510-RICR-00-00-4
510-RICR-00-00-4. RISBC-4 Rhode Island Mechanical Code (version Amendment, 07/01/2013 to 07/01/2013)
RHODE ISLAND
STATE BUILDING CODE
SBC-4 State Mechanical Code
Replaces SBC-4-2010
Effective July 1, 2013
STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS
Department of Administration
BUILDING CODE STANDARDS COMMITTEE
One Capitol Hill
Providence, RI 02908-5859
(401) 222-3033
FAX NO. (401) 222-2599
www.ribcc.ri.gov
11th Edition
1
SBC-4 2013
1
SBC-4 2013
Regulation SBC-4
State Mechanical Code
July 1, 2013
The Building Code Standards Committee, in accordance with the rule making authority
of Title 23, Chapter 23-27.3, Section 109.1, paragraphs a through c inclusive, has
formally adopted and promulgated as the Rhode Island State Building Code, the
provisions of the International Mechanical Code, 2012 edition, as published by the
International Code Council, Inc. (I.C.C.), together with amendments thereto hereinafter
set forth to the articles and sections of this code:
The provisions of Title 23, Chapter 27.3 of the General Laws of Rhode Island
establishing administration and enforcement are hereby incorporated by reference.
Regulatory Administration Chapter 1 immediately follows and is supplemental to the
General Laws.
Editorial Note: Code users please note:
When purchasing or using the International Mechanical 2012 code, please take note of
the particular printing edition. Errata to that printing edition is available on-line directly
at no charge at www.iccsafe.org/cs/codes/pages/errata.aspx or call the office of the State
Building Code Commissioner at 401-222-3033 for further information.
Printed copies of the administrative and enforcement provisions of Title 23, Chapter 27.3
are available at the Office of the State Building Code Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM.
The International Mechanical Code, 2012 Edition, is protected by the copyright that has
been issued to the ICC. As a result, the State Building Code is not available in complete
form to the public in an electronic format. The International Mechanical Code 2012
edition that is referred to within is contained in a printed volume and is also in an
electronic format that have been published by the ICC under an exclusive license.
The Office of the State Building Code Commissioner has purchased volumes of these
codes and they shall be distributed to Rhode Island cities and towns during the month of
June 2013 so that local officials will have access to the code prior to the implementation
of these rules on July 1, 2013.
In order to assure public access to this code the Office of the State Building Code
Commissioner shall provide a copy of this code to the Rhode Island State Library, which
is located on the second floor of the State House. In addition, all codes may be viewed
during business hours at the Department of Administration’s Library which is located on
the fourth floor of the William E. Powers Building, One Capitol Hill, Providence.
The Legislative Regulation Committee approved adoption of this code on July 1, 2013.
By:
John P. Leyden
Executive Secretary
Rhode Island Building Code Standards Committee
1
SBC-4 2013
STATE OF RHODE ISLAND
BUILDING CODE STANDARDS COMMITTEE
CHAIRMAN
VICE CHAIRMAN
William J. Nash, Jr.
Building Official
Bernard J. Bernard, III
Electrical Inspector
EXECUTIVE COMMITTEE
Michael A Newman
Master Plumber
James Fink
Electrical Engineer
Doris Aschman
Public Health Official
Bruce Davey, PE
Structural Engineer
Scott Caron
Fire Official
Michael Daley
Builders Trades Council
Stephen C. Turner, PE
Public Member
Peter Scorpio, III
Building Official
Dana Newbrook
Architect
James R. Carlson, RA
Public Member
Fred Sarno
Building Official
G. Thomas Chabot
Electrical Contractor
David F. Palmisciano
Building Trades Council
Randy Collins, Jr., RLA
Landscape Architect
Gordon W. Preiss, PE
Mechanical Engineer
Robert E. DeBlois, Jr.
Builder
Craig Sutton
Builder
Paul DePace, PE
Representative for the Disabled
Russell Brown
Representative for the Disabled
Robert M. Stillings
Architect
John P. Leyden, CBO
State Building Commissioner
Executive Secretary
Wayne Pimental, CBO
Minimum Housing Inspector
Thomas Coffey
Legal Counsel
1
SBC-4 2013
STATE BUILDING CODE REGULATIONS - 2013
The following list includes all regulations promulgated by the State Building Code
Standards Committee. All regulations are available for a fee at the State Building
Commission.
1.
Building Code
SBC-1-2013
2..
One and Two Family Dwelling Code
SBC-2-2013
3.
Plumbing Code
SBC-3-2013
4.
Mechanical Code
SBC-4-2013
5.
