ARSD 74:56:01:34

ARSD 74:56:01:34. Release detection requirements for pressure piping

Last amended: 2018Year: 2026Length: 209 wordsOfficial source

Cite as S.D. Admin. R. 74:56:01:34

Each owner or operator of an UST system must have release detection for the underground pressure piping connected to each tank that meets the requirements in ยง 74:56:01:24 by the compliance dates established in that section. In addition, owners or operators of UST systems with underground piping that conveys a regulated substance under pressure must meet the following requirements: (1) Be equipped with an automatic line leak detector which alerts the operator to the presence of a leak by restricting or shutting off the flow of regulated substances or triggering an audible or visible alarm, so long as it detects leaks of 3 gallons per hour at 10 pounds psi line pressure within one hour and is annually tested in accordance with subdivision 74:56:01:24(4); and (2) Have an annual line tightness test, so long as the test can detect a 0.1 gallon per hour leak rate at one and one-half times the operating pressure, or have monthly monitoring, so long as the selected monitoring methods are designed to detect a release from any portion of the underground piping that routinely contains regulated substances. (3) Pressure piping installed after October 13, 2018, must comply with subdivision 74:56:01:34(1) and be monitored every thirty days for releases in accordance with ยง 74:56:01:30.
ARSD 74:56:01:34: ARSD 74:56:01:34. Release detection requirements for pressure piping | Justis AI