0080-05-07-.03
Basic Rules
Cite as Tenn. Comp. R. & Regs. 0080-05-07-.03
(1)
REQUIREMENTS FOR CONSTRUCTION AND ORIGINAL TEST OF CONTAINERS:
(a)
Containers shall be constructed and tested in accordance with the unfired pressure vessel code
of the American Society of Mechanical Engineers, except that construction under paragraphs
U-70 and U-200 to U-201 inclusive is not authorized.
(b)
The designed working pressure of these vessels shall not be less than:
1.
250 psi for ASME, unprotected aboveground storage container.
2.
200 psi for ASME, aboveground storage container provided with a shed or sprinkler
system approved by the Commissioner of Agriculture, or farm trailer containers, or
tractor containers.
3.
150 psi for ASME, underground storage containers.
(2)
MARKING ON CONTAINERS:
(a)
Each container shall be marked as specified in the following:
1.
Code qualification
2.
Thickness of shell in inches
3.
Thickness of head in inches
4.
Overall length and outside diameter in inches
5.
Water gallon capacity
6.
Design working pressure
7.
Date of manufacture
8.
Serial number
9.
Name of manufacturer
(b)
The above data shall either be etched, cast or impressed on name plates which shall be
irremovably attached to the vessel and located near a manhole, if any, or handhole, or in some
conspicuous place. The letters and figures on the name plates shall not be less than 5/32 inches
high.
(c)
Each bulk storage tank shall be marked on at least two sides with the words “Anhydrous
Ammonia - DANGEROUS OR CAUTION” in white letters not less than 6 inches high on a
red background or the reverse. In addition the warning sign “No smoking or Open Flame -
Allowed”.
(d)
All transport tanks mounted on trucks and farm trailers shall be marked on both sides and rear
with words “Anhydrous Ammonia - DANGEROUS OR CAUTION”. Letters are to be at least
6 inches high.
(e)
All tanks installed on farm tractors and to be transported over public highways such as in
doing custom-work shall be marked on rear side with words “Anhydrous Ammonia -
DANGEROUS OR CAUTION” in red letters on a white background. In instances where
containers are mounted on side of tractor, the words above specified shall be printed on side of
container with similar display of wording on rear of tractor.
(3)
LOCATION OF CONTAINERS:
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
(a)
Containers shall be located outside of buildings unless the building is especially constructed for
this purpose. In case of bulk storage, no bulk storage tanks shall be installed in the limits of
any municipality without the approval of their governing body and the Commissioner of
Agriculture, and in no instance closer than 200’ to any building other than that of the plant
operator, or that of a building designed specifically as protection for the plant itself.
(4)
CONTAINERS, VALVES AND ACCESSORIES:
(a)
All containers shall be equipped with an approved liquid level gauging device so that the
maximum volume of container filled by liquid shall not exceed 85% of its water capacity.
Containers of 300 water gallons or more shall be equipped also with a vapor pressure
indicating gauge graduated to at least 1 1/2 times the working pressure of the container.
(b)
All valves and accessory equipment shall be constructed of steel or other material approved for
use with anhydrous ammonia, and suitable for a 250 psi working pressure. It is forbidden to
use copper or any of its alloys for ammonia equipment.
(c)
All connections to containers except safety relief and gauging connections shall have shut-off
valves located as close to the container as possible.
(d)
Excess flow valves, where required, shall close automatically at the rated flows of vapor or
liquid as specified by the manufacturer. The connections and lines, including shut-off valves
shall have a greater flow capacity than the rated flow of the excess flow valve.
(e)
Openings from tank to fittings for pressure gauge connections and/or other approved gauging
devices, shall be protected by a No.54 drill size opening when necessary; or excess flow valve.
A hand shut-off valve, with controlling orifice not in excess of 5/16”, located as close to the
container as possible may be used in lieu of the above on containers of 300 gallons or less.
(f)
Openings that require excess flow valve or back pressure check valves, such valve shall be
located inside the container or at a point outside where the line enters the container. If installed
as in the latter case, installation shall be made in such a manner that any undue strain beyond
the excess flow valve or back pressure check valve will not cause breakage between the
container and such valve.
(g)
Excess flow valves may be designed with a bypass, not to exceed a No.60 Drill size opening to
allow equalization of pressure.
(h)
All container valves and fittings shall conform to the following:
1.
The filling connection shall be fitted with an approved combination back pressure check
valve and excess flow valve; one double or two single back pressure check valve; or a
positive cut-off valve, in combination with either an internal back pressure valve or an
internal excess flow valve.
2.
All vapor return valves and liquid withdrawal line, shall be equipped with approved
automatic excess flow valves except that no excess flow valve is required in the
withdrawal service line if the controlling orifice between the contents of the container
and the outlet of the shut-off valve does not exceed 5/16” for liquid withdrawal, and the
capacity of the container does not exceed 300 U.S. Gallons. All excess flow valves shall
be stamped with the name or trademark of the manufacturer, lot number, and rated flow
in gallons per minute.
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
(5)
PIPING, TUBING AND FITTINGS:
(a)
All fittings where subjected to tank pressure shall be extra heavy construction and only steel
(no copper steel), no cast iron, bushings and plugs shall be allowed in the lines or connections.
