510-RICR-00-00-19
510-RICR-00-00-19. RISBC-19 Rhode Island Fuel Gas Code (version Amendment, 07/01/2013 to 07/01/2013)
RHODE ISLAND
STATE BUILDING CODE
SBC-19 State Fuel Gas Code
Replaces SBC-19-2010
Effective July 1, 2013
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS
Department of Administration
BUILDING CODE STANDARDS COMMITTEE
One Capitol Hill
Providence, RI 02908-5859
(401) 222-3033
FAX NO (401)-222-2599
www.ribcc.ri.gov
Regulation SBC-19
State Fuel Gas Code
The Building Code Standards Committee, in accordance with the rule making authority of Title
23, Chapter 23-27.3, Section 109.1, paragraphs a through c inclusive, has formally adopted and
promulgated as the Rhode Island State Building Code, the provisions of the International Fuel
Gas Code, 2012 edition, as published by the International Code Council, Inc. (I.C.C.), together
with amendments thereto hereinafter set forth to the articles and sections of this code:
The provisions of Title 23, Chapter 27.3 of the General Laws of Rhode Island establishing
administration and enforcement are hereby incorporated by reference. Regulatory Administration
Chapter 1 immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
When purchasing or using the International Fuel Gas 2012 code, please take note of the particular
printing edition. Errata to that printing edition is available on-line directly at no charge at
www.iccsafe.org/cs/codes/pages/errata.aspx or call the office of the State Building Code
Commissioner at 401-222-1129 for further information.
Printed copies of the administrative and enforcement provisions of Title 23, Chapter 27.3 are
available at the Office of the State Building Code Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM.
The State Fuel Gas Code, 2013 Edition, is protected by the copyright that has been issued to the
ICC. As a result, the State Building Code is not available in complete form to the public in an
electronic format. The State Fuel Gas Code 2013 edition that is referred to within is contained in
a printed volume and is also in an electronic format that have been published by the ICC under an
exclusive license.
The Office of the State Building Code Commissioner has purchased volumes of these codes and
they shall be distributed to Rhode Island cities and towns during the month of June 2013 so that
local officials will have access to the code prior to the implementation of these rules on July 1,
2013
In order to assure public access to this code the Office of the State Building Code Commissioner
shall provide a copy of this code to the Rhode Island State Library, which is located on the
second floor of the State House. In addition, all codes may be viewed during business hours at
the Department of Administration’s Library which is located on the fourth floor of the William E.
Powers Building, One Capitol Hill, Providence.
The Legislative Regulation Committee approved adoption of this code on July 1, 2013
By:
John P. Leyden
Executive Secretary
Rhode Island Building Code Standards Committee
STATE OF RHODE ISLAND
BUILDING CODE STANDARDS COMMITTEE
CHAIRMAN
VICE CHAIRMAN
William J. Nash, Jr.
Building Official
Bernard J. Bernard, III
Electrical Inspector
EXECUTIVE COMMITTEE
Michael A. Newman
Master Plumber
James Fink
Electrical Engineer
Doris Aschman
Public Health Official
Scott Caron
Fire Official
Michael Daley
Builders Trades Council
Stephen C. Turner, PE
Public Member
Peter Scorpio, III
Building Official
Dana Newbrook
Architect
James R. Carlson, RA
Public Member
Fred Sarno
Building Official
G. Thomas Chabot
Electrical Contractor
David F. Palmisciano
Building Trades Council
Randy Collins, Jr., RLA
Landscape Architect
Gordon W. Preiss, PE
Mechanical Engineer
Robert E. DeBlois, Jr.
Builder
Craig Sutton
Builder
Paul DePace, PE
Representative for the Disabled
Vacant
Representative for the Disabled
Robert M. Stillings
Architect
John P. Leyden, CBO
State Building Commissioner
Executive Secretary
Wayne Pimental
Minimum Housing Inspector
Thomas Coffey
Legal Counsel
STATE BUILDING CODE REGULATIONS - 2013
The following list includes all regulations promulgated by the State Building Code Standards Committee.
All regulations are available for a fee at the State Building Commission.
1.
Building Code
SBC-1-2013
2..
One and Two Family Dwelling Code
SBC-2-2013
3.
Plumbing Code
SBC-3-2013
4.
Mechanical Code
SBC-4-2013
5.
Electrical Code
SBC-5-2011
6.
Property Maintenance Code
SBC-6-2013
7.
Reserved
8.
