R315-265-347
R315-265-347. Incinerators -- Monitoring and Inspections
Cite as Utah Admin. Code R315-265-347
The owner or operator shall conduct, as a minimum, the following monitoring and inspections when incinerating hazardous waste:
(a) Existing instruments that relate to combustion and emission control shall be monitored at least every 15 minutes. Appropriate corrections to maintain steady state combustion conditions shall be made immediately either automatically or by the
operator. Instruments that relate to combustion and emission control would normally include those measuring waste feed, auxiliary fuel feed, air flow, incinerator temperature, scrubber flow, scrubber pH, and relevant level controls.
(b) The complete incinerator and associated equipment, for example pumps, valves, conveyors, pipes, shall be inspected at least daily for leaks, spills, and fugitive emissions, and the emergency shutdown controls and system alarms shall be checked to assure proper operation.