510-RICR-00-00-19. RISBC-19 Rhode Island Fuel Gas Code (version Amendment, 08/01/2007 to 07/01/2010)
RHODE ISLAND
STATE BUILDING CODE
SBC-19 State Fuel Gas Code
Effective August 1, 2007
Replaces SBC-19-2004
Dated September 1, 2004
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS
Department of Administration
BUILDING CODE STANDARDS COMMITTEE
One Capitol Hill
Providence, RI 02908-5859
(401) 222-3033
FAX NO (401)-222-2599
RISBC-19
RISBC-19
THIS PAGE LEFT INTENTIONALLY BLANK
RISBC-19
Regulation SBC-19
State Fuel Gas Code
August 1, 2007
The Building Code Standards Committee, in accordance with the rule making authority of
Title 23, Chapter 23-27.3, Section 109.1, paragraphs a through c inclusive, has formally
adopted and promulgated as the Rhode Island State Building Code, the provisions of the
International Fuel Gas Code, 2006 edition, as published by the International Code Council,
Inc. (I.C.C.), together with amendments thereto hereinafter set forth to the articles and
sections of this code:
The provisions of Title 23, Chapter 27.3 of the General Laws of Rhode Island establishing
administration and enforcement are hereby incorporated by reference. Regulatory
Administration Chapter 1 immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
When purchasing or using the State Fuel Gas 2006 code, please take note of the particular
printing edition. Errata to that printing edition is available on-line directly at no charge at
www.iccsafe.org/cs/codes/errata.html or call the office of the State Building Code Commissioner
at 401-222-3033 for further information.
Printed copies of the administrative and enforcement provisions of Title 23, Chapter 27.3 are
available at the Office of the State Building Code Commission or on-line at
www.rilim.state.ri.us/statutes/title23/23 27.3/index.htm.
The State Fuel Gas Code, 2006 Edition, is protected by the copyright that has been issued to the
ICC. As a result, the State Building Code is not available in complete form to the public in an
electronic format. The State Fuel Gas Code 2006 edition that is referred to within is contained
in a printed volume and is also in an electronic format that have been published by the ICC
under an exclusive license.
The Office of the State Building Code Commissioner has purchased volumes of these codes and
they shall be distributed to Rhode Island cities and towns during the month of June 2007 so that
local officials will have access to the code prior to the implementation of these rules on July 1,
2007.
In order to assure public access to this code the Office of the State Building Code Commissioner
shall provide a copy of this code to the Rhode Island State Library, which is located on the
second floor of the State House. In addition, all codes may be viewed during business hours at
the Department of Administration’s Library which is located on the fourth floor of the William
E. Powers Building, One Capitol Hill, Providence.
The Legislative Regulation Committee approved adoption of this code on July 10, 2007.
By:
John P. Leyden
Executive Secretary
Rhode Island Building Code Standards Committee
i
RISBC-19
THIS PAGE LEFT INTENTIONALLY BLANK
BUILDING CODE STANDARDS COMMITTEE
RISBC-19
CHAIRMAN
VICE CHAIRMAN
Dana Newbrook, RA
Stephen C. Turner, PE
Architect
Public Member
EXECUTIVE COMMITTEE
Allan Durand
Builders Trades Council
Robert M. Stillings
Architect
Bruce Davey, PE
Structural Engineer
Russell Brown
John Pagliaro
Building Official
Building Official
James R. Carlson, RA
David F. Palmisciano
Public Member
Building Trades Council
G. Thomas Chabot
Gordon W. Preiss, PE
Electrical Contractor
Mechanical Engineer
Randy Collins, Jr., RLA
Marie Stoeckel
Landscape Architect
Public Health Official
Robert E. DeBlios, Jr.
Builder
Builder
Vacant
Paul DePace, PE
Building Official
Representative for the Disabled
Vacant
Donald Gagnon
Electrical Inspector
Minimum Housing Inspector
Vacant
John D. Gaskell ,PE
Representative for the Disabled
Electrical Engineer
Vacant
Leonard P. Gemma
John P. Leyden
Master Plumber
Building Commissioner
Executive Secretary
William Howe
Legal Counsel
Fire Official
ii
RISBC-19
THIS PAGE LEFT INTENTIONALLY BLANK
STATE BUILDING CODE REGULATIONS – 2007
The following list includes all regulations promulgated by the State Building Code
Standards Committee. All regulations are available for a fee at the State Building
Commission.
1.
Building Code…………………………………………
SBC-1-2007
2.
One and Two Dwelling Family
Dwelling Code………………………………………...
SBC-2-2007
3.
Plumbing Code………………………………………..
SBC-3-2007
4.
Mechanical Code……………………………………...
SBC-4-2007
5.
Electrical Code………………………………………..
SBC-5-2006
6.
Reserved…………………………………………...….
SBC-6
7.
Reserved…………. …………………………………..
SBC-7
8. State Energy Code…………………………………….
SBC-8-2007
9. Enforcement and Implementation
Procedures for Projects Under
the Jurisdiction of the State
of Rhode Island……………………………………….
SBC-9
10. Code Interpretations…………………………………..
SBC-10
11. Certification of Building Officials,
Building, Electrical, Plumbing and
Mechanical Inspectors………………………………..
SBC-11-2002
12. New Materials and Methods
of Construction……………………………………….
SBC-12
13. State Building Code
For Existing Schools………………………………….
SBC-13
14.
Reserved
15. Reserved
16. Reserved
17. Public Buildings Accessibility
Meeting Standards…………………………………….
