510-RICR-00-00-2
510-RICR-00-00-2. RISBC-2 Rhode Island State One and Two Family Dwellings (version Amendment, 08/01/2019 to 01/04/2022)
2.1 Authority
The Building Code Standards
Committee, in accordance with the rule making authority of R.I. Gen.
Laws § §
23-27.3-109.1 (a) through (c) inclusive, has formally adopted and
promulgated as the Rhode Island State Building Code, the provisions
of the International Building Code, 2015 edition, as published by the
International Code Council, Inc. (I.C.C.), together with amendments
thereto hereinafter set forth to the articles and sections of this
code:
2.2 Incorporated Materials
A. The provisions of R.I. Gen.
Laws Chapter 23-27.3 establishing administration and enforcement are
hereby incorporated by reference. § 2.3 of this Part (Chapter 1:
Administration) immediately follows and is supplemental to the
General Laws. Editorial Note: Code users please note:
1. When purchasing or using
the IRC 2015 code, please take note of the particular printing
edition. Errata to that printing edition is available on-line
directly at no charge at www.iccsafe.org/cs/codes/pages/errata.aspx
or call the office of the State Building Code Commissioner at
401-889-5550 for further information.
2. Printed copies of the
administrative and enforcement provisions of R.I. Gen. Laws Chapter
23-27.3 are available at the Office of the State Building Code
Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM
3. The International
Residential Code, 2015 Edition, is protected by the copyright that
has been issued to the ICC. As a result, the State Building Code is
not available in complete form to the public in an electronic format.
The International Residential Code 2015 edition that is referred to
within is contained in a printed volume and is also in an electronic
format that have been published by the ICC under an exclusive
license.
2.3 Chapter
1: Administration
R101.1 Delete
and substitute the following:
R101.1 Title.
These provisions shall be
known as the Rhode Island One and Two-Family Dwelling Code SBC-2-2019
and shall be cited as such and will be referred to herein as “this
code”.
R101.2
Delete and substitute the following:
R101.2 Scope.
The provisions of this code
shall apply to the construction, alteration, enlargement,
replacement, repair, equipment, use and occupancy and location of
detached one-and two-family dwellings and multiple single-family
dwellings (townhouses) not more than three stories in height with a
separate means of egress, and their accessory structures.
Exception: Existing one and
two-family buildings undergoing a change of use shall comply with the
provisions of the State Building Code SBC-1-2019 ( Part
1 of this Subchapter ) or State Rehabilitation Code
SRC-1-2019 ( Part
20 of this Subchapter ) as applicable.
R101.3
Delete and Substitute the following
R101.3 Intent.
The purpose of this code is
to establish minimum requirements to safeguard the public safety,
health and general welfare through affordability, structural
strength, means of egress facilities, stability, sanitation, light
and ventilation, energy conservation and safety to life and property
from fire and other hazards attributed to the built environment.
R102.5
Delete and substitute the following:
R102.5 Appendices
Appendices A, B, C, D, F, N,
P, U and RP are informative only and not part of this code.
Appendices E, G, H, J, K, M,
O, R and S apply.
Appendices I, L, and Q are
deleted.
New RI Appendix AA is added.
R102.7
Delete and substitute the following:
R102.7 Existing structures.
The legal occupancy of any
structure existing on the date of adoption of this code shall be
permitted to continue without change, except as specifically covered
in this code or as is deemed necessary by the building official for
the general safety and welfare of the occupants and the public.
R105.2
Delete R105.2 and substitute the following:
R105.2 Work exempt from
permit.
Permits shall not be required
for the following.
Exemption from the permit
requirements of this code shall not be deemed to grant authorization
for any work to be done in any manner in violation of the provisions
of this code or any other laws or ordinances of this jurisdiction.
Building:
1. One-story detached
accessory structures provided the floor area does not exceed 64
square feet (18.58 m 2 ).
2. Fences not over 6 feet
(1829 mm) high.
3. Retaining walls that are
not over 32” in height measured from the lower finished grade
to the top of the wall, unless supporting a surcharge.
Exception
1. All cast-in-place concrete
retaining walls greater than 24” in height shall require a
permit.
2. All engineered masonry
retaining wall systems shall be installed in accordance with
manufacturer’s installation instructions
3. Water tanks supported
directly upon grade if the capacity does not exceed 5,000 gallons (18
927L) and the ratio of height to diameter or width does not exceed 2
to 1.
4. Sidewalks and driveways not
more than 30 inches (762 mm) above adjacent grade and not over any
basement or story below.
5. Painting, papering, tiling,
carpeting, cabinets, counter tops and similar finish work.
6. Prefabricated swimming
pools that are less than 24 inches (610mm) deep, and man-made
landscape ponds of any depth.
7. Swings and other playground
equipment and play structures less than 64 square feet.
8. Window awnings supported by
an exterior wall.
9. Replacement window sash
installations.
Exception:
Replacement window
installations that include a frame and sash(es) require a permit.
Electrical:
Maintenance: A permit shall
not be required for replacement of lamps, receptacles, devices, or
fixtures, including the connection of portable electrical equipment
to approved permanently installed receptacle.
Gas:
1. Replacement of any minor
part or appliance that does not alter approval of equipment or make
such equipment unsafe.
Mechanical:
1. Portable heating appliance.
2. Portable ventilation
appliances.
3. Portable cooling unit.
4. Steam, hot or chilled water
piping within any heating or cooling equipment regulated by this
code.
5. Replacement of any minor
part that does not alter approval of equipment or make such equipment
unsafe.
6. Portable evaporative
cooler.
7. Self-contained
refrigeration systems containing 10 pounds (4.54 kg) or less of
refrigerant or that are actuated by motors of 1 horsepower (746 W) or
less.
Plumbing:
The stopping of leaks in
drains, water, soil, waste or vent pipe; provided, however, that if
any concealed trap, drainpipe, water, soil, waste or vent pipe
becomes defective and it becomes necessary to remove and replace the
same with new material, such work shall be considered as new work and
a permit shall be obtained and inspection made as provided in this
code.
The clearing of stoppages or
the repairing of leaks in pipes, valves or fixtures, and the removal
and reinstallation of water closets, provided such repairs do not
involve or require the replacement or rearrangement of valves, pipes
or fixtures.
R105.3.1.1 Delete
and substitute the following:
R105.3.1.1 Substantially
improved or substantially damaged existing buildings or structures.
For application for
reconstruction, rehabilitation, addition, or other improvement of
existing buildings or structures located in an area prone to flooding
as established by Table R301.2(1) and community FIRM documents, the
value of the proposed work or repair shall be provided by the owner
or authorized agent and reviewed by the Building Official. If the
Building Official determines that the proposed work equals or exceeds
50% of the market value of the building or structure, shall comply
with the new code.
R107 Delete
Section R 107 in its entirety and substitute the following new
section R107 Fabric Structures.
Section R107 Fabric Structures
R107.1 Fabric Structures:
Fabric structures shall be
located in accordance with applicable local zoning code provisions.
Permits shall be required for any structure over 200 sq. ft. in area
and shall be installed in accordance with manufacturer’s
installation instructions. Fabric structures over 200 sq. ft. in area
but less than 400 sq. ft. in area shall have engineered wind anchors
installed to withstand design wind loads and shall not remain in
place for more than 6 months in any 12-consecutive month period. All
structures over 400 sq. ft. and/or intended to be in place for more
than a 12-month period, shall only be approved pending a satisfactory
decision by the local Building Code Board of Appeals, unless full
code compliance for permanent structures in all respects is
demonstrated to the satisfaction of the local building official.
R110.2
Delete R110.2 and substitute the following:
R110.2 Change of Use.
Change of use shall only be
made in accordance with the provisions of the State Building Code
SBC-1 ( Part
1 of this Subchapter ).
Delete
R110.3 #8 without substitution
Add
the following section R115:
R115 Other
R115.1 Other Administrative
issues.
The Administrative provisions
of R.I. Gen. Laws Chapter 23-27.3 are included herein into the
balance of § 2.3 of this Part (Chapter 1 Administration).
Delete
the following IRC 2015 sections and refer to appropriate R.I. Gen.
Laws Chapter 23-27.3
R103.1, R103.2, R103.3,
R104.6, R104.7, R104.8, R105.2.2, R105.3.1, R105.3.2, R105.4, R105.5,
R105.6, R105.7, R106.3.1, R106.3.2, R106.3.3, R106.5, R107.1, R107.2,
R107.3, R107.4, R108.1, R108.2, R108.3, R108.4, R108.5, R108.6,
R112.1, R112.2, R112.2.1, R112.2.2, R112.3, R112.4, R113.1, R113.2,
R113.3, R113.4, R114.1, R114.2.
Retain
the following IRC 2015 Sections:
R101.3, R102.1, R102.2,
R102.3, R102.4, R102.6, R104.10, R102.7.1, R104.1, R104.2, R104.3,
R104.4, R104.5, R104.9, R104.9.1, R104.10.1, R104.11, R104.11.1,
R105.1, R105.2.1, R105.2.3, R105.3, R105.8, R106.1, R106.1.1,
R106.1.2, R106.1.3, R106.2, R106.3, R106.4, R109.1, R109.1.1,
R109.1.2, R109.1.3, R109.1.4, R109.1.5, R109.1.5.1, R109.1.6, R109.2,
R109.3, R109.4, R110.1, R110.3, R110.4, R111.1, R111.2, R111.3.
2.4 Chapter
2
To
Chapter 2 Definitions. Delete and Substitute the following:
"Accessory Structure"
means in one- and two-family dwellings not more than three stories
high with separate means of egress, a building, the use of which is
incidental to that of the main building and which is located on the
same lot.
"Fabric Structure"
means structures utilizing wood, metal or plastic frames and covered
with cloth, canvas, or plastic material, excluding tents,
agricultural greenhouses, and furnishings such as umbrellas, awnings
or portable shade canopies, and accessory to the residential use of
the primary structure. If used for non-residential accessory use,
see State Building Code SBC-1-2019 ( Part
1 of this Subchapter ).
"Sleeping Unit"
means a room or space in which people sleep, which can also include
permanent provisions for living, eating, and either sanitation or
kitchen facilities but not both. Such rooms and spaces that are also
part of a dwelling unit are not sleeping units.
2.5 Chapter 3
R301.2
Delete and substitute the following:
R301.2 Climatic and geographic
designs criteria.
Buildings shall be
constructed in accordance with the provisions of this code.
Additional criteria are established and set forth in Table R301.2(1)
Table R301.2(1) Delete and
substitute the following:
Table
R301.2(1)
Ground
Snow Load
Wind
Topographic
Effects
Seismic
Design Criteria
30psf
1, 2
See
figure R301.2(4)
No
None 4
Weathering
Frost
line depth 2, 3
Termite
Decay
Severe
40”
Moderate
to Heavy
Slight
to Moderate
Winter
design Temp
Ice
Shield Underlayment Required
Flood
Hazards
Air
Freezing Index
Mean
Temperature Annual
0
degrees F in Prov. County 5 degrees All Other
Yes
Yes
(See Community FIRMS)
1200-degree
Days B.F.
50
degrees F
NOTES:
1. Roof live load and roof
snow load are not additive
2. New Shoreham frost depth is
30” and Ground Snow Load is 25 psf.
3. Requirements for frost
depth footings for accessory attached and detached structures are as
follows:
a. Structures and detached
accessory buildings of 0-199 sq. feet do not require any frost depth
foundations or footings. Two ground screw anchors or other means
approved by the building official shall be provided to resist
overturning.
b. Accessory attached
structures such as decks, platforms or landings shall have footings
extending to 3’-4” below grade. Exterior stairs and steps
off decks, balconies and platforms greater than 30” above grade
shall have stringer supports extending to 12” below grade and
shall be supported and secured to prevent lateral displacement or
vertical collapse due to grade changes.
4. Seismic design criteria are
not required for buildings and structures regulated by this code.
R301.2.1 Delete
and substitute the following:
R301.2.1 Wind limitations.
Buildings and portions
thereof shall be limited by wind speed, as defined in Table
R301.2(1), and construction methods in accordance with this code.
Basic wind speeds shall be determined from Table R301.2(1) and Figure
R301.2(4) A & B. Where different construction methods and
structural materials are used for various portions of a building, the
applicable requirements of this sections for each portion shall
apply. Where loads for windows, skylights and exterior doors are not
otherwise specified, the loads listed in Table R301.2(2) adjusted for
height and exposure per Table R301.2(3), shall be used to determine
design load performance requirements for windows and doors.
Exception: All accessory
structures less than 200 sq. ft. in area.
R301.2.1.1 Delete and
substitute the following:
R301.2.1.1 Design criteria.
Construction in regions where
the ultimate wind speeds from Figure 301.2(4)(A) equal or exceed 110
miles per hour (177.1 km/h) shall be designed in accordance with one
of the following:
1. American Forest and Paper
Association (AF&PA) Wood Frame Construction Manual for One- and
Two-Family Dwellings (WFCM); or
2. Southern Building Code
Congress International Standard for Hurricane Resistant Residential
Construction (SSTD 10); or
3. International Code Council
(ICC) Standard for Residential Construction in High Wind Regions
(ICC-600); or
4. Hurricane Resistant
Residential Construction (SSTD 10); or Minimum Design Loads for
Buildings and Other Structures (ASCE-7);
5. Cold-formed steel
construction shall be designed in accordance with the provisions of
this code.
6. Concrete construction shall
be designed in accordance with the provisions of this code.
