WAC 51-11C-40345

WAC 51-11C-40345. Section C403.4.5 — Pump isolation

Last amended: 2020Year: 2026Length: 86 wordsOfficial source
C403.4.5 Pump isolation. Chilled water plants including more than one chiller shall be capable of and configured to reduce flow automatically through the chiller plant when a chiller is shut down and automatically shut off flow to chillers that are shut down. Chillers piped in series for the purpose of increased temperature differential shall be considered as one chiller. Boiler systems including more than one boiler shall be capable of and configured to reduce flow automatically through the boiler system when a boiler is shut down.