R307-315-4. Requirements
Cite as Utah Admin. Code R307-315-4
(1) An owner or operator of a boiler subject to this rule shall:
(a) install a burner that meets a NOx emission rate of nine parts per million by volume (ppmv) or less at 3% volume stack gas oxygen on a dry basis; and
(b) meet a CO emission rate of 400 ppmv or less at 3% volume stack gas oxygen on a dry basis.
(2) An owner or operator of a boiler subject to Subsection R307-315-4(1) shall:
(a) operate and maintain the boiler and boiler subsystems, including burners, according to the manufacturer's instructions;
(b) determine continued compliance based on Section R307-315-6; and
(c) meet the applicable recordkeeping requirements for any control device.