260-RICR-30-10-1
260-RICR-30-10-1. Elevator Safety Code (version Amendment, 02/06/2008 to 01/29/2012)
STATE OF RHODE ISLAND
ELEVATOR SAFETY CODE
As of January 14, 2008
SAFETY CODE RELATING TO:
Construction, Inspection and Maintenance of:
Elevators, Dumbwaiters, Escalators, Moving Walks,
Personnel and Material Hoists, Vertical Reciprocating
Conveyors and also, Vertical Wheelchair Lifts
FORWARD & EXPLANATION OF CODE
This State code consists of six sections, each covering a
specific subject. They are as follows:
Section I - New Installations
Section II - Existing Installations
Section III - Personnel Hoists
Section IV - Material Hoists
Section V - Vertical Wheelchair Lifts
Section VI - Vertical Reciprocating Conveyors
Sections I and V of this State of Rhode Island Elevator Safety
Code are mainly an adoption of the American National Safety Code
for Elevators and Dumbwaiters (Often referred to as ASME A 17.1).
Specific exceptions to that national organization's model code
have been adopted as the Rhode Island State Code, and they
appear herein in their respective parts.
Section II (Existing Installations) is different from the other
five sections. It does not depend exclusively upon the national
recommendations for existing elevators and escalators often
referred to as ASME A17.3 SAFETY CODE FOR EXISTING ELEVATORS AND
ESCALATORS. It shall, however, be in addition to those
requirements. Additionally, the following national standards,
ASME A17.2.1, A17.2.2, and A17.2.3 commonly referred to as
Inspectors' Manuals shall also be utilized and/or referenced as
a part of Section II.
Where any rule from the national standards ASME A17.2.1, A17.2.2,
or A17.2.3 is cited, the national standard designation shall be
utilized.
Section VI (Vertical Reciprocating Conveyors) is different from
the other five sections. It is mainly an adoption of the American
National Standard for Conveyors and Related Equipment ANSI/ASME
B20.1. The rules as they appear in Section VI are in addition to
that organization's recommendations.
Sections III and IV are also different from the other five
sections. The specific codes pertaining to these devices are used
as a basis for the installation, construction and operation of
this equipment. The scope of these specific Codes is stated at
the beginning of the respective Section within this Code. The
rules as they appear within these Sections are in addition to any
rules contained within those specific Codes.
PURPOSE FOR CODE
The purpose of these rules and regulations is to provide safety
standards for the installation, construction, operation, repair
or use of elevators and related equipment. Where compliance
would be impracticable, the Director of Labor and Training and/or
the Chief Elevator Inspector may issue an exemption from the
requirements of these rules and regulations and permit the use
of other devices and/or methods, but only when it is established
by clear and convincing evidence that safety is reasonably
assured.
ACCIDENT REPORTS
RULE 1.0
Each elevator, dumbwaiter or escalator accident, or each hoistway
collision, or each equipment failure resulting in an injury to a
person, or in damage to the installation shall:
(A) Be reported by the owner or his authorized agent within
twenty-four (24) hours to the Department of Labor and
Training, Division of Occupational Safety. ANY ACCIDENT
RESULTING IN A FATALITY SHALL BE REPORTED TO SAID OFFICE
IMMEDIATELY.
(B) Summarily revoke the operating certificate or permit
until the Department of Labor and Training shall have
inspected and/or shall have again made valid the
operating certificate or permit of the subject
installation.
(C) Failure to report any accident within the prescribed
time, shall be a violation of Rhode Island General Law
23-33-20(a) and as such, subject to the penalty provided
therein.
(D)
No person shall remove from the premises any part of the
damaged installation or operating mechanism or any other
part of the equipment subject to the provisions of Rhode
Island General Law 23-33, until permission to do so has
been granted by the Chief Elevator Inspector.
ELEVATOR SAFETY CODE
SECTION I. NEW INSTALLATIONS
Rule 1.0
(a) The American National Standard Safety Code for Elevators
and dumbwaiters (ASME A17.1), which also includes
escalators and moving walks, shall govern the
installation, modernization, inspection and testing of
new, or relocation of, such elevators and other devices
with the following exceptions:
(b) REVISION:
303.4(a) Supply Line Shutoff Valve.
A manually operated shut-off valve shall be provided
between the hydraulic machines and hydraulic jack and
shall be located in the pit on all hydraulic elevators.
(c) ADDITION:
A complete and accurate set of wiring diagrams shall be
provided to the owner, who shall cause the diagrams to be
permanently maintained within the machine room/space of
any new or modernized elevator, escalator or other device
subject to the provisions of Rhode Island General Laws
23-33. Any and all wiring changes shall be marked in
permanent red ink. These diagrams shall be considered a
required part of the machine room and as such, shall not
be removed, damaged, destroyed or altered except where
wiring changes are necessitated.
(d) DELETION: ASME A17.1 PART XX
Rule 2000.10a - Key operation
Rule 2001.10a - Key operation
Rule 2002.10a - Key operation
(e) REVISION:
Key operation of accessibilty devices within public
buildings shall be provided only on those devices where
security is necessitated.
(f) DELETION: ASME A17.1 PART XXI
Rule 2100.10a - Key operation
Rule 2101.10a - Key operation
Rule 2102.10a - Key operation
(g) REVISION:
Key operation of accessibility devices located within a
private residence shall be provided only on those devices
where security is necessitated.
SECTION II. EXISTING INSTALLATIONS
Rule 2.0
Section II of the Rhode Island Elevator Safety Code shall
govern existing elevators, escalators, and other devices,
except as otherwise provided within.
Rule 2.1 DEFINITIONS:
CAPACITY-RATED LOAD means the load which the equipment is
designed and installed to lift at the rated speed.
DECOMMISSIONING refers to the requirements that any cable
suspended elevator or other device being placed out of
service, or has been out of service for more than six (6)
months shall have the car and/or counterweights landed in the
pit and all hoist cables removed. Also, that hydraulically
operated units shall be lowered into the pit, all oil or
hydraulic fluid removed and a section of the oil supply
line removed from the premises.
DUMBWAITER means a lifting and lowering mechanism with a
floor area not exceeding nine (9) square feet, with a car top
not more than four (4) feet above the car floor, the capacity
not to exceed five hundred (500) pounds, which is used
exclusively for carrying freight. No persons are permitted
to ride on, in, or to step into the car.
ELEVATOR means a hoisting and lowering mechanism capable of
carrying passengers and authorized personnel, equipped with
an elevator car which moves in fixed guides and serves two
(2) or more fixed landings.
(1) ELEVATOR-PASSENGER means an elevator used primarily
to carry persons other than the operator and persons
necessary for loading and unloading.
(2) ELEVATOR-FREIGHT means an elevator primarily used for
carrying freight and on which only the operator and
the persons necessary for loading and unloading the
freight are permitted to ride.
(3) ELEVATOR-SIDEWALK means a freight elevator, the upper
landing of which is located either partially or wholly
outside the building, and which has no opening into
the building at its upper terminal landing.
(4) ELEVATOR-PLATFORM means an elevator the platform of
which is directly supported at four or more points by
suspension members which are relied upon to maintain
the platform substantially level and giving service
within one story.
(5) ELEVATOR-POWER means an elevator utilizing energy
other than gravitational, (or manual to move the car).
(a) ELEVATOR-ELECTRIC means a power elevator where the
energy is applied by means of an electric driving
machine.
(b) ELEVATOR-HYDRAULIC means a power elevator where
the energy is applied by means of a liquid under
pressure, in a cylinder equipped with a plunger
or piston.
ELEVATOR-HAND means an elevator energized by manual power.
ESCALATOR means a power driven, inclined, continuous stairway
used for raising and lowering passengers.
HOISTWAY DOOR INTERLOCK means a device having two related and
interdependent functions which are:
(a) To prevent the operation of the driving machine
by the normal operating device unless all hoistway
doors are locked in the closed position, and
(b) To prevent the opening of any hoistway
door from the landing side unless the car
is within the landing zone and is either
stopped or being stopped.
NOTE: (Hoistway Door Interlock): These functions are
subject to modifications specified in Rule 111.3a of the
A17.1.
LICENSED COMPANY means a company licensed by the Division of
Occupational Safety to perform installations, construction,
service, repairs, modernizations, decommissioning, removal,
and maintenance of elevators and other devices subject to the
provisions of this code and Rhode Island General Laws 23-33.
LICENSED INDIVIDUAL means an employee of a licensed company
who by reason of competency is authorized to perform any and
all work within the scope as issued.
LOG BOOK means a bound, standardized, industry accepted format
handwritten record of the following activities:
(a) description of maintenance tasks performed and dates
(b) description and dates of examinations, tests, adjustments,
repairs, and replacements
(c) description and dates of call backs (trouble calls) or
reports that are reported to elevator personnel by any
means, including corrective action taken
(d) written record of the findings on the firefighters service
operation required by Rule 8.6.11.1 of ASME A17.1a-2005
The LOG BOOK shall be provided for each elevator or escalator
within that unit’s machine room or space and shall be
maintained as a permanent part of that room or space.
MOVING WALK means a type of passenger-carrying device on
which passengers stand or walk, and in which the
passenger-carrying surface remains parallel to its direction
of motion and is uninterrupted.
