510-RICR-00-00-1
510-RICR-00-00-1. RISBC-1 Rhode Island Building Code (version Amendment, 02/01/2022 to 12/01/2025)
1.1 Authority
The
Building Code Standards Committee, in accordance with the rulemaking
authority of R.I. Gen. Laws §§
23-27.3-109.3 (a) through (c) inclusive, has formally adopted and
promulgated as the Rhode Island State Building Code, the provisions
of the International Building Code (IBC), 2018 edition, as published
by the International Code Council, Inc. (ICC), together with
amendments thereto hereinafter set forth to the articles and sections
of this code:
1.2 Incorporated Materials
A. The provisions of R.I. Gen.
Laws Chapter 23-27.3 establishing administration and enforcement are
hereby incorporated by reference. Chapter 1: Administration
immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
1. When purchasing or using
the IBC 2018 code, please take note of the particular printing
edition. Errata to that printing edition is available online directly
at no charge at www.iccsafe.org/cs/codes/pages/errata.aspx
or call the office of the State Building Code Commissioner at
401-889-5550 for further information.
2. Printed copies of the
administrative and enforcement provisions of R.I. Gen. Laws Chapter
23-27.3 are available at the Office of the State Building Code
Commission or online at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM
3. The International Building
Code, 2018 Edition, is protected by the copyright that has been
issued to the ICC. As a result, the State Building Code is not
available in complete form to the public in an electronic format. The
International Building Code 2018 Edition that is referred to within
is contained in a printed volume and is also in an electronic format
that have been published by the ICC under an exclusive license.
1.3 Chapter 1: Administration
Delete
IBC sections 101.1 Title, 101.2 Scope and 101.2.1 Appendices and
substitute the following:
101.1 Title
This Regulation shall be
known as SBC-1-2021, the Rhode Island State Building Code,
hereinafter referred to as “this code.”
101.2
Scope
The provisions of this code
shall apply to the construction, alteration, movement, enlargement,
replacement, repair, equipment, use and occupancy, location,
maintenance, removal and demolition of every building or structure or
any appurtenances connected or attached to such buildings or
structures.
Exceptions:
1. Detached one (1) and two(2)
family dwellings and multiple single-family dwellings (town houses)
not more than three (3) stories above grade plane in height with a
separate means of egress and their accessory structures shall comply
with the SBC-2-2021, The Rhode Island One and Two-Family Dwelling
Code.
2. Existing buildings
undergoing repair, alterations or additions and changes of occupancy
shall comply with the provisions of this code or the State
Rehabilitation Code SRC-1-2002, Part 20
of this Subchapter (see R.I. Gen. Laws § 23-27.3-106.0).
101.2.1 Appendices
Delete appendices A, B, D, J,
and K. Appendices C, E, F, G, H, I apply.
Delete
IBC sections 101.4, and 101.4.1 through 101.4.7 Referenced Codes in
its entirety and substitute the following:
101.4
Referenced Codes.
The other codes listed in
Sections 101.4.1 through 101.4.7 and referenced elsewhere in this
code shall be considered part of the requirements of this code to the
prescribed extent of each such reference.
101.4.1 Electrical.
The provisions of Rhode
Island Electrical Code SBC-5-2021 (Part 5
of this Subchapter) shall apply wherever referenced in this code as
the ICC Electrical Code, and shall apply to the installation of
electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings and appurtenances thereto.
101.4.2 Gas.
The provisions of the Rhode
Island Fuel Gas Code SBC-19-2021 (Part 19
of this Subchapter) shall apply wherever referenced in this code as
the International Fuel Gas Code and shall apply to the installation
of gas piping from the point of delivery, gas appliances and related
accessories as covered in this code. These requirements apply to gas
piping systems extending from the point of delivery to the inlet
connections of appliances and the installation and operation of
residential and commercial gas appliances and related accessories.
101.4.3 Mechanical.
The provisions of the Rhode
Island Mechanical Code SBC-4-2021 (Part 4
of this Subchapter) shall apply wherever referenced in this code as
the International Mechanical Code and shall apply to the
installation, alterations, repairs and replacement of mechanical
systems, including equipment, appliances, fixtures, fittings and/or
appurtenances, including ventilating, heating, cooling,
air-conditioning and refrigeration systems, incinerators and other
energy-related systems.
101.4.4 Plumbing.
The provisions of Rhode
Island Plumbing Code SBC-3-2021 (Part 3
of this Subchapter) shall apply wherever referenced in this code as
the International Plumbing Code, and shall apply to the installation,
alteration, repair and replacement of plumbing systems, including
equipment, appliances, fixtures, fittings and appurtenances, and
where connected to a water or sewage system and all aspects of a
medical gas system.
101.4.5 Property Maintenance.
The provisions of the Rhode
Island State Property Maintenance Code SBC-6-2021 (Part 6
of this Subchapter) Provides requirements for continued use and
maintenance buildings and property, and of related plumbing,
mechanical, electrical and fire protection systems in existing
residential and non-residential structures.
101.4.6 Fire Prevention Code.
The provisions of or
references to the International Fire Code 2021 edition shall be cross
referenced to the appropriate section of the Rhode Island Fire Code
( 450-RICR-00-00-1
through 10 ). The Chapters referencing construction standards will
apply to either the Rhode Island Uniform Fire Code Standards {R.I.
Gen. Laws § 23-28.01 et seq. } as referenced and amended
NFPA 1 and NFPA 101 and those standards will apply when this code
references such a section or requirement. These cross-references are
not intended to impose any enforcement requirements on State or local
fire officials, and any conflicts with the State Fire Safety Codes
shall be resolved in favor of the more, restrictive standard, and
that standard shall be enforced by the appropriate designated
authority having jurisdiction.
101.4.7 Energy.
The provisions of the Rhode
Island Energy Code SBC-8-2021 (Part 8
of this Subchapter) shall apply wherever referenced in this code as
International Energy Conservation Code and shall apply to all matters
governing the design and construction of buildings for energy
efficiency.
Any and all such references
to the various International Code Council family of codes shall be
substituted for the appropriate state code as indicated above.
101.4.8 Swimming Pool and Spa
Code
The Provisions of the Rhode
Island Swimming Pool and Spa Code SBC-14-2021 (Part 14
of this Subchapter) shall apply whenever the International Swimming
Pool and Spa Code is referenced in this code and shall apply to
matters governing the design and construction of swimming pools and
spas.
Delete IBC sections:
103,
104.1 to 104.8, 105.3, 105.3.1, 105.3.2, 105.5, 107.1, 107.3.1,
107.3.2, 107.3.4, 107.3.4.1, 108.2, 111.4, 113.1, 113.2, 113.3,
114.1, 114.2, 114.3, 115.1, 115.2, 115.3, 116.1, 116.2, 116.3, 116.4,
116.5.
All
other Administrative provisions shall remain in effect. To the extent
that there is an apparent conflict between the provisions of these
administrative sections and R.I. Gen. Laws Chapter 23-27.3, the
provisions of State law shall prevail. Where other provisions of this
code refer to provisions of Chapter 1 Administration, or R.I. Gen.
Laws Chapter 23-27.3 shall apply as appropriate.
1.4 Chapter 2: Definitions
Add the following definitions:
"Commissioner"
means the State Building Code Commissioner, the Building Official
responsible to enforce this code in accordance with the provisions of
R.I. Gen. Laws § 23-27.3-108.2.
"Committee" means
the Rhode Island Building Code Standards Committee
"Nightclub" means
an assembly occupancy in which people congregate in high densities
for social entertainment such as drinking and dancing and
characterized by some or all of the following unique characteristics:
1. Low lighting levels
2. Entertainment by a live
band or recorded music generating above-normal sounds
3. Later-than average
operating hours
4. Tables and seating (if any)
arranged or positioned so as to create ill-definable aisles
5. Flexible fuel loading
6. A specific area designated
for dancing
7. Service facilities for
alcoholic beverages and food
8. Potential for consumption
of legal or illegal drug use contributing to delayed reaction time to
emergency events
9. High occupant load density
10. Movable furnishings
The Building Official shall
have the authority to determine whether a proposed use is deemed a
nightclub or a restaurant (see also section 903.2.1.2).
1.5 Chapter 3: Use and Occupancy
Classification
Delete IBC section 305.2 Day
Care and substitute the following:
305.2 Day Care.
The use of a building or
structure, or portion thereof, for educational, supervision or
personal care services for more than eight children older than two
and one half (2-1/2) years of age, shall be classified as a Group E
occupancy.
305.2.2 Eight or fewer
children. A facility having eight (8) or fewer children receiving
such day care shall be classified as part of the primary occupancy.
305.2.3 Eight or fewer
children in a dwelling unit. A facility such as the above within a
dwelling unit and having eight (8) or fewer children receiving such
day care shall be classified as a Group R-3 occupancy or shall comply
with the International Residential Code.
Delete IBC sections 308.2
Group I-1 and substitute the following:
308.2 Group I-1.
This occupancy shall include
buildings, structures, or parts thereof housing more than sixteen
(16) persons, on a twenty-four (24) hours basis, who because of age,
mental disability or other reasons, live in a supervised residential
environment that provides personal care services. The occupants are
capable of responding to an emergency situation without physical
assistance from staff. This group shall include, but not be limited
to, the following:
1. Residential board and
custodial care facilities
2. Assisted living facilities
3. Halfway houses
4. Group homes
5. Congregate care facilities
6. Social rehabilitation
facilities
7. Alcohol and drug centers
8. Convalescent facilities
A facility such as the above
with eight (8) or fewer persons shall comply with the International
Residential Code in accordance with section 101.2. A facility such as
above, housing at least nine (9) and not more than sixteen (16)
persons, shall be classified as Group R-4.
308..2.4 Eight or fewer
persons receiving care. A facility such as the above with eight (8)
or fewer persons receiving such care shall be classified as Group R-3
or shall comply with the International Residential Code provided an
automatic sprinkler system is installed in accordance with section
903.3.1.3 or with section P2904 of the International Residential
Code.
308.2.3 Eight to sixteen
persons receiving care. A facility such as above, housing not fewer
than eight (8) and not more than sixteen (16) persons receiving such
care, shall be classified as Group R-4.
Delete IBC section 308.3 Group
I-2 and substitute the following:
308. 3 Group I-2.
This occupancy shall include
buildings and structures used for medical, surgical, psychiatric,
nursing or custodial care on a twenty-four (24) hour basis of more
than eight (8) persons who are not capable of self-preservation. This
group shall include, but not be limited to, the following:
1. Child Care Facilities
2. Hospitals
3. Nursing homes (both
intermediate-care facilities and skilled nursing facilities)
4. Mental hospitals
5. Detoxification facilities
A facility such as the above
with six (6) to eight (8) persons shall be classified as a Use Group
R-4.
A facility such as the above
with five (5) or fewer persons shall comply with the International
Residential Code in accordance with section 101.2.
308.3.2 Eight or fewer
persons receiving care. A facility such as the above with eight (8)
or fewer persons receiving such care shall be classified as Group R-3
or shall comply with the International Residential Code provided an
automatic sprinkler system is installed in accordance with section
903.3.1.3 or with section P2904 of the International Residential
Code.
Delete IBC section 308.4.3
Child Care Facility and substitute the following:
308.4.3 Child Care Facility
Facility that provides care
on a twenty-four (24) hour basis to more than eight (8) children two
and one half (2 ½) years of age or less.
Detoxification Facilities
Facilities that serve
patients who are provided treatment for substance abuse on a
twenty-four (24) hour basis and who are incapable of
self-preservation or who are harmful to themselves or others.
Hospitals and Mental Hospitals
Buildings or portions thereof
used on a twenty-four (24) hour basis for the medical, psychiatric,
obstetrical or surgical treatment of inpatients who are incapable of
self-preservation.
Nursing Homes
Nursing homes are long-term
care facilities on a twenty-four (24) hour basis, including both
intermediate care facilities and skilled nursing facilities, serving
more than five (5) persons and any of the persons are incapable of
self-preservation.
Delete IBC section 308.5 I-4
Day Care Facilities and substitute the following:
308.6 Group I-4, Day Care
Facilities.
This group shall include
buildings and structures occupied by persons of any age who receive
custodial care for less than twenty-four (24) hours by individuals
other than parents or guardians, relatives by blood marriage or
adoption and in a place other than the home of the person cared for.
A facility such as the above with eight (8) or fewer persons shall be
classified as a Group R-3 or shall comply with International
Residential Code in accordance with section 101.2. Places of worship
during religious functions are not included.
Delete IBC Section 308.5.2
Child Care Facility and substitute the following:
308..5 Child Day Care Facility
A facility that provides
supervision and personal care on less than a twenty-four (24) hour
basis for more than eight (8) children two and one half (2-1/2) years
of age or less shall be classified as Group I-4.
Exception: A child day care
facility that provides care for more than eight (8) but no more than
one hundred (100) children two and one half (2-1/2) years or less of
age, when the rooms where such children are cared for are located on
the level of exit discharge and each of these child care rooms has an
exit door directly to the exterior, shall be classified as Group E.
308..5.1 Classification as
Group E. A child day care facility that provides care for more than
eight (8) but no more than one hundred (100) children two and one
half (2½) years or less of age, where the rooms in which the
children are cared for are located on a level of exit discharge
serving such rooms and each of these child care rooms has an exit
door directly to the exterior, shall be classified as Group E.
308.5.3 Eight or fewer
persons receiving care. A facility having eight (8) or fewer persons
receiving custodial care shall be classified as part of the primary
occupancy.
308.5.4 Eight or fewer
persons receiving care in a dwelling unit. A facility such as the
above within a dwelling unit and having eight (8) or fewer persons
receiving custodial care shall be classified as a Group R-3 occupancy
or shall comply with the International Residential Code.
Delete
IBC section 310.4 Residential Group R-3 and 310.5 R-4 and substitute
the following:
310.4 R-3 Residential
occupancies where the occupants are primarily permanent in nature and
not classified as R-1, R-2, R-4 or I and where buildings do not
contain more than two dwelling units as applicable in section 101.2,
or adult and child care facilities that provide accommodations for
eight (8) or fewer persons of any age for less than twenty-four (24)
hours. Adult and child care facilities that are within a
single-family home are permitted to comply with the International
Residential Code in accordance with section 101.2.
310.5 R-4 Residential
occupancies shall include buildings arranged for occupancy as
residential care/assisted living facilities including more than eight
(8) but not more than sixteen (16) occupants, excluding staff.
Group R-4 occupancies shall
meet the requirements for construction as defined for Group R-3
except as otherwise provided for in this code or shall comply with
the International Residential Code in accordance with section 101.2.
Group R-4 occupancies shall
meet the requirements for construction as defined for Group R-3
except as otherwise provided for in this code or shall comply with
the International Residential Code in accordance with section 101.2.
Delete
IBC section 310.2 Definition of Residential Care/Assisted Living
Facilities and substitute the following: 310.1.1 Definition
RESIDENTIAL CARE/ASSISTED
LIVING FACILITIES.
A building or part thereof
housing a maximum of sixteen (16) persons, on a twenty-four (24) hour
basis, who because of age, mental disability or other reasons live in
a supervised residential environment which provides personal care
services. The occupants are capable of responding to an emergency
situation without physical assistance from staff. This classification
shall include, but not be limited to, the following: residential
board and care facilities, assisted living facilities, halfway
houses, group homes, congregate care facilities, social
rehabilitation facilities, alcohol and drug abuse centers and
convalescent facilities. Residential care/assisted living facilities
housing more than sixteen (16) persons shall be classified as a Group
I-1.
