510-RICR-00-00-4. RISBC-4 Rhode Island Mechanical Code (version Amendment, 08/01/2019 to 01/04/2022)
4.1 Authority
The Building Code Standards
Committee, in accordance with the rule making authority of R.I. Gen.
Laws §§ 23-27.3-109.1 (a)
through (c) inclusive, has formally adopted and promulgated as the
Rhode Island State Building Code, the provisions of the International
Mechanical Code, 2015 edition, as published by the International Code
Council, Inc. (I.C.C.), together with amendments thereto hereinafter
set forth to the articles and sections of this code:
4.2 Incorporated Materials
A. The provisions of R.I. Gen.
Laws Chapter 23-27.3 establishing administration and enforcement are
hereby incorporated by reference. § 4.3 of this Part (Chapter 1)
immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
1. When purchasing or using
the International Mechanical Code 2015, please take note of the
particular printing edition. Errata to that printing edition is
available on-line directly at no charge at
www.iccsafe.org/cs/codes/pages/errata.aspx
or call the office of the State Building Code Commissioner at
401-889-5550 for further information.
2. Printed copies of the
administrative and enforcement provisions of R.I. Gen. Laws Chapter
23-27.3 are available at the Office of the State Building Code
Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM .
3. The International
Mechanical Code, 2015 Edition, is protected by the copyright that has
been issued to the ICC. As a result, the State Building Code is not
available in complete form to the public in an electronic format. The
International Mechanical Code 2015 edition that is referred to within
is contained in a printed volume and is also in an electronic format
that have been published by the ICC under an exclusive license.
4.3 Chapter
1
Delete IMC section 101.1,
Title, and substitute the following:
101.1 Title. This part shall
be known as Rhode Island State Mechanical Code Regulation SBC-4-2019,
hereafter referred to as "this code".
Add the following new section
101.1.1 Referenced Codes:
101.1.1 Referenced Codes. The
other codes referenced elsewhere in this code shall be considered
part of the requirements of this code to the prescribed extent of
each such reference.
1. Electrical. The provisions
of Rhode Island State Electrical Code SBC-5-2019, ( Part
5 of this Subchapter ), shall apply wherever referenced in this
code as the ICC Electrical Code, and shall apply to the installation
of electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings, and appurtenances thereto.
2. Gas. The provisions of the
Rhode Island State Fuel Gas Code SBC-18-2019, ( Part
19 of this Subchapter ), shall apply wherever referenced in this
code as the International Fuel Gas Code, and shall apply to the
installation of gas piping from the point of delivery, gas appliances
and related accessories as covered in this code. These requirements
apply to gas piping systems extending from the point of delivery to
the inlet connections of appliances and the installation and
operation of residential and commercial gas appliances and related
accessories.
3. Building. The provisions of
the Rhode Island State Building Code SBC-1-2019, ( Part
1 of this Subchapter ), shall apply wherever referenced in this
code as the International Building Code.
4. Plumbing. The provisions of
Rhode Island State Plumbing Code SBC-3-2019, ( Part
3 of this Subchapter ), shall apply wherever referenced in this
code as the International Plumbing Code, and shall apply to the
installation, alteration, repair and replacement of plumbing systems,
including equipment, appliances, fixtures, fittings and
appurtenances, and where connected to a water or sewage system and
all aspects of a medical gas system.
5. Property Maintenance. The
provisions of the Rhode Island State Property Maintenance Code
SBC-6-2019, ( Part
6 of this Subchapter ), provides requirements for continued use
and maintenance buildings and property, and of related plumbing,
mechanical, electrical and fire protection systems in existing
residential nonresidential structures.
6. Fire Prevention Code.
Wherever and whenever provisions of the International Fire Code 2015
editions are referenced, the appropriate Rhode Island Fire Code
( 450-RICR-00-00-1
through 10 ) requirement shall apply.
7. Energy. The provisions of
the Rhode Island State Energy Code SBC-8-2019, ( Part
8 of this Subchapter ), shall apply wherever referenced in this
code as International Energy Conservation Code, and shall apply to
the installation, alteration repair and replacement of energy systems
and all matters governing the design and construction of buildings
for energy efficiency.
Any and all such references
to the various International Code Council family of codes shall be
substituted for the appropriate state code as indicated above.