SPEED-RATED means the maximum velocity of the car in feet per
minute (fpm), with rated load in the car, traveling in an
upward direction.
Rule 2.2 GENERAL PROVISIONS
(a) All parts of elevators, dumbwaiters and escalators,
including machines, cars, hoistways, hoistway landing
opening protective devices, hoisting ropes or cables,
etc., and all appurtenances shall be maintained in a
structurally sound, firmly secured, and satisfactory
condition to perform safely the work which they are
intended to do.
(b) Whenever this code conflicts with the State Building
Code, regarding the materials to be used for
construction purposes and/or the type of construction to
be employed, the requirements of Rhode Island General
Laws shall prevail.
(c) All electric wiring and apparatus shall comply with the
requirements of the National Electrical Code.
(d) No section of these rules and regulations is intended to
be or shall be construed to be more stringent than the
rules and regulations governing similar devices or
applications on new elevators, new dumbwaiters, new
escalators and new moving walks, except as noted in
Section I.
(e) Floating platform type of construction shall not be
permitted for elevator cars.
Rule 2.3 CAPACITY
(a) Passenger elevators shall have a capacity of not less
than the platform area indicated in Figures 2.1, 2.2. A
metal plate shall be provided which shall be fastened in
a conspicuous place in the car, with letters and figures
not less than one quarter inch (l/4") high, bearing the
words CAPACITY___________PERSONS.
(b) A freight elevator may be used to transport employees
only upon written authorization from the Administrator
of the Division of Occupational Safety, and provided
that the following provisions are complied with: Rules
2.4b, 2.5c, 2.20, 2.21, 2.25, 2.33, 2.34, 2.37, 2.38,
2.39, 2.50c.
(c) Freight elevators shall be provided with a conspicuous
plate, with letters and figures not less than one inch
(1") high, indicating the capacity of the elevator and
the type of loading permitted. If the freight elevator
is to be used for employee transportation, said plate
shall also indicate CAPACITY _______________ PERSONS.
The number of persons shall be the capacity divided by
one hundred fifty (150).
(d) No loads greater than the capacity load shall be carried
on any elevator, unless the elevator is equipped with a
special locking device which will hold the car at any
landing independently of the hoisting cables while the
excessive load is being loaded or unloaded, and the
elevator car platform, frame, sheaves, shafts, cables,
safeties, machinery, supports and counterweights are
designed or altered to support the excessive load.
GRAPH TO REPLACE THIS PAGE*******DESTROY****************
RULE 2.4 ALTERATIONS
(a) Where an elevator is altered, all alterations shall be
designed, manufactured and constructed in compliance
with the requirements of Part XII of the ASME A17.1
known as Section I of this Code.
(b) Alteration shall mean any change or changes in the
classification, speed, capacity, or total rise of an
elevator and also, any physical change or changes in the
elevator machinery, car hoistway landing opening
protection devices, etc., car clearances, car safety
devices, car operating devices, or characteristics of
the electrical service of an elevator.
EXCEPTION:
Where worn or defective parts are being replaced with
exact type of replacement parts.
(c) Where any elevator is altered, by the addition of either
car tops, car doors or gates, car sidings, or any
appurtenances thereof, or any combination of the
foregoing features, the capacity of the elevator shall
be reduced to compensate for the weight added thereto,
unless all parts of the equipment affected thereby are
designed or altered to adequately handle the altered car
and the capacity load simultaneously. Departmental
approval is mandatory in all such cases.
(d) Relocation. When an existing elevator is relocated, it
shall comply with Section I of this Code.
(e) Demolition or removal of any device subject to the
provisions of Chapter 23-33 of the Rhode Island General
Laws shall be performed only by individuals licensed by
the Division of Occupational Safety pursuant to Rhode
Island General Laws Section 23-33-2.3, except where a
building is being destroyed in its entirety.
(f) All elevators having travel of twenty five (25) feet or
more shall be provded with Phase I and Phase II Fire
Service subject to the provisions of ASME A17.3 Rule
3.11.3 a standardized key switch for the activation of
fire service shall be required. This key shall be an
ADAMS PART NUMBER AKC-0054A [KEY CODE WD01].
(g) The key required to activate fire service shall be
accessible to fire department personnel, qualified
mechanics and compliance inspectors only.
RULE 2.5 CABLES, CAR AND COUNTERWEIGHT
(a) Cables for power elevator cars and counterweights shall
be of iron or steel.
(b) Wherever cables are renewed, a metal tag shall be
attached to the new cables at their fastenings. On this
tag shall be stated the diameter, rated ultimate
strength and material of the cables, and the date of the
cable installation, and also the name of the concern
installing the cables.
(c) Hoist cables, when replaced, shall be replaced by the
same number, size, type and approximate strength as the
original design.
(d) No winding drum elevator shall be used for passenger
service unless it is equipped with two (2)) or more
hoisting cables.
(e) The tension on all cables performing one operation shall
be maintained substantially equal.
(f) No cable shall be lengthened or repaired by splicing.
(g) Whenever car or counterweight cables are replaced, the
car and/ or counterweight top clearances shall not be
reduced below the requirements of Rule 2.45d.
(h) Where cables pass through floors outside of the hoistway
enclosure, such cables shall be guarded to a height of
not less than seven (7) feet with metal cable guard
enclosures.
(i) Hoist cables shall be replaced when damaged or
deteriorated due to rust, wear or excessive crown wire
breakage and tagged as in 2.5b.
(j) Hoist cables shall be properly maintained and free of
excessive lubrication material.
RULE 2.6 CABLES, SPEED GOVERNOR
(a) Cables for speed governors, when such cables are
replaced, shall be of iron, steel, metal or phosphor
bronze only.
(b) Speed Governor Cables shall be not less than
three-eights (3/8)) inch in diameter.
(c) Tiller rope may be used only for the portion of the
governor cables wound on the safety drum.
(d) When speed governor cables are replaced, they shall be
tagged as in Rule 2.5b.
(e) Speed governor cables shall run clear of governor jaws
during normal operation of the car and the center of the
speed governor cables shall be located not more than
one-eighth (1/8) inch either side of the common center
line of governor jaws.
(f) Wherever the diameter and/or material of a speed
governor cable is changed, approval of the proposed
change shall be obtained from the Department of Labor
and Training and the car safety shall be retested with
the altered governor cables in use before the elevator
is reactivated.
(g) Speed governor cables shall be replaced when damaged or
deteriorated due to rust, wear or excessive crown
breakage and tagged as in 2.5b.
(h) Speed governor cables shall be properly maintained and
free of excessive lubrication material.
(i) Any governor using any type of cable other than that
specified in Rule 2.6a shall be replaced with an
approved type.
RULE 2.7 CABLE CONNECTIONS
(a) When cables are replaced, they shall be fastened to the
car and/or to the counterweight either by individual
tapered babbitted sockets or rope wedge clamps.
(b) All cables anchored to a winding drum shall have not
less than one (1)) complete turn of cable left on the
drum when the car or counterweight has reached the
extreme limit of its overtravel.
(c) The winding drum ends of car and counterweight cables
shall be secured to the winding drum by clamps on the
inside of the drum or as in Rule 2.7a.
(d) The hoisting rope of power elevators having drum-type
driving machines with one-to-one (1:1) roping shall be
reshackled, at the car ends at intervals not longer
than: (1) Twelve (12)) months for machine located over
the hoistway. (2) Twenty-four(24) months for machines
located below or at side of the hoistway.
(e) A metal tag, in addition to the tag required in Rule
2.5b, shall be provided when hoist ropes are reshackled.
Said tag shall state the date of the reshackling, and
also the name of the concern performing the reshackling.
RULE 2.8 MACHINES AND MACHINE SAFETIES FOR POWER ELEVATORS
(a) No set screw fastenings shall be used in lieu of keys or
pins on connections subject to torque or tension.
(B) No friction gearing or clutch mechanism shall be used
for connecting the drum sheaves to the main driving gear
of power elevators.
(c) No worm or gear having cast-iron teeth shall be used for
replacement purposes on a worm and gear driving machine.
(d) No power elevator machine, except hydraulic machines,
shall be operated without electrically released and
mechanically applied brakes.
(e) No belt or chain driven machine shall be used for any
passenger elevators.
(f) Winding drum machines and roped hydraulic elevators
shall be equipped with a slack cable device located on
the machine or on the car to apply the brake and stop
the machine if the car should be obstructed while
descending.
(g) Slack cable switches shall be of the enclosed type and
shall be manually reset.
(h) Flat belts or chain drives for machines shall be
replaced by multiple "v" belt drive with a minimum of
three 5/8 inch belts, or directly connected.
(i) the use of flat belt drive which would shift to control
the direction of the elevator car travel is prohibited.
(j) Drive machine sheaves shall be recut due to slippage or
loss of traction.
(k) Drive machine sheaves shall be replaced due to excessive
wear.
RULE 2.9 HYDRAULIC MACHINES
(a) Cylinders of hydraulic-elevator machines shall be
provided with a means for releasing air or other gas.
(b) Each pump connected to the tank of a hydraulic elevator
shall be equipped with a relief valve (or valves) so
installed that it cannot be shut off. The relief valve
shall be of sufficient size and so located as to pass
the full capacity of the pump at full speed without
exceeding the safe working pressure of the pump, tank or
piping.
