R317-4-13
R317-4-13. Tables
Cite as Utah Admin. Code R317-4-13
TABLE 1.1
Minimum Lot Size (a) by Soil Type and Culinary Water Source
Soil Type
Public Water Supply
Non-public Water Supply (b)
1
12,000 sq. ft.
1.00 Acre
2
15,000 sq. ft.
1.25 Acres
3
18,000 sq. ft.
1.50 Acres
4
20,000 sq. ft.
1.75 Acres
5 (c)
20,000 sq. ft. (c)
1.75 Acres (c)
TABLE 1.2
Soil Type Key (d)
Soil Type
Soil Texture (e)
Soil Structure
Percolation Rate (minutes per inch)
1
Coarse Sand, Sand, Loamy Coarse Sand, Loamy Sand
Single Grain
1-10
2
Fine Sand, Very Fine Sand, Loamy Fine Sand, Loamy Very Fine Sand
Single Grain
11-20
3
Coarse Sandy Loam, Sandy Loam
Prismatic, Blocky, Granular
21-40
4
Coarse Sandy Loam, Sandy Loam
Fine Sandy Loam, Very Fine Sandy Loam, Loam, Silt Loam
Massive, Platy
Prismatic, Blocky, Granular
41-60
5
Fine Sandy Loam, Very Fine Sandy Loam, Loam, Silt Loam
Sandy Clay Loam, Clay Loam, Silty Clay Loam
Sandy Clay Loam, Clay Loam, Silty Clay Loam, Sandy Clay, Clay, Silty Clay, Silt
Massive, Platy
Massive
Prismatic, Blocky, Granular
61-120
6 (f)
Sandy Clay Loam, Clay Loam, Silty Clay Loam
Sandy Clay, Clay, Silty Clay, Silt
Platy
Massive, Platy
>120
NOTES
(a) Excluding public streets and alleys or other public rights-of-way, lands or any portion thereof abutting on, running through or within a building lot for a single-family dwelling. These minimum lot size requirements do not apply to building lots that have received final local health department approval before the adoption of this rule.
Any lot that is part of a subdivision that has received final local health department approval before the adoption of this rule is only exempt from the minimum lot size requirements if the developer has and is proceeding with reasonable diligence. Notwithstanding this grandfather provision for approved lots, the minimum lot size requirements are applicable if compelling or countervailing public health interests would require application of these more stringent requirements. The shape of the lot shall also be acceptable to the regulatory authority.
(b) See the separation requirements in Section R317-4-13 Table 2.
(c) A packed bed media or membrane bioreactor system is required for this soil type.
(d) When there is a substantial discrepancy between the percolation rate and the soil classification, it shall be resolved to the satisfaction of the regulatory authority, or the soil type requiring the largest lot shall be used.
(e) See the USDA soil classification system for a more detailed description.
(f) These soils are unsuitable for any absorption system.
TABLE 2
Minimum Separation Distances in Feet (a)
Item Requiring Setback
From Building Sewer or Effluent Sewer
From Septic, Pump, or Other Tank
From Absorption Area or Replacement Area
Absorption or Replacement Area
5
(b)
Public Culinary Water Source
(c)
100 (c)
100 (c)
Individual or Non-public Culinary Water Source (d)
25
50
100 (c)
Culinary Water Supply Line
(f)
10 (f)
10 (f)
Lake, Pond, Reservoir (a)
10
25
100
Watercourse (live or
25
100 (g)
ephemeral stream, river, subsurface drain, or canal, storm water drainage systems)
Building Foundation
Without foundation drain
With foundation drain
5
10
5 (h)
100 (i)
Curtain Drain
10
10
100 (i)
Dry wash, gulch, or gully
25
50 (j)
Swimming pool, below ground
3
10
25
Dry wells, basins
5
25
Down slope that exceed 35%. This includes any all natural slope or escarpment and any artificial cut, retaining wall, or embankment.
10
50 (j)
Property line
5
5
5
NOTES
(a) All distances are from edge to edge. Where surface waters are involved, the distance shall be measured from the high water line.
(b) See Subsection R317-4-6(14) for setback requirements.
(c) All distances shall be consistent with Rules R309-600 and R309-605.