1.6 Chapter 4
Add the following sections to
IBC section 401 Scope:
401.2 Fire Alarm Systems.
The requirements herein
prescribed for the design, operation and installation of fire alarm
systems, detection devices, suppression systems, communications
systems, etc. shall be construed as supplemental to any applicable
provisions of Rhode Island State Fire Safety Code ( 450-RICR-00-00-1
through 10 ).
401.3 Fire Prevention Code.
The provisions of the
International Fire Code 2019 Edition shall apply when this code
directly references a section or requirement. These cross-references
are not intended to impose any enforcement requirements on State and
local fire officials, and any conflicts with the State Fire Safety
Codes shall be resolved in favor of the stricter standard, and that
standard shall be enforced by the appropriate designated authority
having jurisdiction.
Add the following new
sections:
IBC section 429 Manufactured
Homes
429.1 Manufactured Homes.
Manufactured homes are
constructed in accordance with the Federal Department of Housing and
Urban Development Part 3280 Manufactured Home Construction and Safety
Standards. Refer to Appendix E of SBC2-2021 the Rhode Island One and
Two-Family Dwelling Code (Part 2
of this Subchapter) for specific provisions regarding permitting,
foundation systems, additions, site utility connections and
foundation and anchorage details.
IBC section 430 Modular
Construction
430.1 Modular Construction.
Buildings and structures
partially or completely constructed off-site shall be constructed in
conformance with this code or SBC-2-2021 the Rhode Island Residential
One and Two-Family Code (Part 2
of this Subchapter) as appropriate for the use and occupancy.
Manufacturers shall be registered with the Interstate Industrialized
Building Commission (IIBC) and submit for approvals and permits in
accordance with R.I. Gen. Laws Chapter 23-27.4 and IIBC Compact
Regulations.
1.7 Chapter 7
Reserved
1.8 Chapter 9: Fire Protection
System
Add the following section to
IBC section 901 General.
901.8 Other Codes.
Provisions governing where
fire protection systems are required are also contained in the Rhode
Island Fire Safety Code. The most restrictive provision of each code
shall apply.
Delete IBC section 903.2.1.2
Group A-2 and substitute the following:
903.2.1.2 Group A-2.
An automatic sprinkler system
shall be provided for Group A-2 occupancies where one (1) of the
following conditions exists:
1. The fire area exceeds five
thousand (5,000) square feet (464.5m 2 )
2. The fire area has an
occupant load of three hundred (300) or more.
3. The fire area is located on
a floor other than the level of exit discharge.
4. Nightclubs with an
occupancy load in a single fire area of more than one hundred fifty
(150) occupants (see also § 1.4 of this Part).
Delete IBC section 903.2.3
Group E and substitute the following:
[F] 903.2.3 Group E.
An automatic sprinkler system
shall be provided for Group E occupancies as follows:
1. Throughout all Group E fire
areas greater than twenty thousand (20,000) square feet (1115 m 2 )
in area.
2. Throughout every portion of
educational buildings below the lowest level of exit discharge
serving that portion of the building.
Exception: An automatic
sprinkler system is not required in any area below the lowest level
of exit discharge serving that area where every classroom throughout
the building has at least one (1) exterior exit door at ground level.
IBC section 903.3.1.1.1 Exempt
Locations 1-4. Add the following paragraph five (5)
5. In passenger elevator
shafts, pits and mechanical rooms. If provided, the installation
shall meet all requirements of this code, NFPA 13, the Rhode Island
Fire Safety Code ( 450-RICR-00-00-1
through 10 ) and the Rhode Island Elevator Code
( 260-RICR-30-10-1 ).
Delete IBC section 906 in its
entirety and substitute the following:
IBC section 906 Portable Fire
Extinguishers
906.1 General.
Portable Fire Extinguishers
shall be provided in accordance with the Rhode Island Uniform Fire
Code.
Delete IBC section 907 in its
entirety and substitute the following:
IBC section 907 Fire Alarm and
Detection Systems
907.1 General.
FIRE ALARM AND DETECTION
SYSTEMS shall be provided in accordance with the Rhode Island Uniform
Fire Code.
Delete
section 915 and substitute the following
Section 915 Carbon Monoxide
Detection
915.1 FIRE ALARM AND
DETECTION SYSTEMS shall be provided in accordance with the Rhode
Island Uniform Fire Code.
1.9 Chapter 10: Means of Egress
Delete IBC section 1010.1.4.4
and substitute the following:
1010.1.4.4 Locking
Arrangements in Educational Occupancies
In group E and Group B
educational occupancies egress doors in classrooms, offices and other
occupied rooms shall be permitted to be provided with locking
arrangements designed to keep intruders from entering the room where
such arrangements are in full compliance with the Rhode Island Fire
Code.
1.10 Chapter 11: Accessibility
Add the following definition
to IBC section 1102.1.
CHILDREN:
Students in classes ranging
from pre-kindergarten to sixth (6 th ) grade. All other
students are considered adults for the purposes of this Chapter.
Add the following section 1112
Children’s’ Features
Section 1112.0 Children’s
Features
1112.1 Children’s Water
Closets:
Where provided, at least one
(1) shall comply with the following:
1. Clear floor space: Clear
floor space for water closets shall comply with ICC/ANSI
A117.1-2009-604.3.1. Clear floor space shall be permitted to be
arranged to allow either a left-handed or right-handed approach.
2. Location: The centerline of
the water closet shall be located eleven inches (11”) (11”
= 279 mm) from the nearest side wall for pre-kindergarten; eleven to
fifteen inches (11” to 15”) (11” to 15” = 279
mm to 381 mm) for kindergarten to the third (3 rd ) grade
and fifteen to eighteen inches (15” to 18”) (15” to
18” = 381 mm to 457 mm) for fourth (4 th ) grade to
sixth (6 th ) grade. The water closet shall also be located
forty-two inches (42”) (42” = 1067mm) from the centerline
of the water closet to the opposite wall or closest edge of next
fixture.
3. Height: Water closets shall
be set at a height measured from the floor to the top of the seat as
follows:
Pre-kindergarten:
11-1/2” to 12-1/2”
(292mm to 318mm)
Kindergarten
to third grade:
12”
to 15” (305mm to 381mm)
Fourth
grade to sixth grade:
15”
to 17” (381mm to 343mm)
4. Flush Controls: Controls
for flush valves on water closets used by children shall be mounted
on the wide side of water closet within twenty to thirty inches (20”
to 30”) (20” to 30” = 508 mm to 762 mm) above the
floor.
5. Toilet paper dispensers:
Toilet paper dispensers used by children shall be centered above
finished floor, as follows:
Pre-kindergarten:
14” (356mm)
Kindergarten to third
grade:
14” to 17”
(356mm to 432mm)
Fourth grade to sixth
grade:
17” to 19”
(432mm to 483 mm)
1112.2 Children’s Grab
Bars
1112.2.1
The water closet shall have
two grab bars, forty-two inches (42”) (42” = 1067 mm)
long, one mounted on the wall in back of the water closet and one on
the side wall closest to the water closet and located no more than
six inches (6”) (6” = 152 mm) from the interior corner
where a tank prevents location of the rear grab bar, a bar may be
installed three inches (3”) (3” = 76 mm) above the tank.
Where a flushometer prevents the location of a forty-two inch (42”)
(42” = 1067 mm) rear grab bar, one grab bar, thirty-six inches
(36”) (36” = 914 mm) shall be installed to the side of
the flushometer, located three inches (3”) (3” = 76 mm)
from the closest edge of the flushometer.
1112.2.2 Height:
A grab bar shall be mounted
from the floor to the top of the grab bar as follows:
Pre-kindergarten:
18” to 20”
(457mm to 508mm)
Kindergarten to third
grade:
20” to 25”
(508mm to 635mm)
Fourth grade to sixth
grade:
25” to 27”
(635mm to 686mm)
1112.2.3 Thickness:
The outside diameter of grab
bars shall be as follows:
Pre-kindergarten:
1” (25mm)
Kindergarten to sixth
grade:
1-1/4” to 1-1/2”
(32mm to 38mm)
1112.3 Children’s Sink
Where provided at least one
(1) sink including vanities shall comply with the following:
1112.3.1 Clear floor space:
A clear floor space complying
with ICC/ANSI A117.1-2009-606.2 be provided in front of a sink to
allow a forward approach. The clear floor space shall be on an
accessible route and shall extend no more than a maximum of nineteen
inches (19”)(19” = 483 mm) underneath the sink.
1112.3.2 Height:
Sinks shall be mounted with
the rim no higher than thirty inches (30”) (30” = 762 mm)
above the finish floor. A clearance of at least twenty-five inches
(25”) (25” = 635 mm) above the finish floor to the bottom
of the apron shall be provided. Knee and toe clearance shall be at
least thirty inches (30”) (30” = 762 mm) wide and
nineteen inches (19”) (19” = 483 mm) deep.
1112.3.3 Piping:
Sink traps and drains shall
be located as close to rear walls as possible. Hot water and
drainpipes exposed under sinks shall be recessed, insulated, or
guarded. There shall be no sharp or abrasive surfaces under sinks.
1112.3.4 Faucets:
Faucets shall be operable
with one hand and shall not require tight grasping, pinching, or
twisting of the wrist. Lever-operated push-type, touch-type, or
electronically controlled mechanisms are acceptable designs. If
self-closing valves are used, the faucet shall remain open for at
least ten (10) seconds.
1112.4 Children’s
Urinals
1112.4.1 Urinals:
Where one (1) or more urinal
is provided, at least one (1) urinal shall be accessible.
1112.4.2 Height:
The accessible urinal shall
be stall-type or wall-hung with an elongated rim at a maximum of
fifteen inches (15”) (15” = 381 mm) above the finish
floor.
1112.4.3 Flush Controls:
Flush controls shall be a
hand operated or automatic and shall be mounted no more than thirty
inches (30”) (30” = 762 mm) above the flush floor.
1112.5 Children’s
Mirror.
The top of any shelf and or
bottom of any mirror which is provided above a sink shall be set with
the bottom edge of the reflecting surface no higher than thirty-one
inches (31”) (31” = 787 mm) above the finish floor.
Children’s Dispensers:
Towel dispensers, drying
devices, or other types of devices and dispensers shall have at least
one of each device mounted within the zone of reach, and at least one
(1) of each device shall be located within reach of a person using
the accessible sink.
1112.7 Children’s
Controls and Receptacles.
If controls, receptacles, or
other equipment are provided, then at least one (1) of each shall be
mounted no higher than thirty-six inches (36”) (36” = 914
mm) above the floor to the centerline of the operable portion of the
control.
1.11 Chapter 13: Energy Efficiency
Delete in its entirety and
substitute the following:
1301.1 Scope.
This
Chapter governs the design and construction of buildings for energy
efficiency.
1301. Criteria.
Buildings
shall be designed in accordance with the Rhode Island Energy Code SBC
8-2021 (Part 8
of this Subchapter).
1.12 Chapter 14: Exterior Walls
Add the following new
subsection to IBC section 1404.1 General:
1404.1.1 Re-siding Exterior
Walls.
Materials and methods of
application used for re-siding or replacing an existing wall covering
shall comply with the requirements of this section. New Exterior side
wall covering shall not be installed without first removing existing
wall coverings when any of the following conditions occur:
1. When the existing wall or
wall covering is water-soaked or has deteriorated to the point that
the existing wall or wall covering is not acceptable as a base for
additional covering.
2. When the existing wall has
three (3) or more applications of any wall covering.
Exception: The total number
of wall coverings shall not be limited when any of the existing wall
coverings consists of asbestos cement board or asbestos cement
shingles or any protective encapsulating or protective siding/layer
immediately over the asbestos material.
3. Asbestos cement board or
asbestos cement shingles and any protective encapsulating layer
thereupon shall not be required to be removed unless the existing
wall is unacceptable for use as a base for additional layers of wall
covering.
4. Any disturbance, repair or
removal of existing asbestos cement board or asbestos cement shingles
shall be in accordance with all State and Federal Regulations.
Delete IBC section 1406.3
exceptions 3 and 4 and substitute as follows:
1406.3 Balconies and similar
projections.
Balconies and similar
projections of combustible construction, other than
fire-retardant-treated wood, shall afford the fire-resistance rating
required by Table 601 for floor construction or shall be of Type IV
construction as described in section 602.4, and the aggregate length
shall not exceed fifty percent (50%) of the building perimeter on
each floor.
Exceptions:
1. On buildings of Types I and
II construction, three (3) stories or less in height,
fire-retardant-treated wood shall be permitted for balconies,
porches, decks, and exterior stairways not used as required exits.
2. Untreated wood is permitted
for pickets and rails, or similar guardrail devices that are limited
to forty-two inches (42”) (42” = 1067 mm) in height.
3. Construction Types 3A and
5A are not required to meet the provisions of this section.
4. If the balcony is subject
to deterioration as specified in section 2304.11.5, the provisions of
2304.11.2 shall prevail in lieu of this section’s fire
resistance requirements for Types 3, 4 and 5 constructions.
1.13 Chapter 15: Roof Assemblies
and Rooftop Structures
Delete IBC section 1507.2.6
attachment and substitute the following:
1507.2.6 Attachment.
Asphalt strip shingles shall
have a minimum of six (6) fasteners per shingle strip.
Exceptions:
1. Where the roof slope
exceeds twenty (20) units vertical in twelve (12) units horizontal
(20:12), special fastening details may be required by the
manufacturer.
2. Fastening systems tested by
the manufacturer to one hundred ten (110) MPH shall be permitted to
be installed in any wind zone.
1.14 Chapter 16: Structural
Delete IBC section 1608.1
General and substitute the following:
1608.1 General.
Design snow loads shall be
determined in accordance with section 7 of ASCE 7 using the ground
snow load values determined by Table 1608.1, but the minimum flat
roof snow load shall be not less than that determined by Table
1608.1. The design roof load shall not be less than that determined
by section 1607.
Delete IBC section 1608.2
Ground Snow Load.
Add the following to IBC
section 1608 Snow Loads.
1608.2 Structural Loads.
When a new building is to be
constructed or an existing building extended to a greater height than
an existing adjoining building, a determination of structural
integrity of the roof of the adjoining building shall be made
regarding the snow loads in accordance with section 1608.0 SNOW
LOADS. The person intending to cause the construction or building
height extension shall deliver written notice of intent to the owner
of the potentially affected building. The notice shall request
license to enter the potentially affected building to inspect and
determine the existing building's capacity to sustain additional
imposed snow drift load. The person causing such construction shall
be liable and shall at their own expense preserve, protect and, if
necessary, reconstruct those portions of the adjacent building
affected by this construction. If the owner of the adjacent building
refuses to allow inspection, protection or reconstruction as may be
required, the person causing such new construction or building height
extension shall notify, in writing, both the Building Official and
the owner of the adjacent property. Such notification shall identify
that the responsibility of providing inspection, protection or
reconstruction to the adjacent building has become the exclusive
responsibility of the owner of the adjacent property.
1609.3 Basic Wind Speed.
The basic wind speed, in mph,
shall be determined by Table 1608.1.
