1220-04-05-.44
Gas Leak Classification
Cite as Tenn. Comp. R. & Regs. 1220-04-05-.44
(1)
Introduction
(a)
In the use of the grade classifications for leakage that follow, consideration must be
given to the fact that the analysis of a leak is not an exact science, but rather a
judgment decision. Some of the individual grade classifications do not have precise
limits because of the variable nature of the factors involved.
(b)
Grade classifications shall only be made by individuals who possess training,
experience and knowledge gained through association with leakage work. The
judgment of these individuals based upon information gained at the scene of the leak
will form the basis for the classification.
(c)
Percentages of gas-in-air are based on natural gas. Where liquefied petroleum,
manufactured or other gases are involved, appropriate adjustment shall be made as
may be required consistent with the lower explosive limit (L.E.L.) of such gas or mixture
of gases.
(2)
Definitions
(a)
Blowing Gas - A leak which can be heard, seen or felt.
(b)
Building - Any structure which is normally or occasionally occupied by humans for
business, residential or other purposes.
(c)
Follow-up Inspection - An inspection performed after a repair procedure has been
completed in order to determine the effectiveness of the repair.
(d)
Manhole or Vault - A subsurface structure that a man can enter.
(e)
Reading - Shall be construed to be the stabilized reading taken on a combustible gas
indicator unit.
(f)
Tunnel - A subsurface passageway of a size large enough for a man to enter.
(3)
Leak Repair Records. A leak repair ticket shall be used for the entire history of a leak through
the “follow-up” inspection. The document shall contain information as to corrective action
taken and follow-up results when such follow-up is deemed necessary by the operator. Leaks
may only be reclassified by responsible and suitably experienced individuals whose
identification shall appear on the ticket.
REGULATIONS FOR GAS COMPANIES
CHAPTER 1220-04-05
(4)
General Statement. Any leak or odor call from the general public, police, fire or other
authorities, or notification of damage to facilities by contractors or other outside sources shall
constitute the need for prompt action.
(5)
Grade Classification.
(a)
Grade 1 Leak is a gas leak which due to its location and/or relative magnitude
constitutes a potentially hazardous condition to the public or buildings. Grade 1 leaks
include, but are not limited to:
1.
Any indication of gas entering buildings or tunnels.
2.
Any reading from a combustible gas indicator within five (5) feet of a foundation
wall of a building which in the judgment of the operator is potentially dangerous.
3.
Any reading of at least four percent (4%) or greater gas-in-air on a sidewalk in a
wall-to-wall paved area where the volume of the leak presents a potential hazard
to persons or property.
4.
Blowing gas.
5.
A leak from a transmission line within Class 3 and 4 locations as specified in Part
192.5 of the OPS regulations.
6.
Four percent (4%) or greater gas-in-air reading in manholes, vaults, or
catchbasins.
7.
Any leak which, in the judgment of the supervisor at the scene, is regarded as
potentially hazardous.
(b)
Action Required:
1.
It shall require corrective action which shall consist of immediate effort to protect
life and property and continuous action until the condition is no longer hazardous
and scheduled for immediate daily repair activity.
(c)
Grade 2 Leak shall be a leak that does not constitute an immediate hazardous
condition to the public or buildings, but shall be of a nature requiring scheduled repair.
Grade 2 leaks include, but are not limited to:
1.
Transmission line leaks not classified as Grade 1 leaks.
2.
A leak on a valve or appurtenance which has migrated beyond the valve box
which in the judgment of the operator requires scheduled repair.
3.
Reading between two percent (2%) and four percent (4%) gas-in-air on a
sidewalk in a wall-to-wall paved area where the volume of the leak presents a
potential hazard to persons or property.
4.
Any reading between two percent (2%) and four percent (4%) gas-in-air in a
manhole, vault or catchbasin.
5.
Any Grade 3 leak which under frost conditions could migrate substantially.
6.
A high density of Grade 3 leaks in the street of a business or residential area.
REGULATIONS FOR GAS COMPANIES
CHAPTER 1220-04-05
(d)
Action Required:
1.
Grade 2 leaks shall be scheduled for repair within twelve (12) months or shall be
rechecked during the next annual survey. Rechecked Grade 2 leaks that have
not deteriorated may be rescheduled for repair if they are not in a hazardous
location and the repair would be difficult or expensive.
(e)
Grade 3 Leak is any other leak not classified as either a Grade 1 or Grade 2 leak.
(f)
Action Required:
1.
Grade 3 leaks shall be re-evaluated at the next scheduled survey.