(d) Compliance with separation requirements does not guarantee acceptable water quality in every instance. Where geological or other conditions warrant, greater distances may be required by the regulatory authority.
(e) For an ungrouted well or spring the distance shall be 200 feet. A private or individual well is considered to be grouted if it meets the construction standards required in Section R655-4-11, which requires a minimum 30-foot deep grout surface seal. Any private or individual well not constructed to this minimum standard is considered to be ungrouted. Although this distance shall be generally adhered to as the minimum required separation distance, exceptions maybe approved by the regulatory authority, taking into account geology, hydrology, topography, existing land use agreements, consideration of the drinking water source protection requirements, protection of public health and potential for pollution of water source. Any person proposing to locate an absorption system closer than 200 feet to an individual or non-public ungrouted well or spring must submit a report to the regulatory authority that considers the above items. In no case
may the regulatory authority grant approval for an onsite wastewater system to be closer than 100 feet from an ungrouted well or a spring.
(f) If the water supply line is for a public water supply, the separation distance shall comply with the requirements of Rule R309-550. No culinary water service line may pass through any portion of an absorption area.
(g) Lining or enclosing any watercourse with an acceptable impervious material may permit a reduction in the separation requirement. In any situation where the bottom of a canal or watercourse is at a higher elevation than the ground in which the absorption system is to be installed, a reduction in the distance requirement may be justified, but each case shall be decided on its own merits by the regulatory authority.
(h) Horizontal setback between a deep wall trench or seepage pit and a foundation of any building is at least 20 feet.
(i) The regulatory authority may reduce the separation distance, if it can be shown that the effluent will not enter the drain, but each case must be decided on its own merits by the regulatory authority. In no case may the regulatory authority grant approval for an absorption area to be closer than 20 feet.
(j) This setback may be reduced if a 53 foot reference line originating at the bottom of the distribution pipe, sloped at 35% below horizontal, will not daylight or intersect the ground surface.
TABLE 3
Estimated Flow Rates of Wastewater (a)
Type of Establishment
Gallons per Day
Airports
a. per passenger
b. per employee
3
15
Boarding and Rooming Houses
a. for each resident boarder and employee
b. additional for each nonresident boarder
50 per person
10 per person
Bowling Alleys, not including food service
85 per alley
Camps
a. developed with flush toilets and showers
b. developed with flush toilets
c. developed with no flush toilets
30 per person
20 per person
5 per person
Churches, per person
5
Condominiums, Multiple Family Dwellings, or Apartments
150 per bedroom
Dentist's Office
a. per chair
b. per staff member
200
35
Doctor's Office
a. per patient
b. per staff member
10
35
Fairgrounds
1 per person
Fire Stations
a. with full-time employees and food preparation
b. with no full-time employees and no food preparation
70 per person
5 per person
Food Service Establishment (b)
a. ordinary restaurants, not 24 hour service
b. 24 hour service
35 per seat
50 per seat
c. single service customer utensils only
d. or, per customer served, includes toilet and kitchen wastes
2 per customer
10
Gyms
a. participant and staff member
b. spectator
25 per person
4 per person
Hairdresser, per chair
65
Highway Rest Stops, improved with restroom facilities
5 per vehicle
Hospitals
250 per bed space
Hotels, Motels, and Resorts
125 per unit
Industrial Buildings, exclusive of
industrial waste
a. with showers, per 8 hour shift
b. with no showers, per 8 hour shift
35 per person
15 per person
Labor or Construction Camps
50 per person
Launderette
580 per washer
Mobile Home Parks
400 per unit
Movie Theaters
a. auditorium
b. drive-in
5 per seat
10 per car space
Nursing Homes
200 per bed space
Office Buildings and Business Establishments, not including food service, per eight hour shift
15 per employee
Picnic Parks, toilet wastes only
5 per person
Recreational Vehicle Parks
a. temporary or transient with no sewer connections
b. temporary or transient with sewer connections
50 per space
125 per space
Recreational Vehicle Dump Station, per self-contained vehicle
50
Schools
a. boarding
b. day, without cafeteria, gymnasiums or showers
c. day, with cafeteria but no gymnasiums and showers
d. day, with cafeteria, gymnasium and showers
75 per person
15 per person
20 per person
25 per person
Service Stations, per day, per pump
250
Skating Rink, Dance Halls, Ski Areas, or other recreation facility
10 per person
Stores, including Convenience Stores
a. per public toilet room
b. per employee
500
11
Swimming Pools and Bathhouses, Using Maximum Bather Load
10 per person
Taverns, Bars, Cocktail lounges with No Food Service
20 per seat
Visitor Centers
5 per visitor
NOTES
(a) When more than one use will occur, the multiple use shall be considered in determining total flow. Small industrial plants maintaining a cafeteria or showers and club houses or motels maintaining swimming pools or laundries are typical examples of multiple uses. Uses other than those listed above shall be considered in relation to established flows from known or similar installations.