7. Structural insulated panel
(SIP) walls shall be designed in accordance with the provisions of
this code.
8. For all communities located
in the 110 MPH and 120 MPH wind zones, the prescriptive criteria in
Appendix AA may be used for buildings and structures in lieu of 1-3
above:
Exceptions to item 8:
1. Buildings and structures of
any size in 110 MPH or 120 MPH wind zones located in a V zone as
determined by community FIRMS.
2. Two or more story buildings
and structures of any size located in 120 MPH wind zone with more
than 20% exterior fenestration.
3. Two or more story
structures with a building height greater than 33’ as measured
from Grade Plane to the average height of the highest roof surface.
4. Any two or more-story
structure or building with opening fenestration greater than 40% on
any one wall.
R301.2.1.2
Delete section R301.2.1.2 and substitute the following:
301.2.1.2 Protection of
openings.
Windows in buildings located
in Wind Zone 3 shall have glazed openings protected from windborne
debris or the building shall be designed as a partially enclosed
building in accordance with the International Building Code. Glazed
opening protection for windborne debris shall meet the requirements
of the Large Missile Test of ASTM E 1996 and of ASTM E 1886
referenced therein.
Exception:
Wood structural panels with a
minimum of thickness of 7/16 inch (11.1 mm) and a maximum span of 8
feet (2438 mm) shall be permitted for opening protection in one- and
two-story buildings. Panels shall be precut to cover the glazed
openings with attachment hardware provided. Attachments shall be
provided in accordance with Table R301.2.1.2 or shall be designed to
resist the components and cladding loads determined in accordance
with the provisions of the International Building Code. And shutter
systems approved by Building Code Standards Committee.
Delete
IRC Figures R301.2(4)A and R301.2(4)B and substitute the following:
Delete
without substitution R301.2.1.5 thru R301.2.2.4
Delete
and substitute the following:
R302.1 Exterior walls.
Construction, projections, openings and penetrations of exterior
walls of dwellings and accessory buildings shall comply with Table
R302.1(1); or dwellings equipped throughout with an automatic
sprinkler system installed in guidance with Appendix RP2904 shall
comply with Table R302.1(2).
Delete
section R302.2 exceptions
Add
the following section R302.2 exception and substitute the following:
Exception: A common 2-hour
fire-resistance-rated wall assembly tested in accordance with ASTME
119 or UL 263 is permitted for townhouses if such walls do not
contain plumbing or mechanical equipment, ducts or vents in the
cavity of the common wall. The wall shall be rated for fire exposure
from both sides and shall extend to and be tight against exterior
walls and the underside of the roof sheathing. Electrical
installations shall be installed in accordance with Rhode Island
Electrical Code SBC-5-2019 ( Part
5 of this Subchapter ). Penetrations of electrical
outlet boxes shall be in accordance with Section R302.4.
R302.5.1 Opening protection.
Openings from a private garage directly into a room used for sleeping
purposes shall not be permitted. Other openings between the garage
and residence shall be equipped with solid wood doors not less than 1
3/8 inches (35 mm) in thickness, solid or honeycombed-core steel
doors not less than 1 3/8 inches (35 mm) thick, or 20-minute
fire-rated doors
Add
the following Exception 1 to section R303.1 Habitable rooms.
Exceptions:
The glazed areas need not be
openable where the opening is not required by Section R310 and an
approved mechanical ventilation system capable of producing 0.35 air
change per hour in the room is installed or a whole-house mechanical
ventilation system is installed capable of supplying outdoor
ventilation air of 15 cubic feet per minute (cfm) (78 L/s) per
occupant computed on the basis of two occupants for the first bedroom
and one occupant for each additional bedroom.
Delete
without substitution R303.4 Mechanical ventilation
Delete
without substitution R303.5.2
303.7
Delete section R303.7 and substitute the following:
303.7 Stairway illumination.
All interior and exterior
stairways shall be provided with a means to illuminate the stairs,
including the landings and treads. Interior stairways shall be
provided with an artificial light source located in the immediate
vicinity of each landing of the stairway. Exterior stairways shall be
provided with an artificial light source located in the immediate
vicinity of the top landing of the stairway. Exterior stairways
providing access to a basement from the outside grade level shall be
provided with an artificial light source located in the immediate
vicinity of the bottom landing of the stairway.
Exception:
An artificial light source is
not required at the top and bottom landing, provided an artificial
light source is located directly over each stairway section.
R305.1
Delete R305.1 and substitute the following:
R305.1 Minimum Height.
Habitable rooms, except
kitchens, shall have a ceiling height of not less than 7 feet 6
inches (2286 mm) for at least 50 per cent of their required areas.
Not more than 50 percent of the required area may have a sloped
ceiling less than 7 feet 6 inches (2286 mm) in height with no portion
of the required area less than 5 feet (1524 mm) in height. If any
room has a furred ceiling, the prescribed ceiling height is required
for at least 50 percent of the area thereof, but in no case, shall
the height of the furred ceiling be less than 7 feet (2134 mm)
Exceptions:
1. Beams and girders spaced
not less than 4 feet (1219 mm) on center may project not more than 6
inches (153 mm) below the required ceiling height.
2. All other rooms including
kitchens, baths and hallways may have a ceiling height of not less
than 7 feet (2134 mm) measured to the lowest projection from the
ceiling.
3. Ceiling heights in
basements without habitable spaces may not be less than 6 feet 8
inches (2032 mm) clear except for under beams, girders, ducts or
other obstructions where the clear height shall be 6 feet 4 inches
(1931mm).
4. Bathrooms shall have a
minimum ceiling height of 6 feet 8 inches (2036mm) over the fixture
and at the front clearance area for fixtures as shown in Figure
R307.2. A shower or tub equipped with a showerhead shall have a
minimum ceiling height of 6 feet 8 inches (2036 mm) above a minimum
area 30 inches (762 mm) by 30 inches (762 mm) at the showerhead.
5. Habitable basements used
only as recreation rooms shall have a ceiling height of not less than
7 feet, except for under beams, girders, ducts and soffits, etc.
where the clear height shall be not less than 6’-4”.
6. Existing basements
renovated for habitable rooms except sleeping areas shall have a
minimum ceiling height of 6’-8” except for under beams,
girders, ducts, soffits where the clear height shall be not less than
6’-4”. The required ceiling height of 6’-8”
shall occur over a minimum of 50% of the actual room area.
R307
Add the following new subsection
R-307.3 Privacy required.
Every water closet, bathtub
or shower required by this code shall be installed in a room which
will afford privacy to the occupant.
R309.1
Delete IRC R309.1 and substitute 309.1 as follows:
R309.1 Floor Surface:
Garage and carport floor
surfaces shall be of approved noncombustible material. That area of
floor used for parking of automobiles or other vehicles shall be
sloped to facilitate the movement of liquids toward the main vehicle
entry doorway. Where approved by the building official, other means
of dispersing spilled liquids from the area may be used to prevent
the flow of liquids through doorways into adjoining enclosed areas of
dwelling.
Exception: Floor drains must
discharge to open finish grade only.
The sills of all door
openings between the garage and adjacent interior spaces shall be
raised not less than two inches from above the garage floor, or the
garage floor shall be installed at a lower elevation so as to provide
a minimum four-inch step into the adjacent space.
Remove
without Substitution R309.5
R310.1
Delete R310.1 and substitute the following:
R310.1 Emergency escape and
rescue required.
Basements with habitable
space and every sleeping room shall have at least one openable
emergency escape and rescue window or exterior door opening for
emergency escape and rescue.
Where basements contain one
or more sleeping rooms, emergency egress and rescue openings shall be
required in each sleeping room but shall not be required in adjoining
areas of the basement.
Where openings are provided
as a means of escape and rescue they shall have a sill height of not
more than 44 inches (1118 mm) above the floor.
Where a door opening having a
threshold below the adjacent ground elevation serves as an emergency
escape and rescue opening and is provided with a bulkhead enclosure,
the bulkhead enclosure shall comply with Section R310.3.
The net clear opening
dimensions required by this section shall be obtained by the normal
operation of the window or door opening from the inside.
Escape and rescue window
openings with a finished sill height below the adjacent ground
elevation shall be provided with a window well in accordance with
Section R310.2.
Exception: Basements with
habitable space not used for bedrooms shall not require an emergency
escape under any one of the following two conditions:
1. Residential sprinkler
systems conforming to NFPA 13D or RP 2904 latest edition shall be
installed throughout all areas of the basement or cellar, or
2. Fuel-fired equipment shall
be separated from the habitable room and means of egress with one (1)
hour rated construction and 20 minute rated opening protectives.
R310.1.1 Delete
R310.1.1 and substitute the following:
R310.1.1 Minimum opening area.
All emergency and rescue
openings shall have a minimum net clear opening of 4.4 square feet.
Where the net clear opening dimensions specified below can be met
only with window sashes easily removable without the use of keys,
tools or excessive force, the net clear opening area shall be 5.7
square feet.
R310.6
Add the following new section R310.6
R310.6 Basement or Cellar
Windows:
Except as may be otherwise
provided for habitable or occupiable rooms, at least two (2) operable
windows 12” x 32” nominal size shall be installed
reasonably remote from each other. Security devices shall not
unreasonably impede the use of these windows for light, ventilation
or firefighting purposes.
Delete
R311.3 and substitute the following: R311.3
R311.3 Landings at doors.
There shall be a floor or
landing on each side of each exterior door.
Exception:
Where a stairway of two or
fewer risers is located on the exterior side of a door, other than
the required exit door, a landing is not required for the exterior
side of the door.
The floor or landing at the
exit door required by Section R311.3.1 shall not be more than 1.5
inches (38 mm) lower than the top of the threshold.
The floor or landing at
exterior doors other than the exit door required by Section R311.3.1
shall not be required to comply with this requirement but shall have
a rise no greater than that permitted in Section R311.7.4.
Exception:
The landing at an exterior
doorway shall not be more than 8-1/4 inches (210 mm) below the top of
the threshold, provided the door, other than an exterior storm or
screen door does not swing over the landing.
The width of each landing
shall not be less than the door served. Every landing shall have a
minimum dimension of 36 inches (914mm) measured in the direction of
travel.
Delete
R311.6 and substitute the following:
R311.6 Hallways.
The minimum width of a
hallway shall be not less than 3 feet. Baseboard, casings and other
trim shall not reduce the required width to less than 34-1/2”.
Delete
IRC R311.7.4.1 and R311.7.4.2 and substitute the following:
R311.7.5.1 Riser height.
The maximum riser height
shall be 8-1/4 inches (210 mm).
The riser shall be measured
vertically between leading edges of the adjacent treads.
The greatest riser height
within any flight of stairs shall not exceed the smallest by more
than 3/8 inch (9.5 mm).
R311.7.5.2 Tread depth.
The minimum tread depth shall
be 9 inches (229 mm).
The tread depth shall be
measured horizontally between the vertical planes of the foremost
projection of adjacent treads and at a right angle to the tread’s
leading edge.
The greatest tread depth
within any flight of stairs shall not exceed the smallest by more
than 3/8 inch (9.5 mm).
Winder treads shall have a
minimum tread depth of 9 inches (229 mm) measured as above at a point
12 inches (305) mm from the side where the treads are narrower.
Winder treads shall have a
minimum tread depth of 6 inches (152 mm) at any point. Within any
flight of stairs, the greatest winder tread depth at the 12 inches
(305 mm) walk line shall not exceed the smallest by more than 3/8
inch (9.5 mm).
Delete
IRC R311.7.5.3 and replace with the following:
311.7.5.3. Profile.
The radius of curvature at
the leading edge of the tread shall be no greater than 9/16 inch
(14.3 mm). A nosing not less than ¾ inch (19.1 mm) but not
more than 1-1/4 inches (32 mm) shall be provided on stairways with
solid risers. The greatest nosing projection shall not exceed the
smallest nosing projection by more than 3/8 inch (9.5mm) between two
stories, including the nosing at the level of floors and landings.
Beveling of nosing shall not exceed ½ inch (12.7 mm). Risers
shall be vertical or sloped from the underside of the leading edge of
the tread above at an angle not more than 30 degrees from the
vertical.
Open risers are permitted.
Exception: A nosing is not
required where the tread depth is a minimum of 11 inches (279 mm).
R311 Add
the following new section:
R311.7.10.3 Attic and other
Pull-Down Types of Stairs
Pull-down types of stairs
shall not be required to meet the provisions of sections R311.7.5.1,
R311.7.5.2 and R312.
Delete
IRC R311.8.1 and replace with the following:
R311.8.1 Maximum Slope
Ramps shall have a maximum
slope of one-unit vertical in eight units horizontal (12.5 percent
slope).
R312
Add new section as follows:
R312.3 Seat or Bench Elements.
Guardrails which incorporate
seat or bench elements shall have a guardrail system complying with
R312.3 to a height of 36” measured from the seat surface. The
guardrail system shall also extend to the floor surface below the
bench or seat element.
Exception:
1. Porches, balconies or
raised floors 30” or less above the floor or grade below.
2. Freestanding moveable seat
and bench elements
R313.1
Delete R313.1 and 313.2 and substitute the following
R 313.1 General.
Automatic fire sprinkler if
installed at the applicant’s option will be in conformance with
Appendix RP
R314 Delete R314 Smoke Alarms
and substitute the following:
R
314 Provisions for Fire Detection Systems
Provisions for Fire Detection
Systems are contained within the Rhode Island Uniform Fire Safety
Code.