SBC-17
18. Native Lumber………………………………………...
SBC-18
19. Fuel Gas Code…………………………………………
SBC-19-2007
iii
THIS PAGE LEFT INTENTIONALLY BLANK
Format: These code changes follow numbering sequence and topics of the International
Fuel Gas Code 2006 ( first printing). All Provisions of IFGC 2006 are retained unless
indicated as deleted or revised. Published errata is available from the ICC website
dependent on this printing issue number and date.
Chapter 1
ADMINISTRATION
The following Rhode Island amendments are made to the sections of Chapter 1:
Delete IFG Code section 101.1 Title, and substitute the following:
101.1 Title. These regulations shall be known as The Rhode Island State Fuel Gas Code
Regulation SBC-19-2006 hereafter referred to as " this code"
Add the following new section 101.1.1 referenced codes.
101.1.1 Referenced Codes. The other codes referenced elsewhere in this code shall be
considered part of the requirements of this code to the prescribed extent of each such
reference.
1. Electrical. The provisions of Rhode Island State Electrical Code SBC-5-2006 shall
apply wherever referenced in this code as the ICC Electrical Code, and shall apply to the
installation of electrical systems, including alterations, repairs, replacement, equipment,
appliances, fixtures, fittings, and appurtenances thereto.
2. Mechanical. The provisions of the Rhode Island State Mechanical Code SBC-4-2006
shall apply wherever referenced in this code as the International Mechanical Code and
shall apply to the installation, alterations, repairs and replacement of mechanical systems,
including equipment, appliances, fixtures, fittings and/orappurtenances, including
ventilating, heating, cooling, air-conditioning and refrigeration systems, incinerators and
other energy-related systems.
3. Plumbing. The provisions of Rhode Island State Plumbing Code SBC-3-2006 shall
apply wherever referenced in this code as the International Plumbing Code, and shall
apply to the installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and appurtenances, and where
connected to a water or sewage system and all aspects of a medical gas system.
4.
Property Maintenance. Refer to state or local codes.
5.
Fire Prevention Code. Wherever and whenever provisions of the International
Fire Code 2003 editions are referenced, the appropriate Rhode Island Fire Safety Code
requirements shall apply.
1
6.
Energy Code. The provisions of the Rhode Island State Energy Conservation
Code SBC-8-2006 shall apply wherever referenced in this code as International
Energy Conservation Code, and shall apply to all matters governing the design
and construction of buildings for energy efficiency.
7.
Building Code. The provisions of the Rhode Island State Building Code SBC-1-
2006 shall apply wherever referenced in this code as the International Building
Code.
8.
Residential Code. The provisions of the Rhode Island One and Two Family
Dwelling Code SBC-2-2006 shall apply wherever referenced in this code as the
International Residential Code.
9.
Existing Building Code. The provisions of the State Building Codes SBC-1-2006
in conjunction with the State Rehabilitation Code SRC-1 and the Rhode Island
Fire Safety Code shall apply wherever referenced in this code as the International
Existing Building Code.
Any and all such references to the various International Code Council family of
code shall be substituted for the appropriate state code as indicated above.
101.2.4
Systems and equipment outside the scope.
Delete exception #9 and substitute the following:
9. Liquified Natural Gas (LNG) installations shall be installed in accordance
with this code and the Rhode Island Fire Safety Code.
Delete IFG Code section 101.3 and substitute the following:
101.3 Appendices. Provisions in the appendices are permitted to be used for
determining compliance to this code.
Delete IFG Code sections 103, 104, 106.4.3 through 106 .5.3 and 108 through 109.7.
2
CHAPTER 3
Section 303
Appliance Location
Add the following new exception:
303.3. 6 Gas fired appliances may be installed in loft or open efficiency type apartments
when there is a sleeping area not a sleeping room. The installation of appliances must
comply with section 304.5 for combustion air required volume and the manufacturers’
installation instructions.
3
THIS PAGE INTENTIONALLY LEFT BLANK
4
5
Chapter 4
401.2 Liquefied Petroleum Gas & Storage.
The storage system for liquefied petroleum gas shall be designed and installed in
accordance with NFPA 58 and the following.
401.2.1
For LNG facilities exceeding 1,000 gallons equivalent water capacity structural
engineering design by a licensed RI professional engineer shall include explicit analyses
of seismic, storm, and hurricane impacts including combined wind and storm surge
effects on tank, facility, dock and other associated structure and underlying foundation,
pilings, piers, footings or other associated supports or ground connections.
401.2.2
Spill leak, escape and other failure analyses shall include mapping of impacts on
surrounding existing structures and build able parcels to the distance determined by the
engineer of record to delimit potential flame or heat impacts that could potentially impact
tenability and structural stability of structures, whether adjacent to or beyond the LNG
facility site. Such impacts shall be with respect to worse-case spill or release scenarios,
not less than 14,000 cubic meters of LNG.
401.2.3
Site-specific analyses shall be performed of potential adverse impacts within the
distance determined by the engineer of record to delimit potential flame or heat impacts
on tenability or stability of all facilities that house occupants of reduced independent
mobility. Such occupancies include but are not limited to elderly housing, healthcare
facilities, schools, and daycare facilities.
401.2.4
The RI Building Code Board of Appeals shall review each application for such an
installation where it or its associated docking facilities are located on state land, coastal
land, state waters, or fill areas formerly part of state waters.
404.1 Delete 404.1 and substitute the following:
404.1 Prohibited locations. Piping shall not be installed in or through a
circulating air duct, clothes chute, chimney or gas vent, ventilating duct,
dumbwaiter or elevator shaft.