WAC 51-11C-403326
WAC 51-11C-403326. Table C403.3.2(6) — Minimum efficiency requirements — Gas-fired and oil-fired boilers
Table C403.3.2(6)
Gas- and Oil-Fired Boilers — Minimum Efficiency Requirements
Equipment Type a Subcategory or Rating Condition Size Category (Input) Minimum Efficiency Test Procedure a Boilers, hot water Gas-fired < 300,000 Btu/h g,h for applications outside the U.S. 82% AFUE DOE 10 C.F.R. 430 Appendix N ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/h e 84% E t d DOE 10 C.F.R. 431.86 > 2,500,000 Btu/h and ≤ 10,000,000 Btu/h b 85% E t d > 10,000,000 Btu/h b 82% E c c Oil-fired f < 300,000 Btu/h g,h 84% AFUE DOE 10 C.F.R. 430 Appendix N ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/h e 87% E t d DOE 10 C.F.R. 431.86 > 2,500,000 Btu/h b 88% E c c > 10,000,000 Btu/h b 84% E c d Boilers, steam Gas-fired < 300,000 Btu/h g 81% AFUE DOE 10 C.F.R. 430 Appendix N Gas-fired - all, except natural draft ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/h b 82% E t d DOE 10 C.F.R. 431.86 > 2,500,000 Btu/h a 79% E t d > 10,000,000 Btu/h b 79% E t d Gas-fired - natural draft ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/h b 81% E t d > 2,500,000 Btu/h b 82% E t d > 10,000,000 Btu/h b 79% E t d Oil-fired f < 300,000 Btu/h 82% AFUE DOE 10 C.F.R. 430 Appendix N ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/h b 84% E t d DOE 10 C.F.R. 431.86 > 2,500,000 Btu/h b 85% E t d > 10,000,000 Btu/h b 81% E t d
Equipment Type a
Subcategory or Rating Condition
Size Category (Input)
Minimum Efficiency
Test Procedure a
Boilers, hot water
Gas-fired
< 300,000 Btu/h g,h for applications outside
the U.S.
82% AFUE
DOE 10 C.F.R. 430 Appendix N
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h e
84% E t d
DOE 10 C.F.R. 431.86
> 2,500,000 Btu/h and
≤ 10,000,000 Btu/h b
85% E t d
> 10,000,000 Btu/h b
82% E c c
Oil-fired f
< 300,000 Btu/h g,h
84% AFUE
DOE 10 C.F.R. 430 Appendix N
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h e
87% E t d
DOE 10 C.F.R. 431.86
> 2,500,000 Btu/h b
88% E c c
> 10,000,000 Btu/h b
84% E c d
Boilers, steam
Gas-fired
< 300,000 Btu/h g
81% AFUE
DOE 10 C.F.R. 430 Appendix N
Gas-fired - all, except natural draft
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h b
82% E t d
DOE 10 C.F.R. 431.86
> 2,500,000 Btu/h a
79% E t d
> 10,000,000 Btu/h b
79% E t d
Gas-fired - natural draft
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h b
81% E t d
> 2,500,000 Btu/h b
82% E t d
> 10,000,000 Btu/h b
79% E t d
Oil-fired f
< 300,000 Btu/h
82% AFUE
DOE 10 C.F.R. 430 Appendix N
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h b
84% E t d
DOE 10 C.F.R. 431.86
> 2,500,000 Btu/h b
85% E t d
> 10,000,000 Btu/h b
81% E t d
For SI: 1 British thermal unit per hour = 0.2931 W.
a
Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b
These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
c
E c
=
Combustion efficiency (100 percent less flue losses).
d
E t
=
Thermal efficiency.
e
Maximum capacity – Minimum and maximum ratings as provided for and allowed by the unit's controls.
f
Includes oil-fired (residual).
g
Boilers shall not be equipped with a constant burning pilot light.
h
A boiler not equipped with a tankless domestic water heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.
i
This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements.