ARSD 44:76:11:18
ARSD 44:76:11:18. Steam and hot water systems
Cite as S.D. Admin. R. 44:76:11:18
Boilers shall have the capacity to supply the normal requirements of all systems and equipment. Supply and return mains and risers of space heating and process steam systems shall be valved to isolate the various sections of each system. Each piece of equipment shall be valved at the supply and return end. Boilers, smoke breeching, steam supply piping, high pressure steam return piping, and hot water space heating supply and return piping shall be insulated with insulation having a flame spread of 25 or less and a smoke emission rating of 50 or less using NFPA 255, 2006 edition, "Standard Method of Test for Surface Burning Characteristics of Building Materials" or equivalent test procedures.