R315
Delete Entirely
R 315 Provisions for Fire
Detection Systems
Provisions for Fire Detection
Systems are contained within the Rhode Island Uniform Fire Safety
Code.
Delete
R317.1.3 and substitute the following:
R317.1.3 Geographical areas.
Approved naturally durable or
pressure-treated wood shall be used for those portions of wood
members which form the structural supports of buildings, balconies,
porches, or similar permanent building appurtenances when such
members are exposed to the weather without adequate protection from a
roof, eave, overhang or other covering which would prevent moisture
or water accumulation on the surface or at joints between members.
Depending on local
experience, such members may include:
1 Horizontal members such as
girders, joists and decking.
2 Vertical members such as
posts, poles and columns.
3 Both horizontal and vertical
members.
R322.1
Add the following new section:
R322.1
General.
Buildings and structures
constructed in whole or in part in flood hazard areas (including A or
V Zones) as established in table R301.2(1) shall be designed and
constructed in accordance with ASCE 24. Buildings and structures
located in whole or in part in identified flood ways shall be
designed and constructed in accordance with ASCE 24.
R322.3.6.1 Add
the following new section:
R322.3.6.1 Flood Hazard
Certificates
The following certifications
shall be submitted to the building official:
1. For construction in flood
hazard areas not subject to high-velocity wave action:
1.1 As part of the lowest
floor elevation requirements of Section R324.2.1, certification of
the elevation of the lowest floor, including basement.
1.2 For fully enclosed areas
below the design flood elevation where provisions to allow for the
automatic entry and exit of floodwaters do not meet the minimum
requirements in Section 2.6.1.1, ASCE 24-05, certification by a
registered design professional that the design will provide for
equalization of hydrostatic flood forces in accordance with Section
2.6.1.2, ASCE 24-05.
2. For construction in flood
hazard areas subject to high-velocity wave action:
2.1 As part of the lowest
floor elevation requirements Section R323.3.2, a certification of the
elevation of the lowest horizontal structural member.
2.2 A certificate prepared by
a registered design professional that the building is designed in
accordance with ASCE 24-05, including that the pile or column
foundation and building or structure to be attached thereto is
designed to be anchored to resist flotation, collapse and lateral
movement due to the effects of wind and flood loads acting
simultaneously on all building components, and other load
requirements of R324.3.3.
2.3 For breakaway walls
designed to resist a nominal load of less than 10 pounds per square
foot (0.48 kN/m 2 ) or more than 20 pounds per square foot
(0.96 kN/m 2 ), a certificate prepared by a registered
design professional that the breakaway wall is designed in accordance
with ASCE 24-05.
R322.4
Add the following new Section:
R322.4 Variances and appeals.
The Board of Appeals after
examining the applicant’s hardships shall approve or disapprove
a variance request and shall hear and decide appeals from the
requirements of these regulations, in accordance with the procedures
of R.I. Gen. Laws § 23-27.3-127.0 of the Rhode Island State
Building Code and the following:
Board of Appeals
The local (or state) Board of
Appeals shall hear and decide appeals when it is alleged there is an
error in any requirement, decision or determination made by the
Building Official in the enforcement or administration of these
regulations.
Conditions of Acceptance:
(1) Variances may be issued
for the reconstruction, rehabilitation or restoration of structures
listed on the National Register of the State Inventory of Historic
Places, without regard to the procedures set forth in this Section.
(2) Variances may be issued
for new construction and substantial improvements to be erected on a
lot of one half acre or less in size contiguous to and surrounded by
lots with existing structures constructed below the base flood level
in conformance with the procedures of paragraphs B (3) (4) (5) and
(6) of this Section.
(3) Variances shall only be
issued upon a determination that the variance is the minimum
necessary, considering the flood hazard, to afford relief.
(4) Variances shall only be
issued upon:
1. A showing of good and
sufficient cause,
2. A determination that
failure to grant the variance would result in exceptional hardship to
the applicant, and
3. A determination that the
granting of a variance will not result in increased flood heights,
additional threats to public safety, extraordinary public expense,
create nuisances, cause fraud on or victimization of the public or
conflict with existing local laws or ordinances.
(5) Any applicant to whom a
variance is granted shall be given notice in the written decision
from the Board of Appeals that the structure will be permitted to be
built with a lowest floor elevation X foot below the base flood
elevation.
(6) The Board of Appeals shall
notify the applicant in the written decision that:
The issuance of a variance to
construct a structure below the base flood level will result in
increased premium rates for flood insurances up to amounts as high as
$25 for $100 of insurance coverage and
Such construction below the
base flood level increases risks to life and property. Such
notification shall be maintained with a record of all variances
actions, including justification for their issuance. All such
variances issued shall be reported in the community's Annual Report
to the Federal Insurance Administration.
(7) Variances shall not be
issued by a community within any designated regulatory floodway, if
any increase in flood levels during the base discharge would result.
(For communities which must meet the requirements of Section 60.3 (d)
of the National Flood Insurance Program regulations).
(8) Upon receipt of an
application for a variance the Chairman of the Board of Appeals shall
forward a copy of the application to the Rhode Island Emergency
Management Office, Statewide Flood-Plain Coordinator.
2.6 Chapter
4
R401.3
Delete IRC R401.3 and substitute the following:
R401.3 Drainage.
Lots shall be graded so that
additional accumulation of surface water does not occur across
adjoining property. Surface drainage shall be diverted to a storm
sewer conveyance or other point of collection so as not to create a
hazard. Lots shall be graded so as to drain surface water away from
foundation walls. The grade away from foundation walls shall fall a
minimum of 6” (inches) (153 mm) within the first 10 feet (3048
mm).
Exception.
Where lot lines, walls,
slopes or other physical barrier prohibit 6 inches (153 mm) of fall
within 10 feet (3048 mm), drains or swales shall be provided to
ensure drainage away from the structure.
Table
R401.4.1 Delete IRC Table R401.4.1 and substitute the following:
Table
R401.4.1
Presumptive
Load-Bearing Values of Foundation Materials
Type
of Soil
Load
Bearing Pressure psf
Crystalline
Bedrock
12,000-20,000
psf
Sedimentary
and Foliated Rock
8,000-12,000
psf
Medium
Dense-to-Dense Sandy Gravel and Gravel
4,000
psf
Medium
Dense-to-Dense well-graded Sand, Silty Sand and Silty Gravel
3,000
psf
Firm
Fine Sand, Silty Sand and Silty Gravel
1,500
psf
Loose
Fine Sand, Silty Sand, organic soils, clay and areas suspected at
being filled
1,000
psf
Table
R402.2 Delete Table R402.2 and substitute the following:
TABLE
NO R-402.2
MINIMUM
SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE
LOCATION
MINIMUM
f’ c OF CONCRETE AT 28 DAYS
Basement
and foundation walls, continuous and isolated footings, basement
and garage slabs
2500
psi
*Exterior
slabs, walks and steps exposed to weather
3000
psi
*Exterior
slabs shall be air-entrained concrete
Delete
IRC Table 403.1 and substitute the following:
TABLE
R403.1
MINIMUM
WIDTH OF CONCRETE OR MASONRY FOOTINGS (Inches)
(Where
minimum footing width is 12 inches, a single wythe of solid or
fully grouted 12-inch nominal concrete masonry units is permitted
to be used)
LOAD
BEARING VALUE OF SOIL (psf 0
1,500
2,000
3,000
>4,000
Conventional
light-frame construction
1-story
12
12
10
10
2-story
15
12
10
10
3-story
23
17
12
12
4-inch
brick veneer over light frame or 8-inch hollow concrete masonry
1-story
12
12
12
12
2-story
21
16
12
12
3-story
32
24
16
12
8-inch
solid or fully grouted masonry
1-story
16
12
12
12
2-story
29
21
14
12
3-story
42
32
21
16
For
SI: 1 inch = 25.4 mm. 1 pound per square foot = 0.0479 kN/m2.
Delete
R403.1.4.1 Frost Protection and substitute the following:
R403.1.4.1 Frost Protection.
Except where otherwise
protected from frost, foundation walls, piers and other permanent
supports of buildings and structures shall be protected from frost by
one or more of the following methods:
Extending below the frost
line specified in Table R301.2. (1)
Constructing in accordance
with Section R403.3
Constructing in accordance
with ASCE32-01;
Erected on solid rock.
Exceptions:
Freestanding accessory
structures with an area of 200 square feet (18.5 m 2 ) or
less and an eave height of 10 feet (3048 mm) or less shall not be
required to be protected.
Decks not supported by a
dwelling need not be provided with footings that extend below the
frost line.
Footings shall not bear on
frozen soil unless such frozen condition is of a permanent character.
R403.1.6
Delete R403.1.6 and R403.1.6.1 and substitute the following:
R403.1.6 General Foundation
Anchorage.
Foundation sill plates at
exterior walls shall be anchored to the foundation as follows:
1
+ 2 story buildings
½”
@ 48” o/c or
5/8”
@ 72” o/c
3
story building
½”
@ 24” o/c or
5/8”
@ 36” o/c
Bolts shall be spaced not
more than 12” from the corners.
Bolts shall extend a minimum
of 15” into masonry or 7” into concrete. Sill plates
shall be protected from decay in accordance with Section R323.
Nuts and washers shall be
tightened on each bolt to the plate and shall not be recessed or
countersink into the first plate.
Bolts shall be high enough to
allow for full engagement of the nut and nuts shall be left exposed
for inspection at the framing stage of construction.
Exception:
Foundation anchor straps,
spaced as required to provide equivalent anchorage to ½”
diameter anchor bolts.
R403.1.6.1 Braced Panel
Anchorage.
Shear walls shall be anchored
to the foundation in accordance with Appendix AA or the reference
standards in R301.2.1.1.
The shear wall connections
shall be in addition to general foundation anchorage requirements.
R403.3
Delete R403.3 and substitute the following:
R403.3 Frost protected shallow
foundations.
For buildings where the
monthly mean temperature of the building is maintained at a minimum
of 64o (18 oc), footings are not required to extend below the frost
line when protected from frost by insulation in accordance with
Figure R403.3(1) and Table R403.3(1). The air freezing index
(oF-days) is 1200 for the entire State of Rhode Island.
Exceptions:
No foundation not so
protected may be attached to frost-protected shallow foundations.
Unheated garages, porches, utility rooms and carports shall not be
permitted to be attached to dwelling units with frost-protected
shallow foundations.
The use of frost-protected
shallow foundations shall be limited to 1 story buildings a maximum
of 16’ from average grade to topmost part of main roof.
Materials used below grade
for the purpose of insulating footings against frost shall be labeled
as complying with ASTM C578.
Delete
R403.3.1, R403.3.1.1, Figure R403.3(3), Figure R403.3(4), and
R403.3.1.2.
R403.3.2 Delete
and substitute the following:
R403.3.2 Protection of
vertical and horizontal insulation.
Vertical insulation shall be
protected from damage for its full height from above grade to below
grade by use of cementitious board, plywood rated for below ground
use or other approved impact-resistant materials attached directly to
the surface of the insulation.
A continuous metal flashing
termite barrier shall be installed under the sill plate at the top of
the concrete slab and wall and vertical insulation edge and left
exposed at the exterior. All anchor bolt penetrations shall be
sealed.
TABLE
R404.1.2(1)
MINIMUM
HORIZONTAL REINFORCEMENT FOR CONCRETE BASEMENT WALLS A,B
MAXIMUM
UNSUPPORTED HEIGHT OF BASEMENT WALLS
(feet)
LOCATION
OF HORIZONTAL REINFORCEMENT
>
8
One
No.4 bar within 12 inches of the top of the wall story and one
No.4 bar near third points in the wall story
2.7 Chapter
5
Delete R501.3 without
substitution
2.8 Chapter
6
R602.10
Delete R602.10 and substitute the following:
R602.10 Wall bracing.
Walls shall be braced in
accordance with this section.
Exception:
Structures subject to the
scope limitations of Appendix AA shall be permitted to be braced in
accordance with Appendix AA in lieu of the provisions of this
section.
2.9 Chapter
7
R703.18
Add the following:
R 703.18 Re-siding Exterior
Walls.
Materials
and methods of application used for residing or replacing an existing
wall covering shall comply with the requirements of Section R-703.
New exterior side wall covering shall not be installed without first
removing existing wall coverings when any of the following conditions
occur:
1. When the existing wall or
wall covering is water-soaked or has deteriorated to the point that
the existing wall or wall covering is not acceptable as a base for
additional covering.
2. When the existing wall has
three (3) or more applications of any wall covering.
Exception:
The total number of wall
coverings shall not be limited when any of the existing wall
coverings consist of asbestos cement board or asbestos cement
shingles or any protective encapsulating or protective siding/layer
immediately over the asbestos material.
Asbestos cement board or
asbestos cement shingles and any protective encapsulating layer
thereupon shall not be required to be removed unless the existing
wall is unacceptable for use as a base for additional layers of wall
covering.
Any disturbance, repair or
removal of existing asbestos cement board or asbestos cement shingles
shall be in accordance with all State and Federal regulations.
2.10 Chapter
8
R802.6
Bearing. The ends of each rafter or ceiling joist shall have not less
than 1 ½ inches (38 mm) of bearing on wood or metal and not
less than 3 inches (76 mm) on masonry or concrete.
R802.11.1.3
Delete and substitute the following:
R802.11.1.3 Rafters:
Rafters shall have ties at
the wall plate and ridge bearing points in accordance with Appendix
AA
R807.1
Add the words “or closet” after the word “hallway”
on line 3 paragraph 2.
