ARSD 44:75:14:24. Emergency electrical circuit connections

Last amended: 2015Year: 2026Length: 241 wordsOfficial source

Cite as S.D. Admin. R. 44:75:14:24

Emergency electrical service shall be furnished to circuits as follows: (1) Lighting of exit ways and all necessary ways of approach to them, including exit signs and exit direction signs, exterior of exits, exit doorways, stairways, and corridors; (2) Surgical, obstetrical, and emergency room operating lights; (3) Lighting for nursery, laboratory, recovery room, intensive care areas, nursing stations, medication preparation areas, and labor rooms; (4) Lighting for the generator set location, the switch gear location, and the boiler room; (5) Equipment essential to life safety and for protection of important equipment or vital materials; (6) Nurses calling system; (7) Alarm system, including fire alarms actuated at manual stations; (8) Water flow alarm devices of sprinkler system if electrically operated; (9) Fire detecting and smoke detecting systems; (10) Paging or speaker systems if intended for issuing instructions during emergency conditions; (11) Alarms required for nonflammable medical gas systems, if installed; (12) Receptacles for incubators for infants; (13) Pump for central suction system; (14) Sewage or sump lift pump, if installed; (15) Receptacles for blood bank refrigerator; (16) At least two duplex receptacles for the laboratory; (17) Receptacles in operating, recovery, intensive care, and delivery rooms except those for X ray; (18) At least one duplex receptacle in each nursery; (19) Duplex receptacles in patient corridors; and (20) Equipment, such as burners and pumps, necessary for operation of one or more boilers required for heating and sterilization and their necessary auxiliaries and controls.
ARSD 44:75:14:24: ARSD 44:75:14:24. Emergency electrical circuit connections | Justis AI