(c) Elevator pumps, unless equipped with pressure regulators
which control the motive power, shall be equipped with
automatic bypass.
(d) Pressure tanks, piping, pumps, valves, cylinders,
pistons, and packings of a hydraulic elevator shall be
maintained to withstand successfully a hydrostatic test
wherein the maximum testing pressure is 50% over the
normal working pressure.
(e) Each pressure tank shall be equipped with a water-gauge
glass, having brass valves and fittings attached
directly to the tank and so located as to show the level
of the water when the tank is more than half-filled.
(f) Each pressure tank shall be provided with a correctly
indicating pressure gauge having a capacity of not less
than one and one half (1 1/2) times the normal working
pressure allowed in the tank.
(g) Discharge tanks shall be adequately covered, or
screened.
(h) All packings used in connection with a hydraulic
elevator shall be maintained to prevent any uncontrolled
movement of the elevator.
(i) Hydraulic elevators operated from pressure tanks where
the fluid pressure is obtained by directly admitting
steam, air or other gas to the tank, shall comply with
all the rules covering hydraulic elevators.
(j) The water level in a pressure tank shall be maintained
at about two thirds (2/3) of the capacity of the tank.
(k) Flexible hoses and fitting assemblies shall be of the
approved type, and shall be replaced if damaged, or at
least changed every six (6) years, and tagged as in Rule
2.5b., with the replacement date.
(l) Machine drive belts shall be replaced with a full,
matched set when damaged or deteriorated due to
excessive wear or breakage.
(m) New or replacement hydraulic cylinders shall be
installed within a PVC liner inside of the casing.
(n) Every hydraulic elevator pump unit shall be provided
with an appropriate sized valved connection equipped
with an AEROQUIP 5602-4-4S male connector for attaching
an inspector's test gauge.
(o) every hydraulic elevator shall be subject to a static
load test every three (3) years. as part of this test,
the working pressure of the pump unit shall be tested
and recorded as well as the relief valve setting. A
metal plate shall be attached to the hydraulic tank of
all such elevators indicating (1) the working pressure,
(2) the relief valve setting, (3) the amount and type of
fluid used in the hydraulic system.
(p) All hydraulic elevators equipped with an APOLLO BALL
VALVE (Part number 70-108-01) located in the oil supply
pipe shall have this valve replaced with an equivalent
valve of a different manufacturer.
RULE 2.10 PENTHOUSES AND MACHINE ROOMS
(a) Safe access to penthouses and machine rooms shall be
provided and maintained.
(b) Elevator machine rooms and penthouses shall not be used
as thoroughfares.
(c) Doors to machine rooms shall be provided with spring
type locks and closers. These doors shall be kept
locked and the locks shall be so arranged as to permit
the doors to be opened from within the machine room
without keys. The key for the machine room door shall
not operate any other lock in the building, nor shall
the key be part of a master, grand master or
construction master key system.
(d) Elevator machines not located in elevator machine rooms
shall be enclosed and locked as in Rule 2.10c. This
enclosure shall be at least seven (7) feet high and be
of substantial fire resistant construction.
(e) Permanent, adequate, artificial light shall be provided
in machine rooms and penthouses. The light switch shall
be within easy reach of the machine room entrance.
(f) Elevator disconnect switches, of the approved type,
lockable, manually operated, and of the multiple pole
type, shall be located on the lock jamb side of the
entrance to the machine room and shall be accessible
from the machine location on all elevators. No device
shall be permitted which closes this disconnect switch
from any other part of the building.
(g) Machine rooms shall be provided with a floor. If metal
bar grating is used for flooring, the flooring shall
reject a three-quarter (3/4) inch round ball. If
perforated sheet steel is used for flooring, the
openings shall reject a ball one and one-eighth (1 1/8)
inch in diameter.
(h) Machine rooms shall not be utilized as storage space for
any non-elevator related items.
(i) Each elevator machine located above floor level shall be
provided with a working platform and shall be enclosed
by permanent, standard guard rails and toe boards.
(j) Access into the machine room from the hoistway is
expressly forbidden.
(k) Machine room floors shall be maintained substantially
free of oil, grease and debris.
(l) Machine rooms for hydraulic elevators shall be provided
with a curbing between the machine room door jambs which
shall be hydraulically sealed to the floor and to the
door jambs.
(m) Machine rooms for hydraulic elevators shall be located
adjacent to the hoistway (with ten (10) feet). The
machine room access shall be within sight of the
elevator hoistway landing.
(n) The Log book shall be maintained in all elevator machine
rooms.
RULE 2.11 PIPES AND WIRING
(a) All exposed live parts of electric apparatus in or on
elevator cars or shaftways shall be enclosed.
(b) All machine frames, controller frames, control ropes,
and metal conduits shall be effectively grounded.
(c) The maximum circuit voltage or rated system permitted in
the operating devices of power elevators shall be three
hundred (300) volts A.C. for automatic operation
elevators having operating devices in the car and at the
landings and seven hundred fifty (750) volts D.C., or
six hundred (600) volts A.C., for other types of
operating devices.
(d) Power elevator machine motors operated by polyphase
alternating current shall be equipped with a reverse
phase relay.
(e) No wire or other current-carrying device shall be
substituted for the proper fuse or circuit-breaker in an
elevator circuit.
(f) An approved type emergency stop switch shall be provided
in all areas of moving machinery or sheaves and in all
levels of multi level machine rooms or spaces.
(g) The use of temporary "jumpers' or wires used temporarily
for troubleshooting circuits shall be allowed only while
such work is being performed by a qualified mechanic.
No such device shall be left attached or connected
within any controller or operating panel for any reason
without the mechanic being physically upon the premises
engaged in repairs.
RULE 2.12 COUNTERWEIGHTS, DRUM AND /OR CAR
(a) Broken or cracked sections of counterweights shall be
replaced.
(b) Counterweight hanger rods and/or tie rods or other
acceptable means shall firmly support and secure the
counterweight sections in place.
(c) Counterweights shall run in guide rails or guide boxes
and these guides shall confine the counterweights to a
definite lane of travel in the elevator hoistway.
Counterweight guide boxes outside the elevator hoistway
shall be prohibited.
(d) Cables extending through counterweights shall be guarded
by metal or fiber sleeves attached to the cables.
(e) Counterweight or compensating chains or cables shall be
replaced when damaged or deteriorated due to rust, wear,
or excessive crown wire breakage.
(f) Counterweight cables shall be so maintained as to
provide proper clearance between the counterweight and
the counterweight buffer.
RULE 2.13 HOISTWAYS - CAR
(a) All hoistways shall be of at least two (2) hour fire
resistant rated construction unless written permission
of the fire authorities is provided to the Division
indicating a lesser rated construction is permitted by
that authority.
(b) All non-fire resistant hoistways shall be prohibited.
Fire safety code violations are to be referred to the
state Fire Marshall's Office, or the local fire
authorities.
(c) All landing openings shall be equipped with at least one
and a half (1 1/2) hours, "B" label fire resistant
doors.
(d) No non-fire resistant materials shall be installed
within any hoistway.
(e) Hoistway enclosures shall have substantially flush
surfaces on the hoistway side subject to the following:
(1) On Sides for Loading and Unloading. Landing sills,
hoistway doors, door tracks and hangers may project
inside the general line of the hoistway.
(2) On Sides Not Used for Loading and Unloading.
Recesses except those necessary for installation of
elevator equipment shall not be permitted. Beams,
floor slabs or other building construction shall
not project more than two (2)) inches inside the
general line of the hoistway unless the top surface
of the projection is beveled at an angle of not
less than seventy-five (75)) degrees from the
horizontal. Where setbacks occur in the enclosure
wall, the top of the setback shall be beveled at an
angle of not less than seventy-five (75)) degrees
from the horizontal. Separator beams between
adjacent elevators are not required to have bevels.
(f) There shall be no thoroughfares through a hoistway.
(g) There shall be no thoroughfares under the hoistway of
any elevator or dumbwaiter unless all of the following
conditions exist: (1) Adequate buffers are provided.
(2) The car is provided with speed governor operated
safeties. (3) The counterweight is provided with speed
governor operated safeties. (4) There shall be a
structure under the hoistway strong enough to withstand
without failure the impact of the car with contract load
or counterweight when either is descending at contract
speed or at governor tripping speed where a governor
operated safety is used.
(h) There shall be no thoroughfare under the hoistway of a
dumbwaiter or its counterweight unless there is a
structure under the hoistway sufficiently strong to
withstand without failure the impact of the car with
contract load, or the impact of the counterweight when
either is dropped freely in its guides from the upper
limit of overtravel; provided that for cars or
counterweights equipped with governor operated safeties
the impact shall be computed at governor tripping speed.
Where broken rope safeties are used the impact of the
car or counterweight shall be computed for a free drop
of the car or counterweight from one-third of its
travel.
(i) Hatch covers shall be prohibited. EXCEPTION: Sidewalk
elevators with hinged or vertical lift type covers which
shall be able to support a uniformly distributed load of
three hundred (300) pounds per square foot.
(j) Hoistways shall not be used for the installation of
telecommunication, HVAC control wiring, burglar or fire
alarm wires, except where completely enclosed within an
approved raceway.