2.11 Chapter
9
R905.2.6 Delete R905.2.6 and
substitute the following:
R905.2.6
Attachment.
Asphalt strip shingles shall
have a minimum of six fasteners per shingle.
Exceptions:
1. Where the roof slope
exceeds 20 units vertical in 12 units horizontal (20:12), special
fastening details may be required by the manufacturer.
2. Fastening systems tested by
the manufacturer to ASTM D3161 modified to use a wind speed of 110
MPH shall be permitted to be installed in any wind zone.
R905.2.8.2
#3 Delete and substitute the following:
R905.2.8.2 #3
3. For closed valleys (valley
covered with shingles), valley lining of one ply of smooth roll
roofing complying with ASTM D224 Type II or Type III and at least 36
inches (914 mm) wide or valley lining as described in Items 1 and 2
above shall be permitted. Specialty underlayment complying with ASTM
D 1970 may be used in lieu of the lining material. Other valley
lining systems and techniques acceptable to the shingle manufacturer
shall be approved by the Building Official.
2.12 Chapter
10
Add
the following new section R-1007 Room Heater
R-1007.0 Room Heaters
(Wood/Coal/Pellet Stoves)
1007.1
General:
Solid-fuel-burning room
heaters shall be tested in accordance with UL 1482 listed in Appendix
A of this Code.
Multiple fuel-flue
installations
A solid-fuel-burning room
heater shall not connect to a chimney passageway venting another
appliance.
1007.3 Used or antique stoves
and room heaters:
The Building Official shall
permit the installation and use of non-listed or tested stoves and
heaters when installed in accordance with the provisions of Table
1007.3 as follows:
Table
1007.3 CLEARANCE REDUCTION METHODS
TYPE
OF PROTECTIVE ASSEMBLY a
REDUCED
CLEARANCE WITH PROTECTION (inches) a
Horizontal
combustible assemblies located above the heat source
Horizontal
combustible assemblies located beneath the heat source and all
vertical combustible assemblies
Required
clearance to combustibles without protection (inches) a
Required
clearance to combustibles without protection (inches) a
36
18
9
6
36
18
9
6
Galvanized
sheet metal, minimum nominal thickness of
0.024
inch (No. 24 Gage), mounted on 1-inch glass fiber or mineral wool
batt reinforced with wire on the back, 1 inch off the combustible
assembly
18
9
5
3
12
6
3
3
Galvanized
sheet metal, minimum nominal thickness of 0.024 inch (No. 24
Gage), spaced 1 inch off the combustible assembly.
18
9
5
3
12
6
3
2
Two
layers of galvanized sheet metal, minimum nominal thickness of
0.024 inch (No. 24 Gage), having a 1-inch airspace between layers,
spaced 1 inch off the combustible assembly
18
9
5
3
12
6
3
3
Two
layers of galvanized sheet metal, minimum nominal thickness of
0.024 inch (No. 24 Gage), having 1 inch of fiberglass insulation
between layers, spaced 1 inch off the combustible assembly.
18
9
5
3
12
6
3
3
0.5-inch
inorganic insulating board, over 1 inch of fiberglass or mineral
wool batt, against the combustible assembly.
24
12
6
4
18
9
5
3
3.5-inch
brick wall, spaced 1 inch off the combustible wall
12
6
6
6
3.5-inch
brick wall, against the combustible wall
24
2
6
5
For
SI: 1 inch = 25.4 mm, oC = [(oF)-32]/1.8, 1 pound per cubic foot =
16.02 kg/m 3 , 1.0 Btu x in/ft 2 .h. oF=0.144
W/m 2 . oK.
a
Mineral wool and glass fiber batts (blanket or board) shall
have a minimum density of 8 pounds per cubic foot and a minimum
melting point of 1,500o F. Insulation material utilized as part of
a clearance reduction system shall have a thermal conductivity of
1.0 Btu x in/ft 2 .h. oF) or less.
Insulation
board shall be formed of noncombustible material.
2.13 Chapter
11
N1101.1
Delete N1101.2 and substitute the following:
N1101.1.1 Compliance Methods
Compliance shall be
demonstrated by either:
1. Meeting the requirements of
the Rhode Island Energy Conservation Code SBC-8-2019 ( Part
8 of this Subchapter ).
2. Meeting the requirements of
this chapter using the criteria for climate zone 5 from Figure N
1102A or table 1102.1.2.
3. Compliance submission of
Res-Check for Zone 5 & Chapter 11 Delete Table N1101.8 without
substitution
N
1101. 7 (R301.1) Climate Zones: Rhode Island shall be considered as
climate zone 5 with the following design conditions.
Table
N1101.7 (R301.1) Delete and substitute the following:
Table
N1101.7 (R301.1)
Exterior
Design Conditions.
Value
Value
Climate
zone
Providence
County
All
others
Winter,
design dry-bulb (degree F)
0
5
Summer,
design dry-bulb
87
89
Summer
design wet-bulb
71
73
Degree
days heating
6831
5950
Degree
days cooling
371
811
Delete
without substitute sections N1101.7, N1101.7.2, N1101.7.3 R301.2 and
R301.3, R301.4
Delete
Table N1101.7.2 (1) (R301.3(1)) without substitute
Delete
Table N1101.7.2 (2) (R301.3(2)) without substitute
Delete Figure N1101.7 (R301.1)
and substitute the following: Figure N1101.7 (R301.1)
Figure
N1101.7 (R 301.1)
Delete
Table N1101.14 (R401.3) and substitute the following:
Add
the following to N1101.14 (R401.3), Certificate:
Figure
N1101.14 (R401.3)
A
certificate similar to this shall be attached to or near the
electrical panel board
ENERGY
CERTIFICATE
Street
Address
City
/ Town
Predominant
Values
R-Value
Ceiling / Roof
R-
Value Walls
R-
Value Ducts (outside conditioned space)
U
Factor Fenestration
SHGC
Fenestration
Gas
Fired Un-Vented Room Heater
Baseboard
Electric Heater
Electric
Furnace
U
Factor Skylight / SHGC
AFUE
Value Boiler / Furnace
Efficiency
and type of heating equipment
Efficiency
and type of cooling equipment
Efficiency
and type of service water heater
Contractor
or Design Professional
Address
Registration
Signature
Delete and substitute table
N1102.1.2 (R402.1.2)
TABLE
N1102.1.2 (R402.1.2)
INSULATION
AND FENESTRATION REQUIREMENTS BY COMPONENT a
CLIMATE
ZONE
FENESTRATION
U-FACTOR b
SKYLIGHT
b U-FACTOR
GLAZED
FENESTRATION SHGC b
CEILING
R-VALUE i
WOOD
FRAME WALL R-VALUE g
MASS
WALL R-VALUE
FLOOR
R-VALUE
BASEMENT
C WALL R-VALUE
SLAB
d R-VALUE & DEPTTH
CRAWL
SPACE c WALL
5
0.35
0.60
NR
38
20
or
13+5
f
13/17
30
e
10/13
R-10
for
2 ft
10/13
For SI: 1 foot = 304.8 mm.
R-values are minimums
U-factors and SHGC are maximums. R-19 batts compressed into a nominal
2 × 6 framing cavity such that the R- value is reduced by R-1
or more shall be marked with the compressed batt R-value in addition
to the full thickness R-value.
The fenestration U-factor
column excludes skylights. The SHGC column applies to all glazed
fenestration.
“10/13” means
R-10 continuous insulated sheathing on the interior or exterior of
the home or R-13 cavity insulation at the interior of the basement
wall.
R-5 shall be added to the
entire slab and the required slab edge R-values for heated slabs or
insulation sufficient to fill the framing cavity, R-19 minimum.
“13+5” means R-13
cavity insulation plus R-5 insulated sheathing. If structural
sheathing covers 25 percent or less of the exterior, insulating
sheathing is not required where structural sheathing is used. If
structural sheathing covers more than 25 percent of exterior,
structural sheathing shall be supplemented with insulated sheathing
of at least R-2.
The second R-value applies
when more than half the insulation is on the interior of the mass
wall.
TABLE N1102.1.4(R402.1.4)
EQUIVALENT U-FACTORS a
CLIMATE
ZONE
FENESTRATION
U-FACTOR
SKYLIGHT
U-FACTOR
CEILING
U-FACTOR
FRAME
WALL U-FACTOR
MASS
WALL U-FACTOR b
FLOOR
U-FACTOR
BASEMENT
WALL U-FACTOR
CRAWL
SPACE U-FACTOR
5
0.32
0.55
0.026
0.057
0.082
0.033
0.050
0.055
Delete N1102.1.5 (R402.1.5)
Total UA alternative and substitute the following:
N1102.1.5 (R402.1.5) Total UA
alternative. If the total building thermal envelope UA (sum of
U-factor times assembly area) is less than or equal to the total UA
resulting from using the U-factors in Table R402.1.3 (multiplied by
the same assembly area as in the proposed building), the building
shall be considered in compliance with Table R402.1.1. The UA
calculation shall include the thermal bridge effects of framing
materials. The UA calculation shall include the thermal bridging
effects of framing materials. The SHGC requirements shall be met in
addition to UA compliance
Delete
N1102.4.1.2 (R402.4.1.2) and substitute the following:
N1102.4.1.2 Testing. The
building or dwelling unit shall be tested, and Testing shall be
conducted with a blower door at a pressure of 0.2 inches w.g. (50
Pascals). Maximum air change rates per hour: In 2019 = 8, 2020 = 7,
2021 = 6, and 2022 and subsequent years = 5. Testing shall be
conducted by an approved third party, where required by the building
official. A written report of the results of the test shall be signed
by the party conducting the test and provided to the building
official. Testing shall be performed at any time after creation of
all penetrations of the building thermal envelope.
During testing:
Exterior windows and doors,
fireplace and stove doors shall be closed, but not sealed, beyond the
intended weather-stripping or other infiltration control measures;
Dampers including exhaust,
intake, makeup air, backdraft and flue dampers shall be closed, but
not sealed beyond intended infiltration control measures;
Interior doors, if installed
at the time of the test, shall be open.
Exterior doors for continuous
ventilation systems and heat recovery ventilators shall be closed and
sealed;
Heating and cooling systems,
if installed at the time of the test, shall be turned off; and Supply
and return registers, if installed at the time of the test, shall be
fully open.
N1103.3.3 (R403.3.3) Duct
Testing (Mandatory)
Delete
section N1103.3.3 (R403.3.3) and Substitute the following:
N1103.2.2 (R403.2.2) Sealing
(Mandatory). Ducts, air handlers, and filter boxes shall be sealed.
Joints and seams shall comply with Section M1601.4.1 of this code.
Exceptions:
Air-impermeable spray foam
products shall be permitted to be applied without additional joint
seals.
Where a duct connection is
made that is partially inaccessible, three screws or rivets shall be
equally spaced on the exposed portion of the joint so as to prevent a
hinge effect.
Continuously welded and
locking –type longitudinal joints and seams in ducts operating
at a static pressures less than 2 inches of water column (500 Pa)
pressure classification shall not require additional closure systems.
Duct tightness shall be
verified by either of the following:
Postconstruction test: Total
leakage shall be less than or equal to 8 cfm (113.3 L/min) per 100
square feet (9.29 m 2 ) of conditioned floor area.
Rough-in test: Total leakage
shall be less than or equal to 6 cfm (113.3 L/min) per 100 ft 2
(9.29 m 2 ) of conditioned floor area when tested at a
pressure differential of 0.1 inches w.g. (25 Pa) across the system,
including the manufacturer’s air handler enclosure. All
registers shall be taped or otherwise sealed during the test. If the
air handler is not installed at the time of the test. Total leakage
shall be less than or equal to 4 cfm (85 L/min) per 100 square feet
(9.29 m 2 ) of conditioned floor area.
Exception: The total leakage
test is not required for ducts and air handlers located entirely
within the building envelope.
Delete
Section N1103.3.5 (R403.3.5) and Substitute the following:
N1103.3.5 (R403.3.5) Building
cavities (Mandatory). Interior building framing cavities shall be
permitted to be used as return ducts or plenums. (BP)
Delete
Table N1103.6.1 without substitutions
Reference
Standards
Delete
without substitute
ASHRAE – 2013 ASHRAE
Handbook of Fundamentals.
2.14 Chapter
14
M
1401.3 Delete M1401.3 and substitute the following:
M 1401.3 Sizing.
Heating and cooling equipment
shall be sized based on building loads calculated in accordance with
ACCA Manual J or other approved heating and cooling methodologies. To
recognize equipment sizing availability and to provide for future
additions, equipment shall be sized so as not to exceed 150% of the
submitted building load calculations.
2.15 Chapter
15
M
1502.4.5 Delete and substitute the following:
M 1502.4.5 Length
identification.
The maximum length of dryer
duct may exceed 35’ when a permanent placard, measuring a
minimum 5” wide, 3” high, and 1/8” thick, and
constructed of either wood, metal, or rigid plastic, and bearing
raised or embossed lettering stating the following:
“WARNING: THE EFFECTIVE
LENGTH OF THIS DRYER DUCT IS xxx FEET. ANY DRYER CONNECTED TO THIS
EXHAUST DUCT MUST BE RATED TO USE AN EXHAUST DUCT OF THIS LENGTH, PER
THE MANUFACTURERS SPECIFICATIONS; SEVERE RISK OF FIRE MAY RESULT FOR
NONCOMPLIANCE WITH THIS NOTICE.”