(b) No commercial food waste disposal unit shall be connected to an onsite wastewater system unless first approved by the regulatory authority.
TABLE 4
Minimum Standards for Building Sewer, Effluent Sewer, and Distribution Pipe Materials (a)
Acceptable Building Sewer and Effluent Sewer Materials
Type of Pipe
Minimum Standard
Acrylonitrile-Butadiene Styrene (ABS)
ASTM (b) D-2680 (c), D-2751, F-628
Polyvinyl Chloride (PVC)
ASTM D-2665, D-3033, D-3034
Acceptable Distribution Pipe Materials
Type of Pipe
Minimum Standard
ABS
ASTM D-2661, D-2751
Polyethylene (PE), Smooth Wall
ASTM D-3350
PVC
ASTM D-2665, D-3033, D-3034, D-2729 (d)
NOTES
(a) Each length of building sewer, effluent sewer, and distribution pipe shall be stamped or marked.
(b) American Society for Testing and Materials.
(c) For domestic wastewater only, free from industrial
wastes.
(d) Although perforated PVC, ASTM D-2729 is approved for absorption system application, the solid-wall version of this pipe is not approved for any application.
TABLE 5
Maximum Hydraulic Loading Rates for Percolation Testing
Percolation Rate
(Minutes per Inch)
Absorption Systems
Hydraulic Loading
Rates (a)
(gal/ft2/day) (c)(d)(e)
Absorption Beds
and Mound Systems
Hydraulic Loading Rates (b) (gal/ft2/day)
(c)(d)(f)
0-10 (g)
0.90
0.45
11-20
0.70
0.35
21-30
0.60
0.30
31-40
0.55
0.27
41-50
0.50
0.25 (h)
51-60
0.45
0.22 (h)
61-90 (i)
0.40
(j)
91-120 (i)
0.35
(j)
NOTES
(a) The following formula may be used in place of the values in this table: q = 2.35 divided by the square root of the percolation rate and then add 0.15 where q is the hydraulic loading rate. In no case may the loading rate be greater than 1.0.
(b) The following formula may be used in place of the values in this table: q = 1.2 divided by the square root of the percolation rate and then add 0.08 where q is the hydraulic
loading rate. In no case may the loading rate be greater than 0.5.
(c) Minimum absorption area is equal to the actual or estimated wastewater flow in gallons per day shown in Section R317-4-13 Table 3, divided by the hydraulic loading rate within the applicable percolation rate category.
(d) For non-residential facilities, if a garbage grinder is not used, the absorption area may be reduced by 10% (0.9 multiplier). If any automatic sequence washer is not used, the absorption area may be reduced by 30% (0.7 multiplier). If both of these appliances are not used, the absorption area may be reduced by 40% (0.6 multiplier).
(e) For any non-residential facility, a minimum of 150 square feet of trench bottom or sidewall absorption area shall be provided.
(f) For any non-residential facility, a minimum of 300 square feet of absorption area shall be provided.
(g) Soils with a percolation rate faster than 1 minute per inch are only acceptable with the use of an alternative packed bed media or membrane bioreactor system with a disinfection unit.
(h) Not suitable for absorption beds.
(i) Acceptable for alternative packed bed media or membrane bioreactor system only.
(j) Not suitable for absorption beds or mounds.