RULE 2.14 HOISTWAYS - COUNTERWEIGHT
(a) Hoistways for counterweights located outside of the
elevator hoistway shall be kept enclosed for the full
height of the shaftway. EXCEPTION: If such
counterweight hoistway are located outside of the
building, the shaftway for the counterweight shall be
guarded to a height of seven (7) feet above ground.
(b) Counterweight hoistways located in the enclosed shaftway
of power elevators shall be guarded from a point one (1)
foot above the pit floor to a point seven (7) feet above
the floor of its own pit or above the floor of an
adjacent pit.
(c) Doors leading to the counterweight hoistway shall be
labeled, "Danger - counterweight Hoistway", these doors
shall be kept locked and shall be electrically contacted
to interrupt the operation of the equipment.
(d) Counterweight guards shall be constructed of a
non-combustible material.
RULE 2.15 GUIDE RAILS
(a) Where guide rails are sufficiently worn to cause any
material reduction in the clearances as mentioned in
Rules 2.45 a, b, c, the guide rails shall be replaced.
(b) Guide rails for the car and/or counterweight hoistway
shall extend the full length of the travel plus the
overtravel.
(c) Where guide rails are deteriorated or damaged, they
shall be replaced.
RULE 2.16 OVERHEAD SHEAVES
(a) Overhead sheaves in the hoistway which are suspended
beneath their structural supports shall be guarded by a
substantial cradle or floor constructed beneath such
sheaves.
EXCEPTIONS:
(1) Sidewalk Elevators.
(2) Dumbwaiters.
RULE 2.17 TERMINAL LIMIT SWITCHES AND STOPPING DEVICES
(a) Normal terminal limit switches or stopping devices
(directional limits) shall be provided on all elevators,
and shall be arranged to automatically stop the car and
to function independent of the operation devices and
also independent of such final terminal limit switches
or stopping devices as are required by Rule 2.17b.
(b) Final terminal limit switches or stopping devices shall
be provided on all elevators in addition to the normal
terminal limits or stopping devices and shall be
arranged to automatically prevent all movement of the
car by the operating devices, and to stop the car
independent of the normal terminal limit switches or
stopping devices, and, further, shall, when traveling at
any speed attained during normal operations, bring the
car to rest within the overtravels but the buffers may
be compressed.
(c) Normal and final terminal limits or stopping devices on
all elevators may be located on the car or in the
hoistway, if operated by the movement of the car, or
they may be located in the machine room if mounted on
and operated by a stopping device automatically
connected to the car with no dependence on friction as a
driving means provided on winding drum machine equipped
elevators. (1) If operated by polyphase alternating
current, the final stopping devices shall be in the
machine room and operated by a machine automatic
stopping device, and shall open the elevator service
circuit. EXCEPTION: Machines with direct-current
brakes and direct-current main line switches in the
hoistway.
(d) The cam or cams for operating limit switches shall be of
sufficient length and alignment to hold the switches in
the open position when the car is in contact with the
overhead structure or is resting on the fully compressed
buffers.
(e) All elevators operated in excess of one hundred (100)
f.p.m. shall have independent control contactors for
both normal and final terminal limits or stopping
devices.
RULE 2.18 ELEVATOR PITS
(a) There shall be a pit underneath every elevator. This
pit shall be not less than three (3) feet deep, and
adequately illuminated. EXCEPTION: Sidewalk elevators,
hand elevators, and dumbwaiters.
(b) Elevator pits shall be kept clean and dry. Water or
other liquid which may accumulate in the pit shall be
pumped out. Floor drains in elevator pits shall not be
permitted.
(c) Elevator pits shall not be used for storage space.
(d) Elevator pits shall be provided with a permanently
attached, securely mounted ladder of non-combustible
material which extends a minimum of 42 inches above the
sill of the lower terminal landing and is within reach
of the access landing sill.
(e) Sump pump pits shall be covered in the elevator pit with
a cover of non-combustible material of either solid or
bar type grating which shall be level with the pit
floor.
(f) Walk-in pit doors shall be provided with a properly
operating electrical contact to prevent operation of the
elevator when the pit door is in the open position.
RULE 2.19 SPRING OR OIL BUFFERS
(a) There shall be a spring or oil buffer in the pit
underneath each elevator car and counterweight,
conforming to good engineering practice. EXCEPTION:
Platform elevators, hand elevators, sidewalk elevators,
Private residece elevators, limited use/application
elevators (LULA) and dumbwaiters.
(b) All buffers shall be maintained in a vertical position
and directly under the buffer striker plates affixed to
the car or counterweights. The pit striker plate shall
be kept centered under the buffer in cases where the
inverted buffer is attached to the counterweight.
(c) Oil buffers shall be kept filled with oil to the level
indicated on the reservoir.
(d) Whenever oil is added, oils equivalent to those
recommended by the buffer manufacturer for use in the
buffer shall be used.
RULE 2.20 HOISTWAY DOORS FOR POWER PASSENGER ELEVATORS
(a) No fire door shall lock any landing opening in the
shaftway enclosure nor any exit leading from any
hoistway landing to the outside of the building.
(b) Landing openings in a hoistway shall be protected by
solid, fire/rated, horizontally sliding, or combination
sliding and swinging doors, or by swinging doors.
Hoistway doors shall guard the full width and full
height of the landing opening.
(c) For automatic operation of elevators the distance
between the hoistway side of the hoistway door and the
edge of the landing threshold shall be not more than two
and one-half (2 1/2) inches. (See also Rule 2.37 d.)
(d) All hoistway doors for power passenger elevators shall
be provided with door interlocks.
(e) Hoistway doors for hydraulic passenger elevators shall
be provided with a door closer, and shall be equipped
with a re-leveling device which will compensate for the
creeping of the car away from the landing opening while
the hoistway doors are opened.
(f) Hoistway doors shall be arranged to be opened by hand
from the shaftway side, except when locked "out of
service". Top, main exit and bottom terminal hoistway
doors shall not be locked "out of service" while the
elevator is in service.
(g) Hoistway door interlocks shall be arranged to prevent
the opening of the hoistway doors from the landing side
unless the car is within the landing zone. EXCEPTION:
With the use of special tools the hoistway doors may be
opened for maintenance and emergency purposes.
(h) Power closed hoistway doors in elevators employing a
type of operation which does not require an operator in
the car, shall be driven by a mechanism so designed and
set that the force necessary to prevent the closing of
the door shall not exceed thirty (30) pounds and
further, that the hoistway door, plus the car doors,
plus all parts rigidly connected thereto shall not
develop a kinetic energy in excess of seven (7) foot
pounds, computed for the average closing speed or shall
be provided with other suitably protecting measures.
(i) Glass vision panels, where provided shall be kept
glazed. One-quarter (1/4) inch clear wire glass shall
be used for replacements. The vision panel opening
shall reject a six (6) inch ball, and shall not exceed
one hundred (100) square inches in area.
RULE 2.21 HOISTWAY DOORS FOR FREIGHT ELEVATORS
(a) Each landing opening in a freight elevator hoistway
shall be continuously equipped with properly operating
doors and interlocks. EXCEPTION: The upper landing of
sidewalk elevators.
(b) Hoistway doors shall be located within three (3) inches
of the edge of the landing threshold.
(c) Hoistway doors of the sliding type shall operate in
guides or rails.
(d) Each landing opening in a freight elevator hoistway
shall be protected by solid, fire-rated doors of either
the vertically bi-parting or swing type which shall
protect the full height and width of the landing
opening.
(e) Hoistway doors provided with vision panels shall have
the openings protected with one quarter inch (1/4")
thick clear wire glass and shall reject a six inch (6")
ball.
(f) Vertical bi-parting doors shall be provided with fire
resistant, non-shearing, non-crushing safety asragals on
the upper panel.
(g) Rigid members which overlap the meeting edge, and center
latching devices are prohibited.
RULE 2.22 HOISTWAY DOORS FOR HAND AND POWER DUMBWAITERS
(a) All landing openings in dumbwaiter hoistway enclosures
shall be equipped with fire-rated doors.
(b) All landing doors of power dumbwaiters shall be equipped
with mechanical locks and contacts or electrical/
mechanical interlocks.
RULE 2.23 HOISTWAY DOORS FOR HAND-PASSENGER ELEVATORS
(a) Hoistway doors for hand-powered elevators shall guard
the full hoistway opening.
(b) The word "Elevator" shall be conspicuously displayed on
the landing side of the door.
RULE 2.24 HOISTWAY DOOR INTERLOCKS
(a) Electrically released, gravity or spring applied rope
gripper or locks to prevent the movement of the
operating rope or rod shall be prohibited.
(b) The interlocks for the hoistway doors shall function so
that the doors shall be in a closed and locked condition
before the car may be operated by the operating device
to move the car away from the landing.
(c) Interlock contacts shall be positively opened and the
functioning of the interlock to prevent movement of the
car by the operating devices shall not be solely
dependent on the action of a spring or springs, nor
gravity, nor upon the closing of an electric circuit.
If an electric circuit is used, its interruption shall
prevent the movement of the car by the operating
devices.
(d) Interlocks shall be so located as to be normally
inaccessible from the landing side of the closed
hoistway doors.
(e) Electro-mechanical interlocks or combination mechanical
locks and electric contacts shall be of the approved
type.
(f) Hoistway door interlocks shall be provided with covers
for the electrical contacts at all times.