The provisions of M102.4
shall be used in establishing the effective length of the ductwork
installed and noted on the placard. The placard shall be permanently
attached to the wall or floor within 6” of the terminus of the
duct.
M
1503.4 Delete without substitution
M1506.2
Delete without substitution
2.16 Chapter
16
M1601.4.1 Add
the following exceptions to M1601.4.1
Exceptions:
4. Flexible air ducts shall
be permitted to be joined with or without tapes using approved
mechanically fastened tension straps or flex-ties installed with a
tensioning gun or other similar technologies.
M1601.6
Delete M1601.6 without substitution:
M
1602.2 Add the following to exception #4 M1602.2.4
Exception #4 continued
Return air shall be permitted
to be taken from locations such as a kitchen which is provided its
own separate and individual system providing 100% of the supply air
for that space.
2.17 Chapter
18
To
M1801.3.1 Size add the following exception:
Exception:
Installation of replacement
appliances below an 85% AFUE rating shall be exempt from the
requirement of installing a new chimney liner and must meet the
manufacturer’s recommendations for installation in an unlined
chimney.
2.18 Chapter
19
Delete M1901.3 without
substitution
2.19 Chapter
22
Add
the following exception to M2201.1 Materials.
Exception:
Non-metallic storage tanks
shall meet the requirements of UL subject 2258 and shall be installed
in accordance with manufacturer’s instructions.
Delete
M2201.2 and Substitute the following.
M2201.2 Above ground tanks.
The maximum amount of fuel
oil stored any above ground or inside of a building shall be 1320
gallons (2498L) and the maximum amount of oil connected to any one
(1) appliance shall be 660 gallons. When capacity exceeds 660 gallons
the tanks shall be double walled and sized so that they can be
removed from the building without dismantling of the tank.
M2203.8 Add the following code
section:
M2203.8
Emergency Disconnect Switch.
When an oil-fired heating,
appliance is located inside a structure, a remote means of shutting
off power to the oil pump and firing circuit in addition to the
serviceman’s switch shall be provided as follows:
1. When the appliance is
located in an unfinished basement or cellar, an additional shutdown
switch shall be installed at the entrance to the basement at the top
of the stairs.
2. When the appliance is
located in a separately dedicated utility room, the switch shall be
located outside the room immediately adjacent to its entrance.
3. When the appliance is
located in a crawl space or attic, the switch shall be located
immediately outside the entrance to the crawl space or attic area.
The switch shall be located
on a wall mounted between 60” and 80” above the floor
surface and be identified with a red cover plate suitably identified
as to its purpose.
2.20 Chapter
24
G2406.2
(303.3) Add the following new exception:
(6) Gas fired appliances may
be installed in loft or open efficiency type apartments when there is
a sleeping area not a sleeping room. The installation of appliances
must comply with section 304.5 for combustion air required volume and
the manufacturers’ installation instructions.
G2411.1.1 Delete and
substitute the following:
G2411.1.1 310.1.1 CSST CSST
gas piping systems shall be bonded to the electrical service
grounding electrode system. The bonding jumper shall connect to a
metallic pipe or fitting between the point of delivery and the first
downstream CSST fitting. The bonding jumper shall be copper and not
smaller than 6AWG. The bonding jumper shall not exceed 40’ in
length. CSST system with a conductive jacket deemed to be equivalent
to a direct bonded CSST system by an approved listing agency shall
only be required to be bonded in accordance with section Residential
Code 2411.1 or Fuel Gas Code 310.1. The installation of the bonding
jumper shall be by an electrician with an electrical permit and
inspected by the electrical inspector.
G2415.3 Delete
G2415.3 and substitute the following:
G2415.3 (401.1) Prohibited
locations.
Piping shall not be installed
in or through a ducted supply, return or exhaust, or a clothes chute,
chimney or gas vent, dumbwaiter or elevator shaft. Piping installed
downstream of the point of entry may extend through any townhouse
unit other than the unit served by such piping.
G2415.6 Delete
and substitute the following:
G2415.6 (404.4) Piping through
foundation wall.
Underground piping, where
installed below grade through the outer foundation or basement wall
of a building, shall be encased in a protective pipe sleeve.
The annular space between the
gas piping and the sleeve shall be sealed.
G2425.15 Add
the following exception to G2425.15.1:
Exception:
Installation of replacement
appliances below an 85% AFUE rating shall be exempt from the
requirement of installing a new chimney liner and must meet the
manufacturer’s recommendations for installation in an unlined
chimney.
2.21 Chapter 25
P-2501.1
Delete 2501.1 and substitute the following.
P2501.1 Scope.
The provisions of this
chapter shall govern the installation of plumbing not specifically
covered in other chapters applicable to plumbing systems
P2503.4
Delete P2503.4 Building Sewer Testing without substitution.
Delete
Section 2503.5.1 & Substitute the following
P2503.5.1 Rough plumbing. DWV
systems shall be tested on completion of the rough piping
installation by water or air with no evidence of leakage. Either test
shall be applied to the drainage system in its entirety or in
sections after rough piping has been installed, as follows:
Water test. Each section
shall be filled with water to a point not less than 10 feet (3048 mm)
above the highest fitting connection in that section, or to the
highest point in the completed system. Water shall be held in the
section under test for a period of 15 minutes. The system shall prove
leak free by visual inspection.
Air test. The portion under
test shall be maintained at a gauge pressure of 5 pounds per square
inch (psi) (34 kPa) or 10 inches of mercury column (34kPa). This
pressure shall be held without introduction of additional air for a
period of 15 minutes.
P2503.5.2 Delete
P2503.5.2 Finished Plumbing and substitute the following:
P2503.5.2 Finished Plumbing.
After the plumbing fixtures
have been set and the in traps filled with water, their connections
shall be tested and proved water tight by filling and then draining
each fixture and their traps and fixture connections proven tight by
visual inspection.
2.22 Chapter
26
P2603.4
Add the following exception to P2603.4 Pipes through footings or
foundation walls:
Exception:
PVC schedule 40 minimum pipe
shall not be required to be sleeved or be provided with a relieving
arch.
P2603.5 Add
the following exception to P2603.5 Freezing:
Exception:
Soil and vent stacks located
within exterior walls and vent pipes in attics shall not be required
to be insulated.
P2603.5.1 Delete
P2603.5.1 and substitute the following
P2603.5.1 Sewer Depth.
Building sewers that connect
to private sewage disposal systems shall meet the requirements of the
Department of Environmental Management’s Regulations for onsite
waste water treatment systems.
Building sewers connecting to
a public sewer shall be a minimum of 36 inches below grade.
2.23 Chapter 29
P2902.7
Protection of individual water supplies. An individual water supply
shall be located and constructed so as be safeguarded against
contamination in accordance with Section P2902.7.1 through P2902.7.8.
P2902.7.1
Well locations. A potable ground water source or pump suction line
shall not be located closer to potential sources of contamination
than the distances shown in Table P2902.7.1. In the event the
underlying rock structure is limestone or fragmented shale, the local
or state health department shall be consulted on well site location.
The distances in Table P2902.1 constitute minimum separation and
shall be increased in areas of creviced rock or limestone, or where
the direction of movement of ground water is from sources of
contamination toward the well.
TABLE
P2902.7.1
DISTANCE FROM SOURCES OF
CONTAMINATION TO PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES
Source
of Contamination
Distance
(feet)
(1
foot=304.8mm)
Sewer
50
Septic
Tank
50
Pasture
100
Sewer
(leaded or mechanical
joints
or approved plastic)
10
Subsurface
pits
100c
Seepage
pits
100
Cesspools
100
Barnyard
100
Farm
silo
25
Pump
house floor drain of cast iron draining to ground surface
2
P2902.7.2
Elevation. Well sites shall be positively drained and shall be at
higher elevations than potential sources of contamination.
P2902.7.3
Depth. Private potable well supplies shall not be developed from a
water table less than 10 feet (3048mm) below the ground surface
P2902.7.4
Water-tight casings. Each well shall be provided with a water-tight
casing extending to not less than 10 feet (3048mm) below the ground
surface. Casings shall extend not less than 6 inches (152 mm) above
the well platform. Casings shall be large enough to permit
installation of a separate drop pipe. Casings shall be sealed at the
bottom in an impermeable stratum or extend several feet into the
water-bearing stratum.
P2902.7.5
Drilled or driven well casings. Drilled or driven well casings shall
be of steel or other approved material. Where drilled wells extend
into a rock formation, the well casing shall extend to and set firmly
in the formation. The annular space between the earth and the outside
of the casing shall be filled with cement grout to a depth of not
less than 10 feet (3048 mm) below the ground surface. In an instance
of casing to rock installation, the grout shall extend to the rock
surface.
P2902.7.6
Dug or bored well casings. Dug or bored well casings shall be of
water-tight concrete, tile, galvanized or corrugated metal pipe
extending to not less than 10 feet (3048 mm) below the ground
surface. Where the water table is more than 10 feet (3048) below the
ground surface, the water-tight casing shall extend below the table
surface. Well casings for dug wells or bored wells constructed with
sections of concrete, tile, or galvanized or corrugated metal pipe
shall be surrounded by 6 inches (152 mm) of grout poured into the
hole between the outside of the sassing and the ground and extending
not less than 10 feet (3048) below the ground surface.
P2902.7.7
Cover. Potable water wells shall be equipped with an overlapping
water-tight cover at the top of the well casing or pipe sleeve such
that contaminated water or other substances are prevented from
entering the well through the annular opening at the top of the well
casing, wall or pipe sleeve. Covers shall extend downward not less
than 2 inches (51 mm) over the outside of the well casing or wall. A
dug well cover shall be provided with a pipe sleeve permitting the
withdrawal of the pump suction pipe, cylinder or jet body without
disturbing the cover. Where pump sections or discharge pipes enter or
leave a well through the side of the casing, the circle of contact
shall be water tight.
P2902.7.8
Drainage. Potable water wells and springs shall be constructed such
that surface drainage will be diverted away from the well or spring
P2903.3 Delete
P2903.3 Minimum Pressure and substitute the following:
P2903.3 Minimum Pressure.
Minimum static pressure shall
be 40 psi measured before any meter, or a booster pump shall be
installed after the meter providing 40 psi minimum static pressure.
For private wells, 40 psi
minimum shall be provided at the outlet of any storage tank or pump.
Delete Section P2904 and
substitute the following:
R2904.1 General.
Automatic fire sprinkler if
installed at the applicant’s option will be in conformance with
Appendix RP.
2.24 Chapter
30
P3007.1
Building subdrains. Building subdrains that cannot be discharged to
the sewer by gravity flow shall be discharged into a sump from which
the liquid shall be lifted and discharged into the building gravity
drainage system by automatic pumping equipment or other approved
method. In other than existing structures, the sump shall not receive
drainage from any piping within the building capable of being
discharged by gravity to the building sewer.
P
3008.1 Delete section P3008.1 and substitute the following
P3008.1 Mandatory installation
of check valves.
All new residential
construction that will connect to a sanitary sewer system and any
residential construction where the existing sewer connection will be
substantially altered shall have a check valve installed that is
automatically activated, on the main building sewer line for purposes
of protecting residents from the possible backflow of, and exposure
to, untreated sewage.
2.25 Chapter 32 Traps
P3201.2 Delete
and substitute the following:
P3201.2 Trap seals and trap
seal protection.
Traps shall have a liquid
seal not less than 2 inches (51 mm) and not more than 4 inches (102
mm). Traps for floor drains shall be fitted with a trap primer or
shall be of the deep seal design. Alternative seals that are in
conformance with ASSE 1018 or ASSE 1044 are acceptable.
2.26 Chapter
34
Delete
without substitution
Part VIII Electrical Chapters
34 through 43 and reference Rhode Island Electrical Code RI- SBC-5
( Part
5 of this Subchapter ) most recent edition.
2.27 Appendices
Add
the Following
APPENDIX RP –
RESIDENTIAL SPRINKLERS
Appendix
RP is Informative only and is not part of this code
SECTION R-P2904 DWELLING UNIT
FIRE SPRINKLER SYSTEMS
R-P2904.1 General.
Where installed, residential
fire sprinkler systems, or portions thereof, shall be in accordance
with NFPA 13D or Section P2904, which shall be considered equivalent
to NFPA 13D. Section P2904 shall apply to stand-alone and
multipurpose wet-pipe sprinkler systems that do not include the use
of antifreeze. A multipurpose fire sprinkler system shall supply
domestic water to both fire sprinklers and plumbing fixtures. A
stand-alone sprinkler system shall be separate and independent from
the water distribution system. A backflow flow preventer shall not be
required to separate a stand-alone sprinkler system from the water
distribution system.
R-P2904.1.1 Required sprinkler
locations.
Sprinklers when installed
shall protect all areas of a dwelling unit.
Exceptions:
1. Attics, crawl spaces and
normally unoccupied concealed spaces that do not contain fuel- fired
appliances do not require sprinklers. In attics, crawl spaces and
normally unoccupied concealed spaces that contain fuel-fired
equipment, a sprinkler shall be installed above the equipment;
however, sprinklers shall not be required in the remainder of the
space.
2. Clothes closets, linen
closets and pantries not exceeding 24 square feet (2.2 m2) in area,
with the smallest dimension not greater than 3 feet (915mm) and
having wall and ceiling surfaces of gypsum board.
3. Bathrooms not more than 55
square feet (5.1m 2 ) in area.