Energy Conservation Code
SBC-8-2013
9
Enforcement and Implementation Procedures for
Projects Under the Jurisdiction of The State of
Rhode Island
SBC-9
10.
Code Interpretations
SBC-10
11.
Certification of Building Officials,
Building, Electrical, Plumbing and Mechanical
Inspectors
SBC-11-2010
12.
New Materials and Methods of Construction
SBC-12
13.
State Building Code for Existing Schools
SBC-13
14.
Reserved
15.
Reserved
16.
Reserved
17.
Public Buildings Accessibility Meeting Standards
SBC-17
18.
Native Lumber
SBC-18
19.
Fuel Gas Code
SBC-19-2013
20.
The State of Rhode Island Rehabilitation
Building and Fire Code for Existing Buildings
and Structures
SRC-1-2002
iii
Format: These code changes follow numbering sequence and topics of the International
Fuel Gas Code 2012 (first printing). All Provisions of IFGC 2012 are retained unless
indicated as deleted or revised. Published errata is available from the ICC website
dependent on this printing issue number and date.
Chapter 1
ADMINISTRATION
The following Rhode Island amendments are made to the sections of Chapter 1:
Delete IFG Code section 101.1 Title, and substitute the following:
101.1 Title. These regulations shall be known as The Rhode Island State Fuel Gas Code
Regulation SBC-19-2013 hereafter referred to as "this code"
Add the following new section 101.1.1 referenced codes.
101.1.1 Referenced Codes. The other codes referenced elsewhere in this code shall be
considered part of the requirements of this code to the prescribed extent of each such
reference.
1. Electrical. The provisions of Rhode Island State Electrical Code SBC-5-2011 shall
apply wherever referenced in this code as the ICC Electrical Code, and shall apply to the
installation of electrical systems, including alterations, repairs, replacement, equipment,
appliances, fixtures, fittings, and appurtenances thereto.
2. Mechanical. The provisions of the Rhode Island State Mechanical Code SBC-4-2013
shall apply wherever referenced in this code as the International Mechanical Code and
shall apply to the installation, alterations, repairs and replacement of mechanical systems,
including equipment, appliances, fixtures, fittings and/orappurtenances, including
ventilating, heating, cooling, air-conditioning and refrigeration systems, incinerators and
other energy-related systems.
3. Plumbing. The provisions of Rhode Island State Plumbing Code SBC-3-2013 shall
apply wherever referenced in this code as the International Plumbing Code, and shall
apply to the installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and appurtenances, and where
connected to a water or sewage system and all aspects of a medical gas system.
4. Property Maintenance. The provisions of the Rhode Island State Property
Maintenance Code SBC-6-2013 Provides requirements for continued use and
maintenance buildings and property, and of related plumbing, mechanical, electrical and
fire protection systems in existing residential and non-residential structures.
SBC-19 2013
1
5.
Fire Prevention Code. Wherever and whenever provisions of the International
Fire Code 2012 editions are referenced, the appropriate Rhode Island Fire Safety
Code requirements shall apply.
6.
Energy Code. The provisions of the Rhode Island State Energy Conservation
Code SBC-8-2013 shall apply wherever referenced in this code as International
Energy Conservation Code, and shall apply to all matters governing the design,
alteration and construction of buildings and systems for energy efficiency.
7.
Building Code. The provisions of the Rhode Island State Building Code SBC-1-
2013 shall apply wherever referenced in this code as the International Building
Code.
8.
Residential Code. The provisions of the Rhode Island One and Two Family
Dwelling Code SBC-2-2013 shall apply wherever referenced in this code as the
International Residential Code.
9.
Existing Building Code. The provisions of the State Building Codes SBC-1-2013
in conjunction with the State Rehabilitation Code SRC-1 and the Rhode Island
Fire Safety Code shall apply wherever referenced in this code as the International
Existing Building Code.
Any and all such references to the various International Code Council family of
code shall be substituted for the appropriate state code as indicated above.
101.2.4
Systems and equipment outside the scope.
Delete exception #9 and substitute the following:
9. Liquified Natural Gas (LNG) installations shall be installed in accordance
with this code and the Rhode Island Fire Safety Code.
Delete IFG Code section 101.3 and substitute the following:
101.3 Appendices. Provisions in the appendices are permitted to be used for
determining compliance to this code.
Delete IFG Code sections 103, through 106 and 108 through 109.