RULE 2.25 HOISTWAY DOORS (FOR CARS EQUIPPED WITH INCHING
DEVICES)
(a) Hoistway doors for power elevators with a contract speed
not in excess of one hundred (100) fpm may have the
interlock service arranged to permit the car to be
operated away from the landing a distance of not over
twelve (12) inches before the locking operation takes
place, provided the following requirements are met:
1) If the locking operation fails to take place as
specified, further movement of the car will open
the operating circuit. 2) The car cannot be
started by the operating devices until the hoistway
door is closed. 3) The car platform is equipped
with a substantial vertical face flush with its
outer edge and extending at least fifteen (15)
inches below the car platform.
(b) On existing power opened and/or closed hoistway doors
equipped with door closer, hoistway doors shall be
considered in the closed position and the car may be
started only when the door is within three-quarter (3/4)
inch of the "lock" jam (or the edge of the opposite door
if bi-parting doors are provided).
RULE 2.26 EMERGENCY RELEASES: Emergency releases which by-pass
an interlock or contact circuit are prohibited.
RULE 2.27 FREIGHT ELEVATOR HOISTWAY DOOR LOCKING DEVICES
(a) For automatic or continuous pressure operation power
elevators, Hoistway doors shall be equipped with
properly operating interlocks.
RULE 2.28 CAR GATE OR HOISTWAY DOOR COUNTERWEIGHTS
(a) All car gate or hoistway door counterweights shall
operate in guides or boxes from which they cannot be
dislodged. The bottoms of all guides or boxes shall be
constructed to retain the counterweight if the
counterweight suspension means breaks. Car door or gate
counterweight guides shall be guarded on their enclosure
side.
(b) Car gate or hoistway door counterweight cables or ropes
shall be replaced with steel cable when renewed. Said
cable shall have a minimum diameter of one eighth inch
(1/8").
(c) Car gate or hoistway door counterweight cables shall
replaced when damaged or deteriorated due to rust, wear
or excessive crown wire breakage.
RULE 2.29 LANDING THRESHOLDS- FOR PASSENGER AND FREIGHT
ELEVATORS
(a) Landing thresholds, and ramps leading to landing
thresholds, shall be maintained so that persons will not
readily slip or trip thereon.
(b) All tracks on a landing thresholds shall have the tops
of the rails substantially flush with the landing
threshold.
RULE 2.30 SERVICE KEYS AND EMERGENCY KEYS FOR HOISTWAY
DOORS
(a) Service keys, where provided, shall be available to
authorized persons only and shall open any hoistway
doors which are arranged to be opened by the service
key, only when the car is within the landing zone.
(b) Emergency keys, where provided, shall be kept by the
superintendent or person in charge of the building in a
location where they are not accessible to unauthorized
persons.
(c) Emergency keys, where provided, shall be of a type not
readily duplicated and shall open any hoistway doors
which are arranged to be opened by the emergency key,
regardless of the position of the car in the hoistway.
(d) Hoistway access shall be provided for the upper and
lower terminal landings for all elevator by the use of
emergency keys as provided in Rule 2.30c.
RULE 2.31 ELEVATOR CAR SLINGS AND ELEVATOR FRAMES
(a) Elevator car slings shall be substantially level and
rectangular. Platform frames shall be substantially
level. All power elevators shall be constructed with
metal slings and platform frames.
RULE 2.32 ELEVATOR CAR FLOORS
(a) Elevator car floors shall be safely maintained and free
from hazardous conditions.
(b) Where tracks are located on an elevator car floor, the
tops of the rails shall be substantially flush with the
general surface of the car floors.
Rule 2.33 ELEVATOR CAR SIDES
(a) Elevator car sides of solid construction shall be
provided on all sides of passenger or freight power
elevators which are not used for loading or unloading.
(b) All power elevator car sides shall extend to the top of
the car.
(c) When elevator car sides are replaced, they shall be of
metal construction.
RULE 2.34 POWER ELEVATOR CAR TOPS
(a) Each power elevator shall be equipped with a metal,
solid or openwork car top. Openwork shall reject a one
and one-half (1 1/2) inch ball.
(b) Car tops of a car enclosure shall be so designed and
installed as to be capable of sustaining a load of
seventy-five(75) pounds per square foot.
RULE 2.35 POWER OPERATED SIDEWALK ELEVATORS
(a) Power operated sidewalk elevators shall be provided with
either flat metal tops or metal frames or arched metal
bows of sufficient strength to open the hatch covers, or
be provided with a device that will stop the car before
a person riding on the car platform could be injured, if
the hatch should fail to open.
RULE 2.36 DOUBLE COMPARTMENT POWER ELEVATORS
(a) All double compartment power elevators shall meet the
requirements of ANSI A17.1.
RULE 2.37 CAR DOORS OR GATES FOR POWER PASSENGER ELEVATORS
(a) Car doors or gates shall be provided with car door or
gate electric contacts which shall protect each entrance
of power passenger elevators; and shall be of the
horizontally sliding type, and shall be arranged to
guard the full width and height of the opening.
(b) Car gates of the scissors or pantograph type on
automation operation elevators shall not be opened under
power.
(c) Power closed doors or gates, in elevators employing a
type of operation which does not require an operator in
the car, shall be driven by a mechanism so designed and
set that the force necessary to prevent the closing of
the door or gate shall not exceed thirty (30) pounds,
and further, that the car door or gate plus the hoistway
door or gate, plus parts rigidly connected thereto shall
not develop a kinetic energy in excess of seven (7) foot
pounds computed for the average closing speed, or shall
be provided with other protecting measures.
(d) For automatic operation, passenger elevators having
automatically released, self-closing doors or gates, and
manually closed or self-closing hoistway doors, the
closing of the car door or gate shall be prevented
unless the hoistway door is closed in a position to be
locked.
(e) For automatic operation or continuous-pressure
operation, the maximum clear space between the car doors
or gates and the hoistway doors shall not exceed five
(5) inches. Where this distance is exceeded the
hoistway doors shall be altered to comply with Rule
2.20c.
(f) Collapsible Car Gates shall be constructed to reject a
three (3) inch ball, when the gates are in a extended
position.
(g) Sliding car doors or gates shall be of solid
construction. Vision panels shall be used where
required. Clear wire glass, not less than one-quarter
(l/4) inch thick shall be used for glass vision panels.
The vision panel opening shall reject a six (6) inch
ball, and shall not exceed one-hundred (l00) square
inches in area.
RULE 2.38 CAR DOORS OR GATES FOR POWER FREIGHT ELEVATORS
(a) A car door or gate shall be provided at each entrance to
a power freight elevator, and shall be equipped with an
electric contact.
(b) Car doors or gates for power freight elevators shall be
of the horizontally or vertically sliding type, shall
guard the full width of the car opening and shall extend
from within two (2) inches of, and at least six (6) feet
above the car platform flooring.
(c) Collapsible Car Gates for power freight elevators shall
reject a four and one-half (4 1/2) inch ball when the
gates are fully extended.
(d) Sliding car doors or gates may be solid, or may be
provided with glass or grille vision panels. Grilles,
bars, or vision panels may extend the full height of the
door or gate panel. Clear wire glass, not less than
one-quarter (l/4) inch thick shall be used for glass
vision panels. The vision panel opening shall reject a
six (6) inch ball, and shall not exceed one-hundred
(l00) square inches in area.
RULE 2.39 CAR DOOR OR GATE ELECTRIC CONTACTS
(a) Car door or gate electric contacts shall be arranged to
prevent the starting of the car by the operating device
unless the car door or gate is within two (2) inches of
full closure. EXCEPTION: (1) The contact, when the car
door or gate is opened, shall not prevent the movement
of the car only within the leveling zone by the car
leveling device.
(b) Car door or gate electric contacts shall be positively
opened and the functioning of the contact to prevent the
starting of the car shall not be solely dependent upon
the action of a spring or springs nor upon gravity nor
upon the closing of an electric circuit, and its
interruption shall prevent the starting of the car by
the operating device.
RULE 2.40 ELEVATOR CAR EMERGENCY EXIT
(a) Every elevator car shall be provided with a car top
emergency exit.
(b) Top emergency exit openings, shall be not less than
sixteen (l6) inches by twenty-two (22) inches.
(c) Top emergency exits shall open outward and shall be
hinged or otherwise attached to the car top and so
arranged that the exit cover can be opened from the top
of the car only.
EXCEPTION: Elevators required to meet seismic
conditions must have emergency exits in compliance
with ANSI A17.1-1993 Rule 2406.1.
(d) Side Emergency Exit Panels, where provided, shall be
bolted in a closed position. Use of side emergency
exits shall be prohibited.
(e) All emergency car exits shall be equipped with electric
contacts to prevent the movement of the car if the exit
door or panel is in the open position.
RULE 2.41 CAR LIGHTING
(a) Elevator car interiors shall be adequately illuminated
at all times. Passenger elevator interior illumination
shall be not less than five (5) foot candles. Freight
elevator interior illumination shall be not less than
two and one-half (2 1/2) foot candles. All elevators
shall be provided with emergency lighting.
(b) Elevator lighting circuit switches shall be located in
the car, and shall be operated by a key switch.
(c) The elevator car top exterior shall be equipped with
adequate lighting.