4. Garages; carports; exterior
porches; unheated entry areas, such as mud rooms, that are adjacent
to an exterior door; and similar areas.
R-P2904.2 Sprinklers.
Sprinklers shall be new
listed residential sprinklers and shall be installed in accordance
with the sprinkler manufacturer’s installation instructions.
R-P2904.2.1 Temperature rating
and separation from heat sources.
Except as provided for in
Section P2904.2.2, sprinklers shall have a temperature rating of not
less than 135°F (57°C) and not more than 170°F (77°C).
Sprinklers shall be separated from heat sources as required by the
sprinkler manufacturer’s installation instructions.
R-P2904.2.2 Intermediate
temperature sprinklers.
Sprinklers shall have an
intermediate temperature rating not less than 175°F (79°C)
and not more than 225°F (107°C) where installed in the
following locations:
1. Directly under skylights,
where the sprinkler is exposed to direct sunlight.
2. In attics.
3. In concealed spaces located
directly beneath a roof.
4. Within the distance to a
heat source as specified in Table P2904.2.2
R-P2904.2.3 Freezing areas.
Piping shall be protected
from freezing as required by Section P2603.6. Where sprinklers are
required in areas that are subject to freezing, dry-sidewall or
dry-pendent sprinklers extending from a nonfreezing area into a
freezing area shall be installed.
R-P2904.2.4
Sprinkler coverage.
Sprinkler
coverage requirements and sprinkler obstruction requirements shall be
in accordance with Sections P2904.2.4.1 and P2904.2.4.2.
Table
P2904.2.2 – Locations Where Intermediate Temperature Sprinklers
are Required
Heat
Source
Range
of Distance from Heat Source within which Intermediate Temperature
Sprinklers are Required a, b (inches)
Fireplace,
side of open or recessed fireplace
12
to 36
Fireplace,
front of recessed fireplace
36
to 60
Coal
and wood burning stove
12
to 42
Kitchen
range top
9
to 18
Oven
9
to 18
Vent
connector or chimney connector
9
to 18
Heating
duct, not insulated
9
to 18
Hot
water pipe, not insulated
6
to 12
Side
of ceiling or wall warm air register
12
to 24
Front
of wall mounted warm air register
18
to 36
Water
heater, furnace or boiler
3
to 6
Luminaire
up to 250 watts
3
to 6
Luminaire
250 watts up to 499 watts
6
to 12
For
SI: 1 inch = 25.4 mm
a Sprinklers
shall not be located at distances less than the minimum table
distance unless the sprinkler listing allows a lesser distance.
b Distances
shall be measured in a straight line from the nearest edge of the
heat source to the nearest edge of the sprinkler
R-P2904.2.4.1 Coverage area
limit.
The area of coverage of a
single sprinkler shall not exceed 400 square feet (37 m2) and shall
be based on the sprinkler listing and the sprinkler manufacturer’s
installation instructions.
R-P2904.2.4.2
Obstructions to coverage.
Sprinkler discharge shall not
be blocked by obstructions unless additional sprinklers are installed
to protect the obstructed area. Sprinkler separation from
obstructions shall comply with the minimum distances specified in the
sprinkler manufacturer’s instructions.
R-P2904.2.4.2.1 Additional
requirements for pendent sprinklers.
Pendent sprinklers within 3
feet (915 mm) of the center of a ceiling fan, surface-mounted ceiling
luminaire or similar object shall be considered to be obstructed, and
additional sprinklers shall be installed.
R-P2904.2.4.2.2 Additional
requirements for sidewall sprinklers.
Sidewall sprinklers within 5
feet (1524mm) of the center of a ceiling fan, surface-mounted ceiling
luminaire or similar object shall be considered to be obstructed, and
additional sprinklers shall be installed.
R-P2904.2.5 Sprinkler
installation on systems assembled with solvent cement.
The solvent cementing of
threaded adapter fittings shall be completed and threaded adapters
for sprinklers shall be verified as being clear of excess cement
prior to the installation of sprinklers on systems assembled with
solvent cement.
R-P2904.2.6 Sprinkler
modifications prohibited.
Painting, caulking or
modifying of sprinklers shall be prohibited. Sprinklers that have
been painted, caulked, modified or damaged shall be replaced with new
sprinklers.
R-P2904.3 Sprinkler piping
system.
Sprinkler piping shall be
supported in accordance with the requirements for cold water
distribution piping. Sprinkler piping shall comply with all
requirements for cold water distribution piping. For multipurpose
piping systems, the sprinkler piping shall connect to and be a part
of the cold-water distribution piping system.
R-P2904.3.1 Nonmetallic pipe
and tubing.
Nonmetallic pipe and tubing,
such as CPVC and PEX, shall be listed for use in residential fire
sprinkler systems.
R-P2904.3.1.1 Nonmetallic pipe
protection.
Nonmetallic pipe and tubing
systems shall be protected from exposure to the living space by a
layer of not less than 3/8 inch (9.5 mm) thick gypsum wallboard,
1/2-inch-thick plywood (13 mm), or other material having a 15-minute
fire rating.
Exceptions:
1. Pipe protection shall not
be required in areas that do not require protection with sprinklers
as specified in Section P2904.1.1.
2. Pipe protection shall not
be required where exposed piping is permitted by the pipe listing.
R-P2904.3.2 Shutoff valves
prohibited.
With the exception of shutoff
valves for the entire water distribution system, valves shall not be
installed in any location where the valve would isolate piping
serving one or more sprinklers.
R-P2904.3.3 Single dwelling
limit.
Piping beyond the service
valve located at the beginning of the water distribution system shall
not serve more than one dwelling.
R-P2904.3.4 Drain.
A means to drain the
sprinkler system shall be provided on the system side of the water
distribution shutoff valve.
R-P2904.4 Determining system
design flow.
The flow for sizing the
sprinkler piping system shall be based on the flow rating of each
sprinkler in accordance with Section P2904.4.1 and the calculation in
accordance with Section P2904.4.2.
R-P2904.4.1 Determining
required flow rate for each sprinkler.
The minimum required flow for
each sprinkler shall be determined using the sprinkler manufacturer’s
published data for the specific sprinkler model based on all of the
following:
1. The area of coverage.
2. The ceiling configuration.
3. The temperature rating.
4. Any additional conditions
specified by the sprinkler manufacturer.
R-P2904.4.2 System design
flow rate.
The design flow rate for the
system shall be based on the following:
1. The design flow rate for a
room having only one sprinkler shall be the flow rate required for
that sprinkler, as determined by Section P2904.4.1.
2. The design flow rate for a
room having two or more sprinklers a shall be determined by
identifying the sprinkler in that room with the highest required flow
rate, based on Section P2904.4.1, and multiplying that flow rate by
2.
3. Where the sprinkler
manufacturer specifies different criteria for ceiling configurations
that are not smooth, flat and horizontal, the required flow rate for
that room shall comply with the sprinkler manufacturer’s
instructions.
4. The design flow rate for
the sprinkler system shall be the flow required by the room with the
largest flow rate, based on Items 1, 2 and 3.
5. For the purpose of this
section, it shall be permissible to reduce the design flow rate for a
room by subdividing the space into two or more rooms, where each room
is evaluated separately with respect to the required design flow
rate. Each room shall be bounded by walls and a ceiling. Openings in
walls shall have a lintel not less than 8 inches (203 mm) in depth
and each lintel shall form a solid barrier between the ceiling and
the top of the opening.
R-P2904.5 Water supply.
The water supply shall
provide not less than the required design flow rate for sprinklers in
accordance with Section P2904.4.2 at a pressure not less than that
used to comply with Section P2904.6.
R-P2904.5.1 Water supply from
individual sources.
Where a dwelling unit water
supply is from a tank system, a private well system or a combination
of these, the available water supply shall be based on the minimum
pressure control setting for the pump.
R-P2904.5.2 Required
capacity.
The water supply shall have
the capacity to provide the required design flow rate for sprinklers
for a period of time as follows:
1. 7 minutes for dwelling
units one story in height and less than 2,000 square feet (186 m 2 )
in area.
2. 10 minutes for dwelling
units two or more stories in height or equal to or greater than 2,000
square feet (186 m 2 ) in area. Where a well system, a water
supply tank system or a combination thereof is used, any combination
of well capacity and tank storage shall be permitted to meet the
capacity requirement.
R-P2904.6 Pipe sizing.
The piping to sprinklers
shall be sized for the flow required by Section P2904.4.2. The flow
required to supply the plumbing fixtures shall not be required to be
added to the sprinkler design flow.
R-P2904.6.1 Method of sizing
pipe.
1. Piping supplying sprinklers
shall be sized using the prescriptive method in Section P2904.6.2 or
by hydraulic calculation in accordance with NFPA 13D. The minimum
pipe size from the water supply source to any sprinkler shall be
3/4-inch (19 mm) nominal.
2. Threaded adapter fittings
at the point where sprinklers are attached to the piping shall be a
minimum of 1/2-inch (13 mm) nominal.
R-P2904.6.2 Prescriptive pipe
sizing method.
Pipe shall be sized by
determining the available pressure to offset friction loss in piping
and identifying a piping material, diameter and length using the
equation in Section P2904.6.2.1 and the procedure in Section
P2904.6.2.2.
R-P2904.6.2.1 Available
pressure equation.
The pressure available to
offset friction loss in the interior piping system (Pt) shall be
determined in accordance with the Equation 29-1.
Pt =
Psup–PLsvc–PLm–PLd–PLe–Psp (Equation
29-1) where: Pt = Pressure used in applying Tables P2904.6.2(4)
through P2904.6.2(9).
Psup = Pressure available
from the water supply source.
PLsvc = Pressure loss in the
water-service pipe.
PLm = Pressure loss in the
water meter.
PLd = Pressure loss from
devices other than the water meter.
PLe = Pressure loss
associated with changes in elevation.
Psp = Maximum pressure
required by a sprinkler.
R-P2904.6.2.2 Calculation
procedure.
Determination of the required
size for water distribution piping shall be in accordance with the
following procedure:
Step 1–Determine Psu
Obtain the static supply pressure that will be available from the
water main from the water purveyor, or for an individual source, the
available supply pressure shall be in accordance with Section
P2904.5.1.
Step 2–Determine PLsvc
Use Table P2904.6.2(1) to determine the pressure loss in the water
service pipe based on the selected size of the water service.
Step 3–Determine PLm
Use Table P2904.6.2(2) to determine the pressure loss from the water
meter, based on the selected water meter size.
Step 4–Determine PLd
Determine the pressure loss from devices other than the water meter
installed in the piping system supplying sprinklers, such as
pressure-reducing valves, backflow preventers, water softeners or
water filters. Device pressure losses shall be based on the device
manufacturer's specifications. The flow rate used to determine
pressure loss shall be the rate from Section P2904.4.2, except that 5
gpm (0.3 L/S) shall be added where the device is installed in a
water-service pipe that supplies more than one dwelling.
As alternative to deducting
pressure loss for a device, an automatic bypass valve shall be
installed to divert flow around the device when a sprinkler
activates.
Step 5–Determine PLe
Use Table P2904.6.2(3) to determine the pressure loss associated with
changes in elevation. The elevation used in applying the table shall
be the difference between the elevation where the water source
pressure was measured and the elevation of the highest sprinkler.
Step 6–Determine Psp
Determine the maximum pressure required by any individual sprinkler
based on the flow rate from Section P2904.4.1. The required pressure
is provided in the sprinkler manufacturer's published data for the
specific sprinkler model based on the selected flow rate.
Step 7–Calculate Pt
Using Equation 29-1, calculate the pressure available to offset
friction loss in water-distribution piping between the service valve
and the sprinklers.
Step 8–Determine the
maximum allowable pipe length Use Tables P2904.6.2(4) through
P2904.6.2(9) to select a material and size for water distribution
piping. The piping material and size shall be acceptable if the
developed length of pipe between the service valve and the most
remote sprinkler does not exceed the maximum allowable length
specified by the applicable table. Interpolation of Pt between the
tabular values shall be permitted. The maximum allowable length of
piping in Tables P2904.6.2(4) through P2904.6.2(9) incorporates an
adjustment for pipe fittings, and no additional consideration of
friction losses associated with pipe fittings shall be required.
R-P2904.7 Instructions and
signs.
An owner’s manual for
the fire sprinkler system shall be provided to the owner. A sign or
valve tag shall be installed at the main shutoff valve to the water
distribution system stating the following: “Warning, the water
system for this home supplies fire sprinklers that require certain
flows and pressures to fight a fire. Devices that restrict the flow
or decrease the pressure or automatically shut off the water to the
fire sprinkler system, such as water softeners, filtration systems
and automatic shutoff valves, shall not be added to this system
without a review of the fire sprinkler system by a fire protection
specialist. Do not remove this sign.”
R-P2904.8 Inspections.
The water distribution system
shall be inspected in accordance with Sections P2904.8.1 and
P2904.8.2.
R-P2904.8.1 Pre-concealment
inspection.
The following items shall be
verified prior to the concealment of any sprinkler system piping:
1. Sprinklers are installed in
all areas as required by Section P2904.1.1.
2. Where sprinkler water spray
patterns are obstructed by construction features, luminaries or
ceiling fans, additional sprinklers are installed as required by
Section P2904.2.4.2.
3. Sprinklers are the correct
temperature rating and are installed at or beyond the required
separation distances from heat sources as required by Sections
P2904.2.1 and P2904.2.2.