Electrical Code
SBC-5-2011
6.
Property Maintenance Code
SBC-6-2013
7.
Reserved
8.
Energy Conservation Code
SBC-8-2013
9
Enforcement and Implementation Procedures
for Projects Under the Jurisdiction of The
State of Rhode Island
SBC-9
10.
Code Interpretations
SBC-10
11.
Certification of Building Officials,
Building, Electrical, Plumbing and
Mechanical Inspectors
SBC-11-2010
12.
New Materials and Methods of Construction
SBC-12
13.
State Building Code for Existing Schools
SBC-13
14.
Reserved
15.
Reserved
16.
Reserved
17.
Public Buildings Accessibility Meeting
Standards
SBC-17
18.
Native Lumber
SBC-18
19.
Fuel Gas Code
SBC-19-2013
20.
The State of Rhode Island Rehabilitation
Building and Fire Code for Existing Buildings
and Structures
SRC-1-2002
1
SBC-4 2013
Chapter 1
Delete IMC section 101.1, Title, and substitute the following:
101.1 Title. These regulations shall be known as Rhode Island State Mechanical Code
Regulation SBC-4 - 2010, hereafter referred to as "this code".
Add the following new section 101.1.1 Referenced Codes:
101.1.1 Referenced Codes. The other codes referenced elsewhere in this code
shall be considered part of the requirements of this code to the prescribed extent
of each such reference.
1.
Electrical. The provisions of Rhode Island State Electrical Code SBC-5-2008
shall apply wherever referenced in this code as the ICC Electrical Code, and shall
apply to the installation of electrical systems, including alterations, repairs,
replacement, equipment, appliances, fixtures, fittings, and appurtenances thereto.
2.
Gas. The provisions of the Rhode Island State Fuel Gas Code SBC-19-2010 shall
apply wherever referenced in this code as the International Fuel Gas Code, and
shall apply to the installation of gas piping from the point of delivery, gas
appliances and related accessories as covered in this code. These requirements
apply to gas piping systems extending from the point of delivery to the inlet
connections of appliances and the installation and operation of residential and
commercial gas appliances and related accessories.
3.
Building. The provisions of the Rhode Island State Building Code SBC-1-2010
shall apply wherever referenced in this code as the International Building Code.
4.
Plumbing. The provisions of Rhode Island State Plumbing Code SBC-3-2010
shall apply wherever referenced in this code as the International Plumbing Code,
and shall apply to the installation, alteration, repair and replacement of plumbing
systems, including equipment, appliances, fixtures, fittings and appurtenances,
and where connected to a water or sewage system and all aspects of a medical gas
system.
5.
Property Maintenance. The provisions of the Rhode Island State Property
Maintenance Code SBC-6-2010 Provides requirements for continued use and
maintenance buildings and property, and of related plumbing, mechanical,
electrical and fire protection systems in existing residential nonresidential
structures.
6.
Fire Prevention Code. Wherever and whenever provisions of the International
Fire Code 2003 editions are referenced, the appropriate Rhode Island Fire Safety
Code requirement shall apply
7. Energy. The provisions of the Rhode Island State Energy Code SBC-8-2010
2
SBC-4 2013
shall apply wherever referenced in this code as International Energy Conservation
Code, and shall apply to the installation, alteration repair and replacement of
energy systems and all matters governing the design and construction of buildings
for energy efficiency.
Any and all such references to the various International Code Council family of
codes shall be substituted for the appropriate state code as indicated above.
All other Administrative provisions shall remain in effect. To the extent that there is an
apparent conflict between the provisions of these administrative sections and RIGL 23-
27.3 101.0 et al, the provisions of state law shall prevail. Where other provisions of this
code refer to provisions of Chapter 1 Administration, Chapter 1 Administration, or RIGL
23-27.3-101.0 et al shall apply as appropriate.
Delete IMC Sections 102.8 Exception, 102.10, 102.11, 103, 104, 106.4 through 106.5.3,
108 and 109 and refer to the appropriate sections of SBC-1-2013 and RIGL 23-27.3-100
et al.
102.1.1 Contractor's responsibilities. It shall be the duty of every contractor who enters
into contracts for the installation or repair of mechanical systems for which a permit is
required to comply with adopted state and local rules and regulations concerning
licensing.
Any building owner, authorized agent, person or contractor who installs, modifies or
repairs mechanical systems for which a permit is required shall comply with all state laws
and regulations regarding licensing.
