ARSD 44:75:13:06
ARSD 44:75:13:06. Patient rooms
Cite as S.D. Admin. R. 44:75:13:06
A facility shall ensure a patient room has:
(1) A maximum room capacity not exceeding two patients;
(2) A minimum area, exclusive of toilet rooms, closets, lockers, wardrobes, or vestibules, of one hundred twenty square feet or 10.8 square meters in each one-bed room and two hundred square feet or 18.58 square meters in each two-bed room. The minimum dimension of a patient room is nine feet six inches or 2.90 meters;
(3) For each bed in a two-bed room, cubicle curtains or equivalent built-in devices for full visual privacy that allow access to the toilet room and corridor without entering the roommate's space;
(4) A windowsill not higher than three feet or 0.91 meters above the floor;
(5) A floor that is above grade;
(6) A call button at each bed for calling personnel stations;
(7) A toilet room and lavatory. Each patient toilet room must be directly accessible for each patient without going through the general corridor. In a remodeling project, a one toilet room with hand sink in a patient room may serve two patient rooms, but not more than four beds. For new construction, a toilet room may not be shared between patient rooms. Each patient toilet room must have a water closet, hand sink, mirror, and private individual storage. In two-bed rooms a separate hand sink must be provided in the patient room. All new construction of toilet rooms used by patients must be wheelchair accessible;
(8) A locker, wardrobe, or closet for each patient; and
(9) Each patient room door located not more than one hundred fifty feet or 45.72 meters from the nurse's station.