510-RICR-00-00-19
510-RICR-00-00-19. RISBC-19 Rhode Island Fuel Gas Code (version Amendment, 08/01/2019 to 01/04/2022)
19.1 Authority
The Building Code Standards
Committee, in accordance with the rule making authority of R.I. Gen.
Laws §§ 23-27.3-109.1(a) through (c) inclusive, has
formally adopted and promulgated as the Rhode Island State Building
Code, the provisions of the International Fuel Gas Code, 2015
edition, as published by the International Code Council, Inc.
(I.C.C.), together with amendments thereto hereinafter set forth to
the articles and sections of this code:
19.2 Incorporated Materials
A. The provisions of R.I. Gen.
Laws Chapter 23-27.3 establishing administration and enforcement are
hereby incorporated by reference. § 19.3 of this Part (Chapter
1: Administration) immediately follows and is supplemental to the
General Laws. Editorial Note: Code users please note:
1. When purchasing or using
the International Fuel Gas Code 2015, please take note of the
particular printing edition. Errata to that printing edition is
available on-line directly at no charge at
www.iccsafe.org/cs/codes/pages/errata.aspx
or call the office of the State Building Code Commissioner at
401-889-5550 for further information.
2. Printed copies of the
administrative and enforcement provisions of R.I. Gen. Laws Chapter
23-27.3 are available at the Office of the State Building Code
Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM .
3. The International Fuel Gas
Code, 2015 Edition, is protected by the copyright that has been
issued to the ICC. As a result, the State Building Code is not
available in complete form to the public in an electronic format.
The International Fuel Gas Code, 2015 edition that is referred to
within is contained in a printed volume and is also in an electronic
format that have been published by the ICC under an exclusive
license.
B. Format: These code changes
follow numbering sequence and topics of the International Fuel Gas
Code 2015 (first printing). All Provisions of IFGC 2015 are retained
unless indicated as deleted or revised. Published errata is available
from the ICC website dependent on this printing issue number and
date.
19.3 Chapter
1: Administration
The following Rhode Island
amendments are made to the sections of Chapter 1:
Delete IFG Code section 101.1
Title, and substitute the following:
101.1 Title. These
regulations shall be known as The Rhode Island State Fuel Gas Code
Regulation SBC-19-2019 hereafter referred to as "this code"
Add the following new section
101.1.1 referenced codes.
101.1.1 Referenced Codes. The
other codes referenced elsewhere in this code shall be considered
part of the requirements of this code to the prescribed extent of
each such reference.
1) Electrical. The provisions
of Rhode Island State Electrical Code, SBC-5-2019 ( Part
5 of this Subchapter ), shall apply wherever referenced in this
code as the ICC Electrical Code, and shall apply to the installation
of electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings, and appurtenances thereto.
2) Mechanical. The provisions
of the Rhode Island State Mechanical Code,SBC-4-2019 ( Part
4 of this Subchapter ), shall apply wherever referenced in this
code as the International Mechanical Code and shall apply to the
installation, alterations, repairs and replacement of mechanical
systems, including equipment, appliances, fixtures, fittings and/or
appurtenances, including ventilating, heating, cooling,
air-conditioning and refrigeration systems, incinerators and other
energy-related systems.
3) Plumbing. The provisions of
Rhode Island State Plumbing Code,SBC-3-2019 ( Part
3 of this Subchapter ), shall apply wherever referenced in this
code as the International Plumbing Code, and shall apply to the
installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and
appurtenances, and where connected to a water or sewage system and
all aspects of a medical gas system.
4) Property Maintenance. The
provisions of the Rhode Island State Property Maintenance Code
SBC-6-2019 ( Part
6 of this Subchapter ), Provides requirements for continued use
and maintenance buildings and property, and of related plumbing,
mechanical, electrical and fire protection systems in existing
residential and non-residential structures.