All other Administrative
provisions shall remain in effect. To the extent that there is an
apparent conflict between the provisions of these administrative
sections and R.I. Gen. Laws § 23-27.3-101.0 et al , the
provisions of state law shall prevail. Where other provisions of this
code refer to provisions of § 4.3 of this Part (Chapter 1
Administration) or R.I. Gen. Laws Chapter 23-27.3 shall apply as
appropriate.
Delete IMC Sections 102.8
Exception, 102.10, 102.11, 103, 104, 106.4 through 106.5.3, 108 and
109 and refer to the appropriate sections of Part
1 of this Subchapter and R.I. Gen. Laws Chapter 23-27.3.
102.1.1 Contractor's
responsibilities. It shall be the duty of every contractor who enters
into contracts for the installation or repair of mechanical systems
for which a permit is required to comply with adopted state and local
rules and regulations concerning licensing.
Any building owner, authorized
agent, person or contractor who installs, modifies or repairs
mechanical systems for which a permit is required shall comply with
all state laws and regulations regarding licensing.
4.4 Chapter
3
307.2
Exception: Deleted in Rhode Island
307.3
Deleted in Rhode Island
4.5 Chapter 5
504.8.5 Length Identifications
The maximum length of dryer duct may exceed 35’ when a
permanent placard, measuring a minimum 5” wide, 3” high,
and 1/8” thick, and constructed of either wood, metal, or rigid
plastic, and bearing raised or embossed lettering stating the
following: “WARNING: THE EFFECTIVE LENGTH OF THIS DRYER DUCT IS
xxx FEET. ANY DRYER CONNECTED TO THIS EXHAUST DUCT MUST BE RATED TO
USE AN EXHAUST DUCT OF THIS LENGTH, PER THE MANUFACTURERS
SPECIFICATIONS; SEVERE RISK OF FIRE MAY RESULT FOR NONCOMPLIANCE WITH
THIS NOTICE.”
The provisions of table
504.6.4.1 shall be used in establishing the effective length of the
ductwork installed and noted on the placard. The placard shall be
permanently attached to the wall or floor within 6” of the
terminus of the duct.
4.6 Chapter
6
603.2 Duct sizing Delete and
substitute the following:
603.2 Duct sizing ducts
installed within a single dwelling unit shall be sized in accordance
with ACCA Manual D or other approved methods. Ducts installed within
all other buildings shall be sized in accordance acceptable methods.
606.2.1 Delete and Substitute
the following:
606.2.1 Return air systems
smoke detectors listed for use in air Distribution systems shall be
located as follows:
(1) Downstream of the air
filters and ahead of any branch connections in air supply systems
having a capacity greater than 944L/Sec (2000ft 3 /min)
(2) At each story prior to the
connection to a common return and prior to any recirculation or fresh
air inlet connection in air return systems having a capacity greater
than 7080L/sec (15,000 ft 3 /min) and serving more than one
story.
Revise section 607.5.5 as
follows:
607.5.5 Shaft Enclosures:
Shaft enclosures in use group I and in high-rise structures that are
permitted to be penetrated by ducts and air transfer openings shall
be protected with approved fire and smoke dampers, installed in
accordance with their listing. All other use group shaft enclosure
penetrations shall be protected with approved fire dampers installed
in accordance with their listing.
Retain sections 1, 1.1, 1.2,
1.3, 1.4 and delete exceptions 2, 3, 4 and 5.
4.7 Chapter
10
Add Exception #8 to IMC
section 1001.1 as follows:
8. Permits for steam and
water boiler installation and repairs of boilers over 200,000 BTUs
for commercial uses and 400,000 BTUs for private residences or
apartments shall be issued by the Department of Labor, Division of
Occupational Safety, Boiler Unit.
1003.1 General delete and
substitute
1003.1 General All pressure
vessels shall bear the label of an approved agency and shall be
installed in accordance with the manufacturer’s installation
instruction.
4.8 Chapter 11
Add the following new section
1101.1:
1101.1 "Prohibited
Connections" The uses of potable water as an open loop, single
pass heat exchange fluid for the refrigeration cycle of HVAC
equipment is prohibited.