3
SBC-4 2013
Chapter 3
306.5.2 Delete and substitute the following
306.5.2 Electrical requirements a receptacle outlet shall be provided at or near the
appliance location in accordance with NFPA70
4
SBC-4 2013
Chapter 5
501.3.1
Delete and substitute the following
501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts
discharging to the outdoors shall be located with the following minimum
distances:
1. For ducts conveying explosive or flammable vapors, fumes or dusts:
30 feet (9144 mm) from property lines; 10 feet (3048 mm) from
operable openings into buildings; 6 feet (1829 mm) from exterior walls
and roofs; 30 feet (9144 mm) from combustible walls and operable
openings into buildings which are in the direction of the exhaust
discharge; 10 feet (3048 mm) above adjoining grade.
2. For other product-conveying outlets: 10 feet (3048mm) from the
property lines; 3 feet (914 mm) from exterior walls and roofs; 10 feet
(3048 mm) from operable openings into buildings; 10 feet (3048 mm) \
above adjoining grade of public walkways.
3. For all environmental air exhaust: 3 feet (914 mm) from property lines;
3 feet (914 mm) from operable openings into buildings for all
occupancies other than Group U, and 10 feet (3048 mm) from
mechanical air intakes. Such exhaust shall not be considered
hazardous or noxious.
4. Exhaust outlets serving structures in flood hazard areas shall be
installed at or above the design flood level.
5. For specific systems see the following sections:
5.1. Clothes dryer exhaust, Section 504.4.
5.2. Kitchen hoods and other kitchen exhaust equipment, Sections
506.3.12, 506.4 and 506.5.
5.3. Dust stock and refuse conveying systems, Section 511.
5.4. Sub slab soil exhaust systems, Section 512.4
5.5. Smoke control systems, Section 513.10.3
5.6. Refrigerant discharge, Section1105.7
5.7. Machinery room discharge, Section 1105.6.1.
Delete Section 502.19 in its entirety.
5
SBC-4 2013
504.6.5 Length Identifications The maximum length of dryer duct may exceed 35’ when
a permanent placard, measuring a minimum 5” wide, 3” high, and 1/8” thick, and
constructed of either wood, metal, or rigid plastic, and bearing raised or embossed
lettering stating the following: “WARNING: THE EFFECTIVE LENGTH OF THIS
DRYER DUCT IS xxx FEET. ANY DRYER CONNECTED TO THIS EXHAUST
DUCT MUST BE RATED TO USE AN EXHAUST DUCT OF THIS LENGTH,
PER THE MANUFACTURERS SPECIFICATIONS; SERVERE RISK OF FIRE
MAY RESULT FOR NONCOMPLIANCE WITH THIS NOTICE.”
The provisions of table 504.6.4.1 shall be used in establishing the effective length
of the ductwork installed and noted on the placard. The placard shall be permanently
attached to the wall or floor within 6” of the terminus of the duct.
6
SBC-4 2013
Chapter 6
603.2 Duct sizing Delete and substitute the following
603.2 Duct sizing ducts installed within a single dwelling unit shall be sized in
accordance with ACCA Manual D or other approved methods. Ducts
installed within all other buildings shall be sized in accordance acceptable
methods.
606.2.1 Delete and Substitute the following:
606.2.1 Return air systems smoke detectors listed for use in air
Distribution systems shall be located as follows.
(1) Downstream of the air filters and ahead of any branch connections in air supply
systems having a capacity greater than 944L/Sec (2000ft3/min)
(2) At each story prior to the connection to a common return and prior to any
recirculation or fresh air inlet connection in air return systems having a capacity greater
than 7080L/sec ( 15,000 ft3/min) and serving more than one story.
Revise section 607.5.5 as follows:
607.5.5 Shaft Enclosures: Shaft enclosures in use group I and in high-rise structures that
are permitted to be penetrated by ducts and air transfer openings shall be protected with
approved fire and smoke dampers, installed in accordance with their listing. All other use
group shaft enclosure penetrations shall be protected with approved fire dampers installed
in accordance with their listing.
Retain sections 1, 1.1, 1.2, 1.3, 1.4 and delete exceptions 2, 3, 4 and 5.
7
SBC-4 2013
Chapter 10
Add Exception #8 to IMC section 1001. 1 as follows:
8. Permits for steam and water boiler installation and repairs of boilers over 200, 000
BTUs for commercial uses and 400,000 BTUs for private residences or apartments shall
be issued by the Department of Labor, Division of Occupational Safety, Boiler Unit.
1003.1 General delete and substitute
1003.1 General All pressure vessels shall bear the label of an approved agency and
shall be installed in accordance with the manufacturer’s installation
instruction.