Delete
all IBC Figures 1609 and substitute Rhode Island Wind Speed Map
Figure 1609 and Figure 1609 (A), and Rhode Island frost protection
Figure 1609 (B)
TABLE
1608.1
Basic
Wind Speed, V (mph)
Seismic
Coefficients
Municipality
Ground
Snow Load, Pg (psf
Minimum
Flat Roof Snow Load, Pf (psf)
Risk
Category I
Risk
Category II
Risk
Category III
Frost
Depth
From
fig 1609.3(4)
From
fig 1609.3(1)
From
fig 1609.3(2)
Ss
S1
Barrington
30
30
117
127
135/139
XWB2-WB1
0.175
0.061
3' ‐ 4"
Bristol
30
30
118
128
137/140
WB1/WB2
0.174
0.060
3' ‐ 4"
Burrillville
40
30
111
121
130/135
XWB1
0.175
0.063
4' ‐ 6"
Central
Falls
30
30
114
124
XWB1
133/137
XWB2-WB1
0.178
0.062
4' ‐ 0"
Charlestown
30
30
121
131
WB1
140/143
WB2
0.158
0.057
3' ‐ 4"
Coventry
35
30
116
126
134/138
WB1/WB1
0.171
0.061
4' ‐ 0"
Cranston
(West of 295)
35
30
116
126
XWB1
134/138
XWB2
WB1/WB1
0.174
0.061
4' ‐ 0"
Cranston
(East of 295)
30
30
116
126
XWB1
134/138
XWB2
WB1/WB1
0.178
0.063
4’-6”
Cumberland
40
30
116
123
XWb1
131/136
XWB2
WB1/WB1
0.178
0.063
4' ‐ 6"
East
Greenwich
30
30
118
128
XWB1
136/140
XWB2-WB1/WB2
0.172
0.060
3' ‐ 4"
East
Providence
30
30
115
126
XWB1
134/138
XWB2
WB1/WB1
0.177
0.061
3' ‐ 4"
Exeter
35
30
118
128
WB1
137140
XWB2
WB1/WB2
0.168
0.059
4' ‐ 0"
Foster
40
30
112
123
XWB1
131/135
XWB2
WB1/WB1
0.172
0.062
4' ‐ 6"
Glocester
40
30
112
122
XWB1
131/135
XWB2
WB1/WB1
0.172
0.063
4' ‐ 6"
Hopkinton
35
30
119
128
XWB1
137/141
XWB2
WB1/WB1
0.164
0.058
4' ‐ 0"
Jamestown
30
30
108
121
XWB1
131/139
XWB2
WB1/WB1
0.164
0.058
3' ‐ 4"
Johnston
35
30
114
125
XWB1
133/137
XWB2
WB1/WB1
0.174
0.061
4' ‐ 0"
Lincoln
40
30
113
124
WB1
132/136
XWB2
WB1/WB1
0.177
0.062
4' ‐ 6"
Little
Compton
30
30
121
131
WB1
140/144
WB2/WB2
0.164
0.057
3' ‐ 4"
Middletown
30
30
121
131
WB1
139/143
XWB2
WB1/WB2
0.168
0.058
3' ‐ 4"
Narragansett
30
30
121
131
WB1
140/143
WB2/WB2
0.164
0.058
3' ‐ 4"
New
Shoreham
25
25
124
134
XWB2
WB1
143/149
WB2/WB2
0.142
0.053
2' ‐ 6"
Newport
30
30
121
131
XWB2
WB1
140/144
WB2/WB2
0.164
0.058
3' ‐ 4"
North
Kingstown
30
30
119
129
XWB1
138/141
XWB2
WB1/WB2
0.167
0.059
3' ‐ 4"
North
Providence
35
30
114
124
XWB1
133/137
XWB2
WB1/WB1
0.176
0.062
4' ‐ 0"
North
Smithfield
40
30
112
122
XWB1
131/135
XWB2
WB1/WB2
0.176
0.062
4' ‐ 6"
Pawtucket
35
30
114
125
XWB1
133/137
XWB2
WB1/WB1
0.178
0.062
4' ‐ 0"
Portsmouth
30
30
120
129
XWB1
138/142
XWb2
WB1/WB1
0.170
0.059
3' ‐ 4"
Providence
30
30
115
125
XWB1
124/138
XWB2
WB1/WB1
0.176
0.062
3' ‐ 4"
Richmond
35
30
119
129
XWB1
137/141
XWB2
WB1/WB2
0.164
0.059
4' ‐ 0"
Scituate
35
30
114
124
WB1
133/137
XWB2
WB1/WB1
0.173
0.061
4' ‐ 0"
Smithfield
40
30
113
123
XWB1
131/136
XWB2
WB1/WB1
0.175
0.062
4' ‐ 6"
South
Kingstown
30
30
121
130
WB1
139/143
XWB2
WB1/WB2
0.161
0.058
3' ‐ 4"
Tiverton
30
30
119
129
XWB1
138/142
XWB2
WB1/WB2
0.169
0.058
3' ‐ 4"
Warren
30
30
114
127
XWB1
136/140
XWB2
WB1/WB2
0.176
0.060
3' ‐ 4"
Warwick
30
30
117
127
XWB1
136/139
XWB2
WB1/WB1
0.174
0.060
3' ‐ 4"
West
Greenwich
35
30
117
127
XWB1
135/139
XWB2
WB1/WB1
0.169
0.060
4' ‐ 0"
West
Warwick
30
30
116
126
XWB1
135/139
XWB2
WB1/WB1
0.172
0.060
4' ‐ 0"
Westerly
30
30
120
129
XWB1
138/142
XWB2
WB1/WB2
0.158
0.057
3' ‐ 4"
Woonsocket
40
30
112
122
XWB1
130/135
XWB2
WB1/WB1
0.177
0.063
4' ‐ 6"
Blue
color by model code Wind-borne Debris Region greater than 130 MPH
V-ult within a mile of “mean high coastal water line”
>>
<<
Green Color Wind-borne Debris Region In areas where the ultimate
design wind speed is 140 mph (63.6 m/s) or greater
XWB,
XWB1, and WXW2 – No longer wind borne debris regions.
WB1
= 130 – 139 mph
WB2
= 140 mph and above
Delete
IBC section 1613.3.1 and substitute the following:
1613.3.1 Acceleration
parameters.
The parameters S S
and S 1 for each Rhode Island community are given in Table
1608.1.
1.15 Chapter 18: Soils and
Foundations
Delete IBC section 1801.3 and
substitute the following
1809.5 Frost protection.
Except where otherwise
protected from frost, foundation walls, piers and other permanent
supports of buildings and structures shall be protected by one or
more of the following methods:
1. See Rhode Island Frost
Depth values in Table 1608.1. and Figure 1608.1
2. Construction in accordance
with ASCE 32; 05
3. Erecting on solid rock
Exception: Free-standing
buildings meeting all of the following conditions shall not be
required to be protected:
1. Classified in Occupancy
Category I, in accordance with section 1604.5;
2. Area of six hundred (600)
square feet (56 M 2 ) or less for light-frame construction
or four hundred (400) square feet (37 m 2 ) or less for
other than light-frame construction; and
3. Eave height of ten feet
(10’) (3048 mm) or less
Footings shall not bear on
frozen soil unless such frozen condition is of a permanent character.
1.16 Chapter 21: Masonry
Reserved
1.17 Chapter 23: Wood
Add the following exception to
IBC section 2303.1.1 Lumber
Exception:
Native Lumber used in
accordance with Rhode Island amendment section 2310.
Add the following new section
2310 Native Lumber:
2310 Native Lumber.
2310.1 Scope:
The provisions of this
section shall govern the use of Native Lumber in accordance with R.I.
Gen. Laws § 23-27.3-109.0 of the State Building Code.
Native Lumber is unmarked
structural lumber from wood processed in the State of Rhode Island by
a mill registered in accordance with provisions of this code.
Such lumber which is not
grade marked or certified by a recognized grading organization
designated under section 2303.1.1 shall be classified as an ordinary
material and is not required to meet the test requirement of section
1709.2 and shall be permitted for use as follows.
2310.2 Identification and Use:
1. The producing mills shall
sell or provide the lumber directly to the ultimate consumer or his
contract builder for use in an approved structure;
2. The providing mill shall
certify in writing to the consumer or builder on a form to be
provided by the State Building Code Standards Committee that the
quality and safe working stresses of such lumber are equal to or
exceed No. 2 grade in accordance with grading practices established
by an approved lumber grading or approved testing agency.
Exception: Load bearing walls
shall be of stud grade minimum.
This certification shall be
filed with the local building official having jurisdiction as part of
the building permit application;
3. Native Lumber shall be
limited to the following uses:
a. One (1) and two (2)family
dwellings not exceeding three (3) stories in height, or:
b. General building
construction types 3B, 4 or 5B not exceeding ten thousand (10,000)
square feet of cumulative floor area or thirty-five feet (35’)
in height, but not to exceed two (2) stories, or:
c. Those low stress buildings
not intended for human habitation such as barns, sheds, agricultural,
detached garages, outbuildings and other accessory structures; or
d. Non-structural and non-fire
rated applications in any use group of Type 3, 4 or 5 constructions.
Uses not permitted: Native
lumber shall not be used in engineered plate-truss systems unless
such lumber is graded in accordance with section 2303.1.1.
2310.3 Native Softwoods and
Hardwoods
Native hardwood or softwood
lumber may be used in post and beam timber type construction per
section 602.4. Such uses as beam, girders, headers, and column
supports will require engineering evaluation for the allowable design
values and duration of loading factors for all buildings other than
One (1) & Two (2) Family Dwellings.
Native lumber located near or
in contact with the ground shall be naturally durable or
pressure-treated in accordance with the provisions of section
2304.12.
2310.4 Sizing Criteria for
Native Softwood Lumber
1. Sizing criteria: For lumber
sized in accordance with the AF&PA NDS-01, conventional span
tables in this code shall be permitted to be used for establishing
span and spacing characteristics for all structural members.
2. Stress increases: Lumber
which is sized in excess of the dimensions established by the AF&PA
NDS-01 for the given nominal size referenced shall be allowed to have
increased loads providing structural calculations are submitted
verifying such increases. See Table 2310.
2310.5 Moisture Content
The moisture content for
structural framing shall be nineteen percent (19%) or less unless the
producer indicates that the lumber is surfaced green.
2310.6 Post and Beam Type
Structures
Native hardwood and softwood
lumber are permitted in post and beam timber-type structures. Design
drawings and calculation shall be by a Rhode Island registered
architect or engineer and submitted to the building official for
approval.
2310.7 Responsibilities
The building official shall
indicate the use of native lumber on the building permit application
under the heading “Description of work to be performed”
and also the name of the mill providing the native lumber.
The building official shall
have the right to reject any lumber of questionable quality based on
visual observation.
Table
2310
Native
Lumber Allowable Stress
Actual
Lumber Size Closest Size which does not exceed the Dimensions
Shown
Multiplier
Factor Lumber Based on Width
Factor
to be Added to Column 3 Factor for Lumber Oversized in Thickness
Column
1
Column
2
Column
4
Nominal
Size
Actual
Size Thickness Width
Thickness
Increase of ¼” to ½”
Thickness
Increase of over ½” to 1”
3
x 8
2-1/2
x 7-1/2
1.0
x Fs
+0.10
+0.20
X
7-3/4
1.07
X
8
1.14
3
x 10
2-1/2
x 9-1/2
1.0
+0.10
+0.20
X
9-3/4
1.05
X
10
1.11
3
x 12
2-1/2
x 11-1/2
1.0
+0.10
+0.20
X
11-3/4
1.04
X
12
1.09
3
x 14
2-1/2
x 13-1/2
1.0
+0.10
+0.20
X
13-3/4
1.04
X
14
1.07
4
x 10
3-1/2
x 9-1/2
1.0
+0.07
+0.14
X
9-3/4
1.05
X
10
1.11
4
x 12
3-1/2
x 11-1/2
1.0
+0.07
+0.14
X
11-3/4
1.04
X
12
1.09
4
x 14
3-1/2
x 13-1/2
1.0
+0.07
+0.14
X
13-3/4
1.04
X
14
1.08
Notes
to Table 2310
Note
1.
Notation
FS is the allowable maximum fiber stress for the assumed grade as
established by this code in section 2309.2.2 F’s
(“operating” stress) is the modified allowable maximum
fiber stress which may be used in the span tables and for
calculating required lumber sizes. F’s is found by
multiplying Fs by the factors given in the table
Note
2.
Table
Columns
Column
1
Is
the nominal commonly used lumber size
Column
2
Is
a list of actual sizes of the supplied lumber
Column
2
Lists
the sizes on the basis of a constant thickness and a width
increasing by one quarter of one inch (1/4”) and one half of
one inch (1/2”)
Column
3
Gives
the multiplier for increasing the assumed allowable stress (Fs)
based on the increases in width as listed in Column 2.
Column
4
Gives
the multiplier for increasing the assumed allowable stress (Fs)
based on increases in thickness
Note
3
Example:
Fiber stress for assumed grade = one thousand (1,000) psi –
Actual size 3-1/8 x 9-3/4
Nominal
size 3 X 10
1.
Multiplier factor for Width =
1.05
3-1/8
= increase of 5/8” total
2.
Multiplier factor for Thickness=
.20
3.Operating
stress F’s = 1.25 x Fs F’s = 1.25 x 1,000 = 1,250
Sum
= 1.25
Therefore,
F’s = 1,250 psi is used for calculations and in the span
tables
1.18 Chapter 27: Electrical
1.18.1 GENERAL
Delete
all references to IEC and substitute Rhode Island Electrical Code
SBC-5-2021 (Part 5
of this Subchapter).
Delete
all reference to any other International Code (IBC, IRC, IMC, etc.)
and refer to appropriate SBC Regulations. (See Amendment 2701.6).
The
following revisions are to Chapter 27 of SBC-1-2021
Delete existing Chapter 27 in
its entirety and substitute the following:
2701.1 Scope.
This Chapter governs the
electrical components, equipment and systems used in buildings and
structures covered by this code. Electrical components, equipment and
systems shall be designed and constructed in accordance with the
provisions of SBC-5-2021 (Part 5
of this Subchapter).
Permits.
Electrical wiring including
elevators and other conveyances as regulated by the Department of
Labor and Training, or data, telecommunications, video and sound
installations, shall not be installed in a building or structure, nor
shall alteration of an existing electrical wiring system be made
until a permit has been issued therefore as required in R.I. Gen.
Laws § 23-27.3-113.3.1.
Exception: Work not covered
in SBC-5-2021 section 90.2(b) 1-5 inclusive (Part 5
of this Subchapter). As used in section 4 & 5 a “utility”
is a company or business regulated and/or licensed by the Rhode
Island Public Utilities Commission. Subcontractors employed by a
utility are not exempt from permit requirements unless the proposed
work is being performed in the public right-of-way or within public
utility easements. It shall be unlawful to use or allow the use of,
or to supply current for, an electrical system in a building or
structure, or to allow the use of, or to supply current for data,
telecommunications, video or audio installations unless the required
permits have been issued and approved by the authority having
jurisdiction.
2701.3 Certification.
Except for use group R
(residential use), construction documents shall bear the seal of a
Registered Professional Engineer who shall provide the services as
required by R.I. Gen. Laws § 23-27.3-128.2.2, except as modified
by the authority enforcing this Code, or by the Board for
Registration of Professional Engineers.
2701.4 Re-inspection.
An electrical installation
from which an electrical service has been discontinued for a period
of thirty (30) days or more shall not have service restored until the
system has been re-inspected and a new certificate of inspection
issued.
Exception: Re-inspection of
dwelling units shall only be required if the electrical service has
been discontinued for a period of one (1) year.