TABLE 6
Maximum Hydraulic Loading Rates for Soil Classification
Texture
Structure
Absorption Systems Hydraulic Loading Rate (gal/ft2/day) (a)(b)(c)
Absorption Beds and Mound Systems Hydraulic Loading Rate (gal/ft2/day) (a)(b)(d)
Coarse sand, sand, loamy coarse sand, loamy sand
Single grain
0.90 (e)
0.45 (e)
Fine sand, very fine sand, loamy fine sand, loamy very fine sand
Single grain
0.70
0.35
Coarse sandy loam, sandy loam
Massive
Platy
Prismatic,
blocky,
granular
0.45
0.50
0.65
0.22 (f)
0.25 (f)
0.32 (f)
Fine sandy loam, very fine sandy loam
Massive
Platy
Prismatic,
blocky,
granular
0.40
0.35
0.50
(g)
(g)
0.25 (f)
Loam
Massive
Platy
Prismatic,
blocky,
granular
0.40
(e)
0.50
(g)
(g)
0.25 (f)
Silt loam
Massive
(e)
(g)
Platy
Prismatic,
blocky,
granular
(e)
0.45
(g)
0.22 (f)
Sandy clay loam, clay loam, silty clay loam
Massive
Platy
Prismatic,
blocky,
granular
(e)(h)
(i)
0.40 (e)(h)
(g)
(i)
(g)
Silt, silty clay, sandy clay, clay
Massive
Platy
Prismatic,
blocky,
granular
(i)
(i)
0.35 (e)(h)
(i)
(i)
(g)
NOTES
(a) Minimum absorption area is equal to the actual or estimated wastewater flow in gallons per day, using Section R317-4-13 Table 3, divided by the hydraulic loading rate within the applicable soil texture and structure category.
(b) For any non-residential facility, if a garbage grinder is not used, the absorption area may be reduced by 10% (0.9 multiplier). If any automatic sequence washer is not used, the absorption area may be reduced by 30% (0.7 multiplier). If both of these appliances are not used, the absorption area may be reduced by 40% (0.6 multiplier).
(c) For any non-residential facility, a minimum of 150 square feet of trench bottom or sidewall absorption area shall be provided.
(d) For any non-residential facility, a minimum of 300 square feet of absorption area shall be provided.
(e) These soils are usually considered unsuitable for absorption systems, but may be suitable, depending upon the percentage and type of fines in coarse grained porous soils, and the percentage of sand and structure in fine grained soils. Percolation testing shall be used for further evaluation.
(f) Not suitable for absorption beds.
(g) Not suitable for absorption beds or mounds.
(h) These soils may be permissible for a packed bed media or membrane bioreactor absorption system only.
(i) These soils are unsuitable for any absorption system.
TABLE 7.1
Alternative Onsite Wastewater System
Minimum Inspection Frequency(a)
Type of System
Annual
Semi-annual
Quarterly
Pressure Distribution
X
At-Grade (first 5 years only)
X
Mound
X
Packed Bed Media
X
Sand Lined Trench
X
Membrane Bioreactor
X
Holding Tank
X
Experimental System
X
NOTES
(a) Or more frequently as directed by the regulatory authority.
TABLE 7.2
Components
Type of System
Septic Tank and Other Tanks
Distribution or Drop Boxes
(if acces-sible)
Pumps, floats settings, Control Panel
Pressure Laterals, Absorp-tion Area
Disin-fection Unit (c)
Pressure Distri-bution
X
X
X
At-Grade
X
X
X
X
Mound
X
X
X
Packed Bed Media
X
X
X
X
X
Sand-Lined Trench
X
X
X
Mem-brane Bio-reactor
X
X
X
X
Holding Tank
X
X
X
X
Experi-mental
X
X
X
X
X
NOTES
(a) Inspect other components as directed by the regulatory authority.
(b) Including pumping records.
(c) Required for absorption systems installed in excessively permeable soils, or as directed by the regulatory authority.
TABLE 7.3
Effluent Sampling Parameters
Packed Bed Media and Membrane Bioreactor System
Routine Sampling Parameters
Must sample Turbidity, or BOD5 and TSS.
Field Testing
Maximum Value
Turbidity
=<20 NTU
Laboratory Testing
Maximum Value
BOD5
=<25 mg/l
TSS
=<25 mg/l
COD (a)
=<75 mg/l
E. coli (b)
26/100 ml
NOTES
(a) Chemical oxygen demand (COD) may be used in place of BOD5.
(b) E. coli testing required when a disinfection unit is installed.