(d) Every elevator shall be provided with a separate
electrical circuit and approved disconnect switch in the
machine room for each elevator car lighting circuit.
RULE 2.42 GLASS IN ELEVATOR CARS
(a) No piece of glass, unless laminated or clear wire glass
not less than one-quarter (1/4) inch thick, and
conforming to ANSI Z97.1 shall exceed one (1) square
foot in area when located in the cab of the car.
RULE 2.43 TOE GUARDS FOR ELEVATOR CARS EQUIPPED WITH CAR
LEVELING DEVICES OR INCHING DEVICES
(a) Elevator cars equipped with car leveling devices or
inching devices that operate the car when the hoistway
doors are open shall have the car platform provided with
a toe guard extending a sufficient distance below the
car platform so that no horizontal opening in the
hoistway occurs when the car is moved by the car
leveling devices or inching devices.
RULE 2.44 GUIDE SHOES
(a) When guide shoes or roller guides are excessively worn,
they shall be replaced.
RULE 2.45 CLEARANCE BETWEEN CARS, COUNTERWEIGHTS AND
SHAFTWAYS
(a) There shall be maintained a clearance of not less than
three-quarter inch (3/4) between the sides of the car
and the shaftway enclosure and not less than one inch
(1") clearance between the car and its counterweights.
(b) There shall be maintained a clearance of not less than
one-half inch (1/2") between car platforms and landing
thresholds for elevators using steel guide rails with
side-post construction, and three fourths inch (3/4")
for elevators with wood guide rails or corner post
construction. This clearance shall be maintained so as
not to exceed one and one half inches (1 1/2").
(c) The clearance between the shaftway enclosure and the
open edges of the car platform shall not exceed five (5)
inches.
(D) Overhead Clearances
1) The distance between the top of the elevator car
sling and any obstruction directly above it when
the car floor is level with the top landing shall
be equal to or be greater than the sum of the
following.
a: The bottom counterweight runby,
b: The maximum stroke of the counterweight buffer,
c: Six inches (6").
2) The distance between the top of the counterweight
and any obstruction directly above it when the car
is level with the bottom landing shall be equal to
or greater than the sum of the following:
a: The distance between the top of the buffer and
its striker plate on the car,
b: The maximum stroke of the car buffer,
c: Six inches (6").
3) For cars traveling faster than 200 feet per minute,
add this item to each of the above sums:
a: the stroke of the buffer corresponding to the
governor tripping speed of the car, less
NOTE: This item may be omitted if provision is made to
eliminate the jump of the car or counterweight if its top
clearance is being considered, at buffer engagement.
(e) No structure or apparatus shall be installed either on
the top of the car, or extending upwards above the top
of the car, or extending downwards from the top of the
hoistway which would reduce the overtravel clearances;
unless prior to installation an investigation is made
and permission is given by the Department of Labor and
Training.
RULE 2.46 SIGNAL SYSTEMS FOR POWER ELEVATORS
(a) Each power freight or passenger elevator, or each
grouping of elevators shall be provided with a signal
system by means of which signals can be given from any
landing whenever an elevator is desired at this landing.
RULE 2.47 EMERGENCY SIGNAL
(a) Every elevator shall be equipped with an emergency
signal that can be operated from within the elevator car
with the signal clearly audible from outside the
hoistway, at a designated location.
RULE 2.48 PLATFORM ELEVATORS
(a) No person shall ride a platform elevator.
(b) Platform elevators with a travel in excess of fifteen
(15) feet shall meet all requirements of a freight
elevator.
RULE 2.49 OPERATION AND CONTROL
(a) Power elevators operated mechanically by wire ropes,
rods or any other devices shall have these operating
devices made inaccessible from the outside of the
hoistway, and be of a non-combustible material.
(b) Wheel or lever operating devices shall be provided with
"up" and "down" position indicators on the operating
device.
(c) Sheaves for wire hand ropes shall be equipped with
guards to prevent the ropes from leaving the sheaves or
the hand type cable tension shall be automatically
maintained. Overhead tension weights for hand-ropes
shall be secured by cables or chains fastened to the
weights and to a suitable anchorage. Wire hand ropes
shall be kept smooth, clean, free of oil or grease, and
without projecting wires. Reversing switch shall be
grounded.
(d) All car switch operating devices shall automatically
return to the "stop" position when pressure is released.
(e) Elevators equipped with more than one (1) operating
system shall have the operating systems interlocked to
allow the use of only one operating system at a time.
(f) All elevators shall be provided with an emergency "stop"
switch in the car, and this switch shall be of a type in
which the contacts are mechanically opened and not
solely spring opened.
(g) Defective contacts shall be replaced.
(h) No circuit breaker operated automatically by a fire
alarm system shall render an elevator inoperative.
(i) Automatic operation elevators shall conform with the
following: 1) If the car has started from a given
landing, no impulse can be given to send the car in the
reverse direction. EXCEPTION: Elevator cars equipped
with firemens service. 2) The car can not be started by
the operating devices unless the car door gate is closed
and is equipped with a contact as provided in Rule
2.39a, and all hoistway doors are in a closed position
and are equipped with interlocks.
(j) Continuous pressure operation shall not be used for
passenger elevators unless they are provided with all
the safety devices required for automatic operation.
(k) If an overload circuit breaker is used, the opening of
the motor circuit and the opening of the brake circuit
shall occur simultaneously.
(l) All electric elevators, except electro-hydraulic
elevators shall be equipped with electrically released
brakes.
(m) Electric elevators equipped with electric brakes and
operated by hand ropes, levers, or wheel operating
devices, shall be provided with car emergency switches,
a car door or gate electric contact where required, door
interlocks and have the operating and control circuits
equipped with a sequence relay.
(1) All hand rope operated elevators shall be provided
with a constant pressure switch which must be
activated after the hand rope is operated to enable
the elevator to be activated. This means of
operation shall not override the sequence relay
(n) A pit switch and a crosshead switch shall be installed
and connected in the emergency circuit. These switches
shall be of a type in which the contacts are
mechanically opened and not solely spring opened.
RULE 2.50 CAR AND COUNTERWEIGHT SAFETIES AND SPEED
GOVERNORS
(a) Each elevator suspended by cables shall be equipped with
a mechanically applied car safety (or safeties) located
in a steel safety plank beneath the car capable of
stopping and sustaining the car and its contract load.
(b) Private residence elevators, roped hydraulic, and
limited use/application elevators may have broken rope
actuated car safeties.
(c) All elevator cars regardless of speed which are
suspended by cables shall have car safeties in
conformity with Rule 2.50d, applied by speed governor
devices.
(d) Safety car devices shall be located in the safety plank
beneath the car platform. Five (5) types of safeties
are acceptable: (1) Type I (Instantaneous) which should
be limited to a capacity speed not in excess of one
hundred (100) f.p.m., but shall, on unaltered cars, be
limited to a capacity speed not in excess of one hundred
fifty (150) f.p.m. (2) Type W.C.(Wedge Clamp) with
constant retarding force. (3) Type G.W.C.(Gradual Wedge
Clamp) with gradually increasing retarding force. (4)
Type F.G.C.(Flexible Guide Clamp) with constant
retarding force. (5) Type C (combination instantaneous
and oil buffer) rated speed shall not exceed 500 fpm and
shall comply with the requirements of ANSI A17.1.
(e) Pawl type safeties applying to a rack guide rail are
permitted only on hand freight elevators and only on
power freight elevators where the capacity speed is not
in excess of fifty (50) f.p.m. where also, the capacity
is not in excess of two thousand (2,000) pounds; and
where also, no person other than the operator is
permitted to ride.
(f) Car safeties shall be kept well lubricated and operating
freely.
(g) Car safeties shall be adjusted to operate simultaneously
and the application of the safeties shall not cause the
car platform to become out of level more than
three-eights (3/8) inch per foot measured in any
direction.
(h) Speed governors shall be set to apply either at not less
than fifteen (l5) percent over capacity speed or at not
more than forty (40) percent over capacity speed except
that no speed governor shall be set to apply at less
than one hundred seventy-five (l75) f.p.m.
(i) Car safeties shall be arranged to release by raising the
elevator car however, when the car safeties are applied
no decrease in the tension of the governor cable or
motion of the car in the descending direction shall
release the car safeties.
(j) Safety devices for stopping the car while ascending
shall not be permitted, however, counterweight safeties,
where required shall be installed to stop a descending
counterweight.
(k) Governors shall be located where their full movement is
unobstructed and nothing shall be stored or be permitted
to remain near the governor which might interfere with
their operation.
(l) Every car safety and its speed governor devices shall be
tested in the presence of a State Elevator Inspector or
an authorized inspector at least once every twelve (12)
months that the elevator is in service. NOTES: (1)
Broken rope type safeties shall be tested by obtaining a
minimum of (5') of slack which will cause them to
function when the supports are abruptly removed. (2)
Speed governor applied type safeties shall be applied at
capacity speed by tripping the governor by hand. (3)
Capacity safety load test is required once every five
(5) years. (4) Each over speed governor shall be
calibrated every five (5) years.
(m) Operating mechanisms of speed governors and car safeties
shall not be painted and shall be maintained in proper
working order.
(n) Where car safeties are required by these rules, traction
type power elevators shall have cars which are equipped
with governor operated safeties.
