ARSD 74:56:03:19
ARSD 74:56:03:19. Requirements for release detection
Cite as S.D. Admin. R. 74:56:03:19
Requirements for release detection shall consist of the following:
(1) AST systems must have equipment for release detection as required in ยง 74:56:03:04, including one or more of the following:
(a) Perforated gravity collection pipes or channels in a concrete foundation pad which can be monitored for the presence of a release;
(b) Internal systems designed to detect any changes in regulated substance level, such as in-tank monitors, capable of continuous monitoring and connected to an external alarm system;
(c) External systems designed to detect any releases; or
(d) Comparable release detection systems as approved by the department.
Department approval is required prior to the installation of the release detection systems.