4. The pipe size equals or
exceeds the size used in applying Tables P2904.6.2(4) through
P2904.6.2(9) or, if the piping system was hydraulically calculated in
accordance with Section P2904.6.1, the size used in the hydraulic
calculation.
5. The pipe length does not
exceed the length permitted by Tables P2904.6.2(4) through
P2904.6.2(9) or, if the piping system was hydraulically calculated in
accordance with Section P2904.6.1, pipe lengths and fittings do not
exceed those used in the hydraulic calculation.
6. Nonmetallic piping that
conveys water to sprinklers is listed for use with fire sprinklers.
7. Piping is supported in
accordance with the pipe manufacturer’s and sprinkler
manufacturer’s installation instructions.
8. The piping system is tested
in accordance with Section P2503.7.
R-P2904.8.2 Final inspection.
The following items shall be
verified upon completion of the system:
1. Sprinkler are not painted,
damaged or otherwise hindered from operation.
2. Where a pump is required to
provide water to the system, the pump starts automatically upon
system water demand.
3. Pressure-reducing valves,
water softeners, water filters or other impairments to water flow
that were not part of the original design have not been installed.
4. The sign or valve tag
required by Section P2904.7 is installed and the owner’s manual
for the system is present.
Table
P2904.6.2(1) – Water Service Pressure Loss (PL svc ) a,b
Flow
Rate c (gpm)
¾
INCH WATER SERVICE PRESSURE LOSS (psi)
1
INCH WATER SERVICE PRESSURE LOSS (psi)
1
¼ INCH WATER SERVICE PRESSURE LOSS (psi)
Length
of water service pipe (feet)
Length
of water service pipe (feet)
Length
of water service pipe (feet)
40
or less
41
to 75
76
to 100
101
to 150
40
or less
41
to 75
76
to 100
101
to 150
40
or less
41
to 75
76
to 100
101
to 150
8
5.1
8.7
11.8
17.4
1.5
2.5
3.4
5.1
0.6
1.0
1.3
1.9
10
7.7
13.1
17.8
26.3
2.3
3.8
5.2
7.7
0.8
1.4
2.0
2.9
12
10.8
18.4
24.9
NP
3.2
5.4
7.3
10.7
1.2
2.0
2.7
4.0
14
14.4
24.5
NP
NP
4.2
7.1
9.6
14.3
1.6
2.7
3.6
5.4
16
18.4
NP
NP
NP
5.4
9.1
12.4
18.3
2.0
3.4
4.7
6.9
18
22.9
NP
NP
NP
6.7
11.4
15.4
22.7
2.5
4.3
5.8
8.6
20
27.8
NP
NP
NP
8.1
13.8
18.7
27.6
3.1
5.2
7.0
10.4
22
NP
NP
NP
NP
9.7
16.5
22.3
NP
3.7
6.2
8.4
12.4
24
NP
NP
NP
NP
11.4
19.3
26.2
NP
4.3
7.3
9.9
14.6
26
NP
NP
NP
NP
13.2
22.4
NP
NP
5.0
8.5
11.4
16.9
28
NP
NP
NP
NP
15.1
25.7
NP
NP
5.7
9.7
13.1
19.4
30
NP
NP
NP
NP
17.2
NP
NP
NP
6.5
11.0
14.9
22.0
32
NP
NP
NP
NP
19.4
NP
NP
NP
7.3
12.4
16.8
24.8
34
NP
NP
NP
NP
21.7
NP
NP
NP
8.2
13.9
18.8
NP
36
NP
NP
NP
NP
24.1
NP
NP
NP
9.1
15.4
20.9
NP
For
SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.053
L/s, 1 pound per square inch = 6.895 kPa.
NP
– Not permitted. Pressure loss exceeds reasonable limits.
a. Values
are applicable for underground piping materials listed in Table
P2905.4 and are based on an SDR of 11 and a Hazen Williams C Factor
of 150.
b. Values
include the following length allowances for fittings: 25% length
increase for actual lengths up to 100 feet and 15% length increase
for actual lengths over 100 feet.
c. Flow
rate from Section P2904.4.2. Add 5 gpm to the flow rate required by
Section P2904.4.2 where the water-service pipe supplies more than one
dwelling.
Table
P2904.6.2(2) – Minimum Water Meter Pressure Loss (PL m ) a
FLOW
RATE (gallons per minute, gpm) b
5/8-INCH
METER PRESSURE LOSS (pounds per square inch, psi)
¾-INCH
METER PRESSURE LESS (pounds per square inch, psi)
1-INCH
METER PRESSURE LOSS (pounds per square inch, psi)
8
2
1
1
10
3
1
1
12
4
1
1
14
5
2
1
16
7
3
1
18
9
4
1
20
11
4
2
22
NP
5
2
24
NP
5
2
26
NP
6
2
28
NP
6
2
30
NP
7
2
32
NP
7
3
34
NP
8
3
36
NP
8
3
For
SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.896 kPa, 1 gallon
per minute = 0.063 L/s.
NP
– Not permitted unless the actual water meter pressure loss is
known.
a. Table
2904.6.2(2) establishes conservative values for water meter pressure
loss or installations where the water meter loss is unknown. Where
the actual water meter pressure loss is known, P m shall be
the actual loss.
b. Flow
rate from Section P2904.4.2. Add 5 gpm to the flow rate required by
Section P2904.4.2 where the water-service pipe supplies more than one
dwelling.
Table P2904.6.2(3) –
Elevation Loss (PL e )
ELEVATION
(feet)
PRESSURE
LOSS (psi)
5
2.2
10
4.4
15
6.5
20
8.7
25
10.9
30
13
35
15.2
40
17.4
For SI: 1 foot = 304.8 mm, 1
pound per square inch = 6.895 kPa.
Table
P2904.6.2(4) – Allowable Pipe Length for 3/4-Inch Type M Copper
Water Tubing
SPRINKLER
FLOW RATE a (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
¾
217
289
361
434
506
578
650
723
795
867
9
¾
174
232
291
349
407
465
523
581
639
697
10
¾
143
191
239
287
335
383
430
478
526
574
11
¾
120
160
220
241
281
321
361
401
441
481
12
¾
102
137
171
205
239
273
307
241
375
410
13
¾
88
118
147
177
206
235
265
294
324
353
14
¾
77
103
128
154
180
205
231
257
282
308
15
¾
68
90
113
136
158
181
203
226
248
271
16
¾
60
80
100
120
140
160
180
200
220
241
17
¾
54
72
90
108
125
143
161
179
197
215
18
¾
48
64
81
97
113
129
145
161
177
193
19
¾
44
58
73
88
102
117
131
146
160
175
20
¾
40
53
66
80
93
106
119
133
146
159
21
¾
36
48
61
73
85
97
109
121
133
145
22
¾
33
44
56
67
78
89
100
111
122
133
23
¾
31
41
51
61
72
82
92
102
113
123
24
¾
28
38
47
57
66
76
85
95
104
114
25
¾
26
35
44
53
61
70
79
88
97
105
26
¾
24
33
41
49
57
65
73
82
90
98
27
¾
23
30
38
46
53
61
69
76
84
91
28
¾
21
28
36
43
50
57
64
71
78
85
29
¾
20
27
33
40
47
53
60
67
73
80
30
¾
19
25
31
38
44
50
56
63
69
75
31
¾
18
24
29
35
41
47
53
59
65
71
32
¾
17
22
28
33
39
44
50
56
61
67
33
¾
16
21
26
32
37
42
47
53
58
63
34
¾
NP
20
25
30
35
40
45
50
55
60
35
¾
NP
19
24
28
33
38
42
47
52
57
36
¾
NP
18
22
27
31
36
40
45
49
54
37
¾
NP
17
21
26
30
34
38
43
47
51
38
¾
NP
16
20
24
28
32
36
40
45
49
39
¾
NP
15
19
23
27
31
35
39
42
46
40
¾
NP
NP
18
22
26
29
33
37
40
44
For
SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch =
6.895 kPa, 1 gallon per minute – 0.963 L/s.
NP
– Not permitted
a. Flow
rate from Section P2904.4.2.
Table
P2904.6.2(5) – Allowable Pipe Length for 1-inch Type M
Copper Water TubingSPRINKLER FLOW RATEa (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
1
806
1075
1343
1612
1881
2149
2418
2687
2955
3224
9
1
648
864
1080
1296
1512
1728
1945
2161
2377
2593
10
1
533
711
889
1067
1245
1422
1600
1778
1956
2134
11
1
447
586
745
894
1043
1192
1341
1491
1640
1789
12
1
381
508
634
761
888
1015
1142
1269
1396
1523
13
1
328
438
547
657
766
875
985
1094
1204
1313
14
1
286
382
477
572
668
763
859
954
1049
1145
15
1
252
336
420
504
588
672
756
840
924
1008
16
1
224
298
373
447
522
596
671
745
820
894
17
1
200
266
333
400
466
533
600
666
733
799
18
1
180
240
300
360
420
479
539
599
659
719
19
1
163
217
271
325
380
434
488
542
597
651
20
1
148
197
247
296
345
395
444
493
543
592
21
1
135
180
225
270
315
360
406
451
496
541
22
1
124
165
207
248
289
331
372
413
455
496
23
1
114
152
190
228
267
305
343
381
419
457
24
1
106
141
176
211
246
282
317
352
387
422
25
1
98
131
163
196
228
261
294
326
359
392
26
1
91
121
152
182
212
243
273
304
334
364
27
1
85
113
142
170
198
226
255
283
311
340
28
1
79
106
132
159
185
212
238
265
291
318
29
1
74
99
124
149
174
198
223
248
273
298
30
1
70
92
116
140
163
186
210
233
256
280
31
1
66
88
110
132
153
175
197
219
241
263
32
1
62
83
103
124
145
165
186
207
227
248
33
1
59
78
98
117
137
156
176
195
215
234
34
1
55
74
92
111
129
148
166
185
203
222
35
1
53
70
88
105
123
140
158
175
193
210
36
1
50
66
83
100
116
133
150
166
183
199
37
1
47
63
79
95
111
126
142
158
174
190
38
1
45
60
75
90
105
120
135
150
165
181
39
1
43
57
72
86
100
115
129
143
158
172
40
1
41
55
68
82
96
109
123
137
150
164
For
SI: 1 inch = 25.4mm, 1 foot = 304.8mm, 1 pound per square inch =
6.895 kPa, 1 gallon per minute – 0.963 L/s.
a. Flow
rate from Section P2904.4.2.
Table
P2904.6.2(6) – Allowable Pipe Length for ¾-inch CPVC
Pipe
SPRINKLER
FLOW RATE a (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
¾
348
465
581
697
813
929
1045
1161
1278
1394
9
¾
280
374
467
560
654
747
841
934
1027
1121
10
¾
231
307
384
461
538
615
692
769
845
922
11
¾
193
258
322
387
451
515
580
644
709
773
12
¾
165
219
274
329
384
439
494
549
603
658
13
¾
142
189
237
284
331
378
426
473
520
568
14
¾
124
165
206
247
289
330
371
412
454
495
15
¾
109
145
182
218
254
290
327
363
399
436
16
¾
97
129
161
193
226
258
290
322
354
387
17
¾
86
115
144
173
202
230
259
288
317
346
18
¾
78
104
130
155
181
207
233
259
285
311
19
¾
70
94
117
141
164
188
211
234
258
281
20
¾
64
85
107
128
149
171
192
213
235
256
21
¾
58
78
97
117
136
156
175
195
214
234
22
¾
54
71
89
107
125
143
161
179
197
214
23
¾
49
66
82
99
115
132
148
165
181
198
24
¾
46
61
76
91
107
122
137
152
167
183
25
¾
42
56
71
85
99
113
127
141
155
169
26
¾
39
52
66
79
92
105
118
131
144
157
27
¾
37
49
61
73
86
98
110
122
135
147
28
¾
34
46
57
69
80
92
103
114
126
137
29
¾
32
43
54
64
75
86
96
107
118
129
30
¾
30
40
50
60
70
81
91
101
111
121
31
¾
28
38
47
57
66
76
85
95
104
114
32
¾
27
36
45
54
63
71
80
89
98
107
33
¾
25
34
42
51
59
68
76
84
93
101
34
¾
24
32
40
48
56
64
72
80
88
96
35
¾
23
30
38
45
53
61
68
76
83
91
36
¾
22
29
36
43
50
57
65
72
79
86
37
¾
20
27
34
41
48
55
61
68
75
82
38
¾
20
26
33
39
46
52
59
65
72
78
39
¾
19
25
31
37
43
50
56
62
68
74
40
¾
18
24
30
35
41
47
53
59
65
71
For
SI: 1 inch = 25.4mm, 1 foot – 304.8mm, 1 pound per square inch
– 6.895 kPa, 1 gallon per minute = 0.0963 L/s.
a. Flow
rate from Section P2904.4.2.