5) Fire Prevention Code. The
provisions of or references to the International Fire Code 2019
edition shall be cross referenced to the appropriate section of the
Rhode Island Fire Code ( 450-RICR-00-00-1
through 10 ). The chapters referencing construction standards will
apply to either the Rhode Island Uniform Fire Code Standards, R.I.
Gen. Laws Chapter 23-28.01, as referenced and amended NFPA 1 and NFPA
101 and those standards will apply when this code references such a
section or requirement. These cross-references are not intended to
impose any enforcement requirements on state or local fire officials,
and any conflicts with the State Fire Safety Codes shall be resolved
in favor of the stricter standard, and that standard shall be
enforced by the appropriate designated authority having jurisdiction.
6) Energy Code. The provisions
of the Rhode Island State Energy Conservation Code SBC-8-2019, ( Part
8 of this Subchapter ), shall apply wherever referenced in this
code as International Energy Conservation Code, and shall apply to
all matters governing the design, alteration and construction of
buildings and systems for energy efficiency.
7) Building Code. The
provisions of the Rhode Island State Building Code,SBC-1-2019 ( Part
1 of this Subchapter ), shall apply wherever referenced in this
code as the International Building Code.
8) Residential Code. The
provisions of the Rhode Island One and Two-Family Dwelling
Code,SBC-2-2019 ( Part
2 of this Subchapter ), shall apply wherever referenced in this
code as the International Residential Code.
9) Existing Building Code. The
provisions of the State Building Codes,SBC-1-2019 ( Part
1 of this Subchapter ), in conjunction with the State
Rehabilitation Code, Part
20 of this Subchapter , and the Rhode Island Fire Safety Code
( 450-RICR-00-00-1
through 10 ) shall apply wherever referenced in this code as the
International Existing Building Code.
Any and all such references
to the various International Code Council family of code shall be
substituted for the appropriate state code as indicated above.
101.2.4 Systems and equipment
outside the scope.
Delete exception #9 and
substitute the following:
9. Liquefied Natural Gas
(LNG) installations shall be installed in accordance with this code
and the Rhode Island Fire Safety Code.
Delete IFG Code section 101.3
and substitute the following:
101.3 Appendices. Provisions
in the appendices are permitted to be used for determining compliance
to this code.
Delete IFG Code sections 103,
through 106 and 108 through 109.
19.4 Chapter 3
Section 303 Appliance Location
Add the following new
exception to 303.3:
(6) Gas fired appliances may
be installed in loft or open efficiency type apartments when there is
a sleeping area not a sleeping room. The installation of appliances
must comply with section 304.5 for combustion air required volume and
the manufacturers’ installation instructions.
Delete 305.10 and Substitute
the following:
305.10 (IFGS) Repair garages:
Appliances installed in repair garages shall be installed in a
detached building or room, separated from repair areas by walls or
partitions, floors, or floor-ceiling assemblies that are constructed
so as to prohibit the transmission of vapors and having a
fire-resistance rating of not less than 1 hour, and that have no
openings in the wall separating the repair area within 8 feet (2438
mm) of the floor. Wall penetrations shall be fire stopped. Air for
combustion purposes shall be obtained from the outdoors. The
appliance room shall not be used for the storage of combustible
materials.
Exceptions:
1. Overhead heaters where
installed not less than 8 feet (2438 mm) above the floor shall be
permitted.
2. Heating appliances for
vehicle repair areas where there is no dispensing or transferring of
Class I or II flammable or combustible liquids or liquefied petroleum
gas shall be installed in accordance with NFPA 30A.
Delete 307.6 in Rhode Island
Delete 310.1.1 and Substitute
the following:
310.1.1 CSST. CSST gas piping
systems shall be bonded to the electrical service grounding electrode
system. The bonding jumper shall connect to a metallic pipe or
fitting between the point of delivery and the first downstream CSST
fitting. The bonding jumper shall be copper and not smaller than
6AWG. The bonding jumper shall not exceed 40’ in length. CSST
system with a conductive jacket deemed to be equivalent to a direct
bonded CSST system by an approved listing agency shall only be
required to be bonded in accordance with section Residential Code
2411.1 or Fuel Gas Code 310.1. The installation of the bonding
jumper shall be by an electrician with an electrical permit and
inspected by the electrical inspector.