2701.5 Reference
The following section is
taken directly from current R.I. Gen. Laws (R.I. Gen. Laws §
42-66.9-1) for references purposes only:
2701.5 Emergency generators
for Housing for the Elderly. All housing for the elderly complexes,
as defined in R.I. Gen. Laws § 42-66.1-2 which are serviced by
one (1) or more elevators and/or electrically powered chair lifts,
and which include more than one hundred fifty (150) residential
living units in a single building shall be equipped with emergency
generators which shall provide sufficient power to provide emergency
lighting to all common areas and a community room and power to
operate the elevators and a refrigerator in a common area. Generator
systems shall be in accordance with the national electric code and
R.I. Gen. Laws § 23-28.24-9.
2701.6 References.
Where this code references
other ICC codes, use the appropriate Regulation as adopted by the
State of Rhode Island and SBC-5-2021 (Part 5
of this Subchapter) for the IEC. References to the International Fire
Code (IFC) and its requirements are deleted and refer to the Rhode
Island State Fire Safety Code ( 450-RICR-00-00-1
through 10 ) (for requirements and enforcement by that authority
having jurisdiction.
2701.7 Other Codes.
The Rhode Island Uniform Fire
Safety Code ( 450-RICR-00-00-1
through 10 ) contains provisions for specific wiring methods for
fire alarms, signaling systems, and other building fixtures such as
exit signage, emergency lighting, and emergency and standby power
systems among others. Refer to the latest editions of that code for
the latest provisions.
IBC section 2702: Emergency
and Standby Power
2702.1 Installation.
Emergency and standby power systems shall be installed in accordance
with the SBC-5-2021 (Part 5
of this Subchapter), NFPA 110 and NFPA 111.
2702.2 Where required.
Emergency and standby power systems shall be provided where required
by sections 2702.2.1 through 2702.2.19.
2702.2.1 Group A Occupancies.
Emergency power shall be
provided for voice communication systems in Group A occupancies in
accordance with section 907.2.1.2.
2702.2.2 Smoke control
systems. Standby power shall be provided for smoke control systems in
accordance with section 909.11.
2702.2.3 Exit signs.
Emergency power shall be provided for exit signs in accordance with
section 1003.2.10.5.
2702.2.4 Means of egress
illumination. Emergency power shall be provided for means of egress
illumination in accordance with section 1003.2.11.2.
2702.2.5 Accessible means of
egress elevators. Standby power shall be provided for elevators that
are part of an accessible means of egress in accordance with section
1003.2.13.3.
2702.2.6 Horizontal sliding
doors. Standby power shall be provided for horizontal sliding doors
in accordance with section 1003.3.1.3.3.
2702.2.7 Semiconductor
fabrication facilities. Emergency power shall be provided for
semiconductor fabrication facilities in accordance with section
415.9.10.
2702.2.8 Membrane structures.
Standby power shall be provided for auxiliary inflation systems in
accordance with section 3102.8.2. Emergency power shall be provided
for exit signs in temporary tents and membrane structures in
accordance with the International Fire Code.
2702.2.9 Hazardous materials.
Emergency or standby power shall be provided in occupancies with
hazardous materials in accordance with section 414.5.4.
2702.2.10 Highly toxic and
toxic materials. Emergency power shall be provided for occupancies
with highly toxic to toxic materials in accordance with the
International Fire Code and Rhode Island State Fire Safety Codes
( 450-RICR-00-00-1
through 10 ).
2702.2.11 Organic peroxides.
Standby power shall be provided for occupancies with organic
peroxides in accordance with the International Fire Code and Rhode
Island State Fire Safety Codes ( 450-RICR-00-00-1
through 10 ).
2702.2.12 Pyrophoric
materials. Emergency power shall be provided for occupancies with
pyrophoric materials in accordance with the International Fire Code
and Rhode Island State Fire Safety Codes ( 450-RICR-00-00-1
through 10 ).
2702.2.13 Covered mall
buildings. Covered mall buildings exceeding fifty thousand (50,000)
square feet (4645 m 2 ) shall be provided with standby power
systems which are capable of operating the emergency voice/alarm
communication.
2702.2.14 High rise
buildings. Emergency and standby power shall be provided in high rise
buildings in accordance with Chapter 27 and for the items listed
below:
1. Fire command center.
2. Fire pumps.
3. Emergency voice/alarm
communication systems.
4. Lighting for mechanical
equipment rooms.
5. Elevators.
2702.2.15 Underground
buildings. Emergency and standby power shall be provided in
underground buildings in accordance with sections 405.9 and 405.10.
2702.2.16 Group I-3
occupancies. Emergency power shall be provided for doors in Group I-3
occupancies in accordance with section 408.4.2.
2702.2.17 Airport traffic
control towers. Standby power shall be provided in airport traffic
control towers in accordance with section 412.1.5.
2702.2.18 Elevators. Standby
power for elevators shall be provided as set forth in section 3003.1.
2702.2.19 Smoke proof
enclosures. Standby power shall be provided for smoke proof
enclosures as required by section 909.20.
2702.3 Maintenance. Emergency
and standby power systems shall be maintained and tested in
accordance with the Rhode Island State Fire Safety Codes
( 450-RICR-00-00-1
through 10 ).
1.19 Chapter 28
Delete IBC section 2801.1
Scope and substitute the following:
2801.1 Scope.
Mechanical appliances,
equipment and systems shall be constructed, installed and maintained
in accordance with SBC-4-2021 (Part 4
of this Subchapter) the Rhode Island Mechanical Code and SBC-19-2021
(Part 19
of this Subchapter) the Rhode Island Fuel Gas Code. Masonry chimneys,
fireplaces and barbecues shall comply with the Rhode Island
Mechanical Code (Part 4
of this Subchapter) and Chapter 21 of this code.
1.20 Chapter 29
Delete IBC section 2901. Scope
and substitute the following:
2901.1 Scope.
The provisions of this
Chapter and SBC-3-2021, the Rhode Island Plumbing Code shall govern
the erection, installation, repairs, relocation, replacement,
addition to, use or maintenance or plumbing equipment and systems.
P2902.2 Add the following new
exception #4
4. Separate facilities shall
not be required in existing structures or tenant spaces located
within existing building with a total occupant load of fewer than
fifty (50).
1.21 Chapter 30: Elevators and
Conveying Systems
Delete IBC section 3001.1
Scope and substitute the following:
3001.1 SCOPE
Except as may otherwise be
provided by statute, the provisions of this Chapter shall control the
design, construction and installation of all special hoisting and
conveying equipment hereafter installed, relocated or altered in all
buildings or structures. The design, construction, installation,
maintenance, relocation and operation of all elevators, dumbwaiters,
moving stairways, moving walks, and certain elevating devices used to
handle materials only, shall be subject to the Rules and Regulations
adopted and enforced by the Rhode Island Department of Labor and
Training, Division of Occupational Safety, Elevator Unit. Portable
elevating devices not covered by this Chapter or by the Department of
Labor, shall be constructed, operated and maintained in compliance
with accepted engineering practice.
Delete IBC section 3001.2
Referenced standards and substitute the following:
3001.1.1 PERMITS:
Permits for the installation
of elevators, dumb waiters, moving stairways, moving walks, and
certain elevating devices used to transport materials and personnel
shall be issued only by the Department of Labor and Training,
Division of Occupational Safety, Elevator Unit. Permits for all other
devices shall be issued by the building official.
1.22 Chapter 31: Special
Construction
Delete IBC section 3102.1 and
substitute the following:
3102.1 General
The provisions of this
section shall apply to air-supported, air-inflated, membrane-covered
cable and membrane-covered frame structures, collectively known as
membrane structures, erected for a period of one hundred eighty (180)
days or longer. Those erected for a shorter period of time shall
comply with the Rhode Island Uniform Fire Code. Those erected for one
hundred eighty (180) days or longer are also regulated by existing
code section 3103 Temporary Structures; a Rhode Island amendment to
the International model code.
Membrane structures covering
water storage facilities, water clarifiers, water treatment plants,
sewage treatment plants, greenhouses and similar facilities not used
for human occupancy are required to meet only the requirements of
sections 3102.3.1 and 3102.7. Membrane structures erected on a
building, balcony, deck or other structures for any period of time
shall comply with this section.
Delete
IBC section 3102.2 Definitions of Membrane – Covered Cable
Structures and Membrane – Covered Frame Structure and
substitute the following
3102.2 Definitions.
“Membrane-covered cable
structure” means a non-pressurized structure in which a mast
and cable system provides support and tension to the membrane weather
barrier and the membrane imparts stability to the structure.
Including but not limited to “TENTS”.
“Membrane-covered frame
structure” means a non-pressurized building wherein the
structure is composed of a rigid framework to support a tensioned
membrane which provides the weather barrier. Including but not
limited to “TENTS.”
Delete
IBC section 3103 Temporary Structures in its entirety and substitute
the following:
SECTION 3103.0 TEMPORARY
STRUCTURES
3103.0 General:
Pursuant to a variance
granted by the Board of Appeals the Building Official shall issue a
permit for temporary construction as approved by the Board of Appeal.
Such permits shall be limited as to time of service but such
temporary construction shall not be permitted for more than one (1)
year.
The building official shall
be permitted to issue permits for temporary construction limited to
buildings of less than four hundred (400) square feet and all
construction trailers. Such permits shall be limited as to time of
service but no such construction shall be permitted to remain in
place for more than one (1) year or the time scheduled for the
construction project.
3103.2 Special Approval
All temporary construction,
when intended to be occupied by the owner, employee, or general
public shall conform to structural strength, fire safety, means of
egress, light, ventilation and sanitary requirements of the Code
necessary to insure the public health, safety and general welfare.
3103.3 Termination of Approval
The building official is
hereby authorized to terminate such special approval and to order
demolition and/or removal of any such construction at his discretion.
Add the following new section
to Chapter 31
SECTION 3112 FABRIC STRUCTURES
3112.1 Definition
Fabric Structures are
structures utilizing wood, metal or plastic frames and covered with
cloth, canvas, glass or plastic material, excluding tents,
agricultural and horticultural greenhouses, and furnishings such as
umbrellas, awnings and canopies or portable shade canopies.
3112.2 Fabric Structures:
Fabric Structures: Fabric
Structures shall be located in accordance with applicable local
zoning code provisions. Permits shall be required for all fabric
structures. Fabric structures less than four hundred (400) square
feet in area and installed for a period not exceeding one (1) year
shall be installed in accordance with manufacturer’s
installation instructions. Fabric structures greater than four
hundred (400) square feet in area or intended to be in place for a
period exceeding twelve (12) months shall only be approved pending a
satisfactory decision by the State or local Building Code Board of
Appeals, unless full code compliance for permanent structures in all
respects is demonstrated to the satisfaction of the local building
official. The State Fire Marshal or his authorized representative
shall determine whether the installation is subject to provisions of
the State Fire Safety Code prior to issuance of the permit.
Exceptions:
1. Agricultural and
horticultural greenhouses used primarily for growing.
2. Livestock shelters
arts/crafts, flea markets, etc. of limited duration consisting of
small booths and multiple vendors, and as may be properly licensed by
the municipality.
3. Any structure less than one
hundred (100) square feet.
4. Furnishings such as
umbrellas awnings, etc.
1.23 Chapter 33: Safeguards During
Construction
Add the following new section
to IBC section 3304 Sitework:
Final Grading.
Lots shall be graded so that
surface accumulation of water does not occur across adjoining
property. Retaining walls, which may be necessary to prevent surface
run-off into adjoining property, shall be constructed in accordance
with this code and any applicable ordinances. Storm drainage systems
necessary to divert flows from adjoining property shall be designed
and installed in accordance with SBC-3 – 2021 (Part 3
of this Subchapter) the Rhode Island State Plumbing Code.
Add
the following new section to IBC section 3307 Protection of Adjoining
Property:
3307.2 Structural Loads.
See section 1608.4.
1.24 Chapter 34: Existing
Structures
Substitute the following for
IBC Chapter 34 2018
SECTION 3401 GENERAL
3401.1 Scope.
The provisions of this
Chapter shall control the alteration, repair, addition and change of
occupancy of existing buildings and structures.
Exception: Existing
bleachers, grandstands and folding and telescopic seating shall
comply with ICC 300.
3401.2 Maintenance.
Buildings and structures, and
parts thereof, shall be maintained in a safe and sanitary condition.
Devices or safeguards which are required by this code shall be
maintained in conformance with the code edition under which
installed. The owner or the owner’s designated agent shall be
responsible for the maintenance of buildings and structures. To
determine compliance with this subsection, the building official
shall have the authority to require a building or structure to be
re-inspected. The requirements of this Chapter shall not provide the
basis for removal or abrogation of fire protection and safety systems
and devices in existing structures.
3401.3 Compliance.
Alterations, repairs,
additions and changes of occupancy to, or relocation of, existing
buildings and structures shall comply with the provisions for
alterations, repairs, additions and changes of occupancy or
relocation, respectively, in the International Energy Conservation
Code, International Fire Code, International Fuel Gas Code,
International Mechanical Code, International Plumbing Code,
International Property Maintenance Code, International Private Sewage
Disposal Code, International Residential Code and NFPA 70. Where
provisions of the other codes conflict with provisions of this
Chapter, the provisions of this Chapter shall take precedence.
3401.4 Building materials and
systems.
Building materials and
systems shall comply with the requirements of this section.
3401.4.1 Existing materials.
Materials already in use in a
building in compliance with requirements or approvals in effect at
the time of their erection or installation shall be permitted to
remain in use unless determined by the Building Official to be unsafe
per section 116.
3401.4.2 New and replacement
materials.
Except as otherwise required
or permitted by this code, materials permitted by the applicable code
for new construction shall be used. Like materials shall be permitted
for repairs and alterations, provided no hazard to life, health or
property is created. Hazardous materials shall not be used where the
code for new construction would not permit their use in buildings of
similar occupancy, purpose and location.
3401.4.3 Existing seismic
force-resisting systems.
Where the existing seismic
force-resisting system is a type that can be designated ordinary,
values of R, Ω0, and Cd for the existing seismic
force-resisting system shall be those specified by this code for an
ordinary system unless it is demonstrated that the existing system
will provide performance equivalent to that of a detailed,
intermediate or special system.
3401.6 Alternative compliance.
Work performed in accordance
with the International Existing Building Code shall be deemed to
comply with the provisions of this Chapter.
3401.5 Dangerous conditions.
The Building Official shall
have the authority to require the elimination of conditions deemed
dangerous.
IBC
SECTION 3402 DEFINITIONS
3402.1 Definitions.
The following terms are
defined in Chapter 2:
DANGEROUS.
EXISTING STRUCTURE.
PRIMARY FUNCTION.
SUBSTANTIAL STRUCTURAL
DAMAGE.
TECHNICALLY INFEASIBLE.
IBC
section 3403 ADDITIONS
3403.1 General.
Additions to any building or
structure shall comply with the requirements of this code for new
construction. Alterations to the existing building or structure shall
be made to ensure that the existing building or structure together
with the addition are no less conforming with the provisions of this
code than the existing building or structure was prior to the
addition. An existing building together with its additions shall
comply with the height and area provisions of Chapter 5.
3403.2 Flood hazard areas.
For buildings and structures
in flood hazard areas established in section 1612.3, any addition
that constitutes substantial improvement of the existing structure,
as defined in section 1612.2, shall comply with the flood design
requirements for new construction, and all aspects of the existing
structure shall be brought into compliance with the requirements for
new construction for flood design. For buildings and structures in
flood hazard areas established in section 1612.3, any additions that
do not constitute substantial improvement of the existing structure,
as defined in section 1612.2, are not required to comply with the
flood design requirements for new construction.
3403.3 Existing structural
elements carrying gravity load.