Delete IMC Section 1105.3 and
substitute the following:
1105.3 Refrigerant detector:
Machinery rooms shall contain a refrigerant detector with an audible
and visual alarm. The detector, or a sampling tube that draws air to
the detector, shall be located in an area where refrigerant from leak
will concentrate. The alarm shall be actuated at value not greater
than the corresponding TLV-TWA values shown for the refrigerant
classification. Detectors and alarms shall be placed in approved
locations.
Delete IMC Section 1105.3 and
substitute the following:
1105.9 Emergency pressure
control system. Refrigeration systems containing more than 6.6 pound
(93kg) of flammable, toxic or highly toxic refrigerant or ammonia
shall be equipped with an emergency pressure control system in
accordance with sections 1105.8.1.1 and 1105.8.2
1105.9.1 Automatic crossover
valves. Each high-and-intermediate-pressure zone in a refrigeration
system shall be provided with a single automatic valve providing a
crossover connection to a lower pressure zone. Automatic crossover
valves shall comply with sections 1105.8.1.1 through 1105.8.1.3.
1105.9.1.1 Overpressure light
setpoint. Automatic crossover valves shall be arranged to
automatically relieve excess system pressure to a lower pressure zone
if the pressure in a high-or intermediate-pressure zone rises to
within 15psi (108.4 kPa) of the setpoint for emergency
pressure-relief devices.
1105.9.1.2 Manual operation.
When required by the fire code official, automatic crossover valves
shall be capable of manual operation.
1105.9.1.3 System design
pressure. Refrigeration system zones are connected to a
higher-pressure zone by an automatic crossover valve shall be
designed to safely contain the maximum pressure that can be achieved
by interconnection of the two zones.
1105.9.2 Automatic emergency
stop. An automatic emergency stop feature shall be provided in
accordance with section 1105.9.2.1 and 1105.9.2.2
1105.9.2.1 Operation of an
automatic crossover valve. Operation of an automatic crossover valve
shall cause all compressors on the effected system to immediately
stop. Dedicated pressure-sensing devices located immediately adjacent
to crossover valves shall be permitted as a means for determining
operation of a valve. To ensure that the automatic crossover valve
system provides a redundant means of stopping compressors in an over
pressure condition, high-pressure cutout sensors associated with
compressors shall not be used as a basis for determining operation of
a crossover valve.
1105.9.2.2 Overpressure in
low-pressure zone. The lowest pressure zone in a refrigeration system
shall be provided with a dedicated means of determining a rise in
system pressure to within 15 psi (103.4 kPa) of the setpoint for
emergency pressure-relief devices. Activation of the overpressure
sensing device shall cause all compressors on the effected system to
immediately stop.
4.9 Chapter 12
Table 1202.4 Delete without
substitution
Lead Pipe FS WW-P-325B
Delete IMC section 1208.1.1
and substitute the following:
1208.1.1 Ground source heat
pump loop systems. Before connection (header) trenches are
backfilled, the assembled loop system shall be pressure tested with
water at 100 psi (689 kPa) for 30 minutes with no observed leaks.
Flow pressure loss testing shall be performed, and the actual flow
rates and pressure drops shall be compared to the calculated design
values. If actual flow rate or pressure differs from calculated
design values, the designer of record shall identify the problem and
order corrections as required.
4.10 Chapter 13
Add the following new section
1301.2.1:
1301.2.1 Maximum inside
fuel oil storage. Where connected to a fuel-Oil piping system, the
maximum amount of fuel oil allowed inside any building shall be 1,320
gallons and the maximum amount of oil connected to any one- (1)
appliance shall be 660 gallons. Where the amount of fuel oil stored
inside a building exceeds 1,320 gallons the storage area shall be in
compliance with the R.I. Fire Prevention Code and the State Building
Code.
Add the following new section
1305.8:
1305.8 Fuel Oil Supply and
Vent Piping: Fill and vent lines for above ground fuel storage tanks
shall be permitted to be a minimum of 1 ¼ “in diameter
for a single storage tank up to 500-gallon capacity.
4.11 Chapter 15
Referenced Standards
Delete without substitution
ASHRAE-2013-ASHRAE
Fundamentals handbook-603.2
4.12 APPENDIX
B
Delete APPENDIX B in its
entirety.