0720-29-.14
Disaster Preparedness
Cite as Tenn. Comp. R. & Regs. 0720-29-.14
(1)
Emergency Electrical Power.
(a)
If an HIV supportive living facility chooses to have one or more on-site electrical
generators, they shall be capable of providing emergency electrical power to at least all
life sustaining equipment and life sustaining resources such as: ventilators; blood
banks, biological refrigerators, safety switches for boilers, safety lighting for corridors
and stairwells and other essential equipment.
(b)
Connections shall be through a switch which shall automatically transfer the circuits to
the emergency power source in case of power failure. It is recognized that some
equipment may not sustain automatic transfer and provisions will have to be made to
manually change these items from a non-emergency powered outlet to an emergency
powered outlet or other power source. All emergency power transfer switches shall be
labeled as such. Switches affecting heat, ventilation, and all systems shall be labeled.
(c)
The emergency power system shall have a minimum of twenty four (24) hours of either
propane, gasoline or diesel fuel. The quantity shall be based on its expected or known
connected load consumption during power interruptions. In addition, the HIV supportive
living facility shall have a written contract with an area fuel distributor which guarantees
first priority service for re-fills during power interruptions.
(d)
The emergency power system (generator) shall be inspected weekly and exercised
and under actual load and operating temperature conditions for at least thirty (30)
minutes, once each month, and shall include automatic and manual transfer of
equipment. The generator shall be exercised by trained facility staff who are familiar
with the systems’ operation. Instructions for the operation of the systems and the
manual transfer of emergency power shall be maintained with the facility’s disaster
preparedness plan and shall be separately identified in the plan. Records shall be
maintained for all weekly inspections and monthly tests and be kept on file for a
minimum of three (3) years.
(2)
Physical Facility and Community Emergency Plans.
(a)
Physical Facility (Internal Situations).
STANDARDS FOR HIV SUPPORTIVE LIVING CENTERS
CHAPTER 0720-29
1.
Every HIV supportive living facility shall have a current internal emergency plan,
or plans, that provides for fires, bomb threats, severe weather, utility service
failures, plus any local high risk situations such as floods, earthquakes, toxic
fumes and chemical spills. The plan should consider the probability of the types
of disasters which might occur, both natural and “man-made.”
2.
The plan(s) must include provisions for the relocation of persons within the
building and/or either partial or full building evacuation. Plans that provide for the
relocation of residents to other health care facilities must have written
agreements for emergency transfers. The agreements may be mutual, i.e.
providing for transfers either way.
3.
Copies of the plan(s), either complete or outlines, including specific emergency
telephone numbers related to that type of disaster, shall be available to all staff.
A copy shall be readily available at all times in the telephone operator’s position
or at the security center. Provisions that have security implications may be
omitted from the outline versions.
4.
The plan must provide for additional staffing, medical supplies, blood and other
resources which would probably be needed.
5.
Each of the following disaster preparedness plan drills shall be conducted
annually. Drills are for the purpose of educating staff, resource determination,
testing personnel safety provisions and communications with other facilities and
community agencies. Records of staff orientation, education programs and drills
must be maintained for at least three (3) years.
(i)
Fire Safety Procedures Plan shall include:
(I)
Minor fires
(II)
Major fires
(III)
Fighting the fire
(IV) Evacuation procedures
(V)
Staff functions by department and job assignment
(VI) Fire drill schedules (fire drills shall be held at least quarterly on each
work shift)
(ii)
External disaster procedures plan (for tornado, flood, earthquakes) shall
include:
(I)
Staff duties by department and job assignment
(II)
Evacuation procedures
(iii)
Bomb Threat Procedures Plan:
(I)
Staff duties by department and job assignment
(II)
Search team, searching the premises
STANDARDS FOR HIV SUPPORTIVE LIVING CENTERS
CHAPTER 0720-29
6.
The HIV supportive living facility shall develop and periodically Review with all
employees a pre-arranged plan for the orderly evacuation of all residents in case
of a fire, internal disaster or other emergency. The plan of evacuation shall be
posted throughout the facility. Fire drills shall be held at least quarterly for each
work shift for HIV supportive living facility personnel in each separate resident
occupied HIV supportive living facility building. There shall be a written report
documenting the evaluation of each drill and the action recommended or taken
for any deficiencies found. Records which document and evaluate these drills
must be maintained for at least three (3) years.
(b)
Emergency Planning With Local Government Authorities.
1.
All HIV supportive living facilities shall establish and maintain communications
with the county Emergency Management Agency. This includes the provision of
the information and procedures that are needed for the local comprehensive
emergency plan. The HIV supportive living facilities shall cooperate, to the extent
possible, in area disaster drills and local emergency situations.
2.
Each HIV supportive living facility shall conduct both the physical facility and
community emergency drills as required in these regulations, even if the local
Emergency Management Agency is unable to participate.
3.
A file of documents demonstrating communications and cooperation with the
local agency must be maintained.