Delete 310.1.1.1 - 310.1.1.5:
in Rhode Island
Section 311 Temperature
Control
311.1 Space-heating systems.
Interior spaces intended for human occupancy shall be provided with
active or passive space-heating systems capable of maintaining a
minimum indoor temperature of 68°F (20°C) at point 3 feet
(914 mm) above floor on the design heating day. The installation of
portable space heaters shall not be used to achieve compliance with
this section.
Exception: Interior spaces
where the primary purpose is not associated with human comfort.
19.5 Chapter 4
Delete 401.2 and substitute
the following:
401.2 Liquefied Petroleum Gas
& Storage.
The storage system for
liquefied petroleum gas shall be designed and installed in accordance
with NFPA 58 and the following.
401.2.1
For LNG facilities exceeding
1,000 gallons equivalent water capacity structural engineering design
by a licensed RI professional engineer shall include explicit
analyses of seismic, storm, and hurricane impacts including combined
wind and storm surge effects on tank, facility, dock and other
associated structure and underlying foundation, pilings, piers,
footings or other associated supports or ground connections.
401.2.2
Spill leak, escape and other
failure analyses shall include mapping of impacts on surrounding
existing structures and build able parcels to the distance determined
by the engineer of record to delimit potential flame or heat impacts
that could potentially impact tenability and structural stability of
structures, whether adjacent to or beyond the LNG facility site. Such
impacts shall be with respect to worse-case spill or release
scenarios, not less than 14,000 cubic meters of LNG.
401.2.3
Site-specific analyses shall
be performed of potential adverse impacts within the distance
determined by the engineer of record to delimit potential flame or
heat impacts on tenability or stability of all facilities that house
occupants of reduced independent mobility. Such occupancies include
but are not limited to elderly housing, healthcare facilities,
schools, and daycare facilities.
401.2.4
The RI Building Code Board of
Appeals shall review each application for such an installation where
it or its associated docking facilities are located on state land,
coastal land, state waters, or fill areas formerly part of state
waters.
SECTION 404 (IFGC) PIPING
SYSTEM INSTALLATION
404.1
Installation of materials.
All materials used shall be installed in strict accordance with the
standards under which the materials are accepted and approved. In the
absence of such installation procedures, the manufacturer’s
instructions shall be followed. Where the requirements of referenced
standards or manufacturer’s instructions do not conform to
minimum provisions of this code, the provisions of this code shall
apply.
404.2 CSST.
CSST piping systems shall be
installed in accordance with the terms of their approval, the
conditions of listing, the manufacturer’s instructions and this
code. The installation of the bonding jumper shall be by an
electrician with an electrical permit and inspected by the electrical
inspector.
19.6 Chapter 6
Delete M614.8.5 and substitute
the following:
M614.8.5 Length
identification. The maximum length of dryer duct may exceed 35’
when a permanent placard, measuring a minimum 5” wide, 3”
high, and 1/8” thick, and constructed of either wood, metal, or
rigid plastic, and bearing raised or embossed lettering stating the
following: “WARNING: THE EFFECTIVE LENGTH OF THIS DRYER DUCT IS
xxx FEET. ANY DRYER CONNECTED TO THIS EXHAUST DUCT MUST BE RATED TO
USE AN EXHAUST DUCT OF THIS LENGTH, PER THE MANUFACTURERS
SPECIFICATIONS; SEVERE RISK OF FIRE MAY RESULT FOR NONCOMPLIANCE WITH
THIS NOTICE.”
The provisions of M102.4
shall be used in establishing the effective length of the ductwork
installed and noted on the placard. The placard shall be permanently
attached to the wall or floor within 6” of the terminus of the
duct.