WAC 388-101D-0615. What requirements must the group training home's smoke detectors and fire extinguishers meet?

Last amended: 2019Year: 2026Length: 182 wordsOfficial source
(1) The group training home must install approved automatic smoke detectors: (a) In every client's bedroom; (b) On every floor of the home; and (c) In an interconnected manner so when one alarm is triggered, the whole system reacts. (2) The approved smoke detectors must: (a) Be in working condition at all times; and (b) Meet the specific needs of all clients living in the home. (3) The group training home must have a five-pound 2A:10B-C fire extinguisher on each floor of the home, unless the local fire authority requires a different type of fire extinguisher. (4) Each fire extinguisher must be: (a) Installed according to manufacturer recommendations; (b) Annually replaced or inspected and serviced; (c) In proper working order; and (d) Readily available for use at all times. (5) The group training home must be located in an area with public fire protection. (6) A group training home that was a licensed assisted living facility before January 1, 2019 must: (a) Meet requirements under subsections (1) through (5); or (b) Annually demonstrate they have passed inspection by the state fire marshal.