Any existing gravity
load-carrying structural element for which an addition and its
related alterations cause an increase in design gravity load of more
than five percent (5%) shall be strengthened, supplemented, replaced
or otherwise altered as needed to carry the increased gravity load
required by this code for new structures. Any existing gravity
load-carrying structural element whose gravity load-carrying capacity
is decreased shall be considered an altered element subject to the
requirements of section 3404.3. Any existing element that will form
part of the lateral load path for any part of the addition shall be
considered an existing lateral load-carrying structural element
subject to the requirements of section 3403.4.
3403.3.1 Design live load.
Where the addition does not
result in increased design live load, existing gravity load carrying
structural elements shall be permitted to be evaluated and designed
for live loads approved prior to the addition. If the approved live
load is less than that required by section 1607, the area designed
for the nonconforming live load shall be posted with placards of
approved design indicating the approved live load. Where the addition
does result in increased design live load, the live load required by
section 1607 shall be used.
3403.4 Existing structural
elements carrying lateral load.
Where the addition is
structurally independent of the existing structure, existing lateral
load-carrying structural elements shall be permitted to remain
unaltered. Where the addition is not structurally independent of the
existing structure, the existing structure and its addition acting
together as a single structure shall be shown to meet the
requirements of sections 1609 and 1613.
Exception:
Any existing lateral
load-carrying structural element whose demand-capacity ratio with the
addition considered is no more than ten percent (10%) greater than
its demand-capacity ratio with the addition ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applicable load
combinations with design lateral loads or forces in accordance with
sections 1609 and 1613. For purposes of this exception, comparisons
of demand-capacity ratios and calculation of design lateral loads,
forces and capacities shall account for the cumulative effects of
additions and alterations since original construction.
3403.5 Smoke alarms in
existing portions of a building.
Where an addition is made to
a building or structure of a Group R or I-1 occupancy, the existing
building shall be provided with smoke alarms in accordance with
section 1103.8 of the International Fire Code.
IBC
section 3404 ALTERATIONS
3404.1 General.
Except as provided by section
3401.4 or this section, alterations to any building or structure
shall comply with the requirements of the code for new construction.
Alterations shall be such that the existing building or structure is
no less complying with the provisions of this code than the existing
building or structure was prior to the alteration.
Exceptions:
1. An existing stairway shall
not be required to comply with the requirements of section 1009 where
the existing space and construction does not allow a reduction in
pitch or slope.
2. Handrails otherwise
required to comply with section 1011.11 shall not be required to
comply with the requirements of section 1014.6 regarding full
extension of the handrails where such extensions would be hazardous
due to plan configuration.
3404.2 Flood hazard areas.
For buildings and structures
in flood hazard areas established in section 1612.3, any alteration
that constitutes substantial improvement of the existing structure,
as defined in section 1612.2, shall comply with the flood design
requirements for new construction, and all aspects of the existing
structure shall be brought into compliance with the requirements for
new construction for flood design. For buildings and structures in
flood hazard areas established in section 1612.3, any alterations
that do not constitute substantial improvement of the existing
structure, as defined in section 1612.2, are not required to comply
with the flood design requirements for new construction.
3404.3 Existing structural
elements carrying gravity load.
Any existing gravity
load-carrying structural element for which an alteration causes an
increase in design gravity load of more than five percent (5%) shall
be strengthened, supplemented, replaced or otherwise altered as
needed to carry the increased gravity load required by this code for
new structures. Any existing gravity load-carrying structural element
whose gravity load-carrying capacity is decreased as part of the
alteration shall be shown to have the capacity to resist the
applicable design gravity loads required by this code for new
structures.
3404.3.1 Design live load.
Where the alteration does not
result in increased design live load, existing gravity load carrying
structural elements shall be permitted to be evaluated and designed
for live loads approved prior to the alteration. If the approved live
load is less than that required by section 1607, the area designed
for the nonconforming live load shall be posted with placards of
approved design indicating the approved live load. Where the
alteration does result in increased design live load, the live load
required by section 1607 shall be used.
3404.4 Existing structural
elements carrying lateral load.
Except as permitted by
section 3404.5, where the alteration increases design lateral loads
in accordance with section 1609 or 1613, or where the alteration
results in a structural irregularity as defined in ASCE 7, or where
the alteration decreases the capacity of any existing lateral
load-carrying structural element, the structure of the altered
building or structure shall be shown to meet the requirements of
sections 1609 and 1613.
Exception:
Any existing lateral
load-carrying structural element whose demand-capacity ratio with the
alteration considered is no more than ten percent (10%) greater than
its demand-capacity ratio with the alteration ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applicable load
combinations with design lateral loads or forces per sections 1609
and 1613. For purposes of this exception, comparisons of
demand-capacity ratios and calculation of design lateral loads,
forces, and capacities shall account for the cumulative effects of
additions and alterations since original construction.
3404.5 Voluntary seismic
improvements.
Alterations to existing
structural elements or additions of new structural elements that are
not otherwise required by this chapter and are initiated for the
purpose of improving the performance of the seismic force-resisting
system of an existing structure or the performance of seismic bracing
or anchorage of existing nonstructural elements shall be permitted,
provided that an engineering analysis is submitted demonstrating the
following:
1. The altered structure and
the altered nonstructural elements are no less conforming with the
provisions of this code with respect to earthquake design than they
were prior to the alteration.
2. New structural elements are
detailed as required for new construction.
3. New or relocated
nonstructural elements are detailed and connected to existing or new
structural elements as required for new construction.
4. The alterations do not
create a structural irregularity as defined in ASCE 7 or make an
existing structural irregularity more severe.
3404.6 Smoke alarms.
Individual sleeping units and
individual dwelling units in Group R and I-1 occupancies shall be
provided with smoke alarms in accordance with section 1103.8 of the
International Fire Code.
IBC
section 3405 REPAIRS
3405.1 General.
Buildings and structures, and
parts thereof, shall be repaired in compliance with sections 3405 and
3401.2. Work on non-damaged components that is necessary for the
required repair of damaged components shall be considered part of the
repair and shall not be subject to the requirements for alterations
in this chapter. Routine maintenance required by section 3401.2,
ordinary repairs exempt from permit in accordance with section 105.2,
and abatement of wear due to normal service conditions shall not be
subject to the requirements for repairs in this section.
3405.2 Substantial structural
damage to vertical elements of the lateral force-resisting system.
A building that has sustained
substantial structural damage to the vertical elements of its lateral
force-resisting system shall be evaluated and repaired in accordance
with the applicable provisions of sections 3405.2.1 through 3405.2.3.
Exceptions:
1. Buildings assigned to
Seismic Design Category A, B, or C whose substantial structural
damage was not caused by earthquake need not be evaluated or
rehabilitated for load combinations that include earthquake effects.
2. One (1) and two (2) family
dwellings need not be evaluated or rehabilitated for load
combinations that include earthquake effects.
3405.2.1 Evaluation.
The building shall be
evaluated by a registered design professional, and the evaluation
findings shall be submitted to the building official. The evaluation
shall establish whether the damaged building, if repaired to its
pre-damage state, would comply with the provisions of this code for
wind and earthquake loads. Wind loads for this evaluation shall be
those prescribed in section 1609. Earthquake loads for this
evaluation, if required, shall be permitted to be seventy-five
percent (75%) of those prescribed in section 1613.
3405.2.2 Extent of repair for
compliant buildings.
If the evaluation establishes
compliance of the pre-damage building in accordance with section
3405.2.1, then repairs shall be permitted that restore the building
to its pre-damage state, based on material properties and design
strengths applicable at the time of original construction.
3405.2.3 Extent of repair for
noncompliant buildings.
If the evaluation does not
establish compliance of the pre-damaged building in accordance with
section 3404.2.1, then the building shall be rehabilitated to comply
with applicable provisions of this code for load combinations that
include wind or seismic loads. The wind loads for the repair shall be
as required by the building code in effect at the time of original
construction, unless the damage was caused by wind, in which case the
wind loads shall be as required by this code. Earthquake loads for
this rehabilitation design shall be those required for the design of
the pre-damage building, but not less than seventy-five percent (75%)
of those prescribed in section 1613. New structural members and
connections required by this rehabilitation design shall comply with
the detailing provisions of this code for new buildings of similar
structure, purpose and location.
3405.3 Substantial structural
damage to gravity load-carrying components.
Gravity load-carrying
components that have sustained substantial structural damage shall be
rehabilitated to comply with the applicable provisions of this code
for dead and live loads. Snow loads shall be considered if the
substantial structural damage was caused by or related to snow load
effects. Existing gravity load-carrying structural elements shall be
permitted to be designed for live loads approved prior to the damage.
Nondamaged gravity load-carrying components that receive dead, live
or snow loads from rehabilitated components shall also be
rehabilitated or shown to have the capacity to carry the design loads
of the rehabilitation design. New structural members and connections
required by this rehabilitation design shall comply with the
detailing provisions of this code for new buildings of similar
structure, purpose and location.
3405.3.1 Lateral
force-resisting elements.
Regardless of the level of
damage to vertical elements of the lateral force-resisting system, if
substantial structural damage to gravity load-carrying components was
caused primarily by wind or earthquake effects, then the building
shall be evaluated in accordance with section 3405.2.1 and, if
noncompliant, rehabilitated in accordance with section 3405.2.3.
Exceptions:
1. One (1) and two (2) family
dwellings need not be evaluated or rehabilitated for load
combinations that include earthquake effects.
2. Buildings assigned to
Seismic Design Category A, B, or C whose substantial structural
damage was not caused by earthquake need not be evaluated or
rehabilitated for load combinations that include earthquake effects.
3405.4 Less than substantial
structural damage.
For damage less than
substantial structural damage, repairs shall be allowed that restore
the building to its pre-damage state, based on material properties
and design strengths applicable at the time of original construction.
New structural members and connections used for this repair shall
comply with the detailing provisions of this code for new buildings
of similar structure, purpose and location.
3405.4.1 Repairs for less than
substantial damage due to snow load effects.
Roof framing components that
have sustained less than substantial structural damage caused by or
related to snow load effects shall be rehabilitated to comply with
the applicable provisions for dead and snow loads in Chapter 16.
Undamaged roof framing components that receive dead or snow loads
from rehabilitated components shall also be rehabilitated to comply
with the design loads of the rehabilitated design.
3405.5 Flood hazard areas.
For buildings and structures
in flood hazard areas established in section 1612.3, any repair that
constitutes substantial improvement of the existing structure, as
defined in section 1612.2, shall comply with the flood design
requirements for new construction, and all aspects of the existing
structure shall be brought into compliance with the requirements for
new construction for flood design. For buildings and structures in
flood hazard areas established in section 1612.3, any repairs that do
not constitute substantial improvement or repair of substantial
damage of the existing structure, as defined in section 1612.2, are
not required to comply with the flood design requirements for new
construction.
IBC
section 3406 Fire Escapes
3406.1 Where permitted.
Fire escapes shall be
permitted only as provided for in sections 3406.1.1 through 3406.1.4.
3406.1.1 New buildings.
Fire escapes shall not
constitute any part of the required means of egress in new buildings.
3406.1.2 Existing fire
escapes.
Existing fire escapes shall
be continued to be accepted as a component in the means of egress in
existing buildings only.
3406.1.3 New fire escapes.
New fire escapes for existing
buildings shall be permitted only where exterior stairs cannot be
utilized due to lot lines limiting stair size or due to the
sidewalks, alleys or roads at grade level. New fire escapes shall not
incorporate ladders or access by windows.
3406.1.4 Limitations.
Fire escapes shall comply
with this section and shall not constitute more than fifty percent
(50%) of the required number of exits nor more than fifty percent
(50%) of the required exit capacity.
3406.2 Location.
Where located on the front of
the building and where projecting beyond the building line, the
lowest landing shall not be less than seven feet (7’) (2134 mm)
or more than twelve feet (12’) (3658 mm) above grade and shall
be equipped with a counterbalanced stairway to the street. In
alleyways and thoroughfares less than thirty feet (30’) (9144
mm) wide, the clearance under the lowest landing shall not be less
than twelve feet (12’) (3658 mm).
3406.3 Construction.
The fire escape shall be
designed to support a live load of one hundred (100) pounds per
square foot (4788 Pascals) and shall be constructed of steel or other
approved noncombustible materials. Fire escapes constructed of wood
not less than nominal two inches (2”) (51 mm) thick are
permitted on buildings of Type V construction. Walkways and railings
located over or supported by combustible roofs in buildings of Type
III and IV construction are permitted to be of wood not less than
nominal two inches (2”) (51 mm) thick.
3406.4 Dimensions.
Stairs shall be at least
twenty-two inches (22”) (559 mm) wide with risers not more
than, and treads not less than, eight inches (8”) (203 mm) and
landings at the foot of stairs not less than forty inches (40”)
(1016 mm) wide by thirty-six inches (36”) (914 mm) long,
located not more than eight inches (8”) (203 mm) below the
door.
3406.5 Opening protectives.
Doors and windows along the
fire escape shall be protected with three quarters of one (3/4) hour
opening protectives.
IBC
section 3407 Glass Replacement
3407.1 Conformance.
The installation or
replacement of glass shall be as required for new installations.
IBC
section 3408 Change of Occupancy
3408.1 Conformance.
No change shall be made in
the use or occupancy of any building that would place the building in
a different division of the same group of occupancies or in a
different group of occupancies, unless such building is made to
comply with the requirements of this code for such division or group
of occupancies. Subject to the approval of the building official, the
use or occupancy of existing buildings shall be permitted to be
changed and the building is allowed to be occupied for purposes in
other groups without conforming to all the requirements of this code
for those groups, provided the new or proposed use is less hazardous,
based on life and fire risk, than the existing use.
3408.2 Certificate of
occupancy.
A certificate of occupancy
shall be issued where it has been determined that the requirements
for the new occupancy classification have been met.
3408.3 Stairways.
An existing stairway shall
not be required to comply with the requirements of section 1011 where
the existing space and construction does not allow a reduction in
pitch or slope.
3408.4 Seismic.
When a change of occupancy
results in a structure being reclassified to a higher risk category,
the structure shall conform to the seismic requirements for a new
structure of the higher risk category.
Exceptions:
1. Specific seismic detailing
requirements of section 1613 for a new structure shall not be
required to be met where the seismic performance is shown to be
equivalent to that of a new structure. A demonstration of equivalence
shall consider the regularity, over strength, redundancy and
ductility of the structure.
2. When a change of use
results in a structure being reclassified from Risk Category I or II
to Risk Category III and the structure is located where the seismic
coefficient, SDS, is less than thirty-three one hundredths (0.33),
compliance with the seismic requirements of section 1613 are not
required.
IBC
section 3409 Historic Buildings
3409 Historic Buildings:
Delete IBC section 3407.1
3409.1 Historic Buildings and substitute the following:
3409.1 Approval:
The provisions of this code
relating to the construction, repair, alteration, enlargement,
restoration and moving of buildings or structures shall not be
mandatory for existing buildings or structures identified and
classified by the state or local government authority as historic
buildings, subject to the approval of the Board of Appeals, when such
buildings are judged by the code official to be safe and in the
interest of public health, safety and welfare regarding any proposed
construction, alteration, repair, enlargement and relocation. All
such approvals shall be based on the applicant's complete submission
of professional architectural and engineering plans and
specifications bearing the professional seal of the designer.
3409.2 Flood hazard areas.
Within flood hazard areas
established in accordance with section 1612.3, where the work
proposed constitutes substantial improvement as defined in section
1612.2, the building shall be brought into compliance with section
1612.