(b)
Galvanized pipe is forbidden to be used as ammonia line pipes; black steel or iron piping of at
least 800 pounds minimum test may be used provided welded pipe joints are used. Screwed and
bolted flange joints are permissible with double strength pipe. Where screwed joints are used, it
has been found that common dopes for pipe threads are attacked by ammonia; freshly mixed
Litharge and Glycerin is recommended for use for durability.
(c)
All pipe lines shall be installed as nearly in a straight line as possible with a minimum amount
of pipe, and not restricted by an excessive amount of elbows and bends. Where nipples are
used, they shall be of extra heavy seamless type. Flexible connections shall not be used on
permanently fixed installations; rigid connections are required.
(d)
Provisions shall be made for expansion, contraction, jarring, vibration, and for settling.
(e)
Any section of pipe between shut-off valves that may contain trapped liquid shall be protected
by an ammonia relief valve.
(f)
Provisions shall be made to adequately protect all exposed piping from mechanical injury that
might result from moving machinery, presence of automobiles or trucks, or where any undue
strain may be placed upon the piping.
(g)
All piping and tubing shall be tested with a pressure of 90 psi after assembly and proved free
from leaks. Such test shall be made and certified to by the installer before the system is put into
service.
(h)
Where hose are used as flexible connections or otherwise, they shall meet the following
specifications:
1.
Fabricated of material resistant to ammonia.
2.
Hose subject to container pressure shall be designed for bursting pressure of not less
than five times the maximum pressure for which the container was designed. Hose
connection when made shall be capable of withstanding a test pressure of twice the
maximum working pressure for which the container is designed.
3.
Where hose is to be used for transferring liquid from one container to another, wet hose
is recommended. Such hose shall be equipped with suitable shut-off valves at discharge
end. Provisions shall be made to prevent excessive hydrostatic pressure in the hose.
(6)
SAFETY DEVICES:
(a)
Every container shall be protected with one or more spring-loaded relief valve. Where there is
more than one valve on the same container they shall discharge at the same pressure. All relief
valves shall be stamped with the name or trademark of the manufacturer, valve number,
setpressure at which it begins to discharge, the rating of the valve in the amount of cubic feet
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
per minute it will pass before the pressure of the container exceeds the start to discharge
pressure setting of the device plus 25%.
(b)
All relief valves shall discharge to the free air and in no case nearer than five feet to any
opening into a building.
(c)
Container safety relief valves shall be set to discharge as follows with relation to the design
working pressure of the container:
Minimum
Maximum
100%
125%
(d)
All containers shall be protected by relief valve or valves capable of passing the required
amount of free air as determined from Table One (1) of these rules and regulations.
(e)
Safety relief valves shall have direct communication with the vapor space of the container and
no shut-off valve may be installed between the valve and the container except that a shut-off
valve may be used where the arrangement of this valve is such as always to afford full required
capacity flow through the relief valve.
(f)
Rupture disks may be used with spring-loaded relief valves, provided:
1.
The valve meets the requirements of these rules and regulations.
2.
The disk is made of material non-corroding under exposure to ammonia and is so
designed to rupture at the relief valve setting plus 10%.
3.
There is no chance of fragments of the disk interfering with the proper functioning of
the relief valve.
4.
No more than 70% of the required rate of discharge is provided by these disks.
(g)
Every rupture disk shall have a specified temperature, bursting pressure, and lot number, and
shall be guaranteed by its manufacturer to burst within 5% (plus or minus) of its specified
bursting pressure. The bursting pressure, temperature, lot number, and discharge capacity in
cubic feet per minute shall be stamped on the flange of the disk or upon a metal tag
permanently attached thereto.
(h)
When two or more safety valves are placed on one connection, this connection shall have a
cross-sectional area at least equal to the combined area of these safety valves.
(7)
I. C. C. APPROVAL; GOVERNMENT CONTAINERS:
(a)
All containers and pertinent equipment, subject to the rules and regulations or bearing the
stamp of approval of the Interstate Commerce Commission for the service for which it was
designed, and all containers which are owned or in use by the government of the United States
of America are exempted from these rules and regulations, except that such containers and
equipment shall be subject to inspection by the Commissioner of Agriculture.
(8)
ANHYDROUS AMMONIA SYSTEM TO MEET SPECIFICATIONS:
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
(a)
All dealers operating systems on the effective date of these rules and regulations, that do not
meet the requirements thereof, shall bring such up to specifications set forth herein, within six
(6) months after the effective dates of rules and regulations.
(9)
APPROVAL OF SYSTEM:
(a)
No person or dealer shall fill or permit to be filled any container or system that does not have
attached thereto a tag of approval (permanent or temporary), issued by the Commissioner of
Agriculture.
(b)
Systems installed prior to the effective dates of these rules and regulations shall, WITHIN SIX
(6) MONTHS thereafter, obtain inspection and approval of the container and/or systems and
have securely attached thereto a Metal Tag of Approval issued by the Commissioner of
Agriculture.
