ARSD 20:44:24:03. Additional requirements for temporary installations for carnivals and celebrations

Last amended: 1994Year: 2026Length: 129 wordsOfficial source

Cite as S.D. Admin. R. 20:44:24:03

In addition to the requirements of ยง 20:44:24:02, temporary installations for carnivals and celebrations must conform to the following: (1) Each ride or concession must be provided with only one disconnect switch with overcurrent protection; (2) Splices and taps must be enclosed in a weatherproof box or cabinet and may not be accessible to the public. Splices or taps may not be buried in the ground; (3) Cable must be in good condition, have standard insulating qualities for the voltage level, have adequate mechanical strength, and be a continuous length from box to box. Outdoor cord connectors must be used; (4) All temporary installations must be approved by the electrical inspector before use; and (5) All installations must comply with SDCL chapter 36-16 and all provisions of this article.