ARSD 44:70:03:03

ARSD 44:70:03:03. Fire extinguisher equipment

Last amended: 2019Year: 2026Length: 114 wordsOfficial source

Cite as S.D. Admin. R. 44:70:03:03

Fire extinguisher equipment shall be installed and maintained to the following standards: (1) Portable fire extinguishers must have a minimum rating of 2-A:10-B:C; (2) Fire extinguisher equipment must be inspected monthly and maintained yearly; and (3) Approved fire extinguisher cabinets must be provided throughout the building with one cabinet for each 3,000 square feet or 278.7 square meters of floor space or fraction thereof. The fire resistance rating of corridor walls must be maintained at recessed fire extinguisher cabinets. The glazing in doors of fire extinguisher cabinets must be wire glass or other safety glazing material. Fire extinguisher cabinets must be identified with a sign mounted perpendicular to the wall surface above the cabinet.