0465-02-04-.06
Residential Occupancies - Board And Care
Cite as Tenn. Comp. R. & Regs. 0465-02-04-.06
(1)
Definition - Board and Care facilities include a building or part thereof that is used for the
lodging and boarding of four (4) or more persons supported, not related by blood or marriage
to the owner or operator, to provide care services. Examples of facilities required to meet
board and care occupancy standards are an Intellectual and Developmental Disabilities
Boarding Home Facility and an Intellectual and Developmental Disabilities Residential
Habilitation Facility.
(2)
Criteria - For the purpose of Life Safety, licensees required to meet Board and Care
occupancy must comply with the following:
LIFE SAFETY LICENSURE RULES
CHAPTER 0465-02-04
(a)
Applicable standards of the Life Safety Code of the National Fire Protection
Association, Residential Board and Care Occupancies, or equivalent standards
hereafter adopted by the Office of the State Fire Marshal; and
1.
Provide at least two hundred (200) square feet, gross, of occupiable space per
person.
2.
Provide at least:
(i)
Eighty (80) square feet per person of bedroom space for single occupancy;
or
(ii)
Sixty (60) square feet per person of bedroom space for multiple
occupancy.
3.
Not allow multiple occupancy which exceeds four (4) persons per bedroom.
4.
Equip any stairways with emergency lighting.
5.
Provide emergency lighting in any corridors used as means of egress.
6.
Not use unvented gas heaters.
7.
Use portable electric space heaters only in emergency situations and only under
conditions specified by the Office of Licensure.
8.
Allow the use of fireplaces only under the following conditions:
(i)
For recreation or therapy only;
(ii)
Not used as a primary source of heat;
(iii)
Used in activity or living rooms;
(iv) Under proper supervision and in accordance with specific written fire safety
procedures; and
(v)
Fireplaces may be installed and used only in areas other than sleeping
areas of persons supported, provided the fireplace is equipped with a heat-
tempered glass fireplace enclosure guaranteed against breakage up to a
temperature of six hundred and fifty (650) degrees Fahrenheit.
9.
Allow the use of portable cooking devices in the kitchen only.
10. Document fire-safety drills which shall be conducted:
(i)
Monthly at unexpected times and under varying conditions; and
(ii)
Under direct staff supervision.
11. Provide a functioning UL rated battery-operated smoke detector in each bedroom
occupied by a person supported and document that all smoke-detection devices
are tested monthly and that batteries are changed when no longer operating, but
at least yearly.
LIFE SAFETY LICENSURE RULES
CHAPTER 0465-02-04
12. Provide operable 2A-10B, C multi-purpose fire extinguishers in a fixed location
and readily accessible for use in the facility, and document that all fire
extinguishers are properly maintained and serviced. The Office of Licensure will
determine the number of fire extinguishers required in a particular facility.
13. Document instructions to staff upon employment and persons supported upon
admission in fire evacuation procedures.
14. Adopt a policy on smoking and ensure designated areas are posted.
15. Suspended unit electric heaters may be used, except in means of egress and
sleeping areas of persons supported, provided such heaters are located high
enough to be out of the reach of persons supported using the area and provided
the heaters are equipped with appropriate safety devices and are approved for
use by the Office of Licensure.
16. Use extension cords only on a limited basis and under the conditions acceptable
to the Office of Licensure of the Department.
(b)
Provide services only for persons who require no greater level of care than personal
care as defined at 0465-02-01(51).