(o) Where governor mechanisms are replaced, they shall be
tested and calibrated in the presence of a State
Elevator Inspector.
RULE 2.51 DUMBWAITERS SHALL MEET THE REQUIREMENTS OF THE
FOLLOWING RULES:
(a) Rules: 2.1, 2.2, 2.5, 2.11a & b, 2.12, 2.13c & d &
h, 2.17a, 2.22a & b, and 2.24c,d,f.
RULE 2.52 ESCALATORS
(a) Escalator balustrades shall be maintained in a
smooth condition.
(b) Escalator treads, risers, combs and landings shall
be kept smooth, the treads and landings shall
afford a secure foothold and the combs shall set
into the corrugation on the treads, with a maximum
(3/l6") clearance.
(c) Escalator "stop" buttons, speed limit switches,
starting switches, reversing switches, broken chain
switches and any other safety switch shall be
maintained continuously in proper operating order.
(d) Escalator machine spaces shall be equipped with
adequate, permanent lighting, an access ladder, and
also, there shall be an emergency stop switch
located in all machine spaces and pits of all
escalators and moving walks.
(e) Escalator motors, machinery and running gear shall
be kept properly lubricated.
(f) Escalators shall be operated at a speed of not more
than one hundred twenty-five (l25) feet per minute.
(g) Drip pans, undersides of steps, trusses and the
interior of the escalator shall be free of dirt,
debris oil and combustible material.
(h) Escalators shall be provided with caution and use
signs, placed in a conspicuous location at each end
Rule 2.53 EXCEPTIONS AS STATED AT THE BEGINNING OF THIS
SECTION II
This Section II of the Rhode Island State Code of Safety
Standards shall govern existing elevators, escalators, and
moving walks except the following:
(a) Manlifts within the scope of ANSI A90.1.
(b) Powered platform and equipment for exterior and interior
building maintenance within the scope of ANSI A120.1.
(c) Cranes, derricks, hoists, hooks, jacks and slings within
the scope of ANSI B30.
(d) Industrial Trucks within the scope of ANSI B56.
(e) Line jacks, false cars, shafters, moving platforms and
similar equipment used for installing an elevator.
(f) Tiering or piling machines used to move material to and
from storage located and operating entirely within one
story.
(g) Equipment for feeding or positioning material at machine
tools, printing presses, etc.
(h) Skip or furnace hoists.
(i) Wharf ramps.
(j) Amusement devices.
(k) Lift bridges.
(i) Railroad car lifts or dumpers.
(m) Mechanized parking garage equipment.
(n) Mine elevators not located in or adjacent to a building
or structure.
(o) Material hoists within the scope of ANSI A10.5, which
however, shall be covered by Section IV.
(p) Personnel hoists which, however, shall be governed by
Section III
(q) Scissor lifts Subject to ANSI MH29.1 and dock leveling
devices subject to ANSI MH30.1.
SECTION III
PERSONNEL HOISTS
Rule 1.0
(a) ASME/ ANSI - A10.4 shall govern the design,
construction, installation, operation, inspection,
testing, maintenance, alterations and repair of
structures and hoists which are not a permanent part of
the buildings, and are installed inside or outside
buildings and other structures during construction,
alteration, demolition or other temporary usage and are
used to raise and lower workers and other persons
engaged in the project. The hoist may also be used for
transportation of materials. These devices are subject
to the provisions of Chapter 23-33 of the Rhode Island
General Laws.
Rule 2.0
The following additions shall be part of the within Code:
(a) Installation of said devices shall be subject to the
permit procedures required under the provisions of Rhode
Island General Laws Section 23-33-17. Said devices are
subject to the licensing provisions set forth in Rhode
Island General Laws Sections 23-33-2.2 and 23-33-2.3.
Said devices shall be erected, installed, repaired,
maintained, serviced and/or operated only by persons
licensed by the Division of Occupational Safety.
(b) Car Door & Gate Electric Contacts. Car doors and gates
shall be provided with electric contacts to prevent the
operation of the driving machine if the doors or gates
are in the open position.
(c) Car top exit covers, when in the open position, shall
prevent the operation of the drive machine at all times.
(d) Rack & Pinion drives shall be so affixed as to prevent
the disengagement of the pinion from the rack.
(e) Manually operated drum and/or sheave machines are
prohibited.
SECTION IV
MATERIAL HOISTS
Rule 1.0
(a) ANSI A10.5 shall govern the design, construction,
installation, operation, inspection, testing,
maintenance, alterations and repair of structures and
hoists which are used to raise or lower materials during
construction, alteration or demolition of a building.
These devices may be installed inside or outside of a
building or other structure. This section is not
applicable to the temporary use of permanently installed
passenger elevators as material hoists. These devices
are subject to the provisions of Chapter 23-33 of the
Rhode Island General Laws.
Rule 1.1
(a) Installation of these devices shall be subject to the
permit procedures required under the provisions of Rhode
Island General Laws Section 23-33-17. The devices are
subject to the licensing provisions set forth within
Rhode Island General Laws Sections 23-33-2.2 and
23-33-2.3. These devices shall be erected, installed,
repaired, maintained, serviced and/or operated only by
individuals licensed by the Division of Occupational
Safety except where an Operating Engineer is required to
operate only, the said device.
RULE 2.0
(a) All deletions and revisions refer to National Standard
Rules contained within ANSI A10.5.
(1) DELETION:
(a) RULE 6.4 HOIST TOWER ENCLOSURES. Hoist towers may be
used with or without an enclosure on all sides.
However, whichever alternative is chosen, the applicable
conditions in 6.4.1 through 6.4.3 shall be met.
(2) REVISION:
(a) HOIST TOWER ENCLOSURES. Hoist towers shall be enclosed
on all sides in accordance with Rule 6.4.1.
(3) DELETION:
(a) RULE 6.5 HOISTWAY ENTRANCES. All entrances to hoistways
shall be protected by substantial gates or bars, which
shall guard the full width of the landing entrance.
(4) REVISION:
(a) HOISTWAY ENTRANCES. All entrances to hoistways shall be
protected by substantial gates, which shall guard the
full width of the landing entrance.
(5) DELETION:
(a) RULE 6.5.2 Bars shall be not less than 2x4 inch wooden
bars or the equivalent and shall be located 2 feet from
the hoistway line. Bars shall be located not less than
36 inches nor more than 42 inches above the floor.
SECTION V
WHEELCHAIR LIFTS / STAIRWAY CHAIRLIFTS
Rule 1.0
(a) All wheelchair lifts or stairway chairlifts
installed in locations other than a private
residence, shall be installed and maintained in
accordance with Part XX of the ANSI A17.1 Code.
Rule 1.1
(a) Each wheelchair lift installed within a public
building shall be provided with a signal system by
means of which signals can be given from any
landing to summon assistance whenever operation of
the conveyance is desired and the required key is
not available.
Rule 1.2
(a) All wheelchair lifts or stairway chairlifts
installed in or at a private residence shall be
installed and maintained in accordance with Part
XXI of the ANSI A17.1 Code.
SECTION VI
Vertical Reciprocating Conveyors
RULE 1.0
(a) ASME/ANSI-B20 shall govern permanently installed
vertical reciprocating conveyors used strictly for the
movement of material in or at a building and is not part
of a continuous conveyor system. All personnel are
expressly forbidden to ride on these units. In
addition, the following shall apply.
Rule 1.1
(a) Vertical Reciprocating Conveyor hereinafter (VRC) means
a non portable lifting device for material only which
moves in fixed guides and serves two (2) or more fixed
landings, traveling vertically or at an incline, with a
load carrying unit furnished with flooring of a type
which provides safe footing (platform) for a person to
load or unload material for transport.
Rule 1.2
(a) The only permissible use of the VRC is as material
width. It shall not carry an operator or any
passengers. Each VRC shall have a metal plate securely
attached to the hoistway doors at each landing stating
in letters at least one half inch (1/2") in height:
"Material Only - No Riders."
Rule 1.3
(a) All components of the VRC shall be maintained in a
structurally sound, firmly secured, and satisfactory
condition to perform safely the work which they are
intended to do.
Rule 1.4
(a) All materials and methods used for construction and
installation of these units shall comply with the
requirements of the State Building Code and the State
Fire Code.
Rule 1.5
(a) All electrical wiring and apparatus shall comply with
the requirements of the State Building Code and the
State Fire Code.
Rule 1.6
(a) Operation of a VRC shall only be from the outside of the
hoistway with its controls located no less than four (4)
feet from the hoistway door.
(b) All operating controls of the VRC shall be of the
constant pressure type or, in the alternative, of the
momentary pressure type so long as an emergency stop
switch is incorporated with the operating control
station at each landing serviced by the VRC.
(c) Each landing opening in the conveyor hoistway shall be
equipped with a gate that is no less than six (6) feet
in height and guards the full width of the landing
opening. It shall at all times be equipped with a
properly operating interlock to prevent movement of the
carriage with a gate or door in the open position.
(d) Gates shall be mechanically locked by the interlock
until the conveyor carriage is at the landing.
Rule 1.7
(a) Each cable or chain operated conveyor shall be equipped
with a mechanically-applied safety device ("backstop
device") attached to the carriage frame with a capacity
for stopping and sustaining the carriage and the
contract load in a reasonable level position.