SBC-19 2013
2
CHAPTER 3
Section 303
Appliance Location
303.3 Add the following new exception:
(6)
Gas fired appliances may be installed in loft or open efficiency type apartments
when there is a sleeping area not a sleeping room. The installation of appliances must
comply with section 304.5 for combustion air required volume and the manufacturers’
installation instructions.
310.1.1 Delete and Substitute the following:
310.1.1 CSST CSST gas piping systems shall be bonded to the electrical service
grounding electrode system. The bonding jumper shall connect to a metallic pipe or
fitting between the point of delivery and the first downstream CSST fitting. The bonding
jumper shall be copper and not smaller than 6AWG. The bonding jumper shall not
exceed 40’ in length. CSST system with a conductive jacket deemed to be equivalent to
a direct bonded CSST system by an approved listing agency shall only be required to be
bonded in accordance with section Residential Code 2411.1 or Fuel Gas Code 310.1.
The installation of the bonding jumper shall be by an electrician with an electrical permit
and inspected by the electrical inspector.
Section 311
Temperature Control
311.1 Space-heating systems.
Interior spaces intended for human occupancy shall
be provided with active or passive space-heating systems capable of maintaining a
minimum indoor temperature of 68°F (20°C) at a point 3 feet (914 mm) above floor on
the design heating day. The installation of portable space heaters shall not be used to
achieve compliance with this section.
Exception: Interior spaces where the primary purpose is not associated with
human comfort.
SBC-19 2013
3
Chapter 4
401.2 Delete 401.2 and substitute the following:
401.2 Liquefied Petroleum Gas & Storage.
The storage system for liquefied petroleum gas shall be designed and installed in
accordance with NFPA 58 and the following.
401.2.1
For LNG facilities exceeding 1,000 gallons equivalent water capacity structural
engineering design by a licensed RI professional engineer shall include explicit analyses
of seismic, storm, and hurricane impacts including combined wind and storm surge
effects on tank, facility, dock and other associated structure and underlying foundation,
pilings, piers, footings or other associated supports or ground connections.
401.2.2
Spill leak, escape and other failure analyses shall include mapping of impacts on
surrounding existing structures and build able parcels to the distance determined by the
engineer of record to delimit potential flame or heat impacts that could potentially impact
tenability and structural stability of structures, whether adjacent to or beyond the LNG
facility site. Such impacts shall be with respect to worse-case spill or release scenarios,
not less than 14,000 cubic meters of LNG.
401.2.3
Site-specific analyses shall be performed of potential adverse impacts within the
distance determined by the engineer of record to delimit potential flame or heat impacts
on tenability or stability of all facilities that house occupants of reduced independent
mobility. Such occupancies include but are not limited to elderly housing, healthcare
facilities, schools, and daycare facilities.
401.2.4
The RI Building Code Board of Appeals shall review each application for such an
installation where it or its associated docking facilities are located on state land, coastal
land, state waters, or fill areas formerly part of state waters.
SBC-19 2013
4
SBC-19 2013
5
SECTION 404 (IFGC)
PIPING SYSTEM INSTALLATION
404.1 Installation of materials.
All materials used shall be installed in strict
accordance with the standards under which the materials are accepted and approved. In
the absence of such installation procedures, the manufacturer’s instructions shall be
followed. Where the requirements of referenced standards or manufacturer’s instructions
do not conform to minimum provisions of this code, the provisions of this code shall
apply.
404.2 CSST. CSST piping systems shall be installed in accordance with the terms of
their approval, the conditions of listing, the manufacturer’s instructions and this code.
The installation of the bonding jumper shall be by an electrician with an electrical permit
and inspected by the electrical inspector.
Chapter 6
M614.6.6
Delete and substitute the following:
M614.6.6 Length identification. The maximum length of dryer duct may exceed 35’
when a permanent placard, measuring a minimum 5” wide, 3” high, and 1/8” thick, and
constructed of either wood, metal, or rigid plastic, and bearing raised or embossed
lettering stating the following: “WARNING: THE EFFECTIVE LENGTH OF THIS
DRYER DUCT IS xxx FEET. ANY DRYER CONNECTED TO THIS EXHAUST
DUCT MUST BE RATED TO USE AN EXHAUST DUCT OF THIS LENGTH,
PER THE MANUFACTURERS SPECIFATIONS; SERVERE RISK OF FIRE
MAY RESULT FOR NONCOMPLIANCE WITH THIS NOTICE.”
The provisions of M102.4 shall be used in establishing the effective length of the
ductwork installed and noted on the placard. The placard shall be permanently attached
to the wall or floor within 6” of the terminus of the duct.
SBC-19 2013