1220-04-05-.42
Odorization
Cite as Tenn. Comp. R. & Regs. 1220-04-05-.42
(1)
Any gas distributed to customers through gas mains or gas services or used for domestic
purposes in compressor plants, which does not naturally possess a distinctive odor to the
extent that its presence in the atmosphere is readily detectable at all gas concentrations of
one-fifth of the lower explosive limit and above, shall have an odorant added to it to make it
so detectable. Odorization is not necessary when it is adequately odorized by the supplier.
Suitable tests must be made to determine whether the odor meets the aforementioned
standards.