(b) The "backstop device" shall be set for release by only
raising the carriage.
Rule 1.8
(a) Hydraulically operated conveyors shall be equipped with
a relief valve installed in such a way that it cannot be
shut off. The relief valve shall be of sufficient size
and located so as to pass the full capacity of the pump
at full speed without exceeding the safe working
pressure of the pump tank or piping. The machine relief
valve shall be tested every three (3) years with the
platform at the extreme limit of its overtravel. Pipe
rupture valves shall be provided on all hydraulically
operated conveyors.
(b) All packings used in connection with a hydraulic
conveyor shall be properly maintained to prevent any
uncontrolled movement of the platform.
Rule 1.9
(a) No conveyors shall be installed above any space or work
area capable of occupancy without prior approval by the
Building Official, certifying that the floor or other
structure under the hoistway is of sufficient strength
to safely withstand the impact of the carriage with the
contract load when dropped freely in the guides from the
upper limit of overtravel.
Rule 1.10
(a) Normal terminal limit switches or stopping devices shall
be provided on each VRC and shall be arranged to
automatically stop the platform and to function
independently of the operation devices.
(b) Final terminal limit switches or stopping devices shall
be provided on all VRC's in addition to the normal
terminal limits or stopping devices. They shall be
arranged so that the operation devices shall
automatically prevent movement of the car and stop the
car's movement independently of the normal terminal
limit switches or stopping devices.
Rule 1.11
(a) Deteriorated or damaged guide rails or guide shoes shall
be replaced.
APPENDIX A
PERMITS FOR INSTALLATION AND/OR MODERNIZATION
RULE 1.0
(a) No elevator, escalator, dumbwaiter, moving walk or other
device subject to the provisions of Chapter 22-33 of the
Rhode Island General Laws shall be installed,
constructed or modernized within the limits of this
state without a permit issued by the Division of
Occupational Safety, Elevator Unit.
(b) All applications for a permit to install, modernize or
construct, shall include duplicate sets of data sheets
and complete and accurate plans and/or drawings of the
device, hoistways, machine rooms, landings and
appurtenances. These plans shall also show the device
location and machine room relation within the structure.
All information as required by ANSI A17.1 shall be
included within these plans. The use of "stock" or
computer drawn plans shall be allowed provided that all
required information is provided for each unit or
device. A permit to install shall be issued when the
above required plans and appropriate fee are submitted
and approved. No person, firm or corporation shall
install, construct, modernize or relocate, or attempt to
install, construct, modernize or relocate any device
subject to the provisions of Chapter 23-33 of the Rhode
Island General Laws without having first obtained this
permit.
Rule 2.0 LIMITED OPERATING PERMITS FOR THE USE OF ELEVATORS DURING
CONSTRUCTION
Any person, firm or corporation who has been issued a permit by
the Department of Labor and Training to install, modernize or
construct an elevator pursuant to the provisions of Chapter 23-33
of the Rhode Island General Laws may apply in writing to the
Director of Labor and Training or his/her designee for the
issuance of a sixty (60) day Limited Operating Permit for the
temporary use of an elevator during construction and prior to the
issuance of a regular Certificate of Operation.
The issuance of this Limited Operating Permit is within the sole
discretion of the Director of Labor and Training or his/her
designee and is subject to the following conditions and
restrictions:
A)
The Applicant for this permit must receive the prior
written approval for the limited operation of the elevator
during construction from the State Fire Marshall’s office;
and
B)
The Applicant must fulfill any and all conditions and
requirements set forth by the State Fire Marshall’s office
as part of its approval for such limited elevator use
during construction; and
C)
The Applicant for this permit must provide written
notification of the limited operation of the elevator
during construction to the United States’ (Federal) OSHA
office whose jurisdiction includes the State of Rhode
Island, the Occupational Safety Unit of the Department of
Labor and Training (if applicable), the Fire Department
and Building Inspector’s Office within the City or Town
where the construction project is located, and the State
Building Commissioner’s Office (if applicable); and
D)
The use of the elevator under this Limited Operating
Permit during construction shall be subject to all
applicable laws of the State of Rhode Island, all
Regulations and licensing requirements of the Department
of Labor and Training, and all applicable Federal OSHA
Standards as set forth in the Code of Federal Regulations;
and
E)
The Applicant shall comply with any and all conditions and
requirements set forth by the Director of Labor and
Training or his/her designee as part of his/her issuance
of this Limited Operating Permit for use of the elevator
during construction, including but not limited to safety
requirements and the limitation of hours of operation to a
maximum of seven (7) hours of use per work shift, with
total usage not to exceed twenty-one (21) hours within any
twenty-four (24) hour period; and
F)
The use of the elevator under this Limited Operating
Permit shall not include public use, and any operation of
the elevator without the issuance of this Limited
Operating Permit is restricted to the use for temporary
testing purposes set forth in RI Gen. Laws §28-33-17;and
G)
The initial Limited Operating Permit for Use During
Construction is valid for sixty (60) days. The Applicant
must apply for a renewal and re-inspection to extend the
permit for any additional sixty (60) day periods; and
H)
The fee for the issuance of an initial Limited Operating
Permit is $120.00, and there is no renewal fee for each
subsequent sixty (60) day renewal of the permit that is
issued prior to the issuance of a Certificate of Operation
pursuant to RI Gen. Laws §23-33-16; and
I)
Any violation of this regulation or of the terms and
conditions of any Limited Operating Permit issued
hereunder, may be addressed in the same manner as set
forth in RI Gen. Laws §23-33-15 and §23-33-15.1; and
J)
Any Applicant who is dissatisfied with any decision of the
Director of Labor and Training or his/her designee
regarding the issuance of a Limited Operating Permit
pursuant to this regulation, may appeal said decision in
the same manner as set forth in RI Gen. Laws §23-33-18.
APPENDIX B
LICENSE REQUIREMENTS
RULE 1.0 COMPANY LICENSE:
(a) An annual license is required under the provisions of
Rhode Island Section 23-33-2.2 for any business entity
engaged in the construction, servicing, maintenance,
modernization, removal or repair of any device subject to
the provisions of this code or the provision of Chapter
23-33 of the Rhode General Laws. The annual initial and
renewal fee for company licenses shall be $200.00.
RULE 2.0 REQUIREMENTS
The following conditions shall be met prior to the
issuance of a company license:
(a) Registration with the Rhode Island Secretary of State
indicating that the company does business within this
State of Rhode Island;
(b) Shall register the name and business address of the
individual owner with the names and business addresses of
the corporate officers with the Rhode Island Department
of Labor and Training;
(c) Shall register a list of the types of equipment
installed, constructed, maintained, repaired, or serviced
with the Rhode Island Department of Labor and Training;
(d) Register a list of any other current state or municipal
licenses held and description of same with the Rhode
Island Department of Labor and Training;
(e) Coverage by a liability insurance policy or self
insurance in an amount not less than $500,000; proof of
insurance or adequacy of self-insurance shall be filed at
the time of initial license or renewal application;
(f) Licensure by all employees of said business entities as
required by R.I.G.L. Section 23-33-2.3 and filing of
said employees' names and license types and numbers with
the Chief Elevator Inspector;
(g) For companies created after July 1, 1992 at least (1)
owner or (1) corporate officer shall have a minimum of
ten (10) years experience in the installation,
construction, servicing, maintenance, modernization,
removal or repair of any device subject to the provisions
of this code or of Chapter 23-33 of the Rhode Island
General Laws.
RULE 3.0 INDIVIDUAL LICENSES:
(a) An annual license is required under the provisions of
Rhode Island General Laws Section 23-33-2.3 for any
person employed in the installation, construction,
maintenance, modernization, removal or repair of any
device subject to the provisions of this Code or of
Chapter 23-33 of the Rhode Island General Laws
requirements for individual license.
RULE 4.0 REQUIREMENTS
The following conditions shall be met prior to the
issuance of an individual license;
(a) Employment by a licensed company and licensed by the
Division of Occupational Safety, and pass a written
examination with a score of not less than 70%; filing
all information, forms and payment of the appropriate
fees for examinations, initial and annual renewal of
licenses.
(b) A minimum of (3) years field experience as a
helper/apprentice under supervision with a licensed
mechanic prior to said examination.
(c) Direct and continuous supervision of all helpers/
apprentices;
(d) Annual registration of all helpers and/or apprentices
with the Division of Occupational Safety for three (3)
years; the fee of said registration shall be $25.00;
(e) All helpers and/or apprentices shall be examined after
(3) years of such employment for additional licensure;
the fee of said examination shall be $50.00;
(f) Licenses issued by any foreign licensing authority shall
not authorize work on an elevator or other device
subject to the provisions of this Code or Chapter 23-33
of the Rhode Island General Laws within the State of
Rhode Island;
(g) Examinations for individual licenses shall be given
every February, May, August and November on the first
Tuesday of said months;
(h) Company licenses shall be subject to suspension or
revocation after a hearing before the Director of Labor
and Training, and upon a finding by a preponderance of
the evidence that a licensee has violated the terms and
provisions of within Rules and Regulations or the
provisions of Chapter 23-33 of the Rhode Island General
Laws. Individual Licenses may be suspended by the Chief
until a hearing before the Director is held to determine
if the suspension is to be lifted or the license is
revoked.