1220-04-04-.39
Facilities And Equipment For Meter Testing
Cite as Tenn. Comp. R. & Regs. 1220-04-04-.39
(1)
Each utility shall maintain a meter shop for the purpose of inspecting, testing and repairing
meters. The shop shall be open for inspection by authorized representatives of the
Commission at all reasonable times, and the facilities and equipment, as well as the methods
of measurements and testing employed, shall be subject to the approval of the Commission.
A utility may, however, have all or part of the required tests, repairs and adjustments made or
its portable testing equipment checked by another agency approved by the Commission and
having adequate and sufficient testing equipment to comply with these rules.
(a)
Each location at which the utility conducts tests of meters shall have three (3) phase
voltage supply, one (1) phase of which shall be variable from zero (0) to two hundred
seventy (270) volts.
(2)
Secondary Standards
(a)
Each utility shall have at least one (1) electronic watt-hour standard meter with a
correction of not more than two-tenths percent (0.2%) at commonly used loads. If the
correction percentage varies between successive tests by more than one quarter
percent (0.25%) a complete check must be made to determine the cause of such
variation. If the cause of variation cannot be removed, the use of the instrument should
be discontinued.
(3)
Working Standards
(a)
Each utility shall have at least one (1) portable electronic watt-hour standard meter with
a correction of not more than three-tenths percent (0.3%) at commonly used loads. If
the correction percentage varies between successive tests by more than one quarter
percent (0.25%), a complete check must be made to determine the cause of such
variation. If the cause of variation cannot be removed, the use of the instrument should
be discontinued.
(4)
Secondary standards must be checked periodically (see Rule 1220-04-04-.35(2)) at the
National Institute of Standards and Technology (NIST) or any successor thereto or at a
utility’s option, at a laboratory traceable to NIST.
(5)
Working standards must be checked periodically (see Rule 1220-04-04-.35(2)) by
comparison with a secondary standard in the utility’s meter shop.
(6)
Extreme care must be exercised in the handling of standards to assure that their accuracy is
not disturbed.
(7)
Each standard shall be accompanied at all times by a certificate or calibration card, duly
signed and dated, on which are recorded the corrections required to compensate for errors
found at the customary test points at the time of the last previous test.