0720-26-.10
Life Safety
Cite as Tenn. Comp. R. & Regs. 0720-26-.10
(1)
The department will consider any ACLF that complies with the required applicable building
and fire safety regulations at the time the Board adopts new codes or regulations, so long as
such compliance is maintained (either with or without waivers of specific provisions), to be in
compliance with the requirements of the new codes or regulations.
(2)
An ACLF shall ensure fire protection for residents by doing at least the following:
(a)
Eliminate fire hazards;
(b)
Install necessary fire fighting equipment;
(c)
Adopt a written fire control plan;
(d)
Ensure that each resident sleeping unit shall have a door that opens directly to the
outside or to a corridor which leads directly to an exit door and that is always capable of
being unlocked by the resident;
STANDARDS FOR ASSISTED-CARE LIVING FACILITIES
CHAPTER 0720-26
(e)
Ensure that louvers shall not be present in doors to residents’ sleeping units;
(f)
Keep corridors and exit doors clear of equipment, furniture and other obstacles at all
times. Passage to exit doors leading to a safe area shall be clear at all times;
(g)
Prohibit use of combustible finishes and furnishings;
(h)
Prohibit open flame and portable space heaters;
(i)
Ensure that upon entering the ACLF, the resident or his or her responsible party is
asked if they wish to have a cooking appliance that is appropriate for their level of
cognition. If the facility chooses to provide a requested cooking appliance, it shall be
used in accordance with the facility’s policies. If the resident or his or her responsible
party wishes to provide their own cooking appliance, it shall meet the facility’s policies
and safety standards. The cooking appliances shall be designed so that they can be
disconnected and removed for resident safety or if the resident chooses not to have
cooking capability within his or her apartment. The cooking appliances shall have an
automatic timer;
(j)
Ensure that all heaters shall be guarded and spaced to prevent ignition of combustible
material and accidental burns. The guard shall not have a surface temperature greater
than 120°F;
(k)
Allow use of fireplaces and/or fireplace inserts only if the ACLF ensures that they have
guards or screens which are secured in place;
(l)
Inspect and clean fireplaces and chimneys annually and maintain documentation that
such inspection has occurred;
(m)
Ensure that there are electrically-operated smoke detectors with battery back-up power
operating at all times in, at least, resident sleeping units, day rooms, corridors, laundry
room, and any other hazardous areas; and
(n)
Provide and mount fire extinguishers and maintain travel distance between fire
extinguishers, complying with NFPA 10, so they are accessible to all residents in the
kitchen, laundries and at all exits.
(3)
An ACLF shall conduct fire drills in accordance with the following:
(a)
Fire drills shall be held for each ACLF work shift in each separate ACLF building at
least quarterly;
(b)
There shall be one (1) fire drill per quarter during sleeping hours;
(c)
An ACLF shall prepare a written report documenting the evaluation of each drill that
includes the action that is recommended or taken to correct any deficiencies found;
and,
(d)
An ACLF shall maintain records that document and evaluate these drills for at least
three (3) years.
(4)
An ACLF shall take the following action should a fire occur:
(a)
An ACLF shall report all fires which result in a response by the local fire department to
the department within seven (7) days of its occurrence.
STANDARDS FOR ASSISTED-CARE LIVING FACILITIES
CHAPTER 0720-26
(b)
An ACLF’s report to the department shall contain the following:
1.
Sufficient information to ascertain the nature and location of the fire;
2.
Sufficient information to ascertain the probable cause of the fire; and
3.
A list and description of any injuries to any person or persons as a result of the
fire.
4.
An ACLF may omit the name(s) of resident(s) and parties involved in initial
reports. Should the department later find the identities of such persons to be
necessary to an investigation, the ACLF shall provide such information.
(5)
An ACLF shall take the following precautions regarding electrical equipment to ensure the
safety of residents:
(a)
Provide lighted corridors at all times, to a minimum of one foot candle;
(b)
Provide general and night lighting for each resident and equip night lighting with
emergency power;
(c)
Maintain all electrical equipment in good repair and safe operating condition;
(d)
Ensure that electrical cords shall not run under rugs or carpets;
(e)
Ensure that electrical systems shall not be overloaded;
(f)
Ensure that power strips are equipped with circuit breakers; and
(g)
Prohibit use of extension cords.
(6)
If an ACLF allows residents to smoke, it shall ensure the following:
(a)
Permit smoking and smoking materials only in designated areas under supervision;
(b)
Provide ashtrays wherever smoking is permitted;
(c)
Smoking in bed is prohibited;
(d)
Written policies and procedures for smoking within the ACLF shall designate a room or
rooms to be used exclusively for residents who smoke. The designated smoking room
or rooms shall not be the dining room, the activity room, or an individual resident
sleeping unit, and;
(e)
Post no smoking signs in areas where oxygen is used or stored.
(7)
An ACLF shall not allow trash and other combustible waste to accumulate within and around
the ACLF. It shall store trash in appropriate containers with tight-fitting lids. An ACLF shall
furnish resident sleeping units with an UL approved trash container.
(8)
An ACLF shall ensure that:
(a)
The ACLF maintains all safety equipment in good repair and in a safe operating
condition;
STANDARDS FOR ASSISTED-CARE LIVING FACILITIES
CHAPTER 0720-26
(b)
The ACLF stores janitorial supplies away from the kitchen, food storage area, dining
area or other resident accessible areas;
(c)
The ACLF stores flammable liquids in approved containers and away from the facility
living areas; and
(d)
The ACLF cleans floor and dryer vents as frequently as needed to prevent
accumulation of lint, soil and dirt.
(9)
An ACLF shall post emergency telephone numbers near a telephone accessible to the
residents.
(10) An ACLF shall maintain its physical environment in a safe, clean and sanitary manner by
doing at least the following:
(a)
Prohibit any condition on the ACLF site conducive to the harboring or breeding of
insects, rodents or other vermin;
(b)
Properly identify chemical substances of a poisonous nature used to control or
eliminate vermin and store such substances away from food or medications;
(c)
Ensure that the building shall not become overcrowded with a combination of the
ACLF’s residents and other occupants;
(d)
Ensure that each resident sleeping unit shall contain a chair, bed, mattress, springs,
linens, chest of drawers and wardrobe or closet space, either provided by the ACLF or
by the resident if the resident prefers. All furniture provided by the resident must meet
NFPA standards;
(e)
Maintain all residents’ clothing in good repair and ensure that it is suitable for the use of
elderly persons;
(f)
Maintain the building and its heating, cooling, plumbing and electrical systems in good
repair and in clean condition at all times; and
(g)
Maintain temperatures in resident sleeping units and common areas at not less than
65°F and no more than 85°F.