WAC 296-826-60030
WAC 296-826-60030. Nonrefrigerated containers
You must meet the requirements … in this section: Nonrefrigerated containers WAC 296-826-60030 Refrigerated tanks WAC 296-826-60035 Welding WAC 296-826-60040
You must meet the requirements …
in this section:
Nonrefrigerated containers
WAC 296-826-60030
Refrigerated tanks
WAC 296-826-60035
Welding
WAC 296-826-60040
You must make sure filling densities for nonrefrigerated containers are below or equal to the requirements in Table 15, Filling Densities.
Table 15
Filling Densities
Containers Aboveground Containers Underground Containers Uninsulated 56% 58% Insulated 57% ——
Containers
Aboveground Containers
Underground Containers
Uninsulated
56%
58%
Insulated
57%
——
Note:
For uninsulated, aboveground containers, the 56% corresponds to:
1. 82% by volume at -28°F.
2. 85% by volume at 5°F.
3. 87.5% by volume at 30°F.
4. 90.6% by volume at 60°F.