WAC 296-307-41037
WAC 296-307-41037. Maximum filling densities
(1) Filling density. The percent ratio of the weight of the gas in a container to the weight of water the container will hold at 60°F. All containers must be filled according to the filling densities shown in Table U-4.
TABLE U-4
MAXIMUM PERMITTED FILLING DENSITY
Aboveground containers Specific Gravity at 60°F (15.6°C) 0 to 1,200 U.S. gals. (1,000 imp. gal. 4,500 liters) total water cap 0 to 1,200 U.S. gals. (1,000 imp. gal. 4,500 liters) total water cap Underground containers, all capacities Percent Percent Percent .496-.503 41 44 45 .504-.510 42 45 46 .511-.519 43 46 47 .520-.527 44 47 48 .528-.536 45 48 49 .537-.544 46 49 50 .545-.552 47 50 51 .553-.560 48 51 52 .561-.568 49 52 53 .569-.576 50 53 54 .577-.584 51 54 55 .585-.592 52 55 56 .593-.600 53 56 57
Aboveground containers
Specific
Gravity at
60°F (15.6°C)
0 to 1,200
U.S. gals.
(1,000 imp.
gal. 4,500
liters) total
water cap
0 to 1,200
U.S. gals.
(1,000 imp.
gal. 4,500
liters) total
water cap
Underground containers,
all capacities
Percent
Percent
Percent
.496-.503
41
44
45
.504-.510
42
45
46
.511-.519
43
46
47
.520-.527
44
47
48
.528-.536
45
48
49
.537-.544
46
49
50
.545-.552
47
50
51
.553-.560
48
51
52
.561-.568
49
52
53
.569-.576
50
53
54
.577-.584
51
54
55
.585-.592
52
55
56
.593-.600
53
56
57
(2) Any container including mobile cargo tanks and portable tank containers regardless of size or construction, shipped under DOT jurisdiction or constructed according to DOT specifications must be charged according to DOT requirements.
(3) Exception: Portable containers not subject to DOT jurisdiction must be filled either by weight, or by volume using a fixed length dip tube gauging device.