Exception: Historic buildings
that are:
1. Listed or preliminarily
determined to be eligible for listing in the National Register of
Historic Places;
2. Determined by the Secretary
of the U.S. Department of Interior as contributing to the historical
significance of a registered historic district or a district
preliminarily determined to qualify as an historic district; or
3. Designated as historic
under a State or local historic preservation program that is approved
by the Department of Interior.
IBC
section 3410 Moved Structure
3410.1 Conformance.
Structures moved into or
within the jurisdiction shall comply with the provisions of this code
for new structures.
IBC
section 3411 Accessibility for Existing Buildings
3411.1 Scope.
The provisions of sections
3411.1 through 3411.9 apply to maintenance, change of occupancy,
additions and alterations to existing buildings, including those
identified as historic buildings.
3411.2 Maintenance of
facilities.
A facility that is
constructed or altered to be accessible shall be maintained
accessible during occupancy.
3411.3 Extent of application.
An alteration of an existing
facility shall not impose a requirement for greater accessibility
than that which would be required for new construction. Alterations
shall not reduce or have the effect of reducing accessibility of a
facility or portion of a facility.
3411.4 Change of occupancy.
Existing buildings that
undergo a change of group or occupancy shall comply with this
section.
Exception:
Type B dwelling units or
sleeping units required by section 1107 of this code are not required
to be provided in existing buildings and facilities undergoing a
change of occupancy in conjunction with alterations where the work
area is fifty percent (50%) or less of the aggregate area of the
building.
3411.4.1 Partial change in
occupancy.
Where a portion of the
building is changed to a new occupancy classification, any
alterations shall comply with sections 3411.6, 3411.7 and 3411.8.
3411.4.2 Complete change of
occupancy.
Where an entire building
undergoes a change of occupancy, it shall comply with section
3411.4.1 and shall have all of the following accessible features:
1. At least one (1) accessible
building entrance.
2. At least one (1) accessible
route from an accessible building entrance to primary function areas.
3. Signage complying with
section 1111.
4. Accessible parking, where
parking is being provided.
5. At least one (1) accessible
passenger loading zone, when loading zones are provided.
6. At least one (1) accessible
route connecting accessible parking and accessible passenger loading
zones to an accessible entrance. Where it is technically infeasible
to comply with the new construction standards for any of these
requirements for a change of group or occupancy, the above items
shall conform to the requirements to the maximum extent technically
feasible.
Exception:
The accessible features
listed in Items 1 through 6 are not required for an accessible route
to Type B units.
3411.5 Additions.
Provisions for new
construction shall apply to additions. An addition that affects the
accessibility to, or contains an area of, a primary function shall
comply with the requirements in section 3411.7.
3411.6 Alterations.
A facility that is altered
shall comply with the applicable provisions in Chapter 11 of this
code, unless technically infeasible. Where compliance with this
section is technically infeasible, the alteration shall provide
access to the maximum extent technically feasible.
Exceptions:
1. The altered element or
space is not required to be on an accessible route, unless required
by section 3411.7.
2. Accessible means of egress
required by Chapter 10 are not required to be provided in existing
facilities.
3. The alteration to Type A
individually owned dwelling units within a Group R-2 occupancy shall
be permitted to meet the provision for a Type B dwelling unit.
4. Type B dwelling or sleeping
units required by section 1107 of this code are not required to be
provided in existing buildings and facilities undergoing a change of
occupancy in conjunction with alterations where the work area is
fifty percent (50%) or less of the aggregate area of the building.
3411.7 Alterations affecting
an area containing a primary function.
Where an alteration affects
the accessibility to, or contains an area of primary function, the
route to the primary function area shall be accessible. The
accessible route to the primary function area shall include toilet
facilities or drinking fountains serving the area of primary
function.
Exceptions:
1. The costs of providing the
accessible route are not required to exceed twenty percent (20%) of
the costs of the alterations affecting the area of primary function.
2. This provision does not
apply to alterations limited solely to windows, hardware, operating
controls, electrical outlets and signs.
3. This provision does not
apply to alterations limited solely to mechanical systems, electrical
systems, installation or alteration of fire protection systems and
abatement of hazardous materials.
4. This provision does not
apply to alterations undertaken for the primary purpose of increasing
the accessibility of a facility.
5. This provision does not
apply to altered areas limited to Type B dwelling and sleeping units.
3411.8 Scoping for
alterations.
The provisions of sections
3411.8.1 through 3411.8.14 shall apply to alterations to existing
buildings and facilities.
3411.8.1 Entrances.
Accessible entrances shall be
provided in accordance with section 1105.
Exception:
Where an alteration includes
alterations to an entrance, and the facility has an accessible
entrance, the altered entrance is not required to be accessible,
unless required by section 3411.7. Signs complying with section 1111
shall be provided.
3411.8.2 Elevators.
Altered elements of existing
elevators shall comply with ASME A17.1 and ICC A117.1. Such elements
shall also be altered in elevators programmed to respond to the same
hall call control as the altered elevator.
3411.8.3 Platform lifts.
Platform (wheelchair) lifts
complying with ICC A117.1 and installed in accordance with ASME A18.1
shall be permitted as a component of an accessible route.
3411.8.4 Stairs and escalators
in existing buildings.
In alterations, change of
occupancy or additions where an escalator or stair is added where
none existed previously, and major structural modifications are
necessary for installation, an accessible route shall be provided
between the levels served by the escalator or stairs in accordance
with sections 1104.4 and 1104.5.
3411.8.5 Ramps.
Where slopes steeper than
allowed by section 1012.6.1 are necessitated by space limitations,
the slope of ramps in or providing access to existing facilities
shall comply with Table 3411.8.5.
TABLE
3411.8.5
RAMPS
SLOPE
MAXIMUM
RISE
Steeper
than 1:10 but not steeper than 1:8
3
inches
Steeper
than 1:12 but not steeper than 1:10
6
inches
For
SI: 1 inch = 25.4 mm.
3411.8.6 Performance areas.
Where it is technically
infeasible to alter performance areas to be on an accessible route,
at least one (1) of each type of performance area shall be made
accessible.
3411.8.7 Accessible dwelling
or sleeping units.
Where Group I-1, I-2, I-3,
R-1, R-2 or R-4 dwelling or sleeping units are being altered or
added, the requirements of section 1107 for Accessible units apply
only to the quantity of spaces being altered or added.
3411.8.8 Type A dwelling or
sleeping units.
Where more than twenty (20)
Group R-2 dwelling or sleeping units are being altered or added, the
requirements of section 1107 for Type A units apply only to the
quantity of the spaces being altered or added.
3411.8.9 Type B dwelling or
sleeping units.
Where four (4) or more Group
I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being
added, the requirements of section 1107 for Type B units apply only
to the quantity of the spaces being added. Where Group I-1, I-2, R-1,
R-2, R-3 or R-4 dwelling or sleeping units are being altered and
where the work area is greater than fifty percent (50%) of the
aggregate area of the building, the requirements of section 1107 for
Type B units apply only to the quantity of the spaces being altered.
3411.8.10 Jury boxes and
witness stands.
In alterations, accessible
wheelchair spaces are not required to be located within the defined
area of raised jury boxes or witness stands and shall be permitted to
be located outside these spaces where the ramp or lift access
restricts or projects into the means of egress.
3411.8.11 Toilet rooms.
Where it is technically
infeasible to alter existing toilet and bathing rooms to be
accessible, an accessible family or assisted-use toilet or bathing
room constructed in accordance with section 1109.2.1 is permitted.
The family or assisted-use toilet or bathing room shall be located on
the same floor and in the same area as the existing toilet or bathing
rooms.
3411.8.12 Dressing, fitting
and locker rooms.
Where it is technically
infeasible to provide accessible dressing, fitting or locker rooms at
the same location as similar types of rooms, one (1) accessible room
on the same level shall be provided. Where separate-sex facilities
are provided, accessible rooms for each sex shall be provided.
Separate sex facilities are not required where only unisex rooms are
provided.
3411.8.13 Fuel dispensers.
Operable parts of replacement
fuel dispensers shall be permitted to be fifty-four inches (54”)
(1370 mm) maximum measured from the surface of the vehicular way
where fuel dispensers are installed on existing curbs.
3411.8.14 Thresholds.
The maximum height of
thresholds at doorways shall be three quarters of one inch (3/4”)
(19.1 mm). Such thresholds shall have beveled edges on each side.
3411.9 Historic buildings.
These provisions shall apply
to facilities designated as historic structures that undergo
alterations or a change of occupancy, unless technically infeasible.
Where compliance with the requirements for accessible routes,
entrances or toilet rooms would threaten or destroy the historic
significance of the facility, as determined by the applicable
governing authority, the alternative requirements of sections
3411.9.1 through 3411.9.4 for that element shall be permitted.
Exception:
Type B dwelling or sleeping
units required by section 1107 are not required to be provided in
historical buildings.
3411.9.1 Site arrival points.
At least one (1) accessible
route from a site arrival point to an accessible entrance shall be
provided.
3411.9.2 Multilevel buildings
and facilities.
An accessible route from an
accessible entrance to public spaces on the level of the accessible
entrance shall be provided.
3411.9.3 Entrances.
At least one (1) main
entrance shall be accessible.
Exceptions:
1. If a main entrance cannot
be made accessible, an accessible nonpublic entrance that is unlocked
while the building is occupied shall be provided; or
2. If a main entrance cannot
be made accessible, a locked accessible entrance with a notification
system or remote monitoring shall be provided. Signs complying with
section 1111 shall be provided at the primary entrance and the
accessible entrance.
3411.9.4 Toilet and bathing
facilities.
Where toilet rooms are
provided, at least one (1) accessible family or assisted-use toilet
room complying with section 1109.2.1 shall be provided.
IBC section 3412 Compliance
Alternatives
3412.1 Compliance.
The provisions of this
section are intended to maintain or increase the current degree of
public safety, health and general welfare in existing buildings while
permitting repair, alteration, addition and change of occupancy
without requiring full compliance with Chapters 2 through 33, or
sections 3401.3, and 3403 through 3409, except where compliance with
other provisions of this code is specifically required in this
section.
Delete IBC section 3410.2
3412.2 Applicability and substitute the following:
3412.2 Applicability
Existing buildings in which
there is work involving additions, alterations or changes of
occupancy shall be made to conform to the requirements of this
section or the provisions of sections 3403 through 3407. The
provisions in sections 3410.2.1 through 3410.2.5 shall apply to
existing occupancies that will continue to be, or are proposed to be,
in Groups A, B, E, F, M, R, S and U. These provisions shall not apply
to buildings with occupancies in Group H or I.
3412.2.1 Change in occupancy.
Where an existing building is
changed to a new occupancy classification and this section is
applicable, the provisions of this section for the new occupancy
shall be used to determine compliance with this code.
3412.2.2 Partial change in
occupancy.
Where a portion of the
building is changed to a new occupancy classification, and that
portion is separated from the remainder of the building with fire
barriers or horizontal assemblies having a fire-resistance rating as
required by Table 508.4 for the separate occupancies, or with
approved compliance alternatives, the portion changed shall be made
to comply with the provisions of this section. Where a portion of the
building is changed to a new occupancy classification, and that
portion is not separated from the remainder of the building with fire
barriers or horizontal assemblies having a fire-resistance rating as
required by Table 508.4 for the separate occupancies, or with
approved compliance alternatives, the provisions of this section
which apply to each occupancy shall apply to the entire building.
Where there are conflicting provisions, those requirements which
secure the greater public safety shall apply to the entire building
or structure.
3412.2.3 Additions.
Additions to existing
buildings shall comply with the requirements of this code for new
construction. The combined height and area of the existing building
and the new addition shall not exceed the height and area allowed by
Chapter 5. Where a fire wall that complies with section 706 is
provided between the addition and the existing building, the addition
shall be considered a separate building.
3412.2.4 Alterations and
repairs.
An existing building or
portion thereof, which does not comply with the requirements of this
code for new construction, shall not be altered or repaired in such a
manner that results in the building being less safe or sanitary than
such building is currently. If, in the alteration or repair, the
current level of safety or sanitation is to be reduced, the portion
altered or repaired shall conform to the requirements of Chapters 2
through 12 and Chapters 14 through 33.
3412.2.4.1 Flood hazard areas.
For existing buildings
located in flood hazard areas established in section 1612.3, if the
alterations and repairs constitute substantial improvement of the
existing building, the existing building shall be brought into
compliance with the requirements for new construction for flood
design.
3412.2.5 Accessibility
requirements.
All portions of the buildings
proposed for change of occupancy shall conform to the accessibility
provisions of section 3411.
3412.3 Acceptance.
For repairs, alterations,
additions and changes of occupancy to existing buildings that are
evaluated in accordance with this section, compliance with this
section shall be accepted by the building official.
3412.3.1 Hazards.
Where the building official
determines that an unsafe condition exists, as provided for in
section 116, such unsafe condition shall be abated in accordance with
section 116.
3412.3.2 Compliance with other
codes.
Buildings that are evaluated
in accordance with this section shall comply with the International
Fire Code and the International Property Maintenance Code.
3412.4 Investigation and
evaluation.
For proposed work covered by
this section, the building owner shall cause the existing building to
be investigated and evaluated in accordance with the provisions of
this section.
3412.4.1 Structural analysis.
The owner shall have a
structural analysis of the existing building made to determine
adequacy of structural systems for the proposed alteration, addition
or change of occupancy. The analysis shall demonstrate that the
building with the work completed is capable of resisting the loads
specified in Chapter 16.
3412.4.2 Submittal.
The results of the
investigation and evaluation as required in section 3412.4, along
with proposed compliance alternatives, shall be submitted to the
building official.
3412.4.3 Determination of
compliance.
The building official shall
determine whether the existing building, with the proposed addition,
alteration or change of occupancy, complies with the provisions of
this section in accordance with the evaluation process in sections
3412.5 through 3412.9.
3412.5 Evaluation.
The evaluation shall be
comprised of three categories: fire safety, means of egress and
general safety, as defined in sections 3412.5.1 through 3412.5.3.
3412.5.1 Fire safety.
Included within the fire
safety category are the structural fire resistance, automatic fire
detection, fire alarm, automatic sprinkler system, and fire
suppression system features of the facility.
3412.5.2 Means of egress.
Included within the means of
egress category are the configuration, characteristics and support
features for means of egress in the facility.
3412.5.3 General safety.
Included within the general
safety category are the fire safety parameters and the means of
egress parameters.
3412.6 Evaluation process.
The evaluation process
specified herein shall be followed in its entirety to evaluate
existing buildings. Table 3412.7 shall be utilized for tabulating the
results of the evaluation. References to other sections of this code
indicate that compliance with those sections is required in order to
gain credit in the evaluation herein outlined. In applying this
section to a building with mixed occupancies, where the separation
between the mixed occupancies does not qualify for any category
indicated in section 3412.6.16, the score for each occupancy shall be
determined and the lower score determined for each section of the
evaluation process shall apply to the entire building. Where the
separation between mixed occupancies qualifies for any category
indicated in section 3412.6.16, the score for each occupancy shall
apply to each portion of the building based on the occupancy of the
space.
3412.6.1 Building height.
The value for building height
shall be the lesser value determined by the formula in section
3412.6.1.1. Chapter 5 shall be used to determine the allowable height
of the building, including allowable increases due to automatic
sprinklers as provided for in Chapter 5. Subtract the actual building
height in feet from the allowable and divide by twelve and one half
feet (12-½’). Enter the height value and its sign
(positive or negative) in Table 3412.7 under Safety Parameter
3412.6.1, Building Height, for fire safety, means of egress and
general safety. The maximum score for a building shall be ten (10).
