Leachfield
Construction on Sloping Sites
6.68 Figure 10: Shallow Concrete
Chambers
6.69 Figure 11: Category 1
Technology and Pressurized Drainfield Schematic
6.70 Figure 12: Category 2
Technology and Pressurized Drainfield Schematic
6.71 Figure 13: Demand Dosing Tank
with Centrifugal Pump
6.72 Figure 14: Demand Dosing Tank
With Multi-stage Centrifugal Pump
6.73 Figure 15: Timed-dosing Tank
With Centrifugal Pump and In-line Screen
6.74 Figure 16: Timed-dosing Tank
With Centrifugal Pump and Basket Screen
6.75 Figure 17: Timed-dosing Tank
With Screened Vault and Multi-stage Centrifugal Pump
6.76 Figure 18: Above-ground
Bottomless Sand Filter (Side View)
6.77 Figure 19: In-ground
Bottomless Sand Filter (Side View)
6.78 Figure 20: Typical Bottomless
Sand Filter (Top View)
6.79 Figure 21: Side View Detail-
Typical Bottomless Sand Filter
6.80 Figure 22: Orifice Shield
Detail: Note: Shields shall be able to drain. Details vary from
manufacturer.
6.81 Figure 23: BSF Flushing Valve
Choice Detail
6.82 Figure 24: PSND Cross Section
Details
6.83 Figure 25: PSND Cross Section
Detail (Long Side)
6.84 Figure 26: LPP Details for
Regular Trenches (Top and Isometric Views)
6.85 Figure 27: LPP Details for
Shallow Concrete Chambers (Top and Isometric Views)
6.86 Figure 28: South Shore Salt
Ponds Critical Resource Area
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.
6.87 Figure 29: Narrow River
Critical Resource Area
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.
6.88 Figure 30: Providence Water
Supply Board Drinking Water Supply Watershed
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.
6.89 Figure 31: Cumberland,
Pawtucket Water Supply Board and Woonsocket Drinking Water Supply
Watersheds
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.
6.90 Figure 32: Newport, New
Shoreham and Stone Bridge Fire District Drinking Water Supply
Watersheds
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.
6.91 Figure 33: Eleanor
Slater/Zambarano Unit, Bristol County Water Authority, Yawgoog Scout
Reservation, and Jamestown Drinking Water Supply Watersheds
For a detailed look at a
location, go to the DEM website, go to “Maps,” go to
“Environmental Resource Maps” and build a map of your choice.