Table
P2904.6.2(7) – Allowable Pipe Length for 1-inch CPVC Pipe
SPRINKLER
FLOW RATEa (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
1
1049
1398
1748
2098
2447
2797
3146
3496
3845
4195
9
1
843
1125
1406
1687
1968
2249
2530
2811
3093
3374
10
1
694
925
1157
1388
1619
1851
2082
2314
2545
2776
11
1
582
776
970
1164
1358
1552
1746
1940
2133
2327
12
1
495
660
826
991
1156
1321
1486
1651
1816
1981
13
1
427
570
712
854
997
1139
1281
1424
1566
1709
14
1
372
497
621
745
869
993
1117
1241
1366
1490
15
1
328
437
546
656
765
874
983
1093
1202
1311
16
1
291
388
485
582
679
776
873
970
1067
1164
17
1
260
347
433
520
607
693
780
867
954
1040
18
1
234
312
390
468
546
624
702
780
858
936
19
1
212
282
353
423
494
565
635
706
776
847
20
1
193
247
321
385
449
513
578
642
706
770
21
1
176
235
293
352
410
469
528
586
645
704
22
1
1161
215
269
323
377
430
484
538
592
646
23
1
1149
198
248
297
347
396
446
496
545
595
24
1
137
183
229
275
321
366
412
458
504
550
25
1
1127
170
212
255
297
340
382
425
467
510
26
1
118
158
197
237
276
316
355
395
434
474
27
1
111
147
184
221
258
295
332
368
405
442
28
1
103
138
172
207
241
275
310
344
379
413
29
1
97
129
161
194
226
258
290
323
355
387
30
1
91
121
152
182
212
242
273
303
333
364
31
1
86
114
143
171
200
228
257
285
314
342
32
1
81
108
134
161
188
215
242
269
296
323
33
1
176
102
127
152
178
203
229
254
280
305
34
1
72
96
120
144
168
192
216
240
265
289
35
1
68
91
114
137
160
182
205
228
251
273
36
1
165
87
108
130
151
173
195
216
238
260
37
1
62
82
103
123
144
165
185
206
226
247
38
1
59
78
98
117
137
157
176
196
215
235
39
1
56
75
93
112
131
149
168
187
205
224
40
1
53
71
89
107
125
142
160
178
196
214
For
SI: 1 inch = 25.4mm, 1 foot = 304.8mm, 1 pound per square inch =
6.895 kPa, 1 gallon per minute = 0.963 L/s.
a. Flow
rate from Section P2904.4.2.
Table P2904.6.2(8) –
Allowable Pipe Length for ¾-inch PEX Tubing
SPRINKLER
FLOW RATE a (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
¾
93
123
154
185
216
247
278
309
339
370
9
¾
74
99
124
149
174
199
223
248
273
298
10
¾
61
82
102
123
143
163
184
204
225
245
11
¾
51
68
86
103
120
137
154
171
188
205
12
¾
44
58
73
87
102
117
131
146
160
175
13
¾
38
50
63
75
88
101
113
126
138
151
14
¾
33
44
55
66
77
88
99
110
121
132
15
¾
29
39
48
58
68
77
87
96
106
116
16
¾
26
34
43
51
60
68
77
86
94
103
17
¾
23
31
38
46
54
61
69
77
84
92
18
¾
21
28
34
41
48
55
62
69
76
83
19
¾
19
25
31
37
44
50
56
62
69
75
20
¾
17
23
28
34
40
45
51
57
62
68
21
¾
16
21
26
31
36
41
47
52
57
62
22
¾
NP
19
24
28
33
38
43
47
52
57
23
¾
NP
17
22
26
31
35
39
44
48
52
24
¾
NP
16
20
24
28
32
36
40
44
49
25
¾
NP
NP
19
22
26
30
34
37
41
45
26
¾
NP
NP
17
21
24
28
31
35
38
42
27
¾
NP
NP
16
20
23
26
29
33
36
39
28
¾
NP
NP
15
18
21
24
27
30
33
36
29
¾
NP
NP
NP
17
20
23
26
28
31
34
30
¾
NP
NP
NP
16
19
21
24
27
29
32
31
¾
NP
NP
NP
15
18
20
23
25
28
30
32
¾
NP
NP
NP
NP
17
19
21
24
26
28
33
¾
NP
NP
NP
NP
16
18
20
22
25
27
34
¾
NP
NP
NP
NP
NP
17
19
21
23
25
35
¾
NP
NP
NP
NP
NP
16
18
20
22
24
36
¾
NP
NP
NP
NP
NP
15
17
19
21
23
37
¾
NP
NP
NP
NP
NP
NP
16
18
20
22
38
¾
NP
NP
NP
NP
NP
NP
16
17
19
21
39
¾
NP
NP
NP
NP
NP
NP
NP
16
18
20
40
¾
NP
NP
NP
NP
NP
NP
NP
16
17
19
For
SI: 1 inch = 25.4mm, 1 foot = 304.8mm, 1 pound per square inch =
6.895 kPa, 1 gallon per minute = 0.963 L/s.
NP
– Not permitted.
a. Flow
rate from Section P2904.4.2.
Table P2904.6.2(9) –
Allowable Pipe Length for 1-inch PEX Tubing
SPRINKLER
FLOW RATEa (gpm)
WATER
DISTRIBUTION SIZE (inch)
Available
Pressure – P t (psi)
15
20
25
30
35
40
45
50
55
60
Allowable
length of pipe from service valve to farthest sprinkler (feet)
8
1
314
418
523
628
732
837
941
1046
1151
1255
9
1
252
336
421
505
589
673
757
841
925
1009
10
1
208
277
346
415
485
554
623
692
761
831
11
1
174
232
290
348
406
464
522
580
638
696
12
1
148
198
247
296
346
395
445
494
543
593
13
1
128
170
213
256
298
341
383
426
469
511
14
1
111
149
186
223
260
297
334
371
409
446
15
1
98
131
163
196
229
262
294
327
360
392
16
1
87
116
145
174
203
232
261
290
319
348
17
1
78
104
130
156
182
208
233
259
285
311
18
1
70
93
117
140
163
187
210
233
257
280
19
1
63
84
106
127
148
169
190
211
232
253
20
1
58
77
96
115
134
154
173
192
211
230
21
1
53
70
88
105
123
140
158
175
193
211
22
1
48
64
80
97
113
129
145
161
177
193
23
1
44
59
74
89
104
119
133
148
163
178
24
1
41
55
69
82
96
110
123
137
151
164
25
1
38
51
64
76
89
102
114
127
140
152
26
1
35
47
59
71
83
95
106
118
130
142
27
1
33
44
55
66
77
88
99
110
121
132
28
1
31
41
52
62
72
82
93
103
113
124
29
1
29
39
48
58
68
77
87
97
106
116
30
1
27
36
45
54
63
73
82
91
100
109
31
1
26
34
43
51
60
68
77
85
94
102
32
1
24
32
40
48
56
64
72
80
89
97
33
1
23
30
38
46
53
61
68
76
84
91
34
1
22
29
36
43
50
58
65
72
79
86
35
1
20
27
34
41
48
55
61
68
75
82
36
1
19
26
32
39
45
52
58
65
71
78
37
1
18
25
31
37
43
49
55
62
68
74
38
1
18
23
29
35
41
47
53
59
64
70
39
1
17
22
28
33
39
45
50
56
61
67
40
1
16
21
27
32
37
43
48
53
59
64
For
SI: 1 inch = 25.4mm, 1 foot = 304.8mm, 1 pound per square inch =
6.895 kPa, 1 gallon per minute = 0.963 L/s.
a. Flow
rate from Section P2904.4.2.
2.28 Appendix
AA
Add
the following new Appendix AA
AA 100 HIGH WIND PRESCRIPTIVE
DESIGN
AA 101.1 General.
This appendix contains
prescriptive solutions for compliance on wind path load transfer
requirements and shall be used only within the limitations of section
AA101.2.
AA 101.2 Conditions of use.
The prescriptive solutions
specified in the following sections shall not be permitted to be used
in the following conditions:
(1) Buildings and structures
of any size in 110 MPH or 120 MPH wind zones located in a V zone as
determined by community FIRMS.
(2) Two or more story
buildings and structures of any size located in 120 MPH wind zone
with more than 20% exterior fenestration.
(3) Two or more story
structures with a building height greater than 33’ as measured
from Grade Plane to the average height of the highest roof surface.
(4) Any two or more-story
structure or building with opening fenestration greater than 40% on
any one wall.
AA 202 Roofs
AA 202.1 Scope.
The following applies to
structures conventionally framed or to truss-type roofs.
AA 202.2 Roof Sheathing.
Roof sheathing shall be not
less than 7/16” finished thickness.
AA 202.3 Roof nailing.
Roof attachment shall be
accomplished with minimum 8d ring shank nails as follows:
(1) In the 4-foot perimeter
edge zone along the edges: 6” o/c
(2) To the intermediate
supports within the 4-foot perimeter edge zone: 6” o/c
(3) Along the gable end wall
or rake: 4” o/c
(4) All other areas: 6”
o/c edge; 12” o/c intermediate.
All sheathing edges within
the 4-foot perimeter edge zone shall be blocked with 2x3 minimum
including the ridge line and soffit/fascia area. Provisions for
ventilation air shall be maintained.
Exception: 2 x 3 intermediate
blocking can be eliminated provided all sheathing is 5/8”
nominal tongue and groove structural panels.
AA 202.4 Ridge Straps.
Ridge straps 1-1/4” x
20 gage shall be attached to each pair of opposing rafters with 5-8d
nails at each end into the framing member.
Exceptions:
1. Ridge straps are not
required when collar ties of nominal 1 x 6 or 2 x 4 lumber are
located within the upper third of the attic space and attached to
each rafter with 3-10 d nails
2. Trusses without a framed
ridge connection.
3. Plywood gussets of
equivalent cross section.
4. Other engineered
connections.
5. At hips, straps shall be
installed so each hip jack is connected across the hip line with at
least 1-8d into an opposite framing member.
AA 202.5 Rake and eave
overhangs.
Overhangs shall be limited to
24”. Ladder style rake overhangs attached to the gable end
walls shall be limited to 12”. Cantilevered rake overhangs at
gable end walls shall be limited to 24”.
AA 202.6 Roof assembly to
wall assembly.
See Section R802.11.
Exception: Roof truss to wall
connection shall be designed to withstand either the load
requirements of Table R802.11 or the connection loads indicated on
the truss design shop drawings, whichever is greater.
AA 203 Walls
AA 203.1 Wall sheathing.
Wall sheathing shall be a
minimum 7/16” structural panel. Nailing shall be in accordance
with Table R602.3 (1) and the following:
At the top plate or plates,
the sheathing shall extend from the top of the top plate to a minimum
of 16” beyond the stud-to-bottom of the top plate connection. A
minimum of 4 nails shall be used at each stud fastening, and
edge-nailed to each plate at 6” o/c.
Alternate: prefabricated and
pre-engineered connection straps approved by the Building Official.
If the studs are not
continuous to the foundation plate such as at an intermediate floor,
the wall sheathing shall be continuous and uninterrupted for a
distance of 16” beyond from top of bottom wall plate to 16”
beyond bottom of bottom wall top plate below, with a minimum of 4
nails at each stud, and field-nailed at 6” o/c to floor joist
header framing.
Alternate: Prefabricated and
pre-engineered connection anchors or fasteners approved by the
Building Official.
At the bottom of the wall
assembly to the foundation sill plate, the wall sheathing shall be
continuous from a point 16” above the top of the bottom wall
plate to the bottom of the foundation sill, with a minimum of 4 nails
at each stud, 6” field nailed, and edge nailed to the
foundation sill plate at 6” o/c.
Alternate: Prefabricated
pre-engineered connection anchors or fasteners approved by the
Building Official.
AA 203.2 Shear Walls.
A 4’ segment of wall
sheathing shall be designated as a shear wall at each corner of the
structure at each floor, and no more than 24’ apart along a
wall length. The following additional requirements apply:
1. No openings are permitted
within this 4’ section.
Exception: Window openings
are allowed no closer than 2’ to corner providing the length of
that shear panel is increased to 8’.
2. All edges shall be blocked
and nailed at 6” o/c, and field-nailed at 6” o/c.
3. Studs shall be doubled at
each end of the shear wall panel.
AA 203.2.1 Shear wall
hold-downs.
1st story shear walls shall
be connected to the foundation below with connection anchoring
capable of 3500 lb. hold-down capacity, in addition to conventional
foundation anchor bolt requirements in the remainder of the panel.
The hold downs shall be fastened to each end of the shear wall at the
double stud.
Exceptions
1. Shear wall hold-downs shall
not be required in wind zones I or II (100 mph or 110 mph).
2. Shear wall anchors shall
not be required provided ½” anchor bolts at 48”
o/c max are installed with the top of the bolts anchored through the
floor system to the bottom plate of the exterior wall frame for the
entire foundation perimeter.
AA 203.3 Foundation anchor
bolts.
Anchor bolts shall be
installed in accordance with section R403.1.6 and the following:
1
+ 2 story buildings
½”
@ 48” o/c or
5/8”
@ 72” o/c
3
story building
½”
@ 24” o/c or
5/8”
@ 36” o/c
Alternate
Prefabricated and
pre-engineered connections in design and quantity sufficient to equal
strength of anchor bolt specification above.
Exception.
See Exception #2 to AA
203.2.1 above.
203.4 Wall Framing.
AA203.4.1. Wind Zone
For wind zone 2 (110 mph) and
zone 3 (120 mph) the following conditions apply:
Exterior bearing and
non-bearing walls greater than 10’ in height shall be 2 x 6 @
16” o/c min.
Walls with a total height
greater than 10’ shall be permitted to use 2 x 4 @ 16”
o/c providing the wall is limited to 10’ in length and the
individual studs are not greater than 9’ in length.
AA203.4.2 Garage doors.
In wind zone 3 (120) mph
garage doors shall be limited to 9’ x 8’ nominal.
AA204 Deviations.
AA204.1 Deviations.
Deviations from the above
prescriptive requirements shall only be permitted if stamped
calculations and drawings are provided by a Rhode Island registered
professional engineer for alternative connections.