8
SBC-4 2013
Chapter 11
Add the following new section 1101.1:
1101.1 " Prohibited Connections" The uses of potable water as an open loop, single
pass heat exchange fluid for the refrigeration cycle of HVAC equipment is prohibited.
Delete IMC Section 1105.3 and substitute the following:
1105.3 Refrigerant detector: Machinery rooms shall contain a refrigerant detector with
an audible and visual alarm. The detector, or a sampling tube that draws air to the
detector, shall be located in an area where refrigerant from leak will concentrate. The
alarm shall be actuated at value not greater than the corresponding TLV-TWA values
shown for the refrigerant classification. Detectors and alarms shall be placed in approved
locations.
Delete IMC Section 1105.3 and substitute the following:
1105.9 Emergency pressure control system. Refrigeration systems containing more
than 6.6 pound (93kg) of flammable, toxic or highly toxic refrigerant or ammonia shall be
equipped with an emergency pressure control system in accordance with sections
1105.8.1.1 and 1105.8.2
1105.9.1 Automatic crossover valves. Each high-and-intermediate-pressure zone in a
refrigeration system shall be provided with a single automatic valve providing a
crossover connection to a lower pressure zone. Automatic crossover valves shall comply
with sections 1105.8.1.1 through 1105.8.1.3.
1105.91.1 Overpressure light setpoint. Automatic crossover valves shall be arranged to
automatically relieve excess system pressure to a lower pressure zone if the pressure in a
high-or intermediate-pressure zone rises to within 15psi (108.4 kPa) of the setpoint for
emergency pressure-relief devices.
1105.9.1.2 Manual operation. When required by the fire code official, automatic
crossover valves shall be capable of manual operation.
1105.9.1.3 System design pressure. Refrigeration system zones are connected to a
higher pressure zone by an automatic crossover valve shall be designed to safely contain
the maximum pressure that can be achieved by interconnection of the two zones.
1105.9.2 Automatic emergency stop. An automatic emergency stop feature shall be
provided in accordance with section 1105.9.2.1 and 1105.9.2.2
1105.9.2.1 Operation of an automatic crossover valve. Operation of an automatic
crossover valve shall cause all compressors on the effected system to immediately stop.
Dedicated pressure-sensing devices located immediately adjacent to crossover valves
shall be permitted as a means for determining operation of a valve. To ensure that the
automatic crossover valve system provides a redundant means of stopping compressors in
an over pressure condition, high-pressure cutout sensors associated with compressors
shall not be used as a basis for determining operation of a crossover valve.
9
SBC-4 2013
1105.9.2.2 Overpressure in low-pressure zone. The lowest pressure zone in a
refrigeration system shall be provided with a dedicated means of determining a rise in
system pressure to within 15 psi (103.4 kPa) of the setpoint for emergency pressure-relief
devices. Activation of the overpressure sensing device shall cause all compressors on the
effected system to immediately stop.
10
SBC-4 2013
Chapter 12
Table 1202.4 Delete without substitution
Lead Pipe FS WW-P-325B
Delete IMC section 1208.1.1 and substitute the following:
1208.1.1 Ground source heat pump loop systems. Before connection (header)
trenches are backfilled, the assembled loop system shall be pressure tested with water at
100 psi (689 kPa) for 30 minutes with no observed leaks. Flow pressure loss testing shall
be performed and the actual flow rates and pressure drops shall be compared to the
calculated design values. If actual flow rate or pressure differs from calculated design
values, the designer of record shall identify the problem and order corrections as
required.
11
SBC-4 2013
Chapter 13
Add the following new section 1301.2.1:
1301.2.1 Maximum inside fuel oil storage. Where connected to a fuel-
Oil piping system, the maximum amount of fuel oil allowed inside any building shall be
1, 320 gallons and the maximum amount of oil connected to any one- (1) appliance shall
be 660 gallons. Where the amount of fuel oil stored inside a building exceeds 1, 320
gallons the storage area shall be in compliance with the R.I. Fire Prevention Code and the
State Building Code.
Add the following new section 1305.8:
1305.8 Fuel Oil Supply and Vent Piping: Fill and vent lines for above ground fuel
storage tanks shall be permitted to be a minimum of 1 ¼ “in diameter for a single storage
tank up to 500 gallon capacity.
12
SBC-4 2013
Chapter 15
Referenced Standards
Delete without substitution
ASHRAE-2009
ASHRAE Fundamentals handbook-
603.2
13
SBC-4 2013
APPENDIX B
Appendix B:
Delete APPENDIX B" in its entirety.