(c)
On a new system installed after the effective date of these rules and regulations, a temporary
tag of approval may be attached by the installer, provided said installer furnishes the
Commissioner of Agriculture a certificate, certifying that said system is in compliance with
these rules and regulations.
(d)
The approval of a system bearing a temporary tag of approval shall become NULL and VOID
sixty (60) days after the date of issuance of said temporary tag.
(e)
The approval of any system or container shall become NULL AND VOID upon resale,
alteration, fire or mechanical injury. Such a system or container shall be reinspected by the
Commissioner of Agriculture and a new tag of approval attached thereto before put into use.
(10)
INSTALLATIONS AND CONNECTION OF SYSTEMS:
(a)
After the effective date of these rules and regulations, any person who shall install, connect,
alter, or extend any anhydrous ammonia system, shall within forty-eight (48) hours after the
completion thereof, give notice to the Office of the Commissioner of Agriculture, in writing,
which notice shall give full details with reference thereto. The placing of such in the United
States mail, postage prepaid, properly addressed to the Commissioner of Agriculture, shall be
sufficient notice within the meaning of this paragraph. Provided this ruling shall not apply to
farm tractor dispensing equipment when such change or alteration is equivalent to or better
than the original installation.
(11)
DEALERS’ RESPONSIBILITY:
(a)
Equipment dealers shall be held responsible for the installation of systems they sell, alter, or
connect. It shall be the responsibility of the Fertilizer Dealers to see that the systems they
service meet the requirements set forth in these rules and regulations.
(b)
The Commissioner’s Tag of Approval shall NOT relieve the Dealer of the aforementioned
responsibilities. A prefilling inspection of each system shall be made by the servicing
personnel every time a system is to be filled, and it is the obligation of the Dealer responsible
to see that such is done and report to the Commissioner anything that is not in keeping with
these rules and regulations.
(12)
SALE AND/OR DISTRIBUTION OF EQUIPMENT:
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
(a)
Any and all equipment sold or distributed to consumers or users in the State of Tennessee shall
be sold or distributed through a Dealer bonded as an Anhydrous Ammonia Equipment dealer
in the State of Tennessee.
(13)
INSPECTION:
(a)
Any discrepancy found by the Inspector of the Tennessee Department of Agriculture shall be
corrected within a given length of time as specified by the Inspector.
(14)
FIELD WELDING APPROVAL:
(a)
Field welding, when necessary, may be done on saddle plates or other non-pressure parts by
non-qualified welders. Any welding, when done on pressure parts, shall be done by a qualified
welder, and will enter the category of alteration to vessel, and tank shall be reinspected and
tested as was originally done to requalify it under the code under which it was built.
(15)
BLUEPRINTS AND DATA SHEETS:
(a)
Manufacturers shall forward to the Commissioner of Agriculture two copies of the blueprints
of each container of a different design prior to its delivery to any person, firm or corporation in
the State of Tennessee. One is to be returned to the manufacturer approved or disapproved,
such as the case may be. The other copy is to be retained in the file of the Office of the
Commissioner.
(b)
Manufacturer’s data report of each separate tank shall be forwarded to the Commissioner of
Agriculture. It will be the dealer’s responsibility to see that the manufacturer complies with
this and the above ruling. The Commissioner of Agriculture shall have on hand a copy of said
data sheet before any inspection is made of said system, installation or container.
(c)
Blueprints and data sheets of containers installed prior to the effective date of these rules and
regulations shall be obtained and furnished to the Commissioner of Agriculture by the owner
before inspection will be made and tag of approval attached authorizing use of container.
(16)
PERMITS:
(a)
Any person, firm, corporation, or association desiring to engage in business as a dealer in
anhydrous ammonia as a fertilizer, or as a dealer in equipment used in the handling of
anhydrous ammonia as a fertilizer, within the State of Tennessee shall file formal application
for permit on form furnished by the Commissioner of Agriculture.
(b)
Two types of permits:
1.
Anhydrous Ammonia Fertilizer Dealer and/or Custom Dispensers who furnish the
Anhydrous Ammonia.
2.
Anhydrous Ammonia Equipment Dealer.
(c)
Before any permit will be issued all applicants shall comply with the following:
1.
Application shall have been approved by the Commissioner of Agriculture.
RULES AND REGULATIONS PERTAINING TO ANHYDROUS
CHAPTER-0080-5-7
AMMONIA STORAGE AND EQUIPMENT ACT
2.
Shall have on file in the Office of the Commissioner of Agriculture a Certificate of
Liability Insurance as specified in Section 4 (c) of the Act or shall have filed bond in the
amount of $25,000 as set forth in Section 4 (d): this certificate shall bear the clause that
in the event the insurance or bonding company intends to cancel any or all of the
policies or bonds, they will notify the Office of the Commissioner ten (10) days prior to
date of cancellation.
3.
Shall have properly executed Guarantee Bond in amount of $1,000.00 filed in the Office
of the Commissioner of Agriculture. Section 4 (b).
4.
Storage tank and location shall be approved. (Anhydrous Ammonia Fertilizer Dealer.)
5.
Transportation facilities shall be approved. (Anhydrous Ammonia Fertilizer Dealer.)