3412.6.1.1 Height formula.
The following formulas shall
be used in computing the building height value.
Where:
AH = Allowable height in feet
from Table 504.3
EBH = Existing building height
in feet.
AS = Allowable height in
stories from Table 504.4
EBS = Existing building height
in stories.
CF = 1 if (AH) – (EBH)
is positive.
CF = Construction-type factor
shown in Table 3412.6.6(2) if (AH) – (EBH) is negative.
Note:
Where mixed occupancies are
separated and individually evaluated as indicated in section 3412.6,
the values AH, AS, EBH and EBS shall be based on the height of the
occupancy being evaluated.
3412.6.2 Building area.
The value for building area
shall be determined by the formula in section 3412.6.2.2. Section 506
and the formula in section 3412.6.2.1 shall be used to determine the
allowable area of the building. This shall include any allowable
increases due to frontage and automatic sprinklers as provided for in
section 506. Subtract the actual building area in square feet from
the allowable area and divide by one thousand two hundred (1,200)
square feet. Enter the area value and its sign (positive or negative)
in Table 3412.7 under Safety Parameter 3412.6.2, Building Area, for
fire safety, means of egress and general safety. In determining the
area value, the maximum permitted positive value for area is fifty
percent (50%) of the fire safety score as listed in Table 3412.8,
Mandatory Safety Scores.
3412.6.2.1 Allowable area
formula.
The following formula shall be
used in computing allowable area:
Aa = [At + (At If)
+ (At Is)] (Equation 34-3)
Where:
Aa = Allowable building area
per story (square feet).
At = Tabular building area per
story in accordance with Table 506.2 (square feet).
Is = Area increase factor due
to sprinkler protection as calculated in accordance with section
506.2.
If = Area increase factor due
to for frontage as calculated in accordance with section 506.3.
3412.6.2.2 Area formula.
The following formula shall
be used in computing the area value. Determine the area value for
each occupancy floor area on a floor-by-floor basis. For each
occupancy, choose the minimum area value of the set of values
obtained for the particular occupancy.
Where:
i = Value for an individual
separated occupancy on a floor.
n = Number of separated
occupancies on a floor.
3412.6.3 Compartmentation.
Evaluate the compartments
created by fire barriers or horizontal assemblies which comply with
sections 3412.6.3.1 and 3412.6.3.2 and which are exclusive of the
wall elements considered under sections 3412.6.4 and 3412.6.5.
Conforming compartments shall be figured as the net area and do not
include shafts, chases, stairways, walls or columns. Using Table
3412.6.3, determine the appropriate compartmentation value (CV) and
enter that value into Table 3412.7 under Safety Parameter 3412.6.3,
Compartmentation, for fire safety, means of egress and general
safety.
TABLE
3412.6.3
COMPARTMENTATION VALUES
OCCUPANCY
CATEGORIES a
a
Compartment
size equal
to or greater than 15,000 square feet
b
Compartment
size of
10,000 square feet
c
Compartment
size of
7,500 square feet
d
Compartment
size of 5,000 square feet
e
Compartment
size of
2,500 square feet or less
A-1,
A-3
0
6
10
14
18
A-2
0
4
10
14
18
A-4,
B, E, S-2
0
5
10
15
20
F,
M, R, S-1
0
4
10
16
22
For
SI: 1 Square foot = 0.093 m 2
For
areas between categories, the compartmentation value shall be
obtained by linear interpolation.
3412.6.3.1 Wall construction.
A wall used to create
separate compartments shall be a fire barrier conforming to section
707 with a fire-resistance rating of not less than two (2) hours.
Where the building is not divided into more than one (1) compartment,
the compartment size shall be taken as the total floor area on all
floors. Where there is more than one (1) compartment within a story,
each compartmented area on such story shall be provided with a
horizontal exit conforming to section 1026. The fire door serving as
the horizontal exit between compartments shall be so installed,
fitted and gasketed that such fire door will provide a substantial
barrier to the passage of smoke.
3412.6.3.2 Floor/ceiling
construction.
A floor/ceiling assembly used
to create compartments shall conform to section 711 and shall have a
fire-resistance rating of not less than two (2) hours.
3412.6.4 Tenant and dwelling
unit separations.
Evaluate the fire-resistance
rating of floors and walls separating tenants, including dwelling
units, and not evaluated under sections 3412.6.3 and 3412.6.5. Under
the categories and occupancies in Table 3412.6.4, determine the
appropriate value and enter that value in Table 3412.7 under Safety
Parameter 3412.6.4, Tenant and Dwelling Unit Separations, for fire
safety, means of egress and general safety.
TABLE
3412.6.4
SEPARATION VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
A-1
0
0
0
0
1
A-2
-5
-3
0
1
3
A-3,
A-4, B, E, F, M, S-1
-4
-3
0
2
4
R
-4
-2
0
2
4
S-2
-5
-2
0
2
4
3412.6.4.1 Categories.
The categories for tenant and
dwelling unit separations are:
1. Category a—No fire
partitions; incomplete fire partitions; no doors; doors not
self-closing or automatic-closing.
2. Category b—Fire
partitions or floor assemblies with less than a one (1) hour
fire-resistance rating or not constructed in accordance with sections
708 or 711.
3. Category c—Fire
partitions with a one (1) hour or greater fire-resistance rating
constructed in accordance with section 708 and floor assemblies with
a one (1) hour but less than two (2) hour fire-resistance rating
constructed in accordance with section 711, or with only one (1)
tenant within the floor area.
4. Category d—Fire
barriers with a one (1) hour but less than two (2) hour
fire-resistance rating constructed in accordance with section 707 and
floor assemblies with a two (2) hour or greater fire-resistance
rating constructed in accordance with section 711.
5. Category e—Fire
barriers and floor assemblies with a two (2) hour or greater
fire-resistance rating and constructed in accordance with sections
707 and 711, respectively.
3412.6.5 Corridor walls.
Evaluate the fire-resistance
rating and degree of completeness of walls which create corridors
serving the floor, and constructed in accordance with section 1020.
This evaluation shall not include the wall elements considered under
sections 3412.6.3 and 3412.6.4. Under the categories and groups in
Table 3412.6.5, determine the appropriate value and enter that value
into Table 3412.7 under Safety Parameter 3412.6.5, Corridor Walls,
for fire safety, means of egress and general safety.
TABLE
3412.6.5
CORRIDOR WALL VALUES
OCCUPANCY
CATEGORIES
a a
b a
c a
d a
A-1
-10
-4
0
2
A-2
-30
-12
0
2
A-3,
F, M, R, S-1
-7
-3
0
2
A-4,
B, E, S-2
-5
-2
0
5
a
Corridors not providing at least one-half the travel distance for
all occupants on a floor shall be category b.
3412.6.5.1 Categories.
The categories for Corridor
Walls are:
1. Category a — No fire
partitions; incomplete fire partitions; no doors; or doors not
self-closing.
2. Category b — Less
than one (1) hour fire-resistance rating or not constructed in
accordance with section 708.4.
3. Category c — One (1)
hour to less than two (2) hour fire-resistance rating, with doors
conforming to section 716 or without corridors as permitted by
section 1020.
4. Category d — Two (2)
hour or greater fire-resistance rating, with doors conforming to
section 716.
3412.6.6 Vertical openings.
Evaluate the fire-resistance
rating of exit enclosures, hoistways, escalator openings, and other
shaft enclosures within the building, and openings between two (2) or
more floors. Table 3412.6.6(1) contains the appropriate protection
values. Multiply that value by the construction type factor found in
Table 3412.6.6(2). Enter the vertical opening value and its sign
(positive or negative) in Table 3412.7 under Safety Parameter
3412.6.6, Vertical Openings, for fire safety, means of egress, and
general safety. If the structure is a one (1) story building or if
all the unenclosed vertical openings within the building conform to
the requirements of section 708, enter a value of two (2). The
maximum positive value for this requirement shall be two (2).
TABLE
3412.6.6(1)
VERTICAL OPENING PROTECTION VALUE
Protection
Value
None
(unprotected
opening)
-2
times number floors connected
Less
than 1 hour
-1
times floors connected
1
to less than 2 hours
1
2
hours or more
2
TABLE
3412.6.6(2)
CONSTRUCTION-TYPE FACTOR
FACTOR
TYPE
OF CONSTRUCTION
IA
IB
IIA
IIB
IIIA
IIIB
IV
VA
VB
1.2
1.5
2.2
3.5
2.5
3.5
2.3
3.3
7
3412.6.6.1 Vertical opening
formula.
The following formula shall be
used in computing vertical opening value.
VO = PV × CF (Equation
34-5)
Where:
VO = Vertical opening value.
PV = Protection value [Table
3412.6.6(1)].
CF = Construction type factor
[Table 3412.6.6(2)].
3412.6.7 HVAC systems.
Evaluate the ability of the
HVAC system to resist the movement of smoke and fire beyond the point
of origin. Under the categories in section 3412.6.7.1, determine the
appropriate value and enter that value into Table 3412.7 under Safety
Parameter 3412.6.7, HVAC Systems, for fire safety, means of egress
and general safety.
3412.6.7.1 Categories.
The categories for HVAC
systems are:
1. Category a
Plenums not in accordance
with section 602 of the International Mechanical Code. – ten
(10) points.
2. Category b
Air movement in egress
elements not in accordance with section 1020.5 – five (5)
points.
3. Category c
Both categories a and b are
applicable. – fifteen (15) points.
4. Category d
Compliance of the HVAC system
with section 1020.5 and section 602 of the International Mechanical
Code. Zero (0) points.
5. Category e
Systems serving one story; or
a central boiler/chiller system without ductwork connecting two (2)
or more stories. Five (5) points.
3412.6.8 Automatic fire
detection.
Evaluate the smoke detection
capability based on the location and operation of automatic fire
detectors in accordance with section 907 and the International
Mechanical Code. Under the categories and occupancies in Table
3412.6.8, determine the appropriate value and enter that value into
Table 3412.7 under Safety Parameter 3412.6.8, Automatic Fire
Detection, for fire safety, means of egress and general safety.
TABLE
3412.6.8
AUTOMATIC FIRE DETECTION VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
A-1,
A-3, F, M, R, S-1
-10
-5
0
2
6
A-2
-25
-5
0
5
9
A-4,
B, E, S-2
-4
-2
0
4
8
3412.6.8.1 Categories.
The categories for automatic
fire detection are:
1. Category a
None.
2. Category b
Existing smoke detectors in
HVAC systems and maintained in accordance with the International Fire
Code.
3. Category c
Smoke detectors in HVAC
systems. The detectors are installed in accordance with the
requirements for new buildings in the International Mechanical Code.
4. Category d
Smoke detectors throughout
all floor areas other than individual sleeping units, tenant spaces
and dwelling units.
5. Category e
Smoke detectors installed
throughout the floor area.
3412.6.9 Fire alarm systems.
Evaluate the capability of
the fire alarm system in accordance with section 907. Under the
categories and occupancies in Table 3412.6.9, determine the
appropriate value and enter that value into Table 3412.7 under Safety
Parameter 3412.6.9, Fire Alarm Systems, for fire safety, means of
egress and general safety.
TABLE
3412.6.9
FIRE ALARM SYSTEM VALUES
OCCUPANCY
CATEGORIES
a
b a
c
D
A-1,
A-2, A-3, A-4, B, E, R
-10
-5
0
5
F,
M, S
0
5
10
15
For
buildings equipped throughout with an automatic sprinkler system,
add 2 points for activation by a sprinkler waterflow device.
3412.6.9.1 Categories.
The categories for fire alarm
systems are:
1. Category a
None.
2. Category b
Fire alarm system with manual
fire alarm boxes in accordance with section 907.4 and alarm
notification appliances in accordance with section 907.5.2.
3. Category c
Fire alarm system in
accordance with section 907.
4. Category d
Category c plus a required
emergency voice/alarm communications system and a fire command center
that conforms to section 403.4.6 and contains the emergency
voice/alarm communications system controls, fire department
communication system controls and any other controls specified in
section 911 where those systems are provided.
3412.6.10 Smoke control.
Evaluate the ability of a
natural or mechanical venting, exhaust or pressurization system to
control the movement of smoke from a fire. Under the categories and
occupancies in Table 3412.6.10, determine the appropriate value and
enter that value into Table 3412.7 under Safety Parameter 3412.6.10,
Smoke Control, for means of egress and general safety.
TABLE
3412.6.10
SMOKE CONTROL VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
f
A-1,
A-2, A-3
0
1
2
3
6
6
A-4,
E
0
0
0
1
3
5
B,
M, R
0
2 a
3 a
3 a
3 a
4 a
F,
S
0
2 a
2 a
3 a
3 a
3 a
a
This value shall be 0 if compliance with Category d or e in
Section 3412.6.8.1 has not been obtained.
3412.6.10.1 Categories.
The categories for smoke
control are:
1. Category a
None.
2. Category b
The building is equipped
throughout with an automatic sprinkler system. Openings are provided
in exterior walls at the rate of twenty (20) square feet (1.86 m2)
per fifty (50) linear feet (15,240 mm) of exterior wall in each story
and distributed around the building perimeter at intervals not
exceeding fifty (50) feet (15,240 mm). Such openings shall be readily
openable from the inside without a key or separate tool and shall be
provided with ready access thereto. In lieu of operable openings,
clearly and permanently marked tempered glass panels shall be used.
3. Category c
One (1) enclosed exit
stairway, with ready access thereto, from each occupied floor of the
building. The stairway has operable exterior windows and the building
has openings in accordance with Category b.
4. Category d
One (1) smokeproof enclosure
and the building has openings in accordance with Category b.
5. Category e
The building is equipped
throughout with an automatic sprinkler system. Each floor area is
provided with a mechanical air-handling system designed to accomplish
smoke containment. Return and exhaust air shall be moved directly to
the outside without recirculation to other floor areas of the
building under fire conditions.
The system shall exhaust not
less than six (6) air changes per hour from the floor area. Supply
air by mechanical means to the floor area is not required.
Containment of smoke shall be considered as confining smoke to the
floor area involved without migration to other floor areas. Any other
tested and approved design which will adequately accomplish smoke
containment is permitted.
6. Category f
Each stairway shall be one of
the following: a smokeproof enclosure in accordance with section
1023.11; pressurized in accordance with section 909.20.5 or shall
have operable exterior windows
3412.6.11 Means of egress
capacity and number.
Evaluate the means of egress
capacity and the number of exits available to the building occupants.
In applying this section, the means of egress are required to conform
to the following sections of this code: 1003.7, 1004, 1005, 1006,
1007, 1016.2, 1025.1, 1028.2, 1028.5 1029.2 1029.3 1029.4 and 1030.
The number of exits credited is the number that is available to each
occupant of the area being evaluated. Existing fire escapes shall be
accepted as a component in the means of egress when conforming to
section 3406. Under the categories and occupancies in Table
3412.6.11, determine the appropriate value and enter that value into
Table 3412.7 under Safety Parameter 3412.6.11, Means of Egress
Capacity, for means of egress and general safety.
TABLE
3412.6.11
MEANS OF EGRESS VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
A-1,
A-2, A-3, A-4, E
-10
0
2
8
10
M
-3
0
1
2
4
B,
F, S
-1
0
0
0
0
R
-3
0
0
0
0
a
The values indicated are for buildings six stories or less in
height. For buildings over six stories above grade plane, add an
additional -10 points.
3412.6.11.1 Categories.
The categories for Means of
Egress Capacity and number of exits are:
1. Category a
Compliance with the minimum
required means of egress capacity or number of exits is achieved
through the use of a fire escape in accordance with section 3406.
2. Category b
Capacity of the means of
egress complies with section 1004 and the number of exits complies
with the minimum number required by section 1006.
3. Category c
Capacity of the means of
egress is equal to or exceeds one hundred twenty-five percent (125%)
of the required means of egress capacity, the means of egress
complies with the minimum required width dimensions specified in the
code and the number of exits complies with the minimum number
required by section 1006.
4. Category d
The number of exits provided
exceeds the number of exits required by section 1006. Exits shall be
located a distance apart from each other equal to not less than that
specified in section 1007.1.
5. Category e
The area being evaluated
meets both Categories c and d.
3412.6.12 Dead ends.
In spaces required to be
served by more than one (1) means of egress, evaluate the length of
the exit access travel path in which the building occupants are
confined to a single path of travel. Under the categories and
occupancies in Table 3412.6.12, determine the appropriate value and
enter that value into Table 3412.7 under Safety Parameter 3412.6.12,
Dead Ends, for means of egress and general safety.
TABLE
3412.6.12
DEAD-END VALUES
OCCUPANCY
CATEGORIES a
a
b
c
A-1,
A-3, A-4, B, E, F, M, R, S
-2
0
2
A-2,
E
-2
0
2
a
For dead-end distances between categories, the dead-end value
shall be obtained by linear interpolation.
3412.6.12.1 Categories.
The categories for dead ends
are:
1. Category a
Dead end of thirty-five feet
(35’) (10,670 mm) in non-sprinklered buildings or seventy feet
(70’) (21,340 mm) in sprinklered buildings.
2. Category b
Dead end of twenty feet (20’)
(6,096 mm); or fifty feet (50’) (15,240 mm) in Group B in
accordance with section 1020.4, exception 2.
3. Category c
No dead ends; or ratio of
length to width (l/w) is less than two and one half to one (2.5:1).
3412.6.13 Maximum exit access
travel distance.
Evaluate the length of exit
access travel to an approved exit. Determine the appropriate points
in accordance with the following equation and enter that value into
Table 3412.7 under Safety Parameter 3412.6.13, Maximum Exit Access
Travel Distance, for means of
egress and general safety. The maximum allowable exit access travel
distance shall be determined in accordance with section 1017.1.
3412.6.14 Elevator control.
Evaluate the passenger
elevator equipment and controls that are available to the fire
department to reach all occupied floors. Emergency recall and in-car
operation of elevator recall controls shall be provided in accordance
with the International Fire Code. Under the categories and
occupancies in Table 3412.6.14, determine the appropriate value and
enter that value into Table 3412.7 under Safety Parameter 3412.6.14,
Elevator Control, for fire safety, means of egress and general
safety. The values shall be zero (0) for a single-story building.
TABLE
3412.6.14
ELEVATOR CONTROL VALUES
ELEVATOR
TRAVEL
CATEGORIES
a
b
c
d
Less
than 25 feet of travel above or below the primary level of
elevator access for emergency fire-fighting or rescue personnel
-2
0
0
+2
Travel
of 25 feet or more above or below the primary level of elevator
access for emergency fire-fighting or rescue personnel
-4
NP
0
+4
For
SI: 1 foot = 304.8 mm.
NP = Not Permitted
3412.6.14.1 Categories.
The categories for elevator
controls are:
1. Category a
No elevator.
2. Category b
Any elevator without Phase I
emergency recall operation and Phase II emergency in-car operation.
3. Category c
All elevators with Phase I
emergency recall operation and Phase II emergency in-car operation as
required by the International Fire Code.
4. Category d
All meet Category c; or
Category b where permitted to be without Phase I emergency recall
operation and Phase II emergency in-car operation; and at least one
(1) elevator that complies with new construction requirements serves
all occupied floors.
3412.6.15 Means of egress
emergency lighting.
Evaluate the presence of and
reliability of means of egress emergency lighting. Under the
categories and occupancies in Table 3412.6.15, determine the
appropriate value and enter that value into Table 3412.7 under Safety
Parameter 3412.6.15, Means of Egress Emergency Lighting, for means of
egress and general safety.
TABLE
3412.6.15
MEANS OF EGRESS EMERGENCY LIGHTING VALUES
NUMBER
OF EXITS REQUIRED BY SECTION 1015
CATEGORIES
a
b
C
Two
or more exits
NP
0
4
Minimum
of one exit
0
1
1
3412.6.15.1 Categories.
The categories for means of
egress emergency lighting are:
1. Category a
Means of egress lighting and
exit signs not provided with emergency power in accordance with
Chapter 27.
2. Category b
Means of egress lighting and
exit signs provided with emergency power in accordance with Chapter
27.
3. Category c
Emergency power provided to
means of egress lighting and exit signs which provides protection in
the event of power failure to the site or building.
3412.6.16 Mixed occupancies.
Where a building has two (2)
or more occupancies that are not in the same occupancy
classification, the separation between the mixed occupancies shall be
evaluated in accordance with this section. Where there is no
separation between the mixed occupancies or the separation between
mixed occupancies does not qualify for any of the categories
indicated in section 3412.6.16.1, the building shall be evaluated as
indicated in section 3412.6 and the value for mixed occupancies shall
be zero (0). Under the categories and occupancies in Table 3412.6.16,
determine the appropriate value and enter that value into Table
3412.7 under Safety Parameter 3412.6.16, Mixed Occupancies, for fire
safety and general safety. For buildings without mixed occupancies,
the value shall be zero (0).
TABLE
3412.6.16
MIXED OCCUPANCY VALUES a
OCCUPANCY
CATEGORIES
a
b
c
A-1,
A-2, R
-10
0
10
A-3,
A-4, B, E, F, M, S
-5
0
5
a
For fire-resistance ratings between categories, the value shall be
obtained by linear interpolation.
3412.6.16.1 Categories.
The categories for mixed
occupancies are:
1. Category a
Occupancies separated by
minimum one (1) hour fire barriers or minimum one (1) hour horizontal
assemblies, or both.
2. Category b
Separations between
occupancies in accordance with section 508.4.
3. Category c
Separations between
occupancies having a fire-resistance rating of not less than twice
that required by section 508.4.
3412.6.17 Automatic
sprinklers.
Evaluate the ability to
suppress a fire based on the installation of an automatic sprinkler
system in accordance with section 903.3.1.1. “Required
sprinklers” shall be based on the requirements of this code.
Under the categories and occupancies in Table 3412.6.17, determine
the appropriate value and enter that value into Table 3412.7 under
Safety Parameter 3412.6.17, Automatic Sprinklers, for fire safety,
means of egress divided by two (2) and general safety.
TABLE
3412.6.17
SPRINKLER SYSTEM VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
f
A-1,
A-3, F, M, R, S-1
-6
-3
0
2
4
6
A-2
-4
-2
0
1
2
4
A-4,
B, E, S-2
-12
-6
0
3
6
12
3412.6.17.1 Categories.
The categories for automatic
sprinkler system protection are:
1. Category a
Sprinklers are required
throughout; sprinkler protection is not provided, or the sprinkler
system design is not adequate for the hazard protected in accordance
with section 903.
2. Category b
Sprinklers are required in a
portion of the building; sprinkler protection is not provided, or the
sprinkler system design is not adequate for the hazard protected in
accordance with section 903.
3. Category c
Sprinklers are not required;
none are provided.
4. Category d
Sprinklers are required in a
portion of the building; sprinklers are provided in such portion; the
system is one which complied with the code at the time of
installation and is maintained and supervised in accordance with
section 903.
5. Category e
Sprinklers are required
throughout; sprinklers are provided throughout in accordance with
Chapter 9.
6. Category f
Sprinklers are not required
throughout; sprinklers are provided throughout in accordance with
Chapter 9.
3412.6.18 Standpipes.
Evaluate the ability to
initiate attack on a fire by making a supply of water available
readily through the installation of standpipes in accordance with
section 905. Required standpipes shall be based on the requirements
of this code. Under the categories and occupancies in Table
3412.6.18, determine the appropriate value and enter that value into
Table 3412.7 under Safety Parameter 3412.6.18, Standpipes, for fire
safety, means of egress and general safety.
TABLE
3412.6.18
STANDPIPE SYSTEM VALUES
OCCUPANCY
CATEGORIES
a a
b
c
d
A-1,
A-3, F, M, R, S-1
-6
0
4
6
A-2
-4
0
2
4
A-4,
B, E, S-2
-12
0
6
12
a
This option cannot be taken if Category a or b in Section
3412.6.17 is used.
3412.6.18.1 Standpipe.
The categories for standpipe
systems are:
1. Category a
Standpipes are required;
standpipe is not provided, or the standpipe system design is not in
compliance with section 905.3.
2. Category b
Standpipes are not required;
none are provided.
3. Category c
Standpipes are required;
standpipes are provided in accordance with section 905.
4. Category d
Standpipes are not required;
standpipes are provided in accordance with section 905.
3412.6.19 Incidental uses.
Evaluate the protection of
incidental uses in accordance with section 509.4.2. Do not include
those where this code requires automatic sprinkler systems throughout
the buildings, including covered or open mall buildings, high-rise
buildings, public garages and unlimited area buildings. Assign the
lowest score from Table 3412.6.19 for the building or floor area
being evaluated and enter that value into Table 3412.7 under safety
Parameter 3412.6.19, Incidental Use Area, for fire safety, means of
egress and general safety. If there are no specific occupancy areas
in the building or floor area being evaluated, the value shall be
zero (0).
TABLE
3412.6.19
INCIDENTAL USE AREA VALUES a
PROTECTION
REQUIRED BY TABLE 509
PROTECTION
PROVIDED
None
1
Hour
AS
AS
with SP
1
Hour and AS
2
Hours
2
Hours and AS
2
Hours and AS
-4
-3
-2
-2
-1
-2
0
2
Hours, or 1 Hour and AS
-3
-2
-1
-1
0
0
0
1
Hour and AS
-3
-2
-1
-1
0
-1
0
1
Hour
-1
0
-1
0
0
0
0
1
Hour, or AS with SP
-1
0
-1
0
0
0
0
AS
with SP
-1
-1
-1
0
0
-1
0
1
Hour or AS
-1
0
0
0
0
0
0
a
AS = Automatic sprinkler system; SP = Smoke partitions Note: For
table 3412.7, see next page.
3412.7 Building score.
After determining the
appropriate data from section 3412.6, enter those data in Table
3412.7 and total the building score.
TABLE
3412.7
SUMMARY SHEET-BUILDING CODE
Existing
occupancy:_______________________ Proposed
occupancy:____________________
Year
Building was constructed:______________ Number of
stories:_____ Height in feet:______
Type
of construction:______________________ Area per
floor:__________________________
Percentage
of open perimeter increase:_______%
Completely
suppressed: Yes____ No____ Corridor wall
rating:______________________
Compartmentation:
Yes____ No____ Required door closers:
Yes____ No____
Fire-resistance
rating of vertical opening
enclosures:______________________________________
Type
of HVAC system:________________________, serving number of
floors:_________________
Automatic
fire detection: Yes____ No____ Type and
location:_______________________
Fire
alarm system: Yes____ No____
Type:_________________________________
Smoke
control: Yes____ No____
Type:_________________________________
Adequate
exit routes: Yes____ No____ Dead
ends:___________ Yes____ No____
Maximum
exit access travel distance:__________________ Elevator
controls: Yes____ No____
Means
of egress emergency lighting: Yes____ No____ Mixed
occupancies: Yes____ No____
SAFETY
PARAMETERS
FIRE
SAFETY (FS)
MEANS
OF EGRESS (ME)
GENERAL
SAFETY (GS)
3412.6.1
Building Height
3412.6.2 Building Area
3412.6.3
Compartmentation
3412.6.4
Tenant and Dwelling Unit Separations
3412.6.5 Corridor
Walls
3412.6.6 Vertical Openings
3412.6.7
HVAC Systems
3412.6.8 Automatic Fire Detection
3412.6.9
Fire Alarm Systems
3412.6.10
Smoke Control
3412.6.11 Means of Egress Capacity
3412.6.12
Dead Ends
*
* * *
* * * *
* * * *
3412.6.13
Maximum Exit Access Travel Distance
3412.6.14 Elevator
Control
3412.6.15 Means of Egress Emergency Lighting
*
* * *
*
* * *
3412.6.16
Mixed Occupancies
3412.6.17 Automatic Sprinklers
3412.6.18
Standpipes
3412.6.19 Incidental Use
* * * *
÷ 2 =
Building
score – total value
****No
applicable value to be inserted.
3412.8 Safety scores.
The values in Table 3412.8
are the required mandatory safety scores for the evaluation process
listed in section 3412.6.
TABLE
3412.8
MANDATORY SAFETY SCORES a
OCCUPANCY
FIRE
SAFETY (MFS)
MEANS
OF EGRESS (MME)
GENERAL
SAFETY (MGS)
A-1
20
31
31
A-2
21
32
32
A-3
22
33
33
A-4,
E
29
40
40
B
30
40
40
F
24
34
34
M
23
40
40
R
21
38
38
S-1
19
29
29
S-2
29
39
39
a
MFS = Mandatory Fire Safety;
MME = Mandatory Means of
Egress;
MGS = Mandatory General Safety.
3412.9 Evaluation of building
safety.
The mandatory safety score in
Table 3412.8 shall be subtracted from the building score in Table
3412.7 for each category. Where the final score for any category
equals zero (0) or more, the building is in compliance with the
requirements of this section for that category. Where the final score
for any category is less than zero (0), the building is not in
compliance with the requirements of this section.
TABLE
3412.9
EVALUATION
FORMULAS a
FORMULA
T3412.7
T
3412.8
SCORE
PASS
FAIL
FS
– MFS ≥ 0
(FS)
-
(MFS)
=
ME
– MME ≥ 0
(ME)
-
(MME)
=
GS
– MGS ≥ 0
(GS)
-
(MGS)
=
a
FS = Fire Safety
ME
= Means of Egress
GS
= General Safety
a
MFS = Mandatory Fire Safety
MME
= Mandatory Means of Egress
MGS
= Mandatory General Safety
3412.9.1 Mixed occupancies.
For mixed occupancies, the
following provisions shall apply:
1. Where the separation
between mixed occupancies does not qualify for any category indicated
in section 3412.6.16, the mandatory safety scores for the occupancy
with the lowest general safety score in Table 3412.8 shall be
utilized (see section 3412.6).
2. Where the separation
between mixed occupancies qualifies for any category indicated in
section 3412.6.16, the mandatory safety scores for each occupancy
shall be placed against the evaluation scores for the appropriate
occupancy.
1.25 Chapter 35: Referenced
Standards
To
IBC Chapter 35 add the following General Statement:
The
various State of Rhode Island departments and agencies have
designated powers to adopt and enforce Regulations impacting new and
existing construction. Users of this code are advised to use all
available resources to coordinate the design and approval process.
1.26 Appendices
Delete
Appendices A, B, D, J. & K.
Retain
Appendices C, E, G, H, I.
Appendix
F is permitted to be enforced on a discretionary basis by the local
building code official, when in his opinion, existing site and
environmental conditions warrant additional protective measures
specified herein.
1.27 Appendix G
FLOOD
RESISTANT CONSTRUCTION
Add
the following section to Appendix G105.1 General
G105.1.1 Notice.
Upon receipt of an
application for a variance the Chairman of the Board of Appeals shall
forward a copy of said application to the Rhode Island Emergency
Management Office, Attention: Statewide Flood-Plain Coordinator.