450-RICR-00-00-10
450-RICR-00-00-10. Rhode Island Fire Alarm Code (version Amendment, 07/01/2021 to 01/04/2022)
To view the official Final Regulation for accessibility and readability, click Download Regulation:
Download Regulation
10.1 Rhode Island Fire Alarm Code
A. ADOPTION OF NFPA 72 AS THE
RHODE ISLAND FIRE ALARM CODE.
1. The National Fire Alarm &
Signaling Code, NFPA 72 (2019 Edition), as amended by §
10.1(A)(2) of this Part below, is hereby adopted as the “Rhode
Island Fire Alarm Code.”
2. The specific Rules
addressing which use and occupancy groups require fire alarm systems,
any additional requirements for the installation of these systems,
and designating the party or parties responsible for the approval of
these systems, are outlined in The Rhode Island Life Safety Code,
Part 8
of this Subchapter, Chapter 9 (Building Service and Fire Protection
Equipment) and occupancy Chapters 12 through 44. Any conflict between
the provisions of the Rhode Island Life Safety Code and the 2019
edition of NFPA 72, as adopted by this Part, shall be resolved in
favor of the most stringent requirement as determined by the State
Fire Marshal subject to appeal to the Fire Safety Code Board of
Appeal & Review.
B. EXTENSION OF CERTAIN FIRE
ALARM INSTALLATION DEADLINES
(Reserved)
C. ALARM UPGRADE EXEMPTION FOR
ORIGINAL TIMELY COMPLIANCE
(Reserved)
D. EXEMPTION OF SMALLER
BUSINESS GROUP BUILDINGS
(Reserved)
E. SEPARATION OF CERTAIN
OCCUPANCIES FOR FIRE ALARM REVIEW
1. Where existing low to
ordinary hazard business and/or mercantile occupancies can be
separated from the remainder of a building by construction
maintaining an “approved acceptable separation” as
outlined herein, the fire alarm square footage calculation, for this
existing separated occupancy, shall be limited to the space within
the “approved acceptable separation.”
a. In addition to the
“approved acceptable separations” listed below, any
properly installed Nationally Recognized Testing Laboratories listed
two (2) hour fire rated assembly shall be deemed to provide proper
separation of these occupancies.
b. For the purposes of
determining whether a fire alarm system is required within a
separated low to ordinary hazard business or mercantile space, a wall
assembly, consisting of double five eighth inch (5/8”) type-x
gypsum board over an existing wall and fastened to the structure,
shall be deemed to be an “approved acceptable separation.”
c. For the purposes of
determining whether a fire alarm system is required within a
separated low to ordinary hazard business or mercantile space, a
ceiling and/or floor assembly, consisting of a layer of five eighth
inch (5/8”) type-x gypsum board attached to the existing floor
joists and separated from a second (2 nd ) required layer of
five eighth inch (5/8”) type-x sheetrock, by three quarter inch
(3/4”), or deeper, metal furring strip or stud, shall be deemed
to be an “approved acceptable separation.”
d. The Board recognizes that
full continuity of construction, and/or full support for the rated
assemblies, may never be achieved in retrofitting an existing
business and/or mercantile occupancy with an “approximate”
two (2) hour fire rated assembly. However, the authority having
enforcement jurisdiction may request reasonable additional
construction safeguards, such as the filling of any visible voids
between wall and floor/ceiling assemblies with non-combustible
materials and/or reasonable alternative structural support if
necessary.
e. A building owner may
request review of such “additional construction safeguards”
to the Fire Safety Code Board of Appeal and Review pursuant to the
procedures outlined in